GF Piping Systems

Section 11

Contain-It™ Secondary
Containment Piping
System

76
Glossary
S = Contain-It™ Socket
SPG = Spigot End (same dimension as pipe outside diameter)
MPT = Male Pipe Thread
FPT = Female Pipe Thread

Product Line Description

39 Fittings
41 Pipe
42 Accessories

The technical information given in this publication implies no warranty of any kind and is subject to
change without notice. Please consult our Terms and Conditions of Sale.

Not for Use with Compressed Air or Gases


DO NOT TEST with Air or Air over Water

GF Piping Systems DOES NOT RECOMMEND the use of thermoplastic piping products for systems to transport or store
compressed air or gases, or the testing of thermoplastic piping systems with compressed air or gases in above or below
ground locations. The use of GF Piping products in compressed air or gas systems automatically voids the warranty for
such products, and their use against our recommendation is entirely the responsibility and liability of the installer. GF will
not accept responsibility for damage or impairment from its products, or other consequential or incidental damages caused
by misapplication, incorrect assembly, and/or exposure to harmful substances or conditions. The only exception to this
recommendation is when testing the Contain-It™ Secondary System or the Fuseal Squared™ Double Containment Piping
System’s containment joints.

77
78
Table of contents Page

Contain-It Pipe 80

Contain-It Fittings 81

Contain-It Valve Box 85

Contain-It Flange Box 86

Contain-It Terminations 87

Contain-It Centralizers 90

Contain-It Accessories 93

Leak Detection 96

79
Contain-It Pipe

Split Pipe

Size Lift Qty lengths Code Minimum O.D. Minimum I.D.


(inch) ( ft) ( ft) Order Qty (inch) (inch)
( ft)
3 480 10 37L015030 80 3.548 2.743
4 360 10 37L015040 60 4.215 3.525
6 120 10 37L015060 20 6.275 5.375

Solid Pipe

Size Lift Qty lengths Code Minimum O.D. Minimum I.D.


(inch) ( ft) ( ft) Order Qty (inch) (inch)
( ft)
3 720 20 37L026030 120 3.548 3.248
4 560 20 37L026040 80 4.215 3.882
6 360 20 37L026060 40 6.275 5.782

80
Contain-It Fittings

Contain-It Coupling PVC


Containment Coupling (SxS)

Size Code Pack C G L W O.D. I.D.


(inch) Qty (inch) (inch) (inch) (inch) (inch) (inch)
3 4629-030 5 2.00 0.38 4.38 5.04 3.96 3.55
4 4629-040 5 2.00 0.38 4.38 5.81 4.69 3.88
6 4629-060 5 2.75 0.38 5.81 8.19 6.88 5.97

Contain-It Coupling PVC


Containment Coupling (SxS)

Maximum Gap: 5.50"
 
Size Code Pack C L W O.D. I.D.
(inch) Qty (inch) (inch) (inch) (inch) (inch)
3 4629-030E 5 4.50 9.00 5.04 3.96 3.55
4 4629-040E 5 5.00 10.00 5.81 4.96 3.88
6 4629-060E 5 5.75 11.50 8.19 6.88 5.97

Containment Coupling - Reducing, Split (S x S)

Size Code Pack C1 C2 L W O.D. I.D.


(inch) Qty (inch) (inch) (inch) (inch) (inch) (inch)
4x3 4629-422 1 2.75 2.00 5.13 5.81 4.69 3.88
6x4 4629-532 5 2.00 2.75 5.81 8.19 6.88 5.97

81
Contain-It 90° Elbow PVC
Containment Split (SxS) 90°

Size Code Pack R C G W O.D. I.D.


(inch) Qty (inch) (inch) (inch) (inch) (inch) (inch)
3 4606-030 5 0.00 2.00 2.00 5.04 3.96 3.55
4 4606-040 5 1.97 2.00 2.38 5.75 4.69 4.20
6 4606-060 5 4.00 2.75 3.50 8.13 6.88 6.28

Contain-It 45° Elbow PVC


Containment Split (S x S) 45°

Size Code Pack C G W O.D. I.D.


(inch) Qty (inch) (inch) (inch) (inch) (inch)
3 4617-030 5 2.00 0.94 5.04 3.96 3.34
4 4617-040 5 2.00 2.00 5.81 4.69 3.88
6 4617-060 5 2.75 1.75 8.19 6.88 5.97

Containment Tee, Split (S x S x S)

Code Size C G H L W O.D. I.D. Pack


(inch) (inch) (inch) (inch) (inch) (inch) (inch) (inch) Qty
4601-030 3 2.00 2.00 6.50 8.00 5.04 3.96 3.34 5
4601-040 4 2.00 2.40 7.20 8.65 5.81 4.70 3.88 5
4601-060 6 2.75 3.50 10.25 12.50 8.19 6.85 5.97 5

82
Containment 45° Wye, Split (S x S x S)

Size Code Pack C G GJ L N W O.D. I.D.


(inch) Qty (inch) (inch) (inch) (inch) (inch) (inch) (inch) (inch)
4 4683-040 5 2.00 0.75 5.88 11.00 7.13 5.81 4.69 3.88
6 4683-060 5 2.75 1.32 7.75 15.19 9.75 8.19 6.88 5.97

Contain-It Cap
Containment Cap (S)

Size Code Pack C L O.D.


(inch) Qty (inch) (inch) (inch)
3 4647-030 5 1.88 3.00 4.00
4 4647-040 5 1.75 1.94 4.50
6 4647-060 5 2.75 3.19 6.75

Contain-It Adapter PVC


Containment Female Adapter (S x FPT)

Size Code Pack C L O.D.


(inch) Qty (inch) (inch) (inch)
4 4635-040 5 1.75 3.18 5.00
6 4635-060 5 3.00 5.00 6.75

83
Contain-It Plug PVC
Plug (MPT)

Size Code Pack


(inch) Qty
4 4650-040 5
6 4650-060 5

Contain-It Adapter PVC


Adapter Sleeve

• 3"x3" (IPS S x S)
•  4"x4" and 6"x6" (IPS SPG x S)

Size Code Pack


(inch) Qty
3x3 4687-030 10
4x4 4687-040 10
6x6 4687-060 10

Contain-It Floor Drain PPFR


Containment Floor Drain (IPS Spg x MPT)

For use with Fuseal primary piping only.


Must use 4635-060 for Contain-It transition.
 
Size Code
(inch)
3x6 46104-530
4x6 46104-532

84
Contain-It Valve Box

Valve Box Not Pressure Rated. Pressure Testing Not Recommended.

Size Code W H H1 C L L2 W2
(inch) (inch) (inch) (inch) (inch) (inch) (inch) (inch)
3 150 991 104 10 8 3.46 2.25 8 10 8
4 150 991 105 10 11 4.56 2.25 10 12 12
6 150 991 106 18 15 6.17 3.00 18 20 20

85
Contain-It Flange Box

Flange Box Not Pressure Rated. Pressure Testing Not Recommended.

Size Code A B C D E
(inch) (inch) (inch) (inch) (inch) (inch)
3 150 991 100 10.0 12.0 10.3 14.3 10.0
4 150 991 101 12.0 14.0 12.3 16.5 12.0
6 150 991 102 12.0 14.0 12.3 16.5 12.0

86
Contain-It Terminations

Termination Fitting - Rigid PVC, Split (S to IPS)

Size Code C L W O.D. I.D.


(inch) (inch) (inch) (inch) (inch) (inch)
3 x 1∕2 4628-333 2.00 4.38 5.04 3.96 3.34
3 x 3∕4 4628-334 2.00 4.38 5.04 3.96 3.34
3x1 4628-335 2.00 4.38 5.04 3.96 3.34
3 x 1 1∕4 4628-336 2.00 4.38 5.04 3.96 3.34
3 x 1 1∕2 4628-337 2.00 4.38 5.04 3.96 3.34
3x2 4628-338 2.00 4.38 5.04 3.96 3.34
4 x 1∕2 4628-415 2.00 4.44 5.81 4.69 3.88
4 x 3∕4 4628-416 2.00 4.44 5.81 4.69 3.88
4x1 4628-417 2.00 4.44 5.81 4.69 3.88
4 x 1 1∕4 4628-418 2.00 4.44 5.81 4.69 3.88
4 x 1 1∕2 4628-419 2.00 4.44 5.81 4.69 3.88
4x2 4628-420 2.00 4.44 5.81 4.69 3.88
6x2 4628-528 2.75 5.81 8.19 6.88 5.97
6 x 2 1∕2 4628-529 2.75 5.81 8.19 6.88 5.97
6x3 4628-530 2.75 5.81 8.19 6.88 5.97
6x4 4628-532 2.75 5.81 8.19 6.88 5.97

Test Termination Fitting (with 1/8" NPT Schrader Test Valve) - Rigid PVC, Split (S to IPS)

Size Code C L W O.D. I.D.


(inch) (inch) (inch) (inch) (inch) (inch)
4x1 4628-417T 2.00 4.44 5.81 4.69 3.88
4x2 4628-420T 2.00 4.44 5.81 4.69 3.88
6x3 4628-530T 2.75 5.81 8.19 6.88 5.97
6x4 4628-532T 2.75 5.81 8.19 6.88 5.97

 
 

87
Termination Fitting - Flexible Alcryn, One Piece

Contain-It to IPS/Metric
STD - Standard Fitting / BUSH - Bushed Fitting
 
Size Size Code C L OD1 OD2 Design
(inch) (inch) (inch) (inch) (inch)
3 x 1∕2 20 4628-333A 1.90 3.10 3.90 1.70 BUSH
3 x 3∕4 25 4628-334A 1.90 3.10 3.90 1.70 BUSH
3x1 32 4628-335A 1.90 3.10 3.90 1.70 STD
3 x 1 1∕4 40 4628-336A 1.00 3.10 3.90 2.70 BUSH
3 x 1 1∕2 50 4628-337A 1.00 3.10 3.90 2.70 BUSH
3x2 63 4628-338A 1.00 3.10 3.90 2.70 STD
4 x 1∕2 20 4628-415A 0.58 2.90 4.55 1.69 BUSH
4 x 3∕4 25 4628-416A 0.58 2.90 4.55 1.69 BUSH
4x1 32 4628-417A 0.58 2.90 4.55 1.69 STD
4 x 1 1∕4 40 4628-418A 0.58 3.00 4.55 2.70 BUSH
4 x 1 1∕2 50 4628-419A 0.58 3.00 4.55 2.70 BUSH
4x2 63 4628-420A 0.58 3.00 4.55 2.70 STD
6 x 2 1∕2 75 4628-529A 1.50 3.00 6.55 4.66 BUSH
6x3 90 4628-530A 1.50 3.00 6.55 4.66 BUSH
6x4 110 4628-532A 1.50 3.00 6.55 4.66 STD

Test Termination Fitting - Flexible Alcryn, One Piece (with 1/8" NPT Schrader Test Valve)

Contain-It to IPS/Metric
 
Size Size Code
(inch)
3 x 1∕2 20 4628-333AT
3 x 3∕4 25 4628-334AT
3x1 32 4628-335AT
3 x 1 1∕4 40 4628-336AT
3 x 1 1∕2 50 4628-337AT
3x2 63 4628-338AT
4 x 1∕2 20 4628-415AT
4 x 3∕4 25 4628-416AT
4x1 32 4628-417AT
4 x 1 1∕4 40 4628-418AT
4 x 1 1∕2 50 4628-419AT
4x2 63 4628-420AT
6 x 2 1∕2 75 4628-529AT
6x3 90 4628-530AT
6x4 110 4628-532AT

88
Termination Fitting - Flexible Alcryn, One Piece

Contain-It to Copper Tube Size


 
Size Code
(inch)
3 x 1∕2 4628-333AC
3 x 3∕4 4628-334AC
3x1 4628-335AC
3 x 1 1∕4 4628-336AC
3 x 1 1∕2 4628-337AC
3x2 4628-338AC
4 x 1∕2 4628-415AC
4 x 3∕4 4628-416AC
4x1 4628-417AC
4 x 1 1∕4 4628-418AC
4 x 1 1∕2 4628-419AC
4x2 4628-420AC
6x2 4628-528AC
6 x 2 1∕2 4628-529AC
6x3 4628-530AC
6x4 4628-532AC

Test Termination Fitting - Flexible Alcryn, One Piece (with 1/8" NPT Schrader Test Valve)

Contain-It to Copper Tube Size


 
Size Code
(inch)
3 x 1∕2 4628-333ATC
3 x 3∕4 4628-334ATC
3x1 4628-335ATC
3 x 1 1∕4 4628-336ATC
3 x 1 1∕2 4628-337ATC
3x2 4628-338ATC
4 x 1∕2 4628-415ATC
4 x 3∕4 4628-416ATC
4x1 4628-417ATC
4 x 1 1∕4 4628-418ATC
4 x 1 1∕2 4628-419ATC
4x2 4628-420ATC
6x2 4628-528ATC
6 x 2 1∕2 4628-529ATC
6x3 4628-530ATC
6x4 4628-532ATC

89
Contain-It Centralizers

Centralizer (Contain-It x IPS)

• Fx, Fy, and Fz are rated design loads in lb-f (pounds-force) and N (Newtons) for respective x, y,
and z directions
 
Size Design Code Pack ID OD L Fy, Fz (lbs/N) F-z (lbs/N)
(inch) Qty (inch) (inch) (inch)
3 x 1∕2 Mold 4686-333 25 0.84 3.12 1.88 67 / 300 80.5 / 360
3 x 3∕4 Bush 4686-334 25 1.05 3.12 1.88 67 / 300 80.5 / 360
3x1 Mold 4686-335 25 1.32 3.12 1.88 67 / 300 80.5 / 360
3 x 1 1∕4 Bush 4686-336 25 1.66 3.12 1.88 67 / 300 80.5 / 360
3 x 1 1∕2 Bush 4686-337 25 1.90 3.12 1.88 67 / 300 80.5 / 360
3x2 Mold 4686-338 25 2.35 3.12 1.88 67 / 300 80.5 / 360
4 x 1∕2 Bush 4686-415 25 0.84 3.79 1.88 67 / 300 114 / 510
4 x 3∕4 Bush 4686-416 25 1.05 3.79 1.88 67 / 300 114 / 510
4x1 Mold 4686-417 25 1.32 3.79 1.88 67 / 300 114 / 510
4 x 1 1∕4 Mold 4686-418 25 1.66 3.79 1.88 67 / 300 114 / 510
4 x 1 1∕2 Mold 4686-419 25 1.90 3.79 1.88 67 / 300 114 / 510
4x2 Mold 4686-420 25 2.35 3.79 1.88 67 / 300 114 / 510
6 x 1∕2 Bush 4686-523 25 0.84 5.59 2.13 67 / 300 251 / 1120
6 x 3∕4 Bush 4686-524 25 1.05 5.59 2.13 67 / 300 251 / 1120
6x1 Bush 4686-525 25 1.32 5.59 2.13 67 / 300 251 / 1120
6 x 1 1∕4 Bush 4686-526 25 1.66 5.59 2.13 67 / 300 251 / 1120
6 x 1 1∕2 Bush 4686-527 25 1.90 5.59 2.13 67 / 300 251 / 1120
6x2 Bush 4686-528 25 2.35 5.59 2.13 67 / 300 251 / 1120
6 x 2 1∕2 Mold 4686-529 25 2.89 5.59 2.13 67 / 300 251 / 1120
6x3 Mold 4686-530 25 3.47 5.59 2.13 67 / 300 251 / 1120
6x4 Mold 4686-532 25 4.47 5.59 2.13 67 / 300 251 / 1120
6 x 1∕2 Twin 4686-811 5 0.84 5.77 0.75 67 / 300 251 / 1120
6 x 3∕4 Twin 4686-813 5 1.05 5.77 0.75 67 / 300 251 / 1120
6x1 Twin 4686-815 5 1.32 5.77 0.75 67 / 300 251 / 1120

Centralizer (Contain-It x Copper Tube Size)

• Fx, Fy, and Fz are rated design loads in lb-f (pounds-force) and N (Newtons) for respective x, y,
and z directions
 
Size Design Code Pack ID OD L Fy, Fz (lbs/N) F-z (lbs/N)
(inch) Qty (inch) (inch) (inch)
3 x 1∕2 Bush 4686-333C 10 0.63 3.12 1.88 67 / 300 80.5 / 360
3 x 3∕4 Bush 4686-334C 10 0.88 3.12 1.88 67 / 300 80.5 / 360
3x1 Bush 4686-335C 10 1.13 3.12 1.88 67 / 300 80.5 / 360
3 x 1 1∕4 Bush 4686-336C 10 1.38 3.12 1.88 67 / 300 80.5 / 360
3 x 1 1∕2 Bush 4686-337C 10 1.63 3.12 1.88 67 / 300 80.5 / 360
3x2 Bush 4686-338C 10 2.13 3.12 1.88 67 / 300 80.5 / 360
4 x 1∕2 Bush 4686-415C 10 0.63 3.79 1.88 67 / 300 114 / 510
4 x 3∕4 Bush 4686-416C 10 0.88 3.79 1.88 67 / 300 114 / 510
4x1 Bush 4686-417C 10 1.13 3.79 1.88 67 / 300 114 / 510
4 x 1 1∕4 Bush 4686-418C 10 1.38 3.79 1.88 67 / 300 114 / 510
4 x 1 1∕2 Bush 4686-419C 10 1.63 3.79 1.88 67 / 300 114 / 510
4x2 Bush 4686-420C 10 2.13 3.79 1.88 67 / 300 114 / 510
6x2 Bush 4686-528C 10 2.13 5.59 2.13 67 / 300 251 / 1120
6 x 2 1∕2 Bush 4686-529C 10 2.63 5.59 2.13 67 / 300 251 / 1120
6x3 Bush 4686-530C 10 3.13 5.59 2.13 67 / 300 251 / 1120
6x4 Bush 4686-532C 10 4.13 5.59 2.13 67 / 300 251 / 1120

90
Centralizer (Contain-It x Metric)

• Fx, Fy, and Fz are rated design loads in lb-f (pounds-force) and N (Newtons) for respective x, y,
and z directions
 
Size (in x mm) Design Code Pack ID OD L Fy, Fz (lbs/N) F-z (lbs/N)
Qty (inch) (inch) (inch)
3 x 20 Bush 4686-707 10 0.79 3.12 1.88 67 / 300 80.5 / 360
3 x 25 Bush 4686-708 10 0.98 3.12 1.88 67 / 300 80.5 / 360
3 x 32 Bush 4686-709 10 1.26 3.12 1.88 67 / 300 80.5 / 360
3 x 40 Bush 4686-710 10 1.58 3.12 1.88 67 / 300 80.5 / 360
3 x 50 Bush 4686-711 10 1.97 3.12 1.88 67 / 300 80.5 / 360
4 x 20 Bush 4686-712 25 0.79 3.79 1.88 67 / 300 114 / 510
4 x 25 Bush 4686-713 25 0.98 3.79 1.88 67 / 300 114 / 510
4 x 32 Bush 4686-714 25 1.26 3.79 1.88 67 / 300 114 / 510
4 x 40 Bush 4686-715 25 1.58 3.79 1.88 67 / 300 114 / 510
4 x 50 Bush 4686-716 25 1.97 3.79 1.88 67 / 300 114 / 510
4 x 63 Mach 4686-717 25 2.48 3.79 1.88 67 / 300 114 / 510
6 x 75 Bush 4686-719 25 2.95 5.59 2.13 67 / 300 251 / 1120
6 x 90 Mach 4686-720 25 3.54 5.59 2.13 67 / 300 251 / 1120
6 x 110 Mold 4686-721 25 4.33 5.59 2.13 67 / 300 251 / 1120
6 x 20 Twin 4686-812 5 0.79 5.77 0.75 67 / 300 251 / 1120
6 x 25 Twin 4686-814 5 0.98 5.77 0.75 67 / 300 251 / 1120
6 x 32 Twin 4686-816 5 1.26 5.77 0.75 67 / 300 251 / 1120

Solid Centralizer (Contain-It x IPS)

Model:
• Only for use with GF Contain-It pipe and fitting system. Consult GF Piping Systems for installa-
tion and spacing recommendations. Not for use with split Contain-It pipe. 
• Two-piece PVC centralizer that clam-shells over carrier pipe and bolts together in axial direc-
tion.
• Includes Gr. 5 zinc plated hardware requried for assembly. 
• External pipe support must be aligned with centralizer.
• Fy and Fz are rated design loads in lb-f (pounds-force) and N (Newtons) for respective x, y, and
z directions
• F-z is the rated design loads in lb-f (pounds-force) and N (Newtons) for -z gravity force direc-
tion.
 
Size GF OD ID L Fyz F-z
(inch) Code (inch) (inch) (inch)
3 x 1 1∕2 155 484 835 3.19 1.96 4.76 360lbs / 1600N 373lbs / 1660N
3x2 155 484 836 3.19 2.39 4.76 360lbs / 1600N 373lbs / 1660N
4x2 155 484 837 3.82 2.39 4.76 517lbs / 2300N 564lbs / 2510N
6x3 155 484 839 5.72 3.56 4.76 517lbs / 2300N 701lbs / 3120N
6x4 155 484 840 5.72 4.56 4.76 517lbs / 2300N 701lbs / 3120N

91
Solid Centralizer (Contain-It x Metric)

Model:
• Only for use with GF Contain-It pipe and fitting system. Consult GF Piping Systems for installa-
tion and spacing recommendations. Not for use with split Contain-It pipe. 
• Two-piece PVC centralizer that clam-shells over carrier pipe and bolts together in axial direc-
tion.
• Includes Gr. 5 zinc plated hardware requried for assembly. 
• External pipe support must be aligned with centralizer.
• Fy and Fz are rated design loads in lb-f (pounds-force) and N (Newtons) for respective x, y, and
z directions
• F-z is the rated design loads in lb-f (pounds-force) and N (Newtons) for -z gravity force direc-
tion.
 
Size GF OD ID L Fyz F-z
(inch) Code (mm) (mm) (mm)
3 x 20 155 484 821 81.0 21.0 121 360lbs / 1600N 373lbs / 1660N
3 x 25 155 484 822 81.0 26.0 121 360lbs / 1600N 373lbs / 1660N
3 x 32 155 484 823 81.0 33.0 121 360lbs / 1600N 373lbs / 1660N
3 x 40 155 484 824 81.0 41.0 121 360lbs / 1600N 373lbs / 1660N
3 x 50 155 484 825 81.0 51.0 121 360lbs / 1600N 373lbs / 1660N
4 x 63 155 484 826 97.1 64.0 121 517lbs / 2300N 564lbs / 2510N
6 x 75 155 484 827 145.3 76.0 121 517lbs / 2300N 701lbs / 3120N
6 x 90 155 484 828 145.3 91.0 121 517lbs / 2300N 701lbs / 3120N
6 x 110 155 484 829 145.3 111.0 121 517lbs / 2300N 701lbs / 3120N

92
Contain-It Accessories

Fitting Clip

Size Code Pack


(inch) Qty
3, 4 & 6 4693-101 25

Pipe Clamp

Size Code
(inch)
4&6 4693-102

Drill Bits

Size Code
(inch)
3&4 4693-104
6 4693-106

Test Gauge

Do Not Exceed 5 PSI Air Pressure


 
Size Code
(inch)
3, 4 & 6 4693-150

93
System III

Manual Injection Gun - System III

• Available March 1, 2017


•  Mixing tips not included

d Code
(inch)
3, 4 & 6 4694-600

Pneumatic Injection Gun - System III

• Available March 1, 2017


•  Mixing tips not included

d Code
(inch)
3, 4 & 6 4694-601

Adhesive Cartridge - System III

• Price is for each cartridge


• Limited Shelf Life of 12 Months
•  Mixing tips not included

d Code Pack Qty


(inch)
3, 4 & 6 4694-602 4

Mixing Tips - System III

•  Available March 1, 2017

Description Code Pack Qty


Straight 4694-603 10
Bent 4694-607 10
Flexible 4694-606 10

Injection Gun Conversion Kits - System III

• Available March 1, 2017


•  Converts System II Injection Gun to System III

Description Code
Manual 37X004820
Pneumatic 37X004821

94
System II

Manual Injection Gun - System II

•  Mixing tips not included

d Code
(inch)
3, 4 & 6 4694-200

Pneumatic Injection Gun - System II

•  Mixing tips not included

d Code
(inch)
3, 4 & 6 4694-201

Adhesive Cartridge - System II

• Limited Shelf Life of 18 Months


• Mixing tips not included
•  Price is for each cartridge

d Code Pack
(inch) Qty
3, 4 & 6 4694-302 4

Mixing Tips - System II

Description Code Pack


Qty
Straight 4694-303 10
Bent 4694-307 10
Flexible 4694-306 10

95
Leak Detection

Low Point Leak Detection Alarm Box

• Visual alarm indicators


• Powered on lithium batteries
• Alarm box does not include sensors
• No output option
 
Description Code
4 Sensor Signal
Leak Detection 150 240 001
Alarm Box

Low Point Leak Detection System

• 12 point leak detection system


• 4 Point Leak Detection System
• 14” x 12” NEMA 4 Enclosure with locking latches.
• Internal fusible breaker for power protection.
• (12) Red LED indicators for leak detection at a specific points.
• Input: 120 Vac power
• RS485 Communications for building automation.
• Alarm output terminals for remote alarm indication.
• Other options available upon request.
• Test Button Option - Will momentarily light up all pilot lights when engaged
• PLC for sensor/pilot light control
• BACnet module for building communication
•  Optional audible alarm available.

Description Code
4 Point Leak
Detection Sys- 150 000 060
tem

Continuous Cable Leak Detection System

• Dimensions: 13.75" x 11.81" x 4.00" (350mm x 300mm x 102mm) Type 12 (IP52)


• Power: 110-240VAC, 50/60 Hz, 0.3 A/50 VA 24 VDC, 1 A/24 VA
•  Accepts probe and cable sensors in one sensor string

Maximum Ca- Cable Capac- Code


ble Range ity
( ft)
* 3000 1 150 000 061
* 7500 1 150 000 064
* 7500 4 150 000 065

96
System III Adhesive Requirements

System III Contain-It™ Cartridge Fittings/Pipe # of Sockets/Tube


1 cartridge 3" fittings 14
1 cartridge 4" fittings 12
1 cartridge 6" fittings 9
1 cartridge 3" pipe 20 ft. length, both sides
1 cartridge 4" pipe 17 ft. length, both sides
1 cartridge 6" pipe 9 ft. length, both sides

System III Adhesive Cartridge Requirements Calculation


This table is designed to assist in the accurate determination of the number of System III adhesive cartridges
required for a specific project.

Fittings
Quantity of 3” Tees and Wyes ___________ × 3 =___________

Quantity of 3” Fittings ___________ × 2 =___________


(other than tees and wyes)
___________ /14 = _____________

Quantity of 4” Tees and Wyes ___________ × 3 =___________

Quantity of 4” Fittings ___________ × 2 =___________


(other than tees and wyes)
___________ /12 = (+) _____________

Quantity of 6” Tees and Wyes ___________ × 3 =___________

Quantity of 6” Fittings ___________ × 2 =___________


(other than tees and wyes)
___________ /9 = (+)______________

Split Pipe
_______ Feet 3” Split Pipe/20 (1 cartridge will fill 20 ft., both sides) = (+)____________
_______ Feet 4” Split Pipe/17 (1 cartridge will fill 17 ft., both sides) = (+)____________

_______ Feet 6” Split Pipe/9 (1 cartridge will fill 9 ft., both sides) = (+)____________

TOTAL CARTRIDGES_______________

97
System II Adhesive Requirements

System II Contain-It™ Cartridge Fittings/Pipe # of Sockets/Tube


1 cartridge 3" fittings 16
1 cartridge 4" fittings 14
1 cartridge 6" fittings 10
1 cartridge 3" pipe 23 ft. length, both sides
1 cartridge 4" pipe 20 ft. length, both sides
1 cartridge 6" pipe 10 ft. length, both sides

System II Adhesive Cartridge Requirements Calculation


This table is designed to assist in the accurate determination of the number of System II adhesive cartridges
required for a specific project.

Fittings
Quantity of 3” Tees and Wyes ___________ × 3 =___________

Quantity of 3” Fittings ___________ × 2 =___________


(other than tees and wyes)
___________ /16 = _____________

Quantity of 4” Tees and Wyes ___________ × 3 =___________

Quantity of 4” Fittings ___________ × 2 =___________


(other than tees and wyes)
___________ /14 = (+) _____________

Quantity of 6” Tees and Wyes ___________ × 3 =___________

Quantity of 6” Fittings ___________ × 2 =___________


(other than tees and wyes)
___________ /10 = (+)_____________

Split Pipe
_______ Feet 3” Split Pipe/23 (1 cartridge will fill 23 ft., both sides) = (+)____________
_______ Feet 4” Split Pipe/20 (1 cartridge will fill 20 ft., both sides) = (+)____________

_______ Feet 6” Split Pipe/10 (1 cartridge will fill 10 ft., both sides) = (+)____________

TOTAL CARTRIDGES_______________