Air System Sizing Summary for PT8 Oficina 1

Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1


01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 1 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 538,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 4,2 Tons Load occurs at ................................................... Jun 1700
Total coil load .......................................................... 50,6 MBH OA DB / WB ...................................................... 83,9 / 73,1 °F
Sensible coil load ................................................... 35,8 MBH Entering DB / WB ............................................. 75,1 / 64,3 °F
Coil CFM at Jun 1700 ........................................... 1963 CFM Leaving DB / WB .............................................. 56,2 / 55,2 °F
Max block CFM ..................................................... 1963 CFM Coil ADP ..................................................................... 54,1 °F
Sum of peak zone CFM ........................................ 1963 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,708 Resulting RH ................................................................. 55 %
CFM/Ton ............................................................... 465,5 Design supply temp. ................................................... 54,0 °F
ft²/Ton ................................................................... 127,6 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 94,1 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise .................................... 10,13 gpm

Supply Fan Sizing Data

Actual max CFM .................................................... 1963 CFM Fan motor BHP ........................................................... 0,27 BHP
Standard CFM ....................................................... 1753 CFM Fan motor kW ............................................................. 0,21 kW
Actual max CFM/ft² ................................................. 3,65 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 415 CFM CFM/person .............................................................. 29,61 CFM/person
CFM/ft² ................................................................... 0,77 CFM/ft²

Hourly Analysis Program 5.11 Page  1  of  70 


Zone Sizing Summary for PT8 Oficina 1
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 1 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 538,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 1963 1963 3,65 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 34,1 Dec 1600 2,7 538,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT8 Oficina 1 1 34,1 Dec 1600 1963 2,7 538,0 3,65

Hourly Analysis Program 5.11 Page  2  of  70 


Air System Design Load Summary for PT8 Oficina 1
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 83,9 °F / 73,1 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 270 ft² 12380 - 270 ft² - -
Wall Transmission 286 ft² 2168 - 286 ft² 815 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 270 ft² 1475 - 270 ft² 1908 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 9 ft² 13 - 9 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 673 W 2016 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2152 W 6946 - 0 0 -
People 14 2911 2870 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 2791 144 0% 0 0
>> Total Zone Loads - 30700 3014 - 2724 0
Zone Conditioning - 30631 3014 - -347 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1963 CFM 0 - 1963 CFM 0 -
Ventilation Load 415 CFM 4465 11762 415 CFM 1128 0
Supply Fan Load 1963 CFM 727 - 1963 CFM -727 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 35823 14776 - 53 0
Central Cooling Coil - 35823 14777 - 0 0
>> Total Conditioning - 35823 14777 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  3  of  70 


System Psychrometrics for PT8 Oficina 1
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

June DESIGN COOLING DAY, 1700

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 83,9 0,01721 415 400 4465 11762
Vent - Return Mixing Outlet 75,1 0,01193 1963 751 - -
Central Cooling Coil Outlet 56,2 0,01015 1963 751 35823 14777
Supply Fan Outlet 56,5 0,01015 1963 751 727 -
Cold Supply Duct Outlet 56,5 0,01015 1963 751 - -
Zone Air - 72,7 0,01052 1963 845 30631 3014
Return Plenum Outlet 72,7 0,01052 1963 845 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 30700 Cooling 30631 72,7 1963 845 0 0

Hourly Analysis Program 5.11 Page  4  of  70 


System Psychrometrics for PT8 Oficina 1
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 415 400 -1128 0
Vent - Return Mixing Outlet 60,2 0,01024 1963 437 - -
Central Cooling Coil Outlet 60,2 0,01024 1963 437 0 0
Supply Fan Outlet 60,6 0,01024 1963 437 727 -
Cold Supply Duct Outlet 60,6 0,01024 1963 437 - -
Zone Air - 60,8 0,01024 1963 447 347 0
Return Plenum Outlet 60,8 0,01024 1963 447 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -2724 Deadband 347 60,8 1963 447 0 0

Hourly Analysis Program 5.11 Page  5  of  70 


System Psychrometrics for PT8 Oficina 1
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: June DESIGN COOLING DAY, 1700
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0,018
5. Room Air

0,016

Specific Humidity ( lb/lb )


0,014
2
0,012
5
34
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  6  of  70 


System Psychrometrics for PT8 Oficina 1
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23
4 0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  7  of  70 


Air System Sizing Summary for PT8 Oficina 2
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 2 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 290,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 2,6 Tons Load occurs at ................................................... Aug 1700
Total coil load .......................................................... 30,8 MBH OA DB / WB ...................................................... 84,9 / 73,2 °F
Sensible coil load ................................................... 21,9 MBH Entering DB / WB ............................................. 75,5 / 64,0 °F
Coil CFM at Aug 1700 ........................................... 1114 CFM Leaving DB / WB .............................................. 55,1 / 54,1 °F
Max block CFM ...................................................... 1114 CFM Coil ADP ..................................................................... 52,9 °F
Sum of peak zone CFM ......................................... 1114 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,713 Resulting RH ................................................................. 52 %
CFM/Ton ............................................................... 434,3 Design supply temp. ................................................... 54,0 °F
ft²/Ton .................................................................... 113,0 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ........................................................... 106,2 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise ...................................... 6,16 gpm

Supply Fan Sizing Data

Actual max CFM .................................................... 1114 CFM Fan motor BHP ........................................................... 0,15 BHP
Standard CFM ......................................................... 995 CFM Fan motor kW ............................................................. 0,12 kW
Actual max CFM/ft² ................................................. 3,84 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 248 CFM CFM/person .............................................................. 35,36 CFM/person
CFM/ft² ................................................................... 0,85 CFM/ft²

Hourly Analysis Program 5.11 Page  8  of  70 


Zone Sizing Summary for PT8 Oficina 2
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 2 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 290,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 1114 1114 3,84 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 19,3 Mar 1700 1,1 290,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT8 Oficina 2 1 19,3 Mar 1700 1114 1,1 290,0 3,84

Hourly Analysis Program 5.11 Page  9  of  70 


Air System Design Load Summary for PT8 Oficina 2
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 84,9 °F / 73,2 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 138 ft² 9551 - 138 ft² - -
Wall Transmission 42 ft² 482 - 42 ft² 121 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 138 ft² 832 - 138 ft² 972 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 363 W 1087 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1160 W 3744 - 0 0 -
People 7 1455 1435 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1715 72 0% 0 0
>> Total Zone Loads - 18866 1507 - 1093 0
Zone Conditioning - 18659 1507 - -468 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1114 CFM 0 - 1114 CFM 0 -
Ventilation Load 248 CFM 2869 7346 248 CFM 910 0
Supply Fan Load 1114 CFM 413 - 1114 CFM -413 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 21941 8853 - 29 0
Central Cooling Coil - 21941 8853 - 0 0
>> Total Conditioning - 21941 8853 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  10  of  70 


System Psychrometrics for PT8 Oficina 2
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

August DESIGN COOLING DAY, 1700

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 84,9 0,01705 248 400 2869 7346
Vent - Return Mixing Outlet 75,5 0,01161 1114 694 - -
Central Cooling Coil Outlet 55,1 0,00973 1114 694 21941 8853
Supply Fan Outlet 55,5 0,00973 1114 694 413 -
Cold Supply Duct Outlet 55,5 0,00973 1114 694 - -
Zone Air - 72,9 0,01005 1114 778 18659 1507
Return Plenum Outlet 72,9 0,01005 1114 778 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 18866 Cooling 18659 72,9 1114 778 0 0

Hourly Analysis Program 5.11 Page  11  of  70 


System Psychrometrics for PT8 Oficina 2
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 248 400 -910 0
Vent - Return Mixing Outlet 61,0 0,01024 1114 432 - -
Central Cooling Coil Outlet 61,0 0,01024 1114 432 0 0
Supply Fan Outlet 61,3 0,01024 1114 432 413 -
Cold Supply Duct Outlet 61,4 0,01024 1114 432 - -
Zone Air - 61,8 0,01024 1114 442 468 0
Return Plenum Outlet 61,8 0,01024 1114 442 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -1093 Deadband 468 61,8 1114 442 0 0

Hourly Analysis Program 5.11 Page  12  of  70 


System Psychrometrics for PT8 Oficina 2
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: August DESIGN COOLING DAY, 1700
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0,018
5. Room Air

0,016

Specific Humidity ( lb/lb )


0,014
2 0,012
34 5
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  13  of  70 


System Psychrometrics for PT8 Oficina 2
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23 4
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  14  of  70 


Air System Sizing Summary for PT8 Oficina 3
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 3 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 211,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 2,2 Tons Load occurs at ................................................... Sep 1600
Total coil load .......................................................... 26,2 MBH OA DB / WB ...................................................... 84,4 / 72,7 °F
Sensible coil load ................................................... 18,4 MBH Entering DB / WB ............................................. 75,6 / 64,0 °F
Coil CFM at Sep 1600 ............................................. 924 CFM Leaving DB / WB .............................................. 54,9 / 53,9 °F
Max block CFM ....................................................... 924 CFM Coil ADP ..................................................................... 52,6 °F
Sum of peak zone CFM .......................................... 924 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,705 Resulting RH ................................................................. 52 %
CFM/Ton ............................................................... 423,6 Design supply temp. ................................................... 54,0 °F
ft²/Ton ...................................................................... 96,7 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ........................................................... 124,0 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise ...................................... 5,24 gpm

Supply Fan Sizing Data

Actual max CFM ...................................................... 924 CFM Fan motor BHP ........................................................... 0,13 BHP
Standard CFM ......................................................... 825 CFM Fan motor kW ............................................................. 0,10 kW
Actual max CFM/ft² ................................................. 4,38 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 213 CFM CFM/person .............................................................. 26,59 CFM/person
CFM/ft² ................................................................... 1,01 CFM/ft²

Hourly Analysis Program 5.11 Page  15  of  70 


Zone Sizing Summary for PT8 Oficina 3
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 3 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 211,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 924 924 4,38 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 16,0 Mar 1700 0,9 211,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT8 Oficina 3 1 16,0 Mar 1700 924 0,9 211,0 4,38

Hourly Analysis Program 5.11 Page  16  of  70 


Air System Design Load Summary for PT8 Oficina 3
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 84,4 °F / 72,7 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 118 ft² 8640 - 118 ft² - -
Wall Transmission 9 ft² 82 - 9 ft² 25 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 118 ft² 629 - 118 ft² 834 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 264 W 783 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 844 W 2713 - 0 0 -
People 8 1642 1640 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1449 82 0% 0 0
>> Total Zone Loads - 15938 1722 - 859 0
Zone Conditioning - 15761 1722 - -475 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 924 CFM 0 - 924 CFM 0 -
Ventilation Load 213 CFM 2342 6005 213 CFM 848 0
Supply Fan Load 924 CFM 342 - 924 CFM -342 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 18445 7727 - 30 0
Central Cooling Coil - 18445 7729 - 0 0
>> Total Conditioning - 18445 7729 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  17  of  70 


System Psychrometrics for PT8 Oficina 3
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

September DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 84,4 0,01674 213 400 2342 6005
Vent - Return Mixing Outlet 75,6 0,01162 924 779 - -
Central Cooling Coil Outlet 54,9 0,00964 924 779 18445 7729
Supply Fan Outlet 55,3 0,00964 924 779 342 -
Cold Supply Duct Outlet 55,3 0,00964 924 779 - -
Zone Air - 73,0 0,01008 924 892 15761 1722
Return Plenum Outlet 73,0 0,01008 924 892 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 15938 Cooling 15761 73,0 924 892 0 0

Hourly Analysis Program 5.11 Page  18  of  70 


System Psychrometrics for PT8 Oficina 3
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 213 400 -848 0
Vent - Return Mixing Outlet 61,2 0,01024 924 429 - -
Central Cooling Coil Outlet 61,2 0,01024 924 429 0 0
Supply Fan Outlet 61,6 0,01024 924 429 342 -
Cold Supply Duct Outlet 61,6 0,01024 924 429 - -
Zone Air - 62,1 0,01024 924 438 475 0
Return Plenum Outlet 62,1 0,01024 924 438 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -859 Deadband 475 62,1 924 438 0 0

Hourly Analysis Program 5.11 Page  19  of  70 


System Psychrometrics for PT8 Oficina 3
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: September DESIGN COOLING DAY, 1600
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0,018
5. Room Air 1

0,016

Specific Humidity ( lb/lb )


0,014
2 0,012
5
34 0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  20  of  70 


System Psychrometrics for PT8 Oficina 3
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23 4
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  21  of  70 


Air System Sizing Summary for PT8 Oficina 4
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 4 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 211,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 2,2 Tons Load occurs at ................................................... Sep 1600
Total coil load .......................................................... 26,2 MBH OA DB / WB ...................................................... 84,4 / 72,7 °F
Sensible coil load ................................................... 18,4 MBH Entering DB / WB ............................................. 75,6 / 64,0 °F
Coil CFM at Sep 1600 ............................................. 924 CFM Leaving DB / WB .............................................. 54,9 / 53,9 °F
Max block CFM ....................................................... 924 CFM Coil ADP ..................................................................... 52,6 °F
Sum of peak zone CFM .......................................... 924 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,705 Resulting RH ................................................................. 52 %
CFM/Ton ............................................................... 423,6 Design supply temp. ................................................... 54,0 °F
ft²/Ton ...................................................................... 96,7 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ........................................................... 124,0 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise ...................................... 5,24 gpm

Supply Fan Sizing Data

Actual max CFM ...................................................... 924 CFM Fan motor BHP ........................................................... 0,13 BHP
Standard CFM ......................................................... 825 CFM Fan motor kW ............................................................. 0,10 kW
Actual max CFM/ft² ................................................. 4,38 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 213 CFM CFM/person .............................................................. 26,59 CFM/person
CFM/ft² ................................................................... 1,01 CFM/ft²

Hourly Analysis Program 5.11 Page  22  of  70 


Zone Sizing Summary for PT8 Oficina 4
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 4 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 211,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 924 924 4,38 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 16,0 Mar 1700 0,9 211,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT8 Oficina 4 1 16,0 Mar 1700 924 0,9 211,0 4,38

Hourly Analysis Program 5.11 Page  23  of  70 


Air System Design Load Summary for PT8 Oficina 4
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 84,4 °F / 72,7 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 118 ft² 8640 - 118 ft² - -
Wall Transmission 9 ft² 82 - 9 ft² 25 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 118 ft² 629 - 118 ft² 834 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 264 W 783 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 844 W 2713 - 0 0 -
People 8 1642 1640 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1449 82 0% 0 0
>> Total Zone Loads - 15938 1722 - 859 0
Zone Conditioning - 15761 1722 - -475 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 924 CFM 0 - 924 CFM 0 -
Ventilation Load 213 CFM 2342 6005 213 CFM 848 0
Supply Fan Load 924 CFM 342 - 924 CFM -342 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 18445 7727 - 30 0
Central Cooling Coil - 18445 7729 - 0 0
>> Total Conditioning - 18445 7729 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  24  of  70 


System Psychrometrics for PT8 Oficina 4
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

September DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 84,4 0,01674 213 400 2342 6005
Vent - Return Mixing Outlet 75,6 0,01162 924 779 - -
Central Cooling Coil Outlet 54,9 0,00964 924 779 18445 7729
Supply Fan Outlet 55,3 0,00964 924 779 342 -
Cold Supply Duct Outlet 55,3 0,00964 924 779 - -
Zone Air - 73,0 0,01008 924 892 15761 1722
Return Plenum Outlet 73,0 0,01008 924 892 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 15938 Cooling 15761 73,0 924 892 0 0

Hourly Analysis Program 5.11 Page  25  of  70 


System Psychrometrics for PT8 Oficina 4
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 213 400 -848 0
Vent - Return Mixing Outlet 61,2 0,01024 924 429 - -
Central Cooling Coil Outlet 61,2 0,01024 924 429 0 0
Supply Fan Outlet 61,6 0,01024 924 429 342 -
Cold Supply Duct Outlet 61,6 0,01024 924 429 - -
Zone Air - 62,1 0,01024 924 438 475 0
Return Plenum Outlet 62,1 0,01024 924 438 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -859 Deadband 475 62,1 924 438 0 0

Hourly Analysis Program 5.11 Page  26  of  70 


System Psychrometrics for PT8 Oficina 4
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: September DESIGN COOLING DAY, 1600
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0,018
5. Room Air 1

0,016

Specific Humidity ( lb/lb )


0,014
2 0,012
5
34 0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  27  of  70 


System Psychrometrics for PT8 Oficina 4
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23 4
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  28  of  70 


Air System Sizing Summary for PT8 Oficina 5
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 5 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 550,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 4,4 Tons Load occurs at ................................................... Jun 1600
Total coil load .......................................................... 52,9 MBH OA DB / WB ...................................................... 85,4 / 73,7 °F
Sensible coil load ................................................... 38,8 MBH Entering DB / WB ............................................. 75,6 / 63,9 °F
Coil CFM at Jun 1600 ........................................... 2004 CFM Leaving DB / WB .............................................. 55,6 / 54,5 °F
Max block CFM ..................................................... 2004 CFM Coil ADP ..................................................................... 53,3 °F
Sum of peak zone CFM ........................................ 2004 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,732 Resulting RH ................................................................. 52 %
CFM/Ton ............................................................... 454,4 Design supply temp. ................................................... 54,0 °F
ft²/Ton ................................................................... 124,7 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 96,2 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise .................................... 10,59 gpm

Supply Fan Sizing Data

Actual max CFM .................................................... 2004 CFM Fan motor BHP ........................................................... 0,27 BHP
Standard CFM ....................................................... 1790 CFM Fan motor kW ............................................................. 0,22 kW
Actual max CFM/ft² ................................................. 3,64 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 378 CFM CFM/person .............................................................. 31,46 CFM/person
CFM/ft² ................................................................... 0,69 CFM/ft²

Hourly Analysis Program 5.11 Page  29  of  70 


Zone Sizing Summary for PT8 Oficina 5
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 5 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 550,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 2004 2004 3,64 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 34,8 Jun 1600 2,9 550,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT8 Oficina 5 1 34,8 Jun 1600 2004 2,9 550,0 3,64

Hourly Analysis Program 5.11 Page  30  of  70 


Air System Design Load Summary for PT8 Oficina 5
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 85,4 °F / 73,7 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 321 ft² 16031 - 321 ft² - -
Wall Transmission 214 ft² 1821 - 214 ft² 610 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 321 ft² 1901 - 321 ft² 2268 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 200 ft² 300 - 200 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 688 W 2041 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2200 W 7072 - 0 0 -
People 12 2464 2460 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 3163 123 0% 0 0
>> Total Zone Loads - 34792 2583 - 2878 0
Zone Conditioning - 33641 2583 - -632 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2004 CFM 0 - 2004 CFM 0 -
Ventilation Load 378 CFM 4372 11588 378 CFM 1470 0
Supply Fan Load 2004 CFM 743 - 2004 CFM -743 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 38756 14171 - 95 0
Central Cooling Coil - 38756 14169 - 0 0
>> Total Conditioning - 38756 14169 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  31  of  70 


System Psychrometrics for PT8 Oficina 5
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

June DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 85,4 0,01743 378 400 4372 11588
Vent - Return Mixing Outlet 75,6 0,01155 2004 749 - -
Central Cooling Coil Outlet 55,6 0,00988 2004 749 38756 14169
Supply Fan Outlet 56,0 0,00988 2004 749 743 -
Cold Supply Duct Outlet 56,0 0,00988 2004 749 - -
Zone Air - 73,4 0,01018 2004 830 33641 2583
Return Plenum Outlet 73,4 0,01018 2004 830 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 34792 Cooling 33641 73,4 2004 830 0 0

Hourly Analysis Program 5.11 Page  32  of  70 


System Psychrometrics for PT8 Oficina 5
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 378 400 -1470 0
Vent - Return Mixing Outlet 61,3 0,01024 2004 440 - -
Central Cooling Coil Outlet 61,3 0,01024 2004 440 0 0
Supply Fan Outlet 61,7 0,01024 2004 440 743 -
Cold Supply Duct Outlet 61,7 0,01024 2004 440 - -
Zone Air - 62,0 0,01024 2004 450 632 0
Return Plenum Outlet 62,0 0,01024 2004 450 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -2878 Deadband 632 62,0 2004 450 0 0

Hourly Analysis Program 5.11 Page  33  of  70 


System Psychrometrics for PT8 Oficina 5
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: June DESIGN COOLING DAY, 1600
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0,018
5. Room Air

0,016

Specific Humidity ( lb/lb )


0,014
2 0,012
34 5
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  34  of  70 


System Psychrometrics for PT8 Oficina 5
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23 4
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  35  of  70 


Air System Sizing Summary for PT8 Oficina 6
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 6 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 743,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 4,6 Tons Load occurs at ................................................... Jun 1500
Total coil load .......................................................... 55,6 MBH OA DB / WB ...................................................... 86,0 / 74,0 °F
Sensible coil load ................................................... 41,1 MBH Entering DB / WB ............................................. 75,7 / 63,7 °F
Coil CFM at Jun 1500 ........................................... 2079 CFM Leaving DB / WB .............................................. 55,2 / 54,1 °F
Max block CFM ..................................................... 2079 CFM Coil ADP ..................................................................... 52,9 °F
Sum of peak zone CFM ........................................ 2079 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,739 Resulting RH ................................................................. 51 %
CFM/Ton ............................................................... 448,8 Design supply temp. ................................................... 53,8 °F
ft²/Ton ................................................................... 160,4 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 74,8 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise .................................... 11,12 gpm

Supply Fan Sizing Data

Actual max CFM .................................................... 2079 CFM Fan motor BHP ........................................................... 0,28 BHP
Standard CFM ....................................................... 1856 CFM Fan motor kW ............................................................. 0,23 kW
Actual max CFM/ft² ................................................. 2,80 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 386 CFM CFM/person .............................................................. 38,58 CFM/person
CFM/ft² ................................................................... 0,52 CFM/ft²

Hourly Analysis Program 5.11 Page  36  of  70 


Zone Sizing Summary for PT8 Oficina 6
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 6 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 743,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 2079 2079 2,80 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 36,5 Jun 1500 3,1 743,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT8 Oficina 6 1 36,5 Jun 1500 2079 3,1 743,0 2,80

Hourly Analysis Program 5.11 Page  37  of  70 


Air System Design Load Summary for PT8 Oficina 6
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 86,0 °F / 74,0 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 367 ft² 15336 - 367 ft² - -
Wall Transmission 179 ft² 1351 - 179 ft² 510 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 367 ft² 2212 - 367 ft² 2592 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 929 W 2729 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2972 W 9512 - 0 0 -
People 10 2025 2050 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 3317 103 0% 0 0
>> Total Zone Loads - 36482 2153 - 3102 0
Zone Conditioning - 35586 2153 - -459 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2079 CFM 0 - 2079 CFM 0 -
Ventilation Load 386 CFM 4717 12349 386 CFM 1292 0
Supply Fan Load 2079 CFM 770 - 2079 CFM -770 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 41073 14501 - 63 0
Central Cooling Coil - 41073 14502 - 0 0
>> Total Conditioning - 41073 14502 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  38  of  70 


System Psychrometrics for PT8 Oficina 6
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

June DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 86,0 0,01752 386 400 4717 12349
Vent - Return Mixing Outlet 75,7 0,01137 2079 696 - -
Central Cooling Coil Outlet 55,2 0,00972 2079 696 41073 14502
Supply Fan Outlet 55,6 0,00972 2079 696 770 -
Cold Supply Duct Outlet 55,6 0,00972 2079 696 - -
Zone Air - 73,3 0,00997 2079 764 35586 2153
Return Plenum Outlet 73,3 0,00997 2079 764 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 36482 Cooling 35586 73,3 2079 764 0 0

Hourly Analysis Program 5.11 Page  39  of  70 


System Psychrometrics for PT8 Oficina 6
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 386 400 -1292 0
Vent - Return Mixing Outlet 60,8 0,01024 2079 442 - -
Central Cooling Coil Outlet 60,8 0,01024 2079 442 0 0
Supply Fan Outlet 61,2 0,01024 2079 442 770 -
Cold Supply Duct Outlet 61,2 0,01024 2079 442 - -
Zone Air - 61,5 0,01024 2079 451 459 0
Return Plenum Outlet 61,5 0,01024 2079 451 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -3102 Deadband 459 61,5 2079 451 0 0

Hourly Analysis Program 5.11 Page  40  of  70 


System Psychrometrics for PT8 Oficina 6
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: June DESIGN COOLING DAY, 1500
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet 1
4. Supply Fan Outlet 0,018
5. Room Air

0,016

Specific Humidity ( lb/lb )


0,014

2 0,012
34 5
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  41  of  70 


System Psychrometrics for PT8 Oficina 6
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23
4 0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  42  of  70 


Air System Sizing Summary for PT8 Oficina 7
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 7 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 211,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 1,7 Tons Load occurs at ................................................... Aug 1500
Total coil load .......................................................... 20,0 MBH OA DB / WB ...................................................... 87,0 / 74,0 °F
Sensible coil load ................................................... 14,1 MBH Entering DB / WB ............................................. 76,1 / 65,1 °F
Coil CFM at Aug 1500 ............................................. 770 CFM Leaving DB / WB .............................................. 57,2 / 56,2 °F
Max block CFM ....................................................... 770 CFM Coil ADP ..................................................................... 55,0 °F
Sum of peak zone CFM .......................................... 770 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,703 Resulting RH ................................................................. 56 %
CFM/Ton ............................................................... 461,3 Design supply temp. ................................................... 54,0 °F
ft²/Ton ................................................................... 126,3 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 95,0 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise ...................................... 4,01 gpm

Supply Fan Sizing Data

Actual max CFM ...................................................... 770 CFM Fan motor BHP ........................................................... 0,11 BHP
Standard CFM ......................................................... 688 CFM Fan motor kW ............................................................. 0,08 kW
Actual max CFM/ft² ................................................. 3,65 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 173 CFM CFM/person .............................................................. 28,79 CFM/person
CFM/ft² ................................................................... 0,82 CFM/ft²

Hourly Analysis Program 5.11 Page  43  of  70 


Zone Sizing Summary for PT8 Oficina 7
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 7 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 211,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 770 770 3,65 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 13,4 Mar 1000 0,9 211,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT8 Oficina 7 1 13,4 Mar 1000 770 0,9 211,0 3,65

Hourly Analysis Program 5.11 Page  44  of  70 


Air System Design Load Summary for PT8 Oficina 7
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87,0 °F / 74,0 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 118 ft² 4995 - 118 ft² - -
Wall Transmission 9 ft² 66 - 9 ft² 25 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 118 ft² 781 - 118 ft² 834 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 264 W 775 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 844 W 2701 - 0 0 -
People 6 1215 1230 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1053 62 0% 0 0
>> Total Zone Loads - 11586 1292 - 859 0
Zone Conditioning - 11471 1292 - -428 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 770 CFM 0 - 770 CFM 0 -
Ventilation Load 173 CFM 2336 4656 173 CFM 737 0
Supply Fan Load 770 CFM 286 - 770 CFM -286 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 14093 5947 - 23 0
Central Cooling Coil - 14093 5948 - 0 0
>> Total Conditioning - 14093 5948 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  45  of  70 


System Psychrometrics for PT8 Oficina 7
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

August DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 87,0 0,01728 173 400 2336 4656
Vent - Return Mixing Outlet 76,1 0,01235 770 751 - -
Central Cooling Coil Outlet 57,2 0,01053 770 751 14093 5948
Supply Fan Outlet 57,5 0,01053 770 751 286 -
Cold Supply Duct Outlet 57,5 0,01053 770 751 - -
Zone Air - 73,0 0,01092 770 853 11471 1292
Return Plenum Outlet 73,0 0,01092 770 853 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 11586 Cooling 11471 73,0 770 853 0 0

Hourly Analysis Program 5.11 Page  46  of  70 


System Psychrometrics for PT8 Oficina 7
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 173 400 -737 0
Vent - Return Mixing Outlet 61,4 0,01024 770 432 - -
Central Cooling Coil Outlet 61,4 0,01024 770 432 0 0
Supply Fan Outlet 61,8 0,01024 770 432 286 -
Cold Supply Duct Outlet 61,8 0,01024 770 432 - -
Zone Air - 62,4 0,01024 770 441 428 0
Return Plenum Outlet 62,4 0,01024 770 441 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -859 Deadband 428 62,4 770 441 0 0

Hourly Analysis Program 5.11 Page  47  of  70 


System Psychrometrics for PT8 Oficina 7
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: August DESIGN COOLING DAY, 1500
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0,018
5. Room Air

0,016

Specific Humidity ( lb/lb )


0,014
2

5
0,012
34
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  48  of  70 


System Psychrometrics for PT8 Oficina 7
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23 4
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  49  of  70 


Air System Sizing Summary for PT8 Oficina 8
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 8 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 211,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 1,9 Tons Load occurs at ................................................... Aug 1500
Total coil load .......................................................... 22,6 MBH OA DB / WB ...................................................... 87,0 / 74,0 °F
Sensible coil load ................................................... 15,1 MBH Entering DB / WB ............................................. 76,7 / 65,7 °F
Coil CFM at Aug 1500 ............................................. 794 CFM Leaving DB / WB .............................................. 56,9 / 55,9 °F
Max block CFM ....................................................... 794 CFM Coil ADP ..................................................................... 54,7 °F
Sum of peak zone CFM .......................................... 794 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,671 Resulting RH ................................................................. 57 %
CFM/Ton ............................................................... 422,3 Design supply temp. ................................................... 54,0 °F
ft²/Ton .................................................................... 112,2 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ........................................................... 106,9 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise ...................................... 4,51 gpm

Supply Fan Sizing Data

Actual max CFM ...................................................... 794 CFM Fan motor BHP ........................................................... 0,11 BHP
Standard CFM ......................................................... 709 CFM Fan motor kW ............................................................. 0,09 kW
Actual max CFM/ft² ................................................. 3,76 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 213 CFM CFM/person .............................................................. 26,59 CFM/person
CFM/ft² ................................................................... 1,01 CFM/ft²

Hourly Analysis Program 5.11 Page  50  of  70 


Zone Sizing Summary for PT8 Oficina 8
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 8 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 211,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 794 794 3,76 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 13,8 Mar 1000 0,9 211,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT8 Oficina 8 1 13,8 Mar 1000 794 0,9 211,0 3,76

Hourly Analysis Program 5.11 Page  51  of  70 


Air System Design Load Summary for PT8 Oficina 8
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87,0 °F / 74,0 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 118 ft² 4995 - 118 ft² - -
Wall Transmission 9 ft² 66 - 9 ft² 25 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 118 ft² 781 - 118 ft² 834 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 264 W 775 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 844 W 2701 - 0 0 -
People 8 1620 1640 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1094 82 0% 0 0
>> Total Zone Loads - 12032 1722 - 859 0
Zone Conditioning - 11950 1722 - -500 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 794 CFM 0 - 794 CFM 0 -
Ventilation Load 213 CFM 2891 5702 213 CFM 818 0
Supply Fan Load 794 CFM 294 - 794 CFM -294 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 15135 7424 - 24 0
Central Cooling Coil - 15135 7424 - 0 0
>> Total Conditioning - 15135 7424 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  52  of  70 


System Psychrometrics for PT8 Oficina 8
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

August DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 87,0 0,01728 213 400 2891 5702
Vent - Return Mixing Outlet 76,7 0,01265 794 750 - -
Central Cooling Coil Outlet 56,9 0,01045 794 750 15135 7424
Supply Fan Outlet 57,3 0,01045 794 750 294 -
Cold Supply Duct Outlet 57,3 0,01045 794 750 - -
Zone Air - 72,9 0,01096 794 878 11950 1722
Return Plenum Outlet 72,9 0,01096 794 878 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 12032 Cooling 11950 72,9 794 878 0 0

Hourly Analysis Program 5.11 Page  53  of  70 


System Psychrometrics for PT8 Oficina 8
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 213 400 -818 0
Vent - Return Mixing Outlet 60,9 0,01024 794 424 - -
Central Cooling Coil Outlet 60,9 0,01024 794 424 0 0
Supply Fan Outlet 61,3 0,01024 794 424 294 -
Cold Supply Duct Outlet 61,3 0,01024 794 424 - -
Zone Air - 62,0 0,01024 794 433 500 0
Return Plenum Outlet 62,0 0,01024 794 433 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -859 Deadband 500 62,0 794 433 0 0

Hourly Analysis Program 5.11 Page  54  of  70 


System Psychrometrics for PT8 Oficina 8
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: August DESIGN COOLING DAY, 1500
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0,018
5. Room Air

0,016

Specific Humidity ( lb/lb )


0,014
2

5 0,012
34
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  55  of  70 


System Psychrometrics for PT8 Oficina 8
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23 4
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  56  of  70 


Air System Sizing Summary for PT8 Oficina 9
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 9 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 150,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 1,1 Tons Load occurs at ................................................... Nov 1500
Total coil load .......................................................... 13,4 MBH OA DB / WB ...................................................... 80,0 / 71,0 °F
Sensible coil load ..................................................... 9,7 MBH Entering DB / WB ............................................. 74,7 / 63,9 °F
Coil CFM at Nov 1500 ............................................. 547 CFM Leaving DB / WB .............................................. 56,2 / 55,3 °F
Max block CFM ....................................................... 547 CFM Coil ADP ..................................................................... 54,2 °F
Sum of peak zone CFM .......................................... 547 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,726 Resulting RH ................................................................. 54 %
CFM/Ton ............................................................... 489,3 Design supply temp. ................................................... 54,0 °F
ft²/Ton ................................................................... 134,2 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 89,4 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise ...................................... 2,68 gpm

Supply Fan Sizing Data

Actual max CFM ...................................................... 547 CFM Fan motor BHP ........................................................... 0,07 BHP
Standard CFM ......................................................... 488 CFM Fan motor kW ............................................................. 0,06 kW
Actual max CFM/ft² ................................................. 3,65 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 118 CFM CFM/person .............................................................. 29,38 CFM/person
CFM/ft² ................................................................... 0,78 CFM/ft²

Hourly Analysis Program 5.11 Page  57  of  70 


Zone Sizing Summary for PT8 Oficina 9
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name .................................... PT8 Oficina 9 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 150,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 547 547 3,65 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 9,5 Dec 1400 0,9 150,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT8 Oficina 9 1 9,5 Dec 1400 547 0,9 150,0 3,65

Hourly Analysis Program 5.11 Page  58  of  70 


Air System Design Load Summary for PT8 Oficina 9
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 80,0 °F / 71,0 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 46 ft² 3405 - 46 ft² - -
Wall Transmission 188 ft² 1169 - 188 ft² 537 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 46 ft² 114 - 46 ft² 324 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 161 ft² 241 - 161 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 188 W 551 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 1920 - 0 0 -
People 4 810 820 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 821 41 0% 0 0
>> Total Zone Loads - 9031 861 - 861 0
Zone Conditioning - 8767 861 - -291 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 547 CFM 0 - 547 CFM 0 -
Ventilation Load 118 CFM 765 2820 118 CFM 509 0
Supply Fan Load 547 CFM 203 - 547 CFM -203 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 9735 3681 - 15 0
Central Cooling Coil - 9735 3681 - 0 0
>> Total Conditioning - 9735 3681 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  59  of  70 


System Psychrometrics for PT8 Oficina 9
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

November DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 80,0 0,01622 118 400 765 2820
Vent - Return Mixing Outlet 74,7 0,01177 547 751 - -
Central Cooling Coil Outlet 56,2 0,01018 547 751 9735 3681
Supply Fan Outlet 56,6 0,01018 547 751 203 -
Cold Supply Duct Outlet 56,6 0,01018 547 751 - -
Zone Air - 73,2 0,01055 547 847 8767 861
Return Plenum Outlet 73,2 0,01055 547 847 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 9031 Cooling 8767 73,2 547 847 0 0

Hourly Analysis Program 5.11 Page  60  of  70 


System Psychrometrics for PT8 Oficina 9
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 118 400 -509 0
Vent - Return Mixing Outlet 61,5 0,01024 547 436 - -
Central Cooling Coil Outlet 61,5 0,01024 547 436 0 0
Supply Fan Outlet 61,9 0,01024 547 436 203 -
Cold Supply Duct Outlet 61,9 0,01024 547 436 - -
Zone Air - 62,5 0,01024 547 445 291 0
Return Plenum Outlet 62,5 0,01024 547 445 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -861 Deadband 291 62,5 547 445 0 0

Hourly Analysis Program 5.11 Page  61  of  70 


System Psychrometrics for PT8 Oficina 9
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: November DESIGN COOLING DAY, 1500
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0,018
5. Room Air
1
0,016

Specific Humidity ( lb/lb )


0,014
2
0,012
5
34
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  62  of  70 


System Psychrometrics for PT8 Oficina 9
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23 4
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  63  of  70 


Air System Sizing Summary for PT8 Pasillo de Circulacion
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name ............. PT8 Pasillo de Circulacion Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 807,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 3,6 Tons Load occurs at ................................................... Aug 1500
Total coil load .......................................................... 42,8 MBH OA DB / WB ...................................................... 87,0 / 74,0 °F
Sensible coil load ................................................... 26,7 MBH Entering DB / WB ............................................. 78,6 / 67,1 °F
Coil CFM at Aug 1500 ........................................... 1263 CFM Leaving DB / WB .............................................. 56,6 / 55,7 °F
Max block CFM ..................................................... 1263 CFM Coil ADP ..................................................................... 54,2 °F
Sum of peak zone CFM ........................................ 1263 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,625 Resulting RH ................................................................. 56 %
CFM/Ton ............................................................... 354,5 Design supply temp. ................................................... 55,0 °F
ft²/Ton ................................................................... 226,5 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 53,0 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise ...................................... 8,56 gpm

Supply Fan Sizing Data

Actual max CFM .................................................... 1263 CFM Fan motor BHP ........................................................... 0,17 BHP
Standard CFM ....................................................... 1128 CFM Fan motor kW ............................................................. 0,14 kW
Actual max CFM/ft² ................................................. 1,57 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 482 CFM CFM/person .............................................................. 34,41 CFM/person
CFM/ft² ................................................................... 0,60 CFM/ft²

Hourly Analysis Program 5.11 Page  64  of  70 


Zone Sizing Summary for PT8 Pasillo de Circulacion
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Air System Information


Air System Name ............. PT8 Pasillo de Circulacion Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 807,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 1263 1263 1,57 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 20,7 Mar 1000 0,3 807,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT8 Pasillo de Circulaci 1 20,7 Mar 1000 1263 0,3 807,0 1,57

Hourly Analysis Program 5.11 Page  65  of  70 


Air System Design Load Summary for PT8 Pasillo de Circulacion
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87,0 °F / 74,0 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 46 ft² 1942 - 46 ft² - -
Wall Transmission 2 ft² 15 - 2 ft² 6 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 46 ft² 303 - 46 ft² 324 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 560 ft² 840 - 560 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 857 W 2519 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3228 W 10332 - 0 0 -
People 14 2835 2870 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1879 144 0% 0 0
>> Total Zone Loads - 20665 3014 - 330 0
Zone Conditioning - 19898 3014 - -2235 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1263 CFM 0 - 1263 CFM 0 -
Ventilation Load 482 CFM 6342 13033 482 CFM 2728 0
Supply Fan Load 1263 CFM 468 - 1263 CFM -468 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 26709 16046 - 25 0
Central Cooling Coil - 26709 16047 - 0 0
>> Total Conditioning - 26709 16047 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  66  of  70 


System Psychrometrics for PT8 Pasillo de Circulacion
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

August DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 87,0 0,01728 482 400 6342 13033
Vent - Return Mixing Outlet 78,6 0,01334 1263 626 - -
Central Cooling Coil Outlet 56,6 0,01034 1263 626 26709 16047
Supply Fan Outlet 57,0 0,01034 1263 626 468 -
Cold Supply Duct Outlet 57,0 0,01034 1263 626 - -
Zone Air - 73,3 0,01090 1263 765 19898 3014
Return Plenum Outlet 73,3 0,01090 1263 765 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 20665 Cooling 19898 73,3 1263 765 0 0

Hourly Analysis Program 5.11 Page  67  of  70 


System Psychrometrics for PT8 Pasillo de Circulacion
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:19

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 482 400 -2728 0
Vent - Return Mixing Outlet 61,6 0,01024 1263 414 - -
Central Cooling Coil Outlet 61,6 0,01024 1263 414 0 0
Supply Fan Outlet 62,0 0,01024 1263 414 468 -
Cold Supply Duct Outlet 62,0 0,01024 1263 414 - -
Zone Air - 63,9 0,01024 1263 422 2235 0
Return Plenum Outlet 63,9 0,01024 1263 422 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -330 Deadband 2235 63,9 1263 422 0 0

Hourly Analysis Program 5.11 Page  68  of  70 


System Psychrometrics for PT8 Pasillo de Circulacion
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: August DESIGN COOLING DAY, 1500
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0,018
5. Room Air

0,016

Specific Humidity ( lb/lb )


2 0,014

5
0,012
34
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  69  of  70 


System Psychrometrics for PT8 Pasillo de Circulacion
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:19

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23 4
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  70  of  70 