Professional Documents
Culture Documents
Fire Pump Design & Testing
TS 300‐1‐1
Friday 9:00am‐12:00pm
Greg Trombold
By: Greg Trombold
Code books used during presentation
Terms and definitions
Water supply
Selecting a the correct fire pump for the job
Pressure calculation
Flow calculation
E mpl
Examples
Pump selection
Code issues
Avoiding trouble
Contractors point of view on pump selection
Questions
NFPA 20 – Installation of Stationary Pumps for
Fire Protection
NFPA 13 – Installation of Sprinkler
p Systems
y
NFPA 14 – Installation of Standpipe and hose
systems
y
NFPA 22 – Water tanks for Private Fire
Protection
NPSH – net p positive suction head ((32 feet at sea
level)
Rotation – direction that a pump shaft spins
TDH – total dynamic head – this is a combination
of vertical head, friction loss, and other losses due
to heat or elevation
Brake horse power – actual horse power required
at a specific point on a pump curve
Locked rotor current – maximum amp draw for a
motor
t if th
the shaft
h ft iis h
held
ld in
i a locked
l k d position
iti
Service entrance rated – a device that is rated to
handle direct feed from the utility
Minimum water level – the minimum water
level that a vertical turbine fire pump will
operate to its design parameters
Static pressure – pressure reading at no flow
Residual ppressure – p pressure at a specific
p flow
Churn pressure – pressure that a pump
produces at no flow
AHJ – Authority having jurisdiction
High Rise Building – A building greater than
75 feet in height. Where the building is
measured from the lowest level of fire
department vehicle access to the floor of the
highest occupiable story.
The most important thing you need to consider
when sizing a fire pump is water supply
The first q
question one needs to ask is “does the
municipal supply provide enough volume to
meet the system demand”
For example if a city water test is 75 static, 50
residual at 1350 flowing
Does this provide enough water for a 750 GPM
pump
Answer: Yes – the maximum y
you test a 750 GPM fire
pump to is 1125 GPM or 150% of rated flow
Does this same water supply provide enough water
for a 1500 GPM fire pump
Answer
A : maybe
b – if you plot
l t a fl
flow curve outt you
could have the flow required for the 100% flow point
(1500 GPM) *see curve
However this can be misleading there is a couple of
rules that I follow when talking about a municipal
water supply.
1. Make sure the test is recent – within a year
2. Make sure the residual flow is at least the 100% flow
rating
g of the p
pumpp
3. Avoid winter tests versus summer tests – flow tests done
in the winter are always better than flow tests done in
the summer
If the water supply
pp y does not supply
pp y enough
g
volume what are your options
Gravity feed tank – a ground level storage tank
usually steel providing enough water for the
sprinkler demand
30 of system demand for light hazard
60 min for ordinary hazard
90 min for extra hazard
Below ground tank – usually limited to 50 k of
supply
Lake or reservoir – leads to some system
requirements that may be an issue - goosenecks
Job: warehouse Allentown PA
City water test 82 static, 45 residual with 1941
flowing
Test date February 2011
Main size 8”
S
System d
demand d 2108 GPM at 110 psii
Pump size 2500 GPM at 80 psi
If you plot the water curve out it appears that
you have enough water at 2500 GPM or 100%
of the fire pump
However there are several red flags that
should have been looked at when engineering
this job
1. The water test was done in the winter
2. The main size is 8” when the main is tapped the
coupon ththatt is
i tapped
t d in
i th
the pipe
i isi roughly
hl 7.3”
7 3”
3. The city water test was only run to 1941 GPM – not
full flow of the fire pump
p p
Actual flow when pump was tested in August
2011
Types of pumps
Horizontal split case pumps
Inline fire pumps
p p
End suction pumps
Vertical turbine fire pumps
Horizontal split case pumps – this is also called
a double suction fire pump because the water
pathways direct water to both sides of the
impeller. It is also the most common fire pump
on the market partly because of the ratings
available
il bl in
i this
thi style
t l off pump 250 GPM
through 5000 GPM
This was also the first type of pump used for
fire protection systems
Inline fire pumps – these pumps have
expanded in use in the last five years for
several reasons
Space savings
Increase in ratings allowable by NFPA 20 from max
off 499 GPM,
GPM then
th tot 750 GPM,
GPM to t today
t d whichhi h is
i
unlimited rating. The largest currently available is
1500 GPM
Cost of installation – these are typically less
expensive to install because there is no base plate
that requires grouting
End suction fire pumps – not widely used
mostly because they are limited in size per
code
They are also slightly more expensive than in
line pumps
The one pump application where it is used is
small diesel driven applications 500 GPM or
less
Vertical turbine pumps – these are used for
water supplies that are below the suction
flange of a fire pump
NFPA 20 states that you have to have a positive suction
pressure to a fire pump #
g we should talk about when
The first thing
discussing pressure is height of the building
If a building is more than 75 feet tall the building
will have stand pipes. The pressure required at the
top most outlet is required to be 100 psi at a given
flow rate depending on the number of standpipes
Does this mean that the AHJ will not require 100
PSI on building g less than 75 feet tall that have
standpipes
The answer is maybe different AHJ’s have different
requirements
i t
The code (NFPA 14 chapter 5) states that if a
building is not classified as a high rise the
standpipes installed can be classified as manual
dry, or manual wet.
These types of standpipes do not require 100
psi at the top most outlet.
If that is the case then you simply need end
h d pressure at the
head h top off the
h structure ffor
standard heads this number is usually around
20 PSI
The other bit of info we need before we start is
the city flow test. Unless we are using a ground
level storage tank or reservoir.
Once we have gathered that info most of the
industry would have a form like the one on the
following page to compile the data and come
up with your pressure
Lets do a couple of examples
In both examples we will assume that the city
water test is right
g at the 100% rating g of p
pump
p
1. Height of building is 212 feet. City water test is
45 p
psi static, residual is 35 p
psi with 1250 GPM
flowing
2. Height of the building is 70 feet. City water
test is 95 psi static with 30 residual with 750
flowing
A couple of things to note here about these
examples in example one the pressure is above
175 psi.
Since you are no longer allowed to use main
relief valves to control system pressure you
have to install pressure reducing valves on
sprinkler lines and pressure restricting valves
on fire department connections until you get
high enough in building where the pressure
will be below 175 psi
The other thing which some engineers forget is
that the pump will discharge much higher
pressure at churn than at the design point
Per NFPA 20 fire pumps are allowed to have a
40% rise in pressure from rated flow to churn
This is almost never the case but different
pumps and speeds affect the churn pressure so
you should
h ld always
l llook
k at a curve to d
determine
i
the shut off pressure. (see attached)
In the previous curve rated head is 300 feet or
130 psi
The shut off head is 390 feet or 168 psi
p
This calculates to 29% rise from rated point to
shut off head
This pump is a newer design and is 3500 rpm
both contribute to the higher percentage
Lets look at example one to determine churn
The static pressure is 45 psi plus the churn pressure
of 211 psi for a total of 255 psi.
If the floors are 12 feet apart we would need
pressure reducing valves and pressure restricting
valves on the first 16 floors.
floors
255 psi – 175 psi = 80 psi / 12 = 15.4
Now I have handed out a copy of the pressure
calculation sheet and I want you all to try the
following example:
Building height 160 feet
City water test done 1-5-09, 60 static, 38 residual
with
ith 1000 GPM flowing
fl i
Lets assume the pump is 10 feet below grade in a
basement
Assume backflow, water meter, and friction in
suction piping are constant
There are two main factors in GPM calculations
Area calculation
Standpipe
p p calculation
We will start with the standpipe calculation
NFPA 14 states that the GPM required
q for the
first standpipe is 500 GPM
Each additional standpipe
p p requires
q 250 GPM
with a maximum GPM of 1000 GPM
They have done away with the requirement of
combining GPM with sprinkler system
requirements
Since most area calculations for building with
standpipes come up to be less than 500 GPM
the Fire pump GPM is generally equal to the
stand calc
If a building has 2 standpipes the pump GPM
would be 750 GPM
500 GPM for the first and 250 for the second
If a building has 3 standpipes the pump GPM
would be 1000 GPM
500 GPM , 250 for the second, and 250 for the third
Any building with more standpipes would be
1000 GPM as that is the maximum allowable by
code
For calculating GPM for areas there are a
number of factors that come into play.
The first is the type
y of hazard y
you are protecting
g
there are 5
Light hazard
Ordinary hazard group1
Ordinary hazard group 2
Extra hazard g
group
p1
Extra hazard group 2
The density associated with the hazard
Square
q footage
g of area associated with hazard
Hose allowance
We are not g goingg to discuss how to choose a
hazard as that is a different topic
We are also not going to talk about storage
design approaches. These are for warehouse
type facilities and generally require soft ware
t determine
to d t i pump GPM GPM. ThThese types
t off
systems are better to be left to sprinkler
contractors to design build.
build
Once you have your hazard classification we
use the chart on the following page from NFPA
13.
The density is multiplied by 1500 for light and
ordinary and 2500 for extra hazard
The 1500 and 2500 are the most remote square
footage
You then add in the hose allowance from the
chart on the next page to get your pump GPM
Buildingg with multiple
p types
yp of hazards yyou
calculate each area and take the worst of the
two to determine your pump GPM
Th
There are a b
bunchh off exceptions
i in
i NFPA 13
which we will only talk about so that you
know they are there. We will not use them in
the examples
Make sure the insurance company is consulted
because they can change the density and
square footage requirement depending on the
job.
job
Building is 15,000 square feet, light hazard
Density for light hazard .1
Hose stream for light
g hazard 100 GPM
Calculation 1500 x .1 = 150 + 100 = 250
Pump GPM 250 GPM