You are on page 1of 70

Instruction Manual MN013001EN

Series NRX with PXR – Type NF Low Voltage Power (Air)


Circuit Breaker Instruction Manual
Instructions Apply to:

Type NF Frame Series NRX


ANSI, UL1066, UL489/IEC IZMX16

Typical Drawout Circuit


Breaker and Cassette

Typical Fixed Circuit


Breaker (Rear Connect)

Typical Fixed Circuit Breaker


(Front Connect)
Table of Contents

SECTION 1: INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Qualified Personnel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
General Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Product Labeling and Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Breaker Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Drawout Breaker and Cassette. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fixed Circuit Breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

SECTION 2: RECEIVING, HANDLING, AND INSTALLATION. . . . . . . . . . . . . . . . . 11


Suggested Tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Circuit Breaker Unpacking and Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Storing Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Circuit Breaker Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Installing the Drawout Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Rejection Interlocks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Circuit Breaker Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Installing Fixed Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Operating Mechanism. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

SECTION 3: BREAKER GENERAL OPERATION CIRCUIT BREAKER


DESCRIPTION AND OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Basic Circuit Breaker Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Pole Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Operating Mechanism. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Manual Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Electrical Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Anti-pump Feature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

SECTION 4: CIRCUIT BREAKER FEATURES AND ACCESSORIES. . . . . . . . . . . . 20


Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Arc Chambers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Electronic Tripping System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Microprocessor-based Trip Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Rating Plugs (No Longer Required with PXR Trip Units). . . . . . . . . . . . . . . . . . . . . . . 21
Current Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
General Wiring Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Accessory Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Accessory Tray Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Left Accessory Tray. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Right Accessory Tray. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

ii Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Instruction Manual MN013001EN

Undervoltage Release (UVR). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24


Overcurrent Trip Switch (OTS). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Auxiliary Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Spring Release (SR). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Latch Check Switch (LCS). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Motor Operator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Mechanical Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

SECTION 5. DIMENSIONAL DRAWINGS FOR


INSTALLATION OF DRAWOUT CIRCUIT BREAKERS . . . . . . . . . . . . . . . . . . . . . . 27

SECTION 6: DIMENSIONAL DRAWINGS FOR


INSTALLATION OF FIXED CIRCUIT BREAKERS . . . . . . . . . . . . . . . . . . . . . . . . . . 40
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Fixed Circuit Breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

SECTION 7: INSPECTION AND MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . 59


General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Manual Operation Functional Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

SECTION 8: TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY . . . . . . . . . . . . 66

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com iii
Instruction Manual MN013001EN

WARNING CAUTION
The Warnings and Cautions included as part of the Do not store equipment on its back. This could result in
procedural steps in this manual are for personnel equipment damage.
safety and protection of equipment from damage. This
example of a typical Warning is intended to familiarize CAUTION
personnel with the style of presentation.
It is important to take care when placing a drawout circuit
WARNING breaker on its extension rails. If the circuit breaker is not
properly seated on the rails, the breaker could fall causing
Series NRX circuit breakers are provided with safety fea- equipment damage and/or bodily injury.
tures. Nevertheless, the voltages, currents, and power
levels available around operational equipment are CAUTION
extremely dangerous. Under no circumstances should
interlocks and other safety features be made inopera- Inspection and maintenance procedures should be carried
tive, as this may result in death, bodily injury, or prop- out only by personnel familiar with the hazards associated
erty damage. with working on power circuit breakers. Additionally, they
should become familiar with the specifics associated with
WARNING Series NRX circuit breakers as presented in this manual.

Series NRX circuit breakers should not under any cir-


cumstances be applied outside their nameplate ratings. ! IMPORTANT
Operation outside of these ratings could result in death, Please read and understand these instructions before
bodily injury, or property damage. attempting to unpack, install, operate, or maintain this equip-
ment. Study the breaker and its mechanism carefully before
WARNING attempting to operate it on an energized circuit.

Never attempt to disable any interlocks. Doing so could


result in an electrical fault that could result in death, ! IMPORTANT
bodily injury, and/or equipment damage. A circuit breaker stored for any length of time should be
operated a minimum of five times before it is placed in ser-
WARNING vice.

Failure to inspect, clean, and maintain circuit breakers ! IMPORTANT


can reduce equipment life or cause the equipment to The circuit breaker mechanism is interlocked such that
not operate properly under faulty conditions. This could charged closing springs are automatically discharged if the
result in equipment damage, bodily injury, or even circuit breaker is levered into or out of the cell. Discharge
death. takes place between the DISCONNECT and TEST positions.

WARNING ! IMPORTANT
Arc chutes and their cover plates must always be Different degrees of access to push-buttons on the front
secured properly in place before a breaker is installed in of the circuit breaker can be achieved through the use of
its compartment. Failure to do so could result in equip- optional accessory devices.
ment damage, bodily injury, or even death.

CAUTION ! IMPORTANT
Before doing any work, make sure a drawout breaker is
Do not attempt to lift a breaker or cassette with ordinary levered out to the TEST, DISCONNECT, or WITHDRAWN
crane hooks or chains. Damage to vital circuit breaker parts position. During the levering out and levering in of the cir-
could result. Use two appropriate lifting straps when using cuit breaker, be aware of any signs that would indicate that
any type of lifting device. the levering process is not working properly. If working on
a fixed circuit breaker, bus systems should be de-energized
CAUTION for convenience and safety. All circuit breakers should be
switched to the OFF position and the mechanism springs
Make certain that the cassette is properly mounted or discharged.
seated securely on a work table before attempting to have

!
the breaker fully extended on the cassette’s drawout rails.
Failure to comply could result in the cassette tipping for- IMPORTANT
ward resulting in equipment damage and/or bodily injury. Fixed breakers have an arc hood positioned over the arc
chutes/arc chambers that must be removed first. Refer to
IL01301014E for installation and removal instructions. After
the inspection, reinstall the arc hood.

iv Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 1: Introduction

Section 1: Introduction Safe Practices


To protect personnel associated with the installation, opera-
Purpose tion, and maintenance of this equipment, the following prac-
This instructional manual is intended to generally cover the tices must be followed.
installation, operation, and maintenance of Series NRXTM 1. Only qualified electrical personnel familiar with the
low voltage power (air) circuit breakers and drawout cas- equipment, its operation, and the associated hazards
settes. Basic dimensional information is provided for the should be permitted to work on, install, or operate the
installation of both the circuit breaker and cassette. equipment.
Refer to other documentation for more specific details. 2. Always be certain that the primary and secondary cir-
1. IL0131098EN – Operating Manual for Series NRX PXR cuits are de-energized or the circuit breaker is open and
20/25 Trip Unit removed to a safe work location before attempting any
maintenance.
2. AD013001EN – PXR 20/25 Time Current Curves
3. For maximum safety, only insert an open, completely
3. TD013001EN – Wiring Diagrams for PXR 20/25 assembled breaker into an energized cell.
4. Accessory field installation instruction leaflets (IL) dedi- 4. Always ensure that drawout circuit breakers are in one
cated to specific items are available for download at of their designed cell positions, such as CONNECT,
www.eaton.com/seriesnrx. TEST, DISCONNECT, or WITHDRAWN. A circuit breaker
permitted to remain in an intermediate position could
5. Visit www.eaton.com/seriesnrx for additional support
result in control circuits being improperly connected,
documentation.
resulting in electrical failures.

Safety Qualified Personnel


All safety codes, safety standards, and/or regulations must
For the purpose of operating and maintaining power circuit
be strictly observed in the installation, operation, and main-
breakers, a person should not be considered qualified if
tenance of this equipment.
the individual is not thoroughly trained in the operation of
the circuit breaker and how it interfaces with the assembly
WARNING in which it is used. In addition, the individual should have
The warnings and cautions included as part of the pro- knowledge of the connected loads.
cedural steps in this manual are for personnel safety For the purpose of installing and inspecting circuit breakers
and protection of equipment from damage. This exam- and their associated assembly, a qualified person should
ple of a typical warning is intended to familiarize per- also be trained with respect to the hazards inherent to
sonnel with the style of presentation. working with electricity and the proper way to perform such
work. The individual should be able to de-energize, clear,
! IMPORTANT and tag circuits in accordance with established safety prac-
tices.
Please read and understand these instructions before
attempting to unpack, install, operate, or maintain this
equipment. Study the breaker and its mechanism carefully General Information
before attempting to operate it on an energized circuit. The Series NRX low voltage power (air) circuit breaker uses
an electronic tripping system. It is designed, manufactured,
All possible contingencies that may arise during installation,
and tested for use in both switchboard and metal-enclosed
operation, or maintenance, and all details and variations
switchgear assemblies in keeping with UL® 1066/ANSI
of this equipment do not purport to be covered by these
C3750, UL 489, and IEC 60947-2 requirements. The Series
instructions. If further information is desired by purchaser
NRX circuit breakers are available in a variety of different
regarding a particular installation, operation, or maintenance
connection and mounting possibilities.
of particular equipment, contact the local Eaton representa-
tive. Continuous current rating from 800 - 1600 A and inter-
rupting capacities to 85 kA are available depending on the
WARNING applicable standard. The circuit breaker nameplate provides
complete rating information and should always be inspected
Series NRX circuit breakers are provided with safety fea- to ensure the information shown is in keeping with the
tures. Nevertheless, the voltages, currents, and power product ordered (Figure 1). All Series NRX circuit breakers
levels available around operational equipment are are 100 percent rated except for UL 489 rated breakers. All
extremely dangerous. Under no circumstances should are built and test in an ISO 9002 certified facility.
interlocks and other safety features be made inopera-
tive, as this may result in death, bodily injury, or prop- A series NRX non-automatic breaker is available in a fixed or
erty damage. drawout configuration, and designed in keeping with
IEC 60947-2, UL 1066, and UL 489.

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 1
Section 1: Introduction

The fixed configuration is designed for front/rear bus con- WARNING


nections. The drawout version, in conjunction with its
drawout cassette, is a through-the-door design having Series nrx circuit breakers should not, under any cir-
three breaker positions with the compartment door closed cumstances, be applied outside their nameplate ratings.
(CONNECT, TEST, DISCONNECT) and one position out of its Operation outside of these ratings could result in death,
compartment on extension rails (WITHDRAWN). bodily injury, or property damage.

Product Labeling and Identification


The circuit breaker nameplate, located on the right side of
the breaker, provides complete rating information and
should always be inspected to ensure the information
shown is in keeping with the product ordered (Figure 1).
Become familiar with the nameplate.

Figure 1.  Series NRX Nameplate Location.

NAS6163W
Air Circuit Breaker
Frame
Type NF
1600 Ampere Frame
3 Pole
50/60 Hz
Interrupting Ratings
RMS Symetrical Ampere
Ue Icu kA Ics kA
240~ 85 50
440~ 85 50
690~ 42 42
Uimp 8 kV Catagory B

Withstand Ratings
RMS Symetrical Ampere
Ue Icw kA (1 s)
240~ 42
440~ 42
690~ 42
Trip Unit Auxiliary Voltage = 24 Vm
Accessories
Motor Operator 110-125 Vm
Spring Release 110-127 V~, Vm
Latch Check Switch NONE
Shunt Trip #1 110-127 V~, Vm
Shunt Trip #2 NONE
UVR NONE
Auxiliary Switch NONE
Bell Alarm Sw/OTS NONE

P.O. #
G.O. #
Item #
Seq #
YYMMDD
Cat #
NAS6163WLNDABANENNDX

Enclosure Requirements
68D2555
Installation and Operating
Instructions
MN013001EN

2 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 1: Introduction

The circuit breaker can be identified by a 20-digit catalog number located on the name plate (Figure 2). The drawout cassette
can be identified by a 14-digit catalog number (Figure 2a). An overview of the Catalog number code is provided for refer-
ence.

Figure 2.  Series NRX with PXR Catalog Numbering System. (Continued on Next Page.)

Basic Device Selection Overcurrent Protection Breaker Options


(Position 1-8) (Position 9-11) (Position 12-20)
Positions 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Example N A S 6 1 6 3 W L N D A B A N 4 X N D X

Position 1 Breaker Frame Size Position Electronic Trip Unit Protection ZSI + COMM ARMS
9 & 10 Selection
N Type NF 630 to 1600 A
No Protection - Switch Disconnector
Position 2 Standard, Mechanism, Device
SW None
Q UL 1066, Stored Energy, Power Breaker
PXR20
Y UL 489, Stored Energy, Insulated case Breaker
LN High Load Alarm LI ZSI --
G IEC 60947-2 Stored Energy, Air Breaker - Global
LM Instantaneous Override LI ZSI W/Modbus --
A IEC 60947-2, Stored Energy, Air Breaker - China
2A Breaker Health Summary LSI ZSI --
Position 3, 4 Fault Current Rating
2B Standard CAM LSI ZSI W/Modbus --
S4 42 kA at 480 Vac UL or 415 Vac IEC Connection
2C LSIG+A ZSI --
S5 65 kA at 480 Vac UL or 415 Vac IEC Optional Modbus RTU
2D 50/60Hz LSIG+A ZSI --
S6 65 kA at 480 UL or 415 Vac IEC
2E LSIG+A ZSI ARMS
Position 5, 6 Frame Rating (Amps)
2F LSIG+A ZSI W/Modbus ARMS
07 630 (UEC Only)
PXR25
08 800
2P Advanced Protection LSI ZSI W/Modbus --
10 1000 (UEC Only)
2Q Monitoring features LSI ZSI W/Modbus ARMS
13 1250 (UEC Only)
2R CAM and Modbus RTU LSIG+A ZSI W/Modbus --
16 1600 (On NF: IEC Only) Standard
2S LSIG+A ZSI W/Modbus ARMS
Position 7 Poles, Phasing 50/60/400Hz capability
2T LSI ZSI W/Modbus --
3 3-Pole, ABC
2V LSI ZSI W/Modbus ARMS
4 4-Pole, NABC
2W LSIG+A ZSI W/Modbus --
Position 8 Mounting Configuration
2X LSIG+A ZSI W/Modbus ARMS
W Drawout
X Drawout – Optimized primary disconnects
Z Drawout , with 3 Form C Cell Switches
Y Drawout – Optimized primary disconnects, with 3 Form C
Cell Switches
B Fixed Mount Rear Connect, Mounting Bracket, with
Secondary Terminal
R Fixed Mount Rear Connect, Surface Mount, with Secondary
Terminal Row
T Fixed Mount Front Connect, Surface Mount, Cable Connect,
with Secondary Terminal Row
F Fixed Mount Front Connect, Mounting Bracket, Bus Connect,
with Secondary Terminal Row
S Fixed Mount Front Connect, Surface Mount, Bus Connect,
with Secondary Terminal Row

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 3

(Continued on Next Page)


Section 1: Introduction

Figure 2.  Series NRX with PXR Catalog Numbering System (Continued).

Position 11 In (Amps) – For PXR Position 14 Spring Release/Latch Check Switch (LCS)
1 200 N No Spring Release, No LCS
2 250 A 110-127 Vac/dc, No LCS
3 300 B 110-127 Vac/dc, With LCS
4 400 C 110-127 Vac/dc, External LCS
5 500 R 208-240 Vac/dc, No LCS
6 600 S 208-240 Vac/dc, With LCS
7 630 T 208-240 Vac/dc, External LCS
8 800 L 24 Vdc, No LCS
A 1000 P 24 Vdc, With LCS
B 1200 Q 24 Vdc, External LCS
C 1250 H 48 Vdc, No LCS
D 1600 J 48 Vdc, With LCS
Position 12 Shunt Trip K 48 Vdc, External LCS
N No Shunt Trip 1 60 Vdc, No LCS
A 110-127 Vac/dc 2 60 Vdc, With LCS
R 208-240 Vac/dc 3 60 Vdc, External LCS
L 24 Vdc Position 15 UVR, Second Shunt Trip
H 48 Vdc N None
S 60 Vdc A 110 - 125 Vac/dc, UVR
Position 13 Motor Operator R 208 - 240 Vac/dc, UVR
M Manually Operated L 24 Vdc UVR
B 110-127 Vac/dc H 48 Vdc UVR
W 110 - 125 Vdc S 60 Vdc UVR
T 208-250 Vac/dc 1 110 - 127 Vac/dc, Second Shunt Trip
P 220 - 250 Vdc 2 208 - 240 Vac/dc, Second Shunt Trip
L 24 Vdc 4 24 Vdc Second Shunt Trip
H 48 Vdc 8 48 Vdc Second Shunt Trip
S 60 Vdc 9 60 Vdc Second Shunt Trip
Position 16 Auxiliary Switches
E No Aux. Switches, No Label (Parent)
2 2 Form C, English
4 4 Form C, English
N None

4 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 1: Introduction

Figure 2.  Series NRX with PXR Catalog Numbering System (Continued).

Position 17 Trip Indicator and Bell Alarm/OTS, Secondary Terminal Position 19 Drawout Breaker Shipping, Fixed Breaker Terminals,
Blocks Door Frame Kit
N No Indicator, No OTS, Secondary Terminal Blocks Per Breaker D Drawout (or Parent) Breaker Shipping Alone, Without Door
Options Frame Kit, Without Terminals
X Trip Indicator Provided, No OTS, Secondary Terminal Blocks Per C Drawout Breaker in Cassette, No Shutters, No Terminals, With
Breaker Options Door Frame Kit
Z Trip Indicator Provided, 2 Form C OTS, Secondary Terminal Blocks K Fixed Breaker Rear Connect, No Terminals, Not Mounting Foot,
Per Breaker Options With Door Frame Kit
M Interlocked Trip Indicator Provided, No OTS, Secondary Terminal A Fixed Breaker Rear Connect, Short Vertical/Horizontal Terminals,
Blocks Per Breaker Options No Mounting Foot, With Door Frame Kit
Y Interlocked Trip Indicator Provided, 2 Form C OTS, Secondary B Fixed Breaker Rear Connect, No Terminals, No Mounting Foot,
Terminal Blocks Per Breaker Options With Door Frame Kit
1 No Indicator, No OTS, Full Compliment of Secondary Terminal E Fixed Breaker Rear Connect, Long Vertical/Horizontal Terminals,
Blocks No Mounting Foot, With Door Frame Kit
2 Trip Indicator Provided, No OTS, Full Compliment of Secondary F Fixed Breaker Rear Connect, With Short Vertical/Horrizontal
Terminal Blocks Terminals, With Mounting Foot, With Door Frame Kit
3 Trip Indicator Provided, 2 Form C OTS, Full Compliment of H Fixed Breaker Rear Connect, With Long Vertical/Horizontal
Secondary Terminal Blocks Terminals, With Mounting Foot, With Door Frame Kit
4 Interlocked Trip Indicator Provided, No OTS, Full Compliment of 1 Drawout Breaker in Cassette, No Shutters, Short Vertical/
Secondary Terminal Blocks Horizontal Terminals, With Door Frame Kit
5 Interlocked Trip Indicator Provided, 2 Form C OTS, Full 2 Drawout Breaker in Cassette, No Shutters, Long Vertical/
Compliment of Secondary Terminal Blocks Horizontal Terminals, With Door Frame Kit
4 Drawout Breaker in Cassette, Shutters, Short Vertical/
Position 18 Padlocking Operations Counter Horizontal Terminals, With Door Frame Kit

N No PB Covers No Counter 5 Drawout Breaker in Cassette, Shutters, Long Vertical/Horizontal


Terminals, With Door Frame Kit
A No PB Covers Counter Provided
9 Drawout Breaker in Cassette, Shutters, No Terminals, With
B PB Covers (Plastic/Plastic) No Counter Door Frame Kit

J PB Covers (Plastic/Plastic) Counter Provided Position 20 Future Use

K PB Covers (Metal/Metal) No Counter X All Product

L PB Covers (Metal/Metal) Counter Provided


5 PB Covers (Metal/Metal), Safe-Off No Counter
6 PB Covers (Metal/Metal), Safe-Off Counter Provided

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 5
Section 1: Introduction

Figure 2A.  Series NRX Type RF - Frame Cassette Catalog Numbering System.
NF Cassette Catalog Numbering System
Positions 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Position 1-2 Cassette Family and Breaker Frame Position 8 Door Frame Gasket and Rejection Kits
NQ UL 1066 N-Frame B Door Kit Included (Default)
NY UL 489 N-Frame Position 9 TOC Switches (Truck Operated Cell)
NG IEC 60947-2 N-Frame - Global N Not Included (Default)
NA IEC 60947-2 N-Frame - China Position 10 Shutters
Position 3-4 Continuous Ampere Range N Not Included (Default)
08 800 A (UL 1066) S Included
12 800 - 1200 A (UL 489) Position 11 Secondary Contact Terminals Installed
16 630 - 1600 A (IEC) N None
Position 5 Poles, Phasing (Facing Front of Breaker) F Full Complement
3 3-pole, ABC B Defined by Breaker
4 4-pole, NABC C Common Options
Position 6 Load Terminal Connections Position 12 Future Use
F With Flat Tapped Pads Only N None
G With Vertical/Horizontal Bus Adaptor Kit (Short Style) Position 13 Future Use
H With Front Connected Kit N None
N No Flat Tapped Pads or Cassette Stabs Inter Unit Only) Position 14 Cassette Shipping
Position 7 Arc Hood C Cassette Only
A Arc Hood Installed (Default) B Breaker Shipped in Cassette

Breaker Overview
Figures 3 through 6 highlight the main components that Fixed Circuit Breaker
make up a Series NRX breaker. A fixed circuit breaker is rigidly mounted in its structure with
no drawout feature. The circuit breaker is available in front
and rear-connected configurations (Figure 5).
Drawout Breaker and Cassette
A drawout circuit breaker is used in combination with a dra- The breaker can be mounted on a suitable horizontal mount-
wout cassette (Figures 3 and 4). Mounted on the drawout ing surface using left and right-side mounting feet. A stan-
breaker are the primary finger clusters and levering mecha- dard fixed circuit breaker is supplied with flat primary termi-
nism. These components are located on the breaker to nal pads on the rear of the breaker that will accommodate a
allow Users easy access when performing product inspec- variety of primary connection configurations.
tion or maintenance. The cassette provides all the neces-
sary drawout circuit breaker interfaces, including primary
and secondary connections. Standard flat terminal pads
on the rear of the cassette provide for a variety of primary
connection configurations. Optional primary adapters are
available for front and rear bus or cable connections. For
specific details and mounting instructions for primary adapt-
ers, refer to www.Eaton.com/seriesnrx.
Refer to Section 5 for mounting and installation dimensional
information. Electronic files of dimensional drawings for
customer use are available for download at www.eaton.
com/seriesnrx.

6 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 1: Introduction

Figure 3.  Typical NRX Type NF Drawout Circuit Breaker (Front and Rear Views).

3
4

2
1
3 6

4
1. Arc Chute Cover
5 2. Primary Shroud
3. Lifting Handle
4. Front Cover
5. Drawout Wheels
6. Primary Finger Cluster
8 7. Secondary Contacts
8. Levering Mechanism

NNote: Refer to Figure 6 for more visual details of front cover.

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 7
Section 1: Introduction

Figure 4.  Typical NRX Type NF Drawout Cassette (Front and Rear Views).

7 9

6
9
1

5 7

2
4 3
11

1. Drawout Extension Rail


2. Stationary Primary Contacts
3. Interlock Plate/Pins 10
4. Grounding (Earthing) Bar
5. Safety Shutters (Open)
6. Hand Lifting Indentation
7. Gas Ventilation Opening
8. Secondary Connectors
9. Secondary Wiring Contact Points
10. Primary Terminal Pad
11. One Typical Rear Bus Adapter

NNote: Refer to Figure 6 for more visual details of front cover.

8 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 1: Introduction

Figure 5.  Typical NRX Type NF Fixed Circuit Breaker (Rear Connected Type).

2 5
3

1
4

7
1. Arc Hood Baffle
2. Arc Hood
3. Secondary Contacts
4. Front Cover
5. Secondary Wiring Contact Points
6. Typical Rear Bus Adapter (Horizontally Mounted to
Primary Terminal Pad)
7. Typical Rear Bus Adapter (Vertically Mounted to
Primary Terminal Pad)

NNote: Refer to Figure 6 for more visual details of front cover.

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 9
Section 1: Introduction

Figure 6.  Typical NRX Type NF Drawout Circuit Breaker Front Cover.

1. Contact Status 15 1
2. Spring Status
3. Charging Handle
4. Nameplate 13 2
5. Manual ON
6. Operations Counter
7. Position Indicator
8. Levering Access Door
11 3
9. Frame Rating Module
10. FRM Battery Cover 4
11. Manual OFF
12. USB and Aux. Power Ports
13. Pop-out Trip Flag
14. Trip Unit 5
15. OFF Key Lock
12
16. ln Rating - LCD Display on Trip Unit
17. ln Rating - FRM Battery Cover 6

NNote: The ln Rating on the LCD and


FRM Battery Cover should 7
ALWAYS agree.
NNote: Frame Rating Module should 8
NOT be removed.

10
17

14

16

12

10 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 2: Receiving, Handling, and Installation

Section 2: Receiving, Handling, and Installation Figure 7.  Step 1.

Suggested Tools
●● Flat-blade and Phillips head screwdrivers
●● 3/8-inch levering tool or extension/ratchet
●● 3 mm Allen head screwdriver
●● 1/2 inch socket and ratchet or 1/2 inch wrench

Circuit Breaker Unpacking and Inspection


Inspect the shipping container(s) for obvious signs of exter-
nal damage. Record any observed damage for reporting to
the transportation carrier and Eaton. All reports and claims
should be as specific as possible and include the order num-
ber and other applicable nameplate information.
NNote: Also follow Step 1 when handling a separately
NNote: The outside of the circuit breakers shipping container shipped drawout cassette.
includes a transport “Tip-N-Tell” indicator alerting the
receiver as to whether or not the shipping container Step 2: Save all packing/shipping material and documenta-
was transported and handled in the required manner. tion for future shipments or breaker storage purposes.
Refer to Table 1 for details about the indicator before Step 3: Move the breaker to a convenient place for closer
removing the circuit breaker from its container. examination. Drawout breakers are provided with a lifting
handle on both sides to assist lifting. Repeat for a drawout
cassette. The cassette is provided with a lifting indentation
Table 1.  Transport Indicator. on each side.
Use an appropriate device to lift the breaker or cassette
(Table 2). If one is not available, it is recommended
Triangle that a minimum of two people be used to lift/move a
breaker or cassette.
NNote: Refer to Table 2 for additional precautions and lifting
procedures.

Blue Beads Figure 8.  Step 3.

Lifting
Handle
Triangle at top of indicator is Triangle at top of indicator has no
partially full or totally full of blue blue beads in it.
beads.
• Transport was not in keeping • Breaker container was not tilted or
with instructions (breaker con- overturned during transport.
tainer was tilted or overturned).
• Check breaker closely for dam-
age.

When ready to inspect and/or install a Series NRX circuit


Lifting
breaker, proceed with the following steps:
Area
Step 1: Carefully open the container and remove all packing/
shipping material and documentation.

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 11
Section 2: Receiving, Handling, and Installation

Table 2.  Suggested Lifting Procedures and Precautions.

(Upright Cassette) (Breaker in Cassette)

(Breaker Only)

NNote: When using an appropriate lifting device, attach the lifting harness in the locations shown in Table 2 that best fits
the circumstances.

12 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 2: Receiving, Handling, and Installation

Step 5: Repeat Step 4 for a drawout cassette. The cassette Table 3.  Approximate Weights.
is provided with a lifting indentation on each side.
Item Lbs Kg
Carefully place a breaker or cassette on a solid work surface
capable of handling their weight for examination (Table 3). Drawout Breaker, Three-pole 55 25
A drawout circuit breaker can also be examined while with- Drawout Breaker, Four-pole 72 33
drawn on the drawout extension rails of an already installed
cassette. Fixed circuit breakers already installed in an Fixed Breaker, Three-pole 45 20
assembly can be inspected in their installed location. Fixed Breaker, Four-pole 62 28
Drawout Cassette, Three-pole 32 15
Figure 9.  Step 5. Drawout Cassette, Four-pole 37 17

Lifting
Handle

Storing Circuit Breaker


Store a circuit breaker in its original shipping container with
contacts open and springs discharged. Keep it in a clean
dry place. Ensure there is ample air circulation and heat, if
necessary, to prevent condensation.

! IMPORTANT
A circuit breaker stored for any length of time should be
operated a minimum of five times before it is placed in ser-
vice.

CAUTION
Lifting
Area Do not store equipment on its back. This could result in
equipment damage.

Figure 10. 

CAUTION
Do not attempt to lift a breaker or cassette with ordinary
crane hooks or chains. Damage to vital circuit breaker parts
could result. Use two appropriate lifting straps when using
any type of lifting device.

CAUTION
Make certain that the cassette is properly mounted or (Circuit Breaker)
seated securely on a work table before attempting to have
the breaker fully extended on the cassette’s drawout rails.
Failure to comply could result in the cassette tipping for-
ward resulting in equipment damage and/or bodily injury.

(Breaker in Drawout Cassette)

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 13
Section 2: Receiving, Handling, and Installation

CAUTION Figure 12.  Step 2.

Make certain that the cassette is properly mounted or


seated securely on a work table before attempting to have
the breaker fully extended on the cassette’s drawout rails.
Failure to comply could result in the cassette tipping for-
ward resulting in equipment damage and/or bodily injury.

Circuit Breaker Inspection


All circuit breakers, once removed from their shipping con-
tainers, should be visually inspected for any obvious dam-
age. Check to make sure that the installed trip unit and
nameplate information match the equipment as ordered. All
circuit breakers should be operated as described in Section
3 prior to being put into service.

Installing the Drawout Circuit Breaker


In a structure equipped for a drawout circuit breaker, a
bolted-in cassette with movable, captive extension rails sup-
ports the circuit breaker.

CAUTION Step 3: Carefully place the circuit breaker on the extended


rails. Be certain that the circuit breaker’s metallic support
It is important to take care when placing a drawout circuit wheels (two on each side of the circuit breaker) are properly
breaker on its extension rails. If the circuit breaker is not seated on the extension rails.
properly seated on the rails, the breaker could fall causing
equipment damage and/or bodily injury.
Figure 13.  Step 3.

To install the drawout circuit breaker, proceed first with the


following three steps.
Step 1: Lift the drawout rails located on each side of the
drawout cassette all the way up until released. Each draw-
out rail is provided with a curved cutout to accommodate a
gloved hand.

Figure 11.  Step 1.

Keep in mind that all drawout circuit breakers are provided


with safety interlocks to prevent inserting circuit breakers
into incompatible drawout cassettes.

Extension
Rail

Step 2: Lower both rails down into their extended and


locked position.

14 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 2: Receiving, Handling, and Installation

Rejection Interlocks Figure 15.  DISCONNECT Position.


Series NRX drawout circuit breakers come in a variety of
continuous current and interrupting ratings. To prevent the
insertion of a drawout circuit breaker into a cell with which
it is incompatible, rejection interlock key plates are provided
for both the circuit breaker and the cassette. One key plate
is located on the bottom of the circuit breaker and one is
located on the floor of the cassette. Rejection pins must be
installed in both plates to complete the interlock scheme.
The switchboard builder is responsible for installing the
rejection pins in the appropriate pattern in the rejec-
tion plates on both the circuit breaker and cassette. A
rejection pin installation kit, including the instruction leaflet
IL01301006E, is supplied by the factory for this purpose.

WARNING
Ÿ Breaker in Cassette
Never attempt to disable any interlocks. Doing so could Ÿ Primary Connections not Made
result in an electrical fault that could result in death, Ÿ Secondary Connections not Made
bodily injury, and/or equipment damage.

Figure 16.  TEST Position.


Circuit Breaker Positioning
Series NRX drawout circuit breakers have four normal posi-
tions:
●● WITHDRAWN (Figure 14);
●● DISCONNECT (Figure 15);
●● TEST (Figure 16); and
●● CONNECT (Figure 17).

The WITHDRAWN position is outside the compartment on


the cassette’s drawout rails. The DISCONNECT, TEST, and
CONNECT positions are reached by means of the levering
mechanism and can be achieved with the assembly door
closed. Ÿ Breaker in Cassette
Ÿ Primary Connections not Made
Ÿ Secondary Connections Made
Figure 14.  WITHDRAWN Position.

Ÿ Breaker in Cassette
Ÿ Primary Connections not Made
Ÿ Secondary Connections not Made

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 15
Section 2: Receiving, Handling, and Installation

Figure 17.  CONNECT Position. Figure 19.  Step 3.

Ÿ Breaker in Cassette
Ÿ Primary Connections Made
Ÿ Secondary Connections Made

With the circuit breaker sitting solidly on the extension rails


in its WITHDRAWN position, proceed with the following
five steps to move the circuit breaker through its other posi- Step 4: The breaker is ready to be levered. With the circuit
tions. breaker OPEN. Rotate the levering tool clockwise to and
Step 1: Make sure the circuit breaker position indicator, through the different available positions (DISCONNECT,
located in the right lower portion of the circuit breaker, indi- TEST, CONNECT).
cates DISCONNECT (Figure 15). NNote: The position indicator on the lower right portion of
Step 2: If the indicator window indicates anything other the breaker indicates the position as each position is
than DISCONNECT, use the breaker’s 3/8-inch levering tool reached.
or 3/8-inch drive extension and rachet to get the circuit When the breaker reaches the CONNECT position, a
breaker in the proper levering position. Insert the levering hard stop is encountered. Discontinue levering to avoid
tool into its compatible front accessible fitting, and rotate damage due to torquing beyond the maximum of
it counterclockwise until DISCONNECT is indicated in the 15 ft-lb (20.4 Nm).
window.

Figure 18.  Step 2.

Step 3: Carefully push the circuit breaker into its compart-


ment until it stops. The extension rails can now be folded
up and latched

16 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 2: Receiving, Handling, and Installation

Figure 20.  Step 4. Installing Fixed Circuit Breaker


A fixed circuit breaker is solidly mounted in its structure
with no drawout feature. The circuit breaker is available in
both surface-mounted and rear-connected configurations
(Figure 21). A surface-mounted fixed circuit breaker is front
connected and mounted on a suitable verticle mounting
surface using the appropriate mounting hardware. Refer
to IL01301036E. Rear-connected fixed circuit breakers can
be mounted on a suitable horizontal or vertical mounting
surface using optional left- and right- side mounting feet. In
addition, front-connected fixed circuit breakers can also use
the mounting feet for mounting a breaker on a suitable verti-
cal surface. Refer to specific instruction details provided in
IL01301030E (Figure 22). Refer to Section 5 for breaker and
primary bus stab details and requirements.
Note: Full Connect = Hard Stop
Figure 21. Typical Mounting Configurations.

Step 5: To remove the circuit breaker from any position or


from the compartment completely, reverse the insertion
procedure just described in Steps 1 through 4 by rotating
the levering tool in a counterclockwise direction. When the
DISCONNECT position is reached, the circuit breaker will no
longer move out of the cassette as a result of rotating the
levering tool. At this point, the circuit breaker can be pulled
out of the cassette onto its drawout rails.

! IMPORTANT
The circuit breaker mechanism is interlocked such that
charged closing springs are automatically discharged if the
circuit breaker is levered into or out of the cell. Discharge
Rear Connected
takes place between the disconnect and test positions.

Surface Mounted

Figure 22.  Side-mounted Mounting Feet.

Right Side
Mounting
Foot

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 17
Section 3: Breaker General Operation Circuit Breaker Description and Operation

Operating Mechanism Section 3: Breaker General Operation Circuit


The Series NRX operating mechanism is a two-stage stored
energy trip-free mechanism. Energy is stored for a closing
Breaker Description and Operation
operation with sufficient energy remaining to open the circuit
breaker after a closing operation.
Introduction
All circuit breakers should be operated manually and/or elec- Series NRX low voltage circuit breakers are available in both
trically before they are put into service. This can be done drawout and fixed mounting configurations (Figure 3 and
during the installation process or some later date prior to Figure 4). All circuit breakers are available as three-pole or
startup. To perform this operational check, follow the proce- four-pole breakers with the available connection configura-
dures outlined in the next section entitled “Circuit Breaker tions and specific ratings dictated by the applicable stan-
Description and Operation”. dards (Table 4).
All features and accessories common to both the drawout
and fixed configurations are covered briefly in this section.
Unique features to either configuration are covered individu-
ally in Sections 4 and 5. Controls and indicators are function-
ally grouped on the front of the circuit breaker (Figure 6).

Table 4.  Series NRX Ratings and Configurations (Three-Pole and Four-Pole).
Applicable Standards
Ratings IEC 60947-2 ANSI/UL 1066 UL 489
Continuous Current 800 A, 1250 A, 1600 A  800 A 800 A, 1200A b
Interrupting Capacity c 85 kA/254 Vac 85 kA/240 Vac
85 kA/240/254 Vac 65 kA/508 Vac 65 kA/480 Vac
65 kA/415/435 Vac 35 kA/635 Vac 35 kA/600 Vac
42 kA/690/725 Vac
Short-time Withstand 42 kA d 42 kA 42 kA
Mechanical Operations e 20,000 20,000 20,000
Electrical Operations 10,000 10,000 10,000
Connection Configurations Drawout Drawout Drawout
Fixed Rear Connection Fixed Cable Connection Fixed Rear Connection
Fixed Front Connection Fixed Rear Connection Fixed Front Connection
Fixed Front Connection Fixed Front Connection

1 1600A open air, bus connection only.


2 100% in open air, 80% in enclosure.
3 All currents = Icu.
4 kA = Icw for 1 sec.
5 O/C = 1 operation.

18 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 3: Breaker General Operation Circuit Breaker Description and Operation

Basic Circuit Breaker Assembly Step 2: It takes approximately seven full downward strokes
Series NRX circuit breakers use a rigid frame housing con- to complete the charging process. It is possible to manually
struction. This construction provides high-strength structural recharge the spring immediately after closing the breaker,
properties, excellent dielectric characteristics, and arc track- before it has been tripped open. The status of the spring
ing resistance. (charged or discharged) is indicated in the mechanism spring
status window just above the pushbuttons.

Pole Units Figure 24.  Step 2.


Each pole unit has one primary contact assembly comprised
of a moving portion and a fixed portion. The exact design
configuration depends upon the breaker’s frame size.

Operating Mechanism
The Series NRX operating mechanism is a two-stage stored
energy trip-free mechanism. Energy is stored for a closing
operation with sufficient energy remaining to open the cir-
cuit breaker after a closing operation.

Manual Operation
On manually operated circuit breakers, the closing spring
can only be charged manually. To manually charge the
spring and operate the circuit breaker, proceed with the fol-
lowing three steps:
Step 1: Insert one finger in the curved recess behind the
charging handle and pull out and down.
Step 3: Standard manually operated circuit breakers are
Figure 23.  Step 1. closed and opened by hand using the Manual ON and
Manual OFF buttons located on the front of the circuit
breaker. To perform either operation, press and release
the appropriate button. The status of the contacts (open or
close) is indicated in the Contact Status Window just above
the pushbuttons on the front of the breaker.

Figure 25.  Step 3.

Optional electrically operated accessories are available to


automatically close/trip a manually operated breaker.

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 19
Section 4: Circuit Breaker Features and Accessories

Electrical Operation Section 4: Circuit Breaker Features and


The springs on an electrically operated circuit breaker are
normally charged automatically through the use of an electri- Accessories
cal operator. The springs can, however, be charged manual-
ly as just described in the last section. Electrically operated
circuit breakers can also be manually closed and opened Introduction
through the use of the front mounted ON and OFF buttons. Series NRX low voltage circuit breakers are available in both
An electrically operated circuit breaker can be equipped with drawout and fixed mounting configurations (Figure 3 and
an optional spring release (closing coil) to close the circuit Figure 5). All circuit breakers are available as three-pole or
breaker remotely. The breaker can also be equipped with a four-pole breakers with the available connection configura-
shunt trip (opening coil) to open the breaker remotely. tions and specific ratings dictated by the applicable stan-
dards.

!
All features and accessories common to both the drawout
IMPORTANT and fixed configurations are covered briefly in this section.
Different degrees of access to pushbuttons on the front Details and installation instructions on trip units and indi-
of the circuit breaker can be achieved through the use of vidual accessories are covered in their respective IL’s.
optional accessory devices.
Arc Chambers
Anti-pump Feature An arc chamber, one for each pole, includes an arc chute
Series NRX circuit breakers have both mechanical and elec- mounted around a set of primary contacts. The chambers
trical anti-pump features. If the circuit breaker is closed on act to quench arcs and channel gases up and out of the
a fault condition and trips open while the CLOSE signal is breaker during interruption.
maintained (using either the mechanical pushbutton or the
electrical close coil), it will not make a subsequent attempt
to close until the close command is removed and reapplied. Electronic Tripping System
Series NRX circuit breakers use a three-part tripping system:
NNote: If the close signal is applied prematurely (before the
breaker is completely charged and latched), the close
●● Microprocessor-based trip unit;
command will be ignored until it is removed and ●● Rogowski coil type current sensors; and
reapplied.
For electrical closing, a Latch Check Switch (LCS) ●● Trip actuator.
option is available that will block the application of All three parts of the tripping unit are discussed here in gener-
the electrical close command until the breaker is al. For detailed information pertaining to the different available
ready. trip unit models and other breaker or accessory information,
refer to Eaton’s website www.eaton.com/seriesnrx.
See important Frame Rating Module information on next
page regarding the tripping system.

Microprocessor-based Trip Unit


Series NRX circuit breakers utilize the PXR family of elec-
tronic trip units whose main features are summarized in
Table 5. The Digitrip 1150 is also still available for purchase.
The electronic trip units are self-powered devices (Figure
25). The protection settings can be set from the front.
When the circuit breaker is closed, no external power is
required to operate their protective systems. Current signal
levels and the control power are derived from the current
sensors. All trip unit devices are true RMS current sensing
devices.
A functional local test of the trip unit’s primary electronic
circuitry and the circuit breaker’s mechanical tripping action
can be verified through the trip unit’s USB receptacle
(Figure 6).

20 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 4: Circuit Breaker Features andAccessories

Figure 26.  Installed PXR 520 Trip Unit. Current Sensors


Three Rogowski coil type current sensors are installed on
the load terminals at the bottom rear of the circuit breaker.
The sensors furnish the trip unit with a signal and the ener-
gy required to trip the circuit breaker.
A neutral current sensor is available for customer installa-
tion, and must be ordered separately.

Frame Rating Module


The frame rating module is a component that is used with
the trip unit to establish the maximum RMS current that can
be continuously carried. The frame rating module, mounted
just behind the trip unit, is intended not to be replaced and
stores pertinent data related to the ratings, manufacturing
and health of the breaker frame. (Figure 6).
Frame rating modules installed on Series NRX with
PXR air circuit breakers SHOULD NOT BE REMOVED. 
The frame rating module battery cover (see Figure 6)
marked with the In rating, should not be changed without
Table 5.  Series NRX Trip Units. proper reprogramming of the trip unit.  The In rating pro-
grammed from the factory is constantly displayed in the
Functions PXR20 PXR 25 lower left hand corner of the LCD screen when power is
applied to the trip unit (see Figure 6).  The LCD screen In
LSIG Protection Yes Yes
rating reflects the actual In rating of the breaker, whereas
Disable (I) Yes Yes the frame rating module battery cover In rating is for
GF Protection Yes Yes informational purposes only when the LCD has no control
power.  The In rating displayed on the LCD screen and In
GF Alarm Yes Yes rating printed on the frame rating module battery cover
Display Yes Yes MUST ALWAYS AGREE.  See IL0131098EN for more infor-
mation. 
Programmable No No
Please contact your Eaton sales representative for details
Metering Yes Yes on proper In rating reprogramming of the trip unit. 
Power/Energy No Yes
Power Quality No Yes Trip Actuator
Communication Yes Yes The low-energy trip actuator is a small electromagnetic
device that provides the necessary mechanical force to initi-
ate the tripping action of the circuit breaker. The electronic
trip unit provides a pulse to the coil of the trip actuator,
allowing the mechanical tripping action to take place. The
Rating Plugs (No Longer Required with PXR Trip trip actuator is reset by the operating mechanism.
Units)
Series NRX circuit breaker PXR trip units no longer require
a fixed type rating plug. The continuous current (In) rating is Fixed High Instantaneous Non-adjustable Trip
programmed in the frame rating module. Series NRX circuit breakers have a fixed instantaneous non-
The (In) rating is shown on the trip unit’s display and printed adjustable setting. This value is set at 96 kA peak current
on the lower right corner of the trip unit. for 42 kA withstand circuit breakers. This setting is always
active, regardless of the instantaneous setting.
The (In) rating displayed and programmed in the frame rat-
ing module will be equal to or less than the maximum rated
current (Iu) as listed on the name plate in (Figure 1).

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 21
Section 4: Circuit Breaker Features andAccessories

High Instantaneous Trip Table 6.  Series NRX Wiring Index (TD013001EN).
Series NRX circuit breakers have a high instantaneous trip Wiring Topic
feature. A signal is transmitted back to the trip unit when
the rating of the circuit breaker is exceeded. The result is an Zone Interlock Wiring Figure 1
instantaneous trip by the circuit breaker. This high instan- Ground Fault Residual 3-Phase 4-Wire Figure 2
taneous trip option permits Series NRX circuit breakers to
be applied where a higher than acceptable fault is possible, Source Ground Fault Sensing Figure 3
while selectivity up to the high instantaneous trip value is Zero Sequence Ground Fault Sensing Figure 4
maintained.
PXR Alarm Wiring Figure 5
INCOM Communication Module (ICAM) Figure 6
Non-Automatic Circuit Breaker
MODBUS Communication Module (MCAM) Figure 7
Series NRX is available in a non-automatic configuration. It
is derived from the corresponding NRX automatic breaker, PROFIBUS Communication Module (PCAM) Figure 8
less the trip unit, Rogowski coil type current sensors, and ETHERNET Communication Module (ECAM) Figure 9
the high instantaneous trip feature. The overall dimensions
and the capability of mounting most accessory items are Maintenance Mode Wiring Figure 10
maintained. Non-automatic breakers are tested in keeping Communication Control (SR and ST Wiring) Figure 11
with UL 1066, IEC 60947-2 and UL 489 requirements.
Undervoltage Release Figure 12
Circuit Breaker Control- Type NF Frame Figure 13
Secondary Contacts and Connection Diagrams
Circuit Breaker Control -Type RF Frame Figure 14
A maximum of 56 secondary wiring connection points are
available, each dedicated to a specific function. The num- Series NRX NF Mounted Breaker (with external PT Figure 15
ber of secondary blocks mounted depends on a number Module)
of considerations, such as whether the circuit breaker is Typical Breaker Master Connection Diagram - NF Figure 16
electrically or manually operated and how many features
are required. All necessary customer secondary connection Typical Breaker Master Connection Diagram- RF Figure 17
point are accessible without removing the breaker’s front
cover. Each connection point is permanently identified.
The customer secondary wiring contact point map is iden-
tifiable on the product (Figure 27). For a drawout breaker,
this label is on the arc hood of the drawout cassette (Figure
3). For a fixed mount breaker, this is a label applied to the
top of the front cover of the breaker (Figure 5).
The connection diagram and specific secondary contact
information for the Series NRX circuit breakers using PXR
trip units can be found in the Series NRX Wiring Diagram
document TD013001EN.

Figure 27.  Secondary Point Identification.

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55
+ +
MODBG
MODBB MODBA
ACCY2

ACCY5

ACCY7
CMM1

CMM3
ZCOM
ALMC

ALM2
OT1C

OT1B

PTVA

PTVC
+24V
UV1

SR1
EO1
ST1

ARMSIN ZIN

66B2589H04
N1

G1

C1

B1

C2

C3

B3

C4
-
UV2 -

ACCY1

ACCY3

ACCY4

ACCY6
CMM2

CMM4
OT1M

AGND
ALM1

ALM3

ZOUT

PTVN
PTVB

SR2
EO2
ST2

N2

G2

SC

A1

B2

A2

A3

B4

A4

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56

PXR TRIP UNITS

22 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 4: Circuit Breaker Features andAccessories

General Wiring Notes Table 7.  Customer Wiring Details.


1. Each contact block on the Secondary Terminal Block consists
of four contacts (Figure 28). A possible 14 terminal blocks will Type of Connection Tension Clamp Connection
provide 56 contact points for the type NF frame.
Clamping Range, rated connection 0.05 - 4 mm2
(min-max)
Figure 28.  Secondary Point Identification. Conductor cross section , solid or flexible 0.5 - 4 mm2
(min-max)
Conductor connection cross-section AWG 26 - 12 AWG
(min-max)
Stripping Length 8 mm (0.31”)
Gauge to IEC 60947-1 A3
Conductor cross section, flexible plus 0.5 - 2.5 mm2
plastic DIN 46228/1, rated connection
(min-max)
Cross-section for connected conductor, 0.5 - 2.5 mm2
finely stranded with wire-end ferrules
Fixed Terminal Block Drawout Terminal Block and plastic collars DIN 46228/4, rated
connection, (min-max)

2. Drawout circuit breakers use Style 67C3246 contact


blocks that mount onto an insulated support frame.
10. For secondary contacts, odd numbers should be treat-
3. Fixed mounted circuit breakers use Style 67C3247 con- ed as positive voltage for any accessory. This will not
tact blocks that mount onto an insulated support frame. apply for AC ratings
The customer tension connectors are at an angle.
11. Reference tool for removing leads from secondary con-
4. Customer wiring is done using a tension clamp termina- tact connector plug – 68D3288 Extraction Tool (Figure
tion on each contact. 31).
5. Contact blocks are individually mounted and hence con- NNote: The connector plug must be oriented as shown in
tact positions may be empty depending on accessories Figure 30 before making the connection.
and options ordered.
6. The tension clamp terminals will support solid or flex- Figure 29.  Accessory Plug and Crimp Contact.
ible conductors, #12/4 mm2 through #26/0.5 mm2 AWG
and are rated for 600 V, 10 A.
7. The recommended wire strip length is 8 mm (0.31”).
8. The tension clamp terminals also support finely strand-
ed conductors with wire-end ferrules and plastic collars
DIN 46228/4, rated connection.
9. The two-point blue plugs house two female crimp con-
tacts, Stlye 67C3249, with the odd assigned numbers
having the coded rib feature on the blue plug (Figure
30).
NNote: Note that the connector plug must be oriented as
shown in Figure 29 before making the connection.

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 23
Section 4: Circuit Breaker Features andAccessories

Figure 30.  Extraction Tool in Use. Accessory Tray Devices


Certain accessory devices are mounted in a mounting tray.
The tray is then installed in a left- or right-hand slot located
in the upper left- and right-hand sides of the circuit breaker
(Figure 30 and Figure 31).

Figure 32.  Right Accessory Tray.

Connector Terminal
Plug Extraction
Tool

Accessory Devices
A variety of accessory devices are available for use with
Series NRX circuit breakers. Unless otherwise stated, they
are all considered optional devices in the sense that they
are not provided as standard on a manually operated cir-
cuit breaker. Available accessories are discussed in general
terms. For more detailed information and/or installation
instructions, refer to individual instruction leaflets dedicated
to individual items.
Series NRX circuit breaker accessories are designed to be
plug-and-play and can be field installed. The accessories fall Left Accessory Tray
into one of three categories: The left accessory tray will accommodate a maximum of
●● Accessory tray devices; four devices as follows:
●● Other internal electrical devices; and ●● Zero, one, or two shunt trips (ST);
●● Mechanical devices. ●● Zero or one undervoltage release (UVR);
●● Combination (one ST and one UVR); or
Figure 31.  Left Accessory Tray. ●● Zero or two overcurrent trip switches (OTS).

Right Accessory Tray


The right accessory tray will accommodate up to six 2a/2b
auxiliary switch combinations.
●● Two sets of two switches

●● One set of two switches

Shunt Trip (ST)


The shunt trip opens the circuit breaker instantaneously
when its coil is energized by a voltage input.

Undervoltage Release (UVR)


The undervoltage release opens the circuit breaker when
its supply voltage falls into the range of 35–70% of rated
voltage. If the release is not energized to 85% of its supply
voltage, the breaker cannot be closed electrically or manu-
ally.

24 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 4: Circuit Breaker Features andAccessories

Overcurrent Trip Switch (OTS) Mechanical Devices


An overcurrent trip switch (bell alarm) provides an electri- The following are optional mechanical type accessories:
cal indication when a circuit breaker trips as a result of the
trip unit reacting to an overcurrent condition. Opening as a
●● Pop-out trip indicator, non-interlocked and interlocked;
result of a circuit breaker’s manual open button, shunt trip, ●● Operations counter;
or undervoltage release does not cause the overcurrent trip
switch to operate. Overcurrent trip switches are available in ●● Off key lock;
two switch combinations only. ●● Pushbutton cover;
●● Prevent close cover;
Auxiliary Switch
An auxiliary switch provides remote electrical indication if
●● Lockout cover;
the circuit breaker is open or closed. Each switch has one ●● Cassette safety shutters;
normally open (“a”) and one normally closed (“b”) type con-
tact. Auxiliary switches are available in two switch combina- ●● Door escutcheon;
tions only. ●● IP55 waterproof cover; and

Other Internal Electrical Devices ●● Mechanical interlock.


There are three types of internally mounted electrical devic-
es: Non-interlocked Pop-out Mechanical Trip Indicator
●● Spring release; A non-interlocking red, pop-out mechanical trip indicator,
located to the right of the trip unit on the breaker’s front
●● Latch check switch; and
faceplate (Figure 6), operates by releasing and popping out
●● Motor operator. any time the breaker trips due to an overcurrent condition.
It will not prevent the breaker from being reclosed. The indi-
cator is reset manually by pushing it back in.
Spring Release (SR) An optional overcurrent trip switch (bell alarm) can be used
The spring release (closing coil) remotely closes the circuit in conjunction with the mechanical trip indicator. The over-
breaker when the coil is energized by a voltage input. When current trip switch operates off the position of the mechani-
the spring release is used in conjunction with a latch check cal trip indicator, and is reset when the indicator is reset.
switch, the closing spring must be fully charged and the trip
latch reset (not held in the tripped position) for the SR to
operate. If these conditions are not met, the close signal Interlocked Pop-out Mechanical Trip Indicator
will be ignored until it is removed and re-applied.
An interlocked, red, pop-out mechanical trip indicator is an
optional feature. It is located in the front of the breaker
near the top and to the right of the trip unit (Figure 6). It
Latch Check Switch (LCS) operates by releasing and popping out any time the circuit
A latch check switch indicates when the circuit breaker is breaker trips due to an overcurrent condition.
“ready to close.” Two versions of the LCS are available.
1. The LCS wired to the spring release will not permit acti-
vation of the spring release until the circuit breaker is NNote: The interlocked mechanical trip indicator will prevent
fully charged and the trip latch is reset. the breaker from being reclosed until the red, pop-
out indicator is reset or pushed back in.
2. The LCS used for remote indication consists of one
Form C contact wired to the circuit breaker secondary The indicator is reset manually by pushing it back in. If the
contacts for integration into external control schemes. interlocked indicator is not reset, the circuit breaker will not
close until the indicator is pushed back in.
NNote: Wiring the LCS for remote indication directly in series with
the SR accessory is not recommended as this will override An overcurrent trip switch (bell alarm), discussed later in this
the “anti-pump” feature. Wiring the latch check switch section, that operates off the position of the mechanical trip
for remote indication directly in series with the spring indicator is also available.
release accessory is not recommended as this will
override the “anti-pump” feature
Operations Counter
The operations counter is a mechanical device used to pro-
Motor Operator vide a record of the number of circuit operations. It can be
A motor operator is an electric motor assembly internally viewed through the breaker’s front cover (Figure 6).
mounted in the circuit breaker. It charges the closing springs
electrically for remote or local operation. The motor operator
can be factory or field installed.

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 25
Section 4: Circuit Breaker Features andAccessories

Off Key Lock Table 8.  Series NRX Publications


The off key lock secures the circuit breaker in the OFF posi- Publication
tion. It can be viewed through the front cover (Figure 6). Description Number Frame
The customer supplies the key lock. The provisions available
are for Kirk, Castell, Ronis, and CES. IL for Drawout Circuit Breaker Cassette IL01301006E NF and RF
Rejection Interlock
Series NRX with PXR – Instructions for IL0131096EN NF
Pushbutton Cover Auxiliary Switch
Padlockable covers are available to limit access to the ON
Series NRX with PXR - Instructions for IL0131087EN NF and RF
and OFF pushbuttons.
Undervoltage Release, Shunt Trip, and
Overcurrent Trip Switch
Safe-off Pushbutton Cover Series NRX with PXR - Instructions for IL0131088EN NF and RF
When padlocked, it maintains the OFF button in the actu- Spring Release, Latch Check Switch,
ated position, which prevents closure of the breaker. and Motor Operator
IL for Operation Counter IL01301011E NF
IL for Door Escutcheon and Gasket Kit IL01301012E NF and RF
Cassette Safety Shutters
IL for Drawout Cassette IP20 Safety IL01301013E NF
Automatically operated insulating type safety shutters
Shutters
(Figure 4) are available for use with the drawout cassette to
cover the fixed primary contacts when the circuit breaker is IL for Fixed Breaker Arc Hood IL01301014E NF
not in the CONNECT position.
IL for Fixed Breaker Primary Adapters IL01301015E NF
IL for Drawout Breaker Primary IL01301016E NF
Door Escutcheon Adapters
The door escutcheon is a molded frame used to seal the IL for Drawout Levering (Racking) IL01301018E NF
space between the circuit breaker and the compartment Mechanism
door cutout. It is supplied with a mounting gasket. Refer to IL for Mechanical Pop-Out Indicator IL01301019E NF
IL01301012E for installation information. and Interlocked Indicator
IL for Breaker and Cassette Interphase IL01301021E NF
Barriers
IP55 Dust and Water Resistant Cover
A hinged dome-shaped waterproof cover attaches to the IL for Cassette Extension Rails IL01301025E NF
metal compartment door to provide waterproof protection IL for Mounting Feet IL01301030E NF
for the circuit breaker.
Series NRX with PXR – Instructions IL0131089EN NF and RF
for Source Ground and Zero Sequence
Ground Sensor
Mechanical Interlock
Series NRX with PXR - Instructions for IL0131090E NF
Mechanical interlocks are available to interlock the closing of Neutral Current Sensor - Type NF
two or three Series NRX circuit breakers. The mechanical
interlock holds one or more circuit breakers tripped (pre- IL for INCOM Communications Adapter IL01301033E NF and RF
vents closure) when others are closed. Consult Eaton for Module
details. Series NRX with PXR - Instructions IL0131091EN NF and RF
for Modbus Communications Adapter
Module (MCAM)
Series NRX with PXR - Instructions for IL0131092EN NF and RF
PROFIBUS DP Communications Adaptor
Module (PCAM)
IL for Surface Mount IL01301036E NF
Series NRX with PXR - Instructions for IL0131093EN NF and RF
Secondary Terminal Blocks
IL for IP55 Cover IL01301038E NF and RF
IL for Kirk Key Lock IL01301039E NF and RF
IL for Ronis Key Lock IL01301040E NF and RF
IL for Pushbutton Cover Kit IL01301041E NF

26 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 5. Dimensional Drawings for Installation of Drawout Circuit Breakers

Table 8.  Series NRX Publications (Continued) Section 5. Dimensional Drawings for
Publication Installation of Drawout Circuit Breakers
Description Number Frame
Series NRX with PXR - Instructions for IL0131097EN NF
Cassette Cell Switch - Type NF General
IL for CES Key Lock IL01301049E NF and RF Section 3 discussed topics and features common to all
Series NRX circuit breakers, no matter what the mounting
IL for Castell Key Lock IL01301050E NF and RF configuration or type. In this section, features unique to the
IL for PXR 20/25 IL0131098EN NF and RF drawout type circuit breaker and drawout cassette not cov-
ered elsewhere are discussed.
IL for Ethernet Communications IL01301052E NF and RF
Adapter Module
IL for Drawout Circuit Breaker 2-Way IL01301069E NF Drawout Cassette
Cable Interlock Kit A drawout circuit breaker is used in combination with a
IL for Drawout Circuit Breaker 3-Way IL01301070E NF drawout cassette (Figure 4). The cassette provides all the
Cable Interlock Kit necessary drawout circuit breaker interfaces, including
automatic primary and secondary connections. Standard flat
IL for Fixed Circuit Breaker 2-Way IL01301071E NF terminal pads on the rear of the cassette provide for a vari-
Cable Interlock Kit ety of primary connection configurations. Optional primary
IL for Fixed Circuit Breaker 3-Way IL01301072E NF adapters are available for front and rear bus or cable connec-
Cable Interlock Kit tions. For specific details and mounting instructions, refer to
IL01301016E.
IL for Cassette Door Interlock IL01301073E NF
PT Module IL01301074E NF and RF
Refer to Figure 33 through Figure 44 for selected mounting
and installation dimensional information. Complete dimen-
IL for Time Delay Undervoltage Module IL5721B33 NF and RF sional and installation drawings are available from www.
PXR 20/25 Time Current Curves AD013001EN NF and RF eaton.com/seriesnrx.

Series NRX with PXR - Circuit Breaker TD013001EN NF and RF


Wiring Diagrams

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 27
Section 5. Dimensional Drawings for Installation of Drawout Circuit Breakers

Figure 33.  Three-pole Drawout Cassette - Rear/Top Views in Inches (mm).

M8 x 1.25 Tapped
0.35-in Max. Thread
Depth from Copper
Surface

Copper
6 Places Surface

Alternate Mounting
Locations.
Must Use Reduced Head
Height Hardware at These
Locations

28 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 5. Dimensional Drawings for Installation of Drawout Circuit Breakers

Figure 34.  Three-pole Drawout Cassette - Side Views CONNECTED and TEST Positions in Inches (mm).

90˚ Travel
(10˚ Free Travel)
(80˚ Charge Stroke)

CONNECTED Position

TEST Position

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 29
Section 5. Dimensional Drawings for Installation of Drawout Circuit Breakers

Figure 35.  Three-pole Drawout Cassette - Side Views DISCONNECTED and WITHDRAWN Positions in Inches (mm).

DISCONNECTED Position

WITHDRAWN Position

30 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 5. Dimensional Drawings for Installation of Drawout Circuit Breakers

Figure 36.  Three-pole Drawout Cassette—Top/Side Views with Horizontal Universal Bus Adapters in Inches (mm).

Recommended
Barrier

Recommended
Barrier

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 31
Section 5. Dimensional Drawings for Installation of Drawout Circuit Breakers

Figure 37. Three-pole Drawout Cassette - Top/Side Views with Vertical Universal Bus Adapters in Inches (mm).

Recommended
Barrier

Recommended
Barrier

32 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 5. Dimensional Drawings for Installation of Drawout Circuit Breakers

Figure 38.  Three-pole Drawout Cassette—Front View Door and Cassette Cutout Details in Inches (mm).

8.39 Ø 0.17
(213,1) (4,3)

Cassette
Sheet Metal

3.25
(82,5)

4.00 12.22
(101,6) (310,4)

3.25
(82,5)

0.86
(21,8)
2.72 4.00 2.20 0.53
(69,2) (101,6) (55,8) (13,4)

9.00
(228,6)
4.50
(114,3) Ø 0.38
(9,7)

3.75
(95,3)

9.86 7.50
(250,5) (190,5)

8.75
(222,3)

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 33
Section 5. Dimensional Drawings for Installation of Drawout Circuit Breakers

Figure 39.  Four-pole Drawout Cassette—Rear/Top Views in Inches (mm).

M8 x 1.25
Tapped
0.35 in Max.
Thread Depth
from Copper
Surface

Copper
Surface
6 Places

6x Ø0.32 (8.1)
Alternate Mounting Locations.
Must Use Reduced Head Height
Hardware at These Locations.

34 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 5. Dimensional Drawings for Installation of Drawout Circuit Breakers

Figure 40.  Four-pole Drawout Cassette—Top/Side Views with Horizontal Universal Bus Adapters in Inches (mm).

Recommended
Barrier

Recommended
Barrier

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 35
Section 5. Dimensional Drawings for Installation of Drawout Circuit Breakers

Figure 41.  Four-pole Drawout Cassette—Top/Side Views with Vertical Universal Bus Adapters in Inches (mm).

Recommended
Barrier

Recommended
Barrier

36 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 5. Dimensional Drawings for Installation of Drawout Circuit Breakers

Figure 42.  Four-Pole Drawout Cassette—Side Views CONNECTED and TEST Positions in Inches (mm).

90o Travel
(10o Free Travel)
(80o Charge
Stroke)

CONNECTED Position

TEST Position

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 37
Section 5. Dimensional Drawings for Installation of Drawout Circuit Breakers

Figure 43.  Four-pole Drawout Cassette - Side Views DISCONNECTED and WITHDRAWN Positions in Inches and (mm).

DISCONNECTED Position

WITHDRAWN Position

38 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 5. Dimensional Drawings for Installation of Drawout Circuit Breakers

Figure 44.  Four-pole Drawout Cassette—Front View Door and Cassette Cutout Details in Inches (mm).

8.39 Ø 0.17
(213,1) (4,3)

Cassette
Sheet Metal

3.25
(82,5)

4.00 12.22
(101,6) (310,4)

3.25
(82,5)

0.86
(21,8)

2.72 4.00 2.20 0.53


(69,2) (101,6) (55,8) (13,4)

11.75
(298,5)
5.88
(149,2)

Ø 0.38
(9,7)

3.75
(95,6)

9.86 7.50
(250,5) (190,5)

11.50 4P - Front View Cassette Cut Out Detail


(292,1)

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 39
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Section 6: Dimensional Drawings for Figure 45.  Surface Mounted.


Installation of Fixed Circuit Breakers

Arc
General Hood
Section 3 discussed topics and features common to all
Series NRX circuit breakers, no matter what the mounting
configuration or type. In this section, features unique to the
fixed configuration not covered elsewhere are discussed.

Fixed Circuit Breaker


A fixed circuit breaker is solidly mounted in its structure
with no drawout feature. The circuit breaker is available in
both surface-mounted and rear-connected configurations
(Figure 45 and Figure 46).
A surface-mounted fixed circuit breaker is front connected
and mounted on a suitable vertical mounting surface using
the appropriate mounting hardware. Refer to specific
hardware and mounting instruction details provided in
IL01301036E. The arc hood and shroud conceal internally
mounted straight bus adapters that will accommodate bus
or cable adapter connections.
The rear-connected breaker can be mounted on a suitable Shroud
horizontal mounting surface using optional left and right-side
mounting feet. Refer to specific hardware and mounting
instruction details provided in IL01301030E. A standard rear-
connected fixed circuit breaker is supplied with flat primary
terminal pads on the rear of the breaker that will accommo-
date a variety of primary connection configurations.
Figure 46.  Rear Connected.
Optional primary adapters are available for front and rear
bus or cable connections. For specific details and mounting
instructions, refer to IL01301015E.
Refer to Figure 47 through Figure 63 for selected mounting
and installation dimensional information. Complete dimen-
sional and installation drawings are available from www.
eaton.com/seriesnrx.

Primary
Terminal
Pads with
Optional
Adapters
Attached

40 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 47.  Three-pole Fixed Breaker Overall Views and Dimensions in Inches (mm) (UL 800–1200 A/IEC 630–1600 A).

Arc Exhaust Area


Do Not Obstruct

Top View

Front View

Side View

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 41
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 48.  Three-pole Fixed Breaker Overall Views and Dimensions in Inches (mm) (UL 800–1200 A/IEC 630–1600 A).

M8 x 1.25
Tapped
0.35” in
Max. Thread
Depth from
Copper Surface

Copper
Surface
6 Places

Rear View

Side View with Rear Barriers

42 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 49.  Three-pole Fixed Breaker Foot Mount Dimensions in Inches (mm) (UL 800 –1200 A/IEC 630 –1600 A).

90o Travel
(10o Free Travel)
(80o Charge
Stroke)

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 43
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 50.  Three-pole Fixed Breaker Surface Mount, Cable Connect Dimensions in Inches (mm) (UL 800–1200 A/IEC
630 –1600 A, 800 MCM, 750 MCM, and 500 MCM Lugs).

90o Travel
(10o Free Travel)
(80o Charge
Stroke)

NNote: Refer to www.eaton.com/seriesnrx for complete dimensional and installation drawings associated with 800 MCM,
750 MCM, and 500 MCM lugs.

44 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 51.  Three-pole Fixed Breaker Parallel Bus Mounting Dimensions in Inches (mm) (UL 800 –1200 A/IEC 630
–1600 A).

Arc Exhaust Area


Do Not Obstruct

Bus
Mounting
Plane

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 45
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 52.  Three-pole Fixed Breaker Vertical Universal Bus Adapters Dimensions in Inches (mm) (UL 800 –1200 A/IEC
630–1600 A).

NNote: Views shown with mounting feet option installed.

46 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 53.  Three-pole Fixed Breaker Horizontal Universal Bus Adapter Dimensions in Inches (mm) (UL 800–1200 A/
IEC 630–1600 A).

NNote: Views shown with mounting feet option installed.

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 47
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 54.  Three-pole Fixed Breaker Accessory Tray Installation and Removal Clearance Dimensions in Inches (mm).

Right
Accessory
Tray

NNote: A minimum of 2-inches (50.8 mm) of side clearance is required.

48 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 55.  Three-pole Fixed Breaker—Front View Door Cutout Detail Dimensions in Inches (mm).

8.39
(213,1)

2 x 4.00
(101,6)

2 x 10.50
(266,7)

10.38
2 x 4.00 (263,5)
(101,6)

12 x Ø0.188
(4,78) 2 x 9.45
(101,6)

Door Cutout

5.16
(131,1)

12.00
(304,8)

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 49
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 56.  Four-pole Fixed Breaker Overall Views and Dimensions in Inches (mm) (UL 800–1200 A/IEC 630–1600 A.

Arc Exhaust Area


Do Not Obstruct

Top View

Front View

Side View

50 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 57.  Four-pole Fixed Breaker Overall Views and Dimensions in Inches (mm) (UL 800–1200 A/IEC 630–1600 A).

M8 x 1.25
Tapped
0.35 in.
Max. Thread
Depth from
Copper Surface

See
Detail
A
Copper
Surface
6 Places

Rear View

Side View with Rear Barriers

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 51
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 58.  Four-pole Fixed Breaker Foot Mount Dimensions in Inches (mm) (UL 800–1200 A/IEC 630–1600 A).

Arc
Hood

90o Travel
(10o Free Travel)
(80o Charge
Stroke)

Bus
Mounting
Plane

Charging
Handle

Bottom Mounting Surface

52 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 59.  Four-pole Fixed Breaker Surface Mount, Cable Connect Dimensions in Inches (mm) (UL 800–1200 A/IEC 630–
1600 A, 800 MCM, 750 MCM, and 600 MCM Lugs).

6 x MB x 1.25
(recessed)

Arc Hood

6 x Ø0.217
(5.5)
Mounting
Holes

Recommended Barriers

4.37
(110,9)

Shroud
9.83
(249,7)

90° Travel
(10° Free
Travel)
(80° Charge
Stroke)

Charging 2.90
Handle (73,7)

2 x 5.24
(133,1)
15.99
(406,3)

11.00
(279,4)

NNote: Refer to www.eaton.com/seriesnrx for complete dimensional and installation drawings associated with 800 MCM,
750 MCM, and 500 MCM lugs.

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 53
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 60.  Four-pole Fixed Breaker Parallel Bus Mounting Dimensions in Inches (mm) (UL 800–1200 A/IEC 630–1600 A).

Arc Exhaust Area


Do Not Obstruct

Bus
Mounting
Plane

54 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 61.  Four-pole Fixed Breaker Universal Bus Adapters Vertical Dimensions in Inches (mm) (UL 800–1200 A/IEC 630–1600
A) .

NNote: Versions shown with mounting feet option installed.

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 55
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 62.  Four-pole Fixed Breaker Universal Bus Adapters Horizontal Dimensions in Inches (mm) (UL 800–1200 A/IEC 630–
1600 A).

NNote: Views shown with mounting feet option installed.

56 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 63.  Four-pole Fixed Breaker Accessory Tray Installation and Removal Clearance Dimensions in Inches (mm).

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 57
Section 6: Dimensional Drawings for Installation of Fixed Circuit Breakers

Figure 64.  Four-pole Fixed Breaker—Front View Door Cutout Detail Dimensions in Inches (mm).

8.39
(213.1)
2x4.00
(101.6)

2x10.50
(266.7)

2x4.00 10.38
(101.6) (263.5)

12xø0.188
(4.78) 2x9.45
(101.6)

Door Cutout

5.16
(131.1)

12.00
(304.8)

58 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 7: Inspection and Maintenance

Section 7: Inspection and Maintenance Table 9.  Inspection Frequency.


1
Breaker Frame Size Interval (Cycles)
800 A and below 1750
General
Between 800 and 4000 A 500
WARNING 1
Cycle = 1 no load open/close operation.
Failure to inspect, clean, and maintain circuit break- After the first inspection, inspect at least once a year. If
ers can reduce equipment life or cause the equipment these recommended inspections show no maintenance
to not operate properly under faulty conditions. This requirements, the period may be extended to a more eco-
could result in equipment damage, bodily injury, or even nomical point. Conversely, if the recommended inspection
death. shows, for instance, a heavy accumulation of dirt or other
foreign matter or other electrical damage, the inspection
CAUTION and maintenance interval should be decreased.
Inspection and maintenance procedures should be carried
out only by personnel familiar with the hazards associated
What to Inspect
with working on power circuit breakers. Additionally, they
should become familiar with the specifics associated with
Series NRX circuit breakers as presented in this manual. ! IMPORTANT
Before doing any work, make sure a drawout breaker is
levered out to the test, disconnect, or withdrawn position.
Because of the variability of application conditions and the During the levering out and levering in of the circuit breaker,
great dependence placed upon these circuit breakers for be aware of any signs that would indicate that the levering
protection and the assurance of service continuity, inspec- process is not working properly. If working on a fixed circuit
tion and maintenance activities should take place on a regu- breaker, bus systems should be de-energized for conve-
larly scheduled basis. Since maintenance of these circuit nience and safety. All circuit breakers should be switched
breakers consists mainly of keeping them clean, the fre- to the off position and the mechanism springs discharged.
quency of scheduled inspection and maintenance depends
to some degree on the cleanliness and humidity of the
surroundings. It is recommended that maintenance record
sheets be completed for the equipment. Once the circuit breaker has been cleaned as described pre-
viously under the topic entitled “General recommendations,”
visually inspect it for any signs of damage, missing or loose
General Recommendations parts, and unusual wear. Be especially alert for foreign mat-
ter that must be removed. On drawout circuit breakers,
Circuit breaker cleaning activities should be a part of an
inspect the primary disconnect finger clusters for signs of
overall activity that includes the assembly in which the
wear and erosion (Figure 3). Make appropriate corrections
circuit breaker is installed. Loose dust and dirt can be
to anything found out of order.
removed from external surfaces using an industrial quality
vacuum cleaner and/or lint-free cloth. Unless otherwise
indicated, never use high pressure blowing air, since dirt or
foreign objects can be driven into areas, such as the breaker Functional Field Testing
mechanism, where additional friction sources could create Eaton recommends that the following three functional
problems. Never use a wire brush to clean any part of the tests be performed on Series NRX circuit breakers as part
circuit breaker. of any maintenance procedure. Circuit breakers should be
removed from service and Eaton notified if the circuit break-
er fails to perform any of these tests successfully. Provide
When to Inspect the number of operations the breaker has performed to date
as well as the following nameplate information (Figure 65).
Industry standards for this type of equipment recommend
a general inspection and lubrication after the number of
1. G.O. #: It: Seq:
operations listed in Table 9. This should also be conducted
at the end of the first six months of service, if the number 2. Cust. P.O.:
of operations has not been reached. 3. Date Code
4. Cat. #:

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 59
Section 7: Inspection and Maintenance

Figure 65.  Typical Nameplate. Manual Operation Functional Test


Perform the following seven steps and verify if the circuit
breaker is appropriately opened or closed as indicated by
the indicator flags on the front of the breaker (Figure 6).
Step 1: Charge the mechanism springs using charging han-
NAS6163W dle or motor operator.
Air Circuit Breaker Step 2: Press the ON pushbutton to close breaker manually.
Frame
Step 3: Charge the mechanism springs using either the
Type NF charging handle or motor operator. (If using motor opera-
1600 Ampere Frame tor, disconnect the power to motor to prevent automatic
3 Pole recharging).
50/60 Hz Step 4: Press the OFF pushbutton to manually open the
Interrupting Ratings breaker.
RMS Symetrical Ampere Step 5: Press the ON pushbutton to manually close the
Ue Icu kA Ics kA breaker.
240~ 85 50
Step 6: Press the OFF pushbutton to manually open the
440~ 85 50 breaker.
690~ 42 42
Uimp 8 kV Catagory B Step 7: Repeat the first six steps three times.

Withstand Ratings
RMS Symetrical Ampere Electrical Operation Functional Test
Ue Icw kA (1 s) This test procedure is based on the assumption that the
240~ 42 circuit breaker is equipped with both a shunt trip and spring
440~ 42 release. If one of the accessories is missing, use the
690~ 42 manual button to replace the accessory’s function. Perform
Trip Unit Auxiliary Voltage = 24 Vm the following seven steps and verify if the circuit breaker is
appropriately opened or closed as indicated by the indicator
Accessories flags on the front of the breaker (Figure 20).
Motor Operator 110-125 Vm Step 1: Charge the mechanism springs using the charging
Spring Release 110-127 V~, Vm handle or motor operator.
Latch Check Switch NONE
Shunt Trip #1 110-127 V~, Vm Step 2: Close the breaker by applying the rated voltage to
Shunt Trip #2 NONE the spring release accessory.
UVR NONE Step 3: Charge the mechanism springs using either the
Auxiliary Switch NONE charging handle or motor operator. (If using motor operator,
Bell Alarm Sw/OTS NONE disconnect power to motor prevent automatic recharging.)

P.O. # Step 4: Open the breaker by applying the rated voltage to


shunt trip accessory.
G.O. #
Item # Step 5: Close the breaker using the spring release acces-
sory.
Seq #
YYMMDD Step 6: Open the breaker using the shunt trip accessory.

Cat # Step 7: Repeat the first six steps three times.


NAS6163WLNDABANENNDX

Enclosure Requirements
68D2555
Installation and Operating
Instructions
MN013001EN

60 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 7: Inspection and Maintenance

Trip Unit Test Procedure Step 2: Lift the arc chute up and out of the arc chamber.
The trip unit may be tested via its front panel display inter-
face or through the USB connection to a PC with the PXR
Configuration and Test Tool installed. Refer to the “operat- Figure 67.  Step 2.
ing Manual for Series NRX PXR 20/25” for instructions on
testing via the display interface. For testing through the
USB interface, refer to the Quick Start Guide for the “PXR
Configuration and Test Tool”.

Arc Chute Inspection


When a circuit breaker experiences a high level fault, or dur-
ing regularly scheduled maintenance periods, the arc chutes
should be inspected for any kind of damage or dirt. Be
especially alert for signs of significant erosion within the arc
chute.

! IMPORTANT
Fixed breakers have an arc hood positioned over the arc
chutes/arc chambers that must be removed first. Refer
to IL01301014E for installation and removal instructions.
After the inspection, reinstall the arc hood.

To remove the arc chutes and inspect both the arc chutes
and arc chambers, proceed with the following five steps.
Step 1: Using a 3 mm Allen head driver (Phillips screw driv-
er), remove four top-inserted mounting screws and cover
plate. Step 3: Follow the same procedure to remove the remain-
ing two arc chutes.
Figure 66.  Step 1. Step 4: Inspect the arc chutes for obvious damage and turn
them over to inspect the inside for obvious damage or dirt
accumulation. Series NRX arc chutes cannot be replaced.
If damage or dirt accumulation is observed, contact Eaton
for additional information.

Figure 68.  Step 3.

Step 5: When inspections are complete, secure arc chutes


in place with their mounting screws.

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 61
Section 8: Troubleshooting

WARNING Section 8: Troubleshooting


Arc chutes and their cover plates must always be
secured properly in place before a breaker is installed in
its compartment. Failure to do so could result in equip- Introduction
ment damage, bodily injury, or even death. Table 10 will help to determine the probable causes of sim-
ple circuit breaker problems and possible corrective actions.
Possible problems associated with the electronic trip unit
Primary Contact Inspection are covered in a companion publication, IL0131098EN (PXR).
With the arc chutes removed, visually inspect each primary If the problem cannot be resolved with the aid of one or
contact structure for signs of wear and/or damage with the both of these guides, contact the Eaton service center for
circuit breaker open. Series NRX primary contacts/carrier more in-depth assistance.
assemblies cannot be replaced. Contact Eaton for addi-
tional information.

Miscellaneous Modifications and/or Changes


The topics discussed here cover additional actions that
relate to updating, maintaining, or repairing Series NRX cir-
cuit breakers. Some actions may not be able to be accom-
plished in the field. In addition, this information does not
include most accessory devices that are covered by sepa-
rate instruction leaflets dedicated to individual devices.

Trip Unit Replacement


To replace a trip unit, refer to MN013003EN, Operating
Manual for Series NRX PXR 20/25.

Current Sensor Replacement


The Rogowski type current sensors are not field replace-
able.

Frame Rating Module Replacement


The frame rating module is not field replaceable.

62 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 8: Troubleshooting

Table 10.  Circuit Breaker Troubleshooting Guide.


Symptom Probable Cause Corrective Action
The circuit breaker trips open (red fault trip Repeated closing on transient (in-rush) current with Wait for circuit breaker (and loads) to cool before
indicator button is out and/or fault indicator thermal reclosing
LED is lighted) when closed on a load current memory active
An overload or fault current condition Use status and fault indicators to help locate and
remove overload or fault condition
Circuit breaker opens (fault trip indicator but- Undervoltage release operates; voltage too low or Check and correct the UVR supply voltage (85–110%
ton is not out) zero rated voltage)
Shunt trip opens Check control signal(s) to shunt trip; correct if neces-
sary
Trip latch is defective Inspect latch condition and engagement before clos-
ing; consult Eaton
Circuit breaker cannot be opened remotely, Shunt trip control signal absent or too low Check supply voltage exceeds 70% of rated voltage
but can be opened locally when signal is applied to shunt trip
Shunt trip is faulty or improperly installed Check voltage supplied to shunt trip; make sure ST is
seated in its tray; check for ST motion; replace ST if
faulty
Secondary wiring problem Make sure electrical connections are properly made
and verify proper wiring
Circuit breaker cannot be opened locally OPEN pushbutton locked Remove lock
Faulty mechanism or main contacts welded Contact Eaton
Circuit breaker makes no attempt to close Closing spring not fully charged (check SPRING Charge spring manually; check voltage to electrical
with either local (manual) or remote controls; CHARGED indicator) operator; replace operator if faulty
springs do not discharge
If equipped with undervoltage release, undervoltage Remove left accessory tray containing UVR and retry
release is not energized or is faulty closing operation; if OK, check voltage supply to UVR
(>85%); replace UVR if faulty
Circuit breaker locked in OPEN position Check reason for lock
Drawout position interlock is operating; levering Make sure circuit breaker is at a position that permits
screw closure; check that shutter door over levering screw is
fully closed
Circuit breaker interlocked with another circuit Check for presence of an interlocking scheme (cable
breaker or device or key); check to see if interlocked circuit breaker is
CLOSED
Circuit breaker cannot be closed remotely Spring release (closing) coil supply voltage low or SR Check power supply voltage; replace spring release if
(can be closed locally) faulty faulty
Secondary contact wiring problem Make sure electrical connections are properly made
and verify proper wiring
Circuit breaker cannot be closed locally (can Opening and/or closing pushbuttons locked Check reason for lock
be closed remotely)
Circuit breaker does not recharge electrically Charging motor supply voltage absent or too low Check charging motor electrical circuit voltage (under
but will recharge manually (<85%) load)
Charging motor faulty Replace motor assembly
Drawout circuit breaker will not lever in Cell rejection code plate Breaker rating not compatible with cassette require-
ment
Levering-in screw not fully in DISCONNECT position Rotate levering handle counterclockwise to
at insertion DISCONNECT position,
then insert circuit breaker fully into cassette
Circuit breaker not pushed into cassette far enough Push circuit breaker in as far as possible
Protective shutters jammed/locked Clear problem
Position detent is engaged Reset detent system

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 63
Section 8: Troubleshooting

Notes:

64 Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com
Section 8: Troubleshooting

Notes:

Series NRX with PXR – Type NF Low Voltage Power (Air) Circuit Breaker Instruction Manual MN013001EN May 2015 www.eaton.com 65
Disclaimer of Warranties and Limitation of Liability
The information, recommendations, descriptions, and safety In no event will Eaton be responsible to the purchaser or
notations in this document are based on Eaton experience user in contract, in tort (including negligence), strict liability,
and judgment, and may not cover all contingencies. If fur- or otherwise for any special, indirect, incidental, or conse-
ther information is required, an Eaton sales office should be quential damage or loss whatsoever, including but not lim-
consulted. ited to damage or loss of use of equipment, plant or power
system, cost of capital, loss of power, additional expenses
Sale of the product shown in this literature is subject to the in the use of existing power facilities, or claims against the
terms and conditions outlined in appropriate Eaton selling purchaser or user by its customers resulting from the use
policies or other contractual agreement between Eaton and of the information, recommendations, and descriptions con-
the purchaser. tained herein.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, The information contained in this manual is subject to
WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING change without notice.
WARRANTIES OF FITNESS FOR A PARTICULAR
PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE
SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT
BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES
THE ENTIRE OBLIGATION OF EATON. THE CONTENTS
OF THIS DOCUMENT SHALL NOT BECOME PART OF OR
MODIFY ANY CONTRACT BETWEEN THE PARTIES.

Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com

© 2015 Eaton
All Rights Reserved
Printed in USA Eaton is a registered trademark.
Publication No. MN013001EN / TBG1221
Part Number: MN013001ENH01 All trademarks are property
May 2015 of their respective owners.

You might also like