This spreadsheet accomplishes a storm sewer design using the rational method. Enter the data in the non-shaded areas only.
Please use one spreadsheet per stormsewer run.
Project Name:
DO NOT SKIP
ANY ROWS
ONE
RUN
PER
SPREAD
SHEET
For pipe cover calculation, Pipe cover = (Ground or Rim Elevation - Pipe invert elevation) - (pavement thickness) - (top of pipe thickness) - (pipe diameter).
The pipe thickness is based on the pipe diameter per WSDOT Manual Concrete for Shallow Pipe Cover Installations Fill Height Table 8-12.3
Please specify the largest pipe thickness of the storm sewer run being analyzed.
The spreadsheet will only calculate one storm sewer line at a time. Please copy the "Blank Template" and use this for calculating new storm sewer lines.
If analyzing complicated stormsewer system with multiple lateral lines to the trunk line, it is recommended that Stormshed be used to
model the conveyance system. Please contact your Region Hydraulics Engineer.
WARNING: START YOUR STORMSEWER RUN ON ROW 12. DO NOT SKIP ANY ROWS IN BETWEEN. USE ONE SHEET PER STORMSEWER RUN
23 24 25 26 27 24
m= 6.39 n= 0.589 Design Storm Event = 25 Pavement thickness (ft) = 0.5 Pipe Thickness (inches) = 0.5
For pipe cover calculation, Pipe cover = (Ground or Rim Elevation - Pipe invert elevation) - (pavement thickness) - (top of pipe thickness) - (pipe diameter).
The pipe thickness is based on the pipe diameter per WSDOT Manual Concrete for Shallow Pipe Cover Installations Fill Height Table 8-12.3
Please specify the largest pipe thickness of the storm sewer run being analyzed.
The spreadsheet will only calculate one storm sewer line at a time. Please copy the "Blank Template" and use this for calculating new storm sewer lines.
If analyzing complicated stormsewer system with multiple lateral lines to the trunk line, it is recommended that Stormshed be used to
model the conveyance system. Please contact your Region Hydraulics Engineer.
WARNING: START YOUR STORMSEWER RUN ON ROW 12. DO NOT SKIP ANY ROWS IN BETWEEN. USE ONE SHEET PER STORMSEWER RUN
23 24 25 26 27 24
380.00 7.96 9.96 More than 2 ft of cover More than 2 ft of cover
378.00 7.96 9.96 More than 2 ft of cover More than 2 ft of cover
376.00 7.96 9.96 More than 2 ft of cover More than 2 ft of cover
374.00 7.46 11.46 More than 2 ft of cover More than 2 ft of cover
372.00 9.46 10.46 More than 2 ft of cover More than 2 ft of cover
m= 6.39 n= 0.589 Design Storm Event = 25 Pavement thickness (ft) = 0.5 Pipe Thickness (inches) = 0.5
For pipe cover calculation, Pipe cover = (Ground or Rim Elevation - Pipe invert elevation) - (pavement thickness) - (top of pipe thickness) - (pipe diameter).
The pipe thickness is based on the pipe diameter per WSDOT Manual Concrete for Shallow Pipe Cover Installations Fill Height Table 8-12.3
Please specify the largest pipe thickness of the storm sewer run being analyzed.
The spreadsheet will only calculate one storm sewer line at a time. Please copy the "Blank Template" and use this for calculating new storm sewer lines.
If analyzing complicated stormsewer system with multiple lateral lines to the trunk line, it is recommended that Stormshed be used to
model the conveyance system. Please contact your Region Hydraulics Engineer.
WARNING: START YOUR STORMSEWER RUN ON ROW 12. DO NOT SKIP ANY ROWS IN BETWEEN. USE ONE SHEET PER STORMSEWER RUN
23 24 25 26 27 24
380.00 7.96 9.96 More than 2 ft of cover More than 2 ft of cover
378.00 7.96 9.96 More than 2 ft of cover More than 2 ft of cover
376.00 7.96 9.96 More than 2 ft of cover More than 2 ft of cover
374.00 7.46 11.46 More than 2 ft of cover More than 2 ft of cover
372.00 9.46 12.46 More than 2 ft of cover More than 2 ft of cover
365.00 5.46 7.46 More than 2 ft of cover More than 2 ft of cover
364.00 6.46 8.46 More than 2 ft of cover More than 2 ft of cover
360.00 4.46 6.46 More than 2 ft of cover More than 2 ft of cover
357.00 3.46 4.46 More than 2 ft of cover More than 2 ft of cover
355.00 2.46 4.46 More than 2 ft of cover More than 2 ft of cover
352.00 1.46 3.46 Low Cover - See Notes at Bottom More than 2 ft of cover May need concrete pipe
350.00 1.46 3.46 Low Cover - See Notes at Bottom More than 2 ft of cover May need concrete pipe
350.00 3.46 5.46 More than 2 ft of cover More than 2 ft of cover
347.00 2.46 4.46 More than 2 ft of cover More than 2 ft of cover
345.00 2.46 3.46 More than 2 ft of cover More than 2 ft of cover
343.00 1.46 3.46 Low Cover - See Notes at Bottom More than 2 ft of cover May need concrete pipe