You are on page 1of 1

1.

Location : MRS#2/22 KV SWBD

Equipment Name : Tie feeder to MRS – 3 PNL No: 16 / P. No: 09

2. Equipment Details:

Make Alstom
Type VAJHM23
Sl.No. 93124532007
Volts 110 – 125 V DC
3. Pickup and Dropoff Voltage Test:

Reference Pickup Voltage(V) Dropoff Voltage(V)


9,10 38.9 HR

4. Functional Checks: (Whether Operational Checks OK/Not Ok/ Not Applicable)

1 Correct Operation of Appropriate Indication/Flag OK


2 Correct Operation of output Contacts OK
3 Correct Operation of Reset Knobs. OK

5. Comments : Nil.

6. Remarks : Relay Found Healthy.

You might also like