DAILY REPORT: LE GRAND CHATEAU

ELECTRICAL METER READINGS


MDB - 1
CURRENT 1479972
PREVIOUS 1479360
CONSUM(CUR) 612
CONSUM(PREV) 706
WATER METER READING
CURRENT 23879
PREVIOUS 23865
CONSUM(CUR)
CONSUM(PREV)
DAILY ACTIVITIES: COMMON AREAS
S.NO TYPE DESCRIPTIONS

General Checking of Common area, Fire alarm Panel, Gas Panel,Equipment


Room, LV room,Roof Equipments,Airconditioning Equipments.
1 General

2 Plumbing Irrigation pump Stainer filter cleaning work

3 Plumbing Storm water pump Checking and cleaning work in Basement


Generator Monthly maintenance by GWB intl. Co-ordination work. Water
4 Electrical temp- 52degc .Oil press- 5.94, RPM- 1500,Battery volt- 23.7

4 Electrical C block 3rd floor 3 watts LED lamp fuse.

6 A/C Heat exchanger checking for E3 flow error.


POWER GROUP SUB CONTRACTORS ACTIVITIES
S.NO COMPANY NAME
1 GWB INTL-GENERATOR Carried out monthly maintenance for Diesel Generator
2 LANDCARE-LANDSCSAPE
3 NEW LINE SYSTEMS- CCTV
NEW LINE SYSTEMS-GATE BARRIER
4

5 SWIMMING POOL-DEEP BLUE

6 TANK CLEANING- DEEP BLUE


7 SUMP TANK CLEANING
PPM - ACTIVITES

2 2.30- 4.30PM C block ground floor 4th unit PPM work.


AMC - CONTRACTORS - ACTIVITIES
S.NO COMPANY NAME DESCRIPTIONS

1
VISION SAFETY(FA&FF)

2
AL SABBAH (GAS)
3 ETA (ELEVATORS)
4 RENTOKIL (PEST CONT)

5
SPORTS LINK (GYM EQU)

6 ABCL- LIFT THIRD PARTY


APARTMENTS COMPLAINTS & ACTIONS

1 Plumbing C-213 water leaking checking work


2 Plumbing B-209 main incoming line damage.
U DATE:13/1/14
TER READINGS
MDB - 2 MDB - 3 MDB - 4 CLUB HOUSE
2441552 2736875 3845022 168490
2440655 2735872 3843812 168410
897 1003 1210 6
1019 1217 1693 6
R READING

U.S.GALLON LITERS
1400 5320
1400 5320
COMMON AREAS
LOCATIONS ACTION TAKEN STATUS REMARKS

Gas Panel Indication


Fault- Zone 27.Informed to
All common Area Completed alsabbah- Sachin

Basement Stainer filter cleaned Completed

Slightly water leaking .


Taking specification. Today
we inform to sub
Basement contractor. Completed
Basement genset room Completed

C block 3rd floor Changed the Lamps Completed

Heat exchanger Filter air block removed Completed


NTRACTORS ACTIVITIES

TIVITES

C block ground floor PPM done completed


ORS - ACTIVITIES
LOCATION SERVICES STATUS REMARKS

LAINTS & ACTIONS

C-213 Pending
B-209 Pipe line work Completed
ELECTRICAL & WATER METER REDADING MONTH OF JANUARY - 2014
DATE MDB1 MDB2 MDB3 MDB4 CLUB HOUSE
1-Jan 1471867 2429963 2722825 3824845 167394
2-Jan 1472515 2430900 2723980 3826550 167483
3-Jan 1473194 2431920 2725185 3828296 167588
4-Jan 1474018 2432926 2726422 3830040 167670
5-Jan 1474714 2433890 2727654 3831825 167782
6-Jan 1475383 2434800 2728859 3833588 167884
7-Jan 1476007 2435724 2729983 3835213 167959
8-Jan 1476636 2436664 2731070 3836971 168050
9-Jan 1477285 2437676 2732188 3838742 168145
10-Jan 1477956 2438625 2733413 3840432 168235
11-Jan 1478654 2439636 2734655 3842119 168325
12-Jan 1479360 2440655 2735872 3843812 168410
13-Jan 1479972 2441552 2736875 3845022 168490
14-Jan
15-Jan
16-Jan
17-Jan
18-Jan
19-Jan
20-Jan
21-Jan
22-Jan
23-Jan
24-Jan
25-Jan
26-Jan
27-Jan
28-Jan
29-Jan
30-Jan
31-Jan
NUARY - 2014
WATER METER
23697
23713
23727
23742
23752
23765
23783
23801
23819
23837
23851
23865
23879
S.NO DATE & TIME LOCATIONS
1.9.2013/1.15PM Common area, 1 st floor corridor
1
1.9.2013/12.15Pm B Block 3rd floor
2
2..9.2013/1.30Pm Common area, c block corridor
3
2.9.2013/3 PM B block ground floor
4
2.9.2013/3 PM B block ground floor
5
3.9.2013/10.30AM Common area, c block corridor
6
4.9.2013/10 AM Common Area ,Basement
7

8 6.9.2013/2.30PM 2nd floor A block Common area

7.9.2013/1.15Pm 4th floor corridor A block


12
11.9.2013/1.20Pm Swimming pool
13
12.9.2013/1.30Pm C block 2 nd floor corridor
19
13.9.2013/11.30AM Ablock 2nd floor, C block 4th floor
20
14.9.2013/12.15Pm B Block 3rd floor
21
15.9.2013/3 PM B block ground floor
22
16.9.2013/9 AM Basement c bock
23
17.9.2013/12.15pm S.pool
24
18.9.2013/ 10 AM Common area
25
21.8.2013/8am S.pool
26
23.8.2013/9Am C block 2nd floor corridor
27
25.9.2013/12.45Pm B block 3rd floor corridor
28
27.9.2013/9 AM Basement c bock
29
29.9.2013/12.15Pm B Block 3rd floor
30
30.9.2013/11.30Am A block Ground floor Corridor
31
1/10/2013 Gym room
32
1/10/2013 A block corridor 1 st floor
33
1/10/13 9.00 A.M Roof c block
34
2/10/2013 8.40 A.M Gym room
35
3/10/2013 10.15
A.M C block 2 nd floor lift lobby
36
7/10/2013 6.30 A.M Swimming pool
37
7/10/2013 9.05 A.M Health Club
38
7/10/2013 10.40 A.M Swimming pool
39
8/10/13 5.00 P.M A block 3 rd floor corridor
40
9/10/2013 3.40 P.M C block reception
41
9/10/2013 3.00 P.M Block A Floor 2nd floor corridor
42
10/10/13 11.30 A.M Club House
43
11/10/2013 9.15 A.M Block A Floor 4
44
11/10/13 4.50 P.M Irrigation pump room
45
12/10/13 4.40 P.M Party hall
46
13/10/13 11.30 A.M Block A Floor 1
47
14/10/13 5.05 P.M Block B Floor 2
48
15/10/13 12.15 P.M Gym entrance door
49
17/10/13 8.10 A.M Swimming Pool
50
18/10/13 8.10 A.M Block B Floor 3
51
20/10/13 8.15 A.M Roof C block
52
22/10/13 10.30 A.M Gym room
53
26/10/13 5.10 P.M Block A Basement
54
27/10/13 11 AM A block
55
28/10/13 11 AM B block
56
30/10/13 7.50 A.M Fire pump room
57
31/10/13 7.50 A.M Lift lobby and stair case
58
3/11/2013 Basement room
59
3/11/2013 A block 1 st floor
60
4/11/2013 C block outside
61
62 5/11/2013 All Blocks
Basement firepump room near
63 5/11/2013 Watchman room

64 5/11/2013 A-409 basement car parking

65 5/11/2013 A block Garden side

66 5/11/2013 C block entrance

67 5/11/2013 C block roof

68 5/11/2013 Gym children area cabin

69 5/11/2013 C block basement

70 5/11/2013 Electrical room

71 6/11/2013 `

72 6/11/2013 Health club

73 6/11/2013 A block roof

74 6/11/2013 All blocks roof

75 6/11/2013 Garden side

76 6/11/2013 Basement

77 6/11/2013 A block

78 6/11/2013 C block basement

79 6/11/2013 Electrical room


7/11/2013 C block 2 nd floor corridor
80
7/11/2013 Ablock 2nd floor, C block 4th floor
81
7/11/2013 B Block 3rd floor
82
7/11/2013 B block ground floor
83
8/11/2013 B block 3rd floor corridor
84
8/11/2013 Basement c bock
85
8/11/2013 B Block 3rd floor
86
8/11/2013 A block Ground floor Corridor
87
9/11/2013
88 All common Area
9/11/2013
89 S.pool Party hall
9/11/2013
90 S.pool Health club
9/11/2013
91 All blocks roof
9/11/2013
92 Gym room
9/11/2013
93 C block 1 st floor
9/11/2013
94 B-block
9/11/2013
95 C block corridor

96 10/11/2013 All common Area

97 10/11/2013 S.pool Party hall

98 10/11/2013 Gym room

99 10/11/2013 Swimming pool

100 10/11/2013 Basement C-212

101 10/11/2013 C block corridor

102 11/11/2013 All common Area

103 11/11/2013 A block-2nd floor

104 11/11/2013 Roof B block

105 11/11/2013 Swimming pool

106 11/11/2013 Basement- B block

107 12/11/2013 All common Area

108 12/11/2013 Basement- B block

109 12/11/2013 Ground floor near 007

110 12/11/2013 Swimming pool

111 12/11/2013 Swimming pool

112 12/11/2013 B block

113 12/11/2013 C- Block 2nd floor

114 13/11/2013 All common Area

115 13/11/2013 Villa


116 13/11/2013 Basement A,B,C

117 13/11/2013 Health club toilet

118 13/11/2013 B block -2 nd floor

119 13/11/2013 A block 1 st floor

120 13/11/2013 B block basement

121 13/11/2013 Swimming pool

122 14/11/2013 All common Area

123 14/11/2013 Swimming pool

124 14/11/2013 Basement

125 14/11/2013 Gym inside

126 14/11/2013 Garden side

127 14/11/2013 A block 1 st floor

128 14/11/2013 B block basement

129 14/11/2013 A block basement

130 14/11/2013 B blcok Basement

131 15/11/2013 A,B,C blocks

132 17/11/2013 All common Area

133 17/11/2013 A block -3rd floor

134 17/11/2013 Health club

135 17/11/2013 Garden side


136 17/11/2013 Near A-103

137 17/11/2013 Gym inside

138 17/11/2013 A block

139 18/11/2013 All common Area

140 18/11/2013 Gym inside

14 18/11/2013 B block -3rd floor

142 18/11/2013 C-206 Basement

143 18/11/2013 Garden side

144 18/11/2013 Bblock basement


A block 1st floor near electric
145 18/11/2013 room

Swimming pool pump room opp-


146 18/11/2013 haet exchanger area roof.

147 19/11/2013 All common Area

148 19/11/2013 S.pol opp rof area

149 19/11/2013 Basement bath room

150 19/11/2013 Garden side

151 19/11/2013 B block roof area

152 19/11/2013 Garden side

Swimming pool pump room opp-


153 19/11/2013 haet exchanger area roof.

154 20/11/2013 All common Area

155 20/11/2013 S.pol opp rof area

156 20/11/2013 B -Block 3rd floor

157 20/11/2013 Basement electric room

158 20/11/2013 A block ground floor near lift


Swimming pool pump room opp-
159 20/11/2013 haet exchanger area roof.
160 21/11/2013 All common Area

161 21/11/2013 S.pol opp rof area

162 21/11/2013 A-Block 4th floor

163 21/11/2013 B block ground floor

164 21/11/2013 B block 4th floor

165 21/11/2013 Gym outside

166 23/11/2013 All common Area

167 23/11/2013 Roof

168 23/11/2013 A-Block 3rd floor

169 23/11/2013 A block roof

170 23/11/2013 Ablock 4th floor near 401

171 23/11/2013 Basement fire pump room

172 24/11/2013 All common Area


173 24/11/2013 Swimming pool opp roof

174 24/11/2013 A-Block 2nd floor

175 24/11/2013 A block ground and first floor

176 24/11/2013 Ablock 2nd floor near 212

177 24/11/2013 A block ground and first floor

178 24/11/2013 Heat exhanger area

179 25/11/2013 All common Area

180 25/11/2013 Gym room

A-Block Basement electrical


181 25/11/2013 room

182 25/11/2013 A block Roof

183 25/11/2013 B Block corridor Corridor

184 25/11/2013 A block Basement

185 26/11/2013 All common Area

186 26/11/2013 Service room inside

187 26/11/2013 Basement pump room


188 26/11/2013 Gym entrance

189 26/11/2013 B Block corridor Corridor

190 26/11/2013 A block Basement

191 27/11/2013 All common Area

192 27/11/2013 A block Basement

193 27/11/2013 B block 1st floor no 105

194 27/11/2013 C block exit

195 27/11/2013 A block 3rd floor

196 27/11/2013 swimming pool pump room

197 27/11/2013 swimming pool pump room

198 28/11/2013 All common Area

199 28/11/2013 C block

200 28/11/2013 C block -Ground floor

201 28/11/2013 A blcok near 402- 4th floor

202 29/11/2013 All common Area

203 29/11/2013 B block 3rd floor

204 29/11/2013 C block corridor


205 29/11/2013 Basement parking area 102

206 29/11/2013 B301

207 30/11/2013 All common Area

208 30/11/2013 C-302

209 30/11/2013 A block 4 th floor Lift lobby

210 30/11/2013 B block 1st floor corridor

211 30/11/2013 Swimming pool opp Roof

212 30/11/2013 Fire alarm panel- B block


214 1.12.2013 All common Area

215 1.12.2013 C block roof

216 1.12.2013 Swimming pool filter

217 1.12.2013 B block ground floor

218 1.12.2013 B block 3rd floor

219 1.12.2013 Lift in B block

220 1.12.2013 Swimming pool opp Roof

221 2.12.13 All common Area

222 2.12.13 Health club

223 2.12.13 Roof B block

224 2.12.13 Health club

225 2.12.13 Basement Fire pump room

226 2.12.13 Bcblock 1sd floor

227 2.12.13 Lift in B block

228 2.12.13 A block

229 2.12.13 Swimming pool opp Roof

230 7.12.13 All common Area

231 7.12.13 Health club

232 7.12.13 Basement Fire pump room

233 7.12.13 Health club

234 7.12.13 Basement Fire pump room

235 7.12.13 Bblock 1sd floor

236 7.12.13 C block ground floor

237 7.12.13 Swimming pool opp Roof

238 8.12.13 All common Area

239 8.12.13 All common Area


240 8.12.13 Basement Fire pump room

241 8.12.13 Health club

242 8.12.13 Bblock 3rd floor

243 8.12.13 B block -4th floor

244 8.12.13 Swimming pool opp Roof

245 9.12.13 All common Area

246 9.12.13 All common Area

247 9.12.13 Swimming pool

248 9.12.13 A block

249 9.12.13 Gym room

250 9.12.13 B block -4th floor

251 9.12.13 Opp A107

252 10.12.13 All common Area

253 10.12.13 Basement Fire pump room

254 10.12.13 Swimming pool

255 10.12.13 C block ground floor

256 10.12.13 Gym room

257 10.12.13 B block 3rd floor

258 10.12.13 Basement Fire pump room

259 11.12.13 All common Area

260 11.12.13 Basement Fire pump room

261 11.12.13 Swimming pool

262 11.12.13 Swimming pool staircase

263 11.12.13 A block 2nd floor

264 11.12.13 Basement Fire pump room


265 13.12.13 All common Area

266 13.12.13 A - basement near 305

267 13.12.13 Roof tank

268 13.12.13 Gym ladies bath room

269 13.12.13 Watchman room Basement

270 14.12.13 All common Area

271 14.12.13 A - basement near -202

272 14.12.13 B block

273 14.12.13 C block outside

274 14.12.13 Storm water pump room

275 14.12.13 Watchman room Basement

276 15.12.13 All common Area

277 15.12.13 C block

278 15.12.13 Health club

279 15.12.13 A block 2nd floor

280 15.12.13 S.pool opp roof

281 15.12.13 B block roof

282 16.12.13 All common Area

283 16.12.13 Health club

284 16.12.13 Basement kitchen

285 16.12.13 B block

286 16.12.13 S.pool opp roof

287 16.12.13 A block 1st floor

288 17.12.13 All common Area

289 17.12.13 B block


290 17.12.13 Basement kitchen

291 17.12.13 B block

292 17.12.13 A block 1st floor

293 18.12.13 All common Area

294 18.12.13 C block basement

295 18.12.13 Swimming pool outside

296 18.12.13 A block Ground floor

297 18.12.13 A block 1st floor

298 19.12.13 All common Area

299 19.12.13 C block basement

300 19.12.13 C block

301 19.12.13 Swimming pool opp roof

302 19.12.13 A block 1st floor

303 22.12.13 All common Area

304 22.12.13 A & B block roof

305 22.12.13 B block roof

306 22.12.13 Gym room inside

307 22.12.13 S.pool opp roof

308 23.12.13 All common Area

309 23.12.13 B block basement

310 23.12.13 B block 4th floor

311 23.12.13 S.pool opp roof

312 23.12.13 Gym room Bathroom

313 23.12.13 Gym room inside

314 23.12.13 S.pool opp roof


315 24.12.13 All common Area

316 24.12.13 Roof area

317 24.12.13 B block 4th floor

318 24.12.13 S.pool opp roof

319 24.12.13 Gym room

320 24.12.13 Service room

321 25.12.13 All common Area

322 25.12.13 Gym room

323 25.12.13 Fire panel

324 26.12.13 B block basement

325 26.12.13 Gym room

326 26.12.13 Heat exchanger

327 28.12.13 All common Area

328 28.12.13 health club

329 28.12.13 Doors

330 28.12.13 C block basement

331 28.12.13 Service room

332 28.12.13 Heat exchanger

333 29.12.13 General

334 29.12.13 Plumbing

335 29.12.13 AC

336 29.12.13 AC

337 29.12.13 Electrical

338 31.12.13 All common Area


339 31.12.13 Swimming pool pump room

340 31.12.13 Swimming pool pump room

341 31.12.13 B block 2nd floor

342 31.12.13 Swimming pool pump room

343 31.12.13 Swimming pool pump room

344 31.12.13 Basement A block electrical room

345 4.1.2014 All common Area

346 4.1.2014 B block basement

347 4.1.2014 Swimming pool

348 4.1.2014 Swimming pool pump room.

349 4.1.2014 A block Basement

350 4.1.2014 Swimming pool

351 4.1.2014 Swimming pool area

352 4.1.2014 Basement A block electrical room

353 6.1.2014 All common Area

354 6.1.2014 C block Fountain

355 6.1.2014 A block Fountain

356 6.1.2014 Steam room


357 6.1.2014 Gents steam room

358 6.1.2014 B block basement

359 6.1.2014 Garbage bin trolley

360 6.1.2014 Basement A block electrical room

361 7.1.2014 All common Area


362 7.1.2014 Swimming pool pump room

363 7.1.2014 A block

364 7.1.2014 B blcok.

365 7.1.2014 A block 2nd floor

366 7.1.2014 A block 3rd floor

367 7.1.2014 A block 4th floor

368 8.1.2014 All common Area

369 8.1.2014 Swimming pool pump room

370 8.1.2014 Jackozi

371 8.1.2014 B blcok.

372 8.1.2014 A block 4th floor

373 12.1.2014 All common Area

374 12.1.2014 Club house party hall

375 12.1.2014 Swimming pool filter

376 12.1.2014 B block basement

377 12.1.2014 Gym room

378 12.1.2014 Heat exchanger

379 13.1.2014 All common Area

380 13.1.2014 Basement

381 13.1.2014 Basement

382 13.1.2014 Basement genset room

383 13.1.2014 C block 3rd floor

384 13.1.2014 Heat exchanger


DESCRIPTIONS TYPE OF WORK
Lamp not glowing in B block 1 st floor corridor Electrical

FCU drain Leakage HVAC

Lamp not glowing, C block ground floor Corridor Electrical

Lamp not glowing Electrical

Lamp not glowing Electrical

Lamp not glowing, C block ground floor Corridor Electrical

A block domestic tank over flow Plum

Water Leak from FCU HVAC

Lamp not glowing Electrical

S.Pool pump water leakage in body. S.Pool

Lamp not Glowing Electrical

FCU not working HVAC

FCU drain Leakage HVAC

Lamp not glowing Electrical

Lamp not glowing Electrical

S.pool pump pipe line leakage Plumbing

Door handle problem in Club house Bath room Others

S.pool pressure filter doom leakage. Others

Painting work to be done Painting

A/C is not cooling HVAC

Lamp not glowing Electrical

FCU drain Leakage HVAC

Water is leaking in FCU HVAC

13 Watts Lamp Fused-8 Nos Electrical

3 Watts lamp fused Electrical

Pressure vessel water leak Mechanical


50 W halogen lamp fused Electrical

3 Watts lamp fused Electrical

Swimming pool Shower drainage block Plumbing

Health club Bath room flush tank Repair Plumbing

Shut off valve problem Plumbing

No light in Swimming pool Area Electrical

Main door catch mechanism fault Electrical

AC drain Leakage Electrical

Access control Activated in Club house others

CFL 18 W lamp gets fused Electrical

Contactor burn Electrical

Wall clock fixing Others

CFL 18 W lamp gets fused Electrical

CFL 18 W lamp gets fused Electrical

Door stopper fixing work Electrical

S.pool filter doom cover Leakage Painting

AC darin block A/C

Booster pump not working Electrical

Ceiling gypsum fixing work Others

Domestic water tank overflow Plumbing

Ceiling lights changing in reception using scaffolding others

Ceiling lights changing in reception using scaffolding others

Brick pasting work for Doors Others

Basement Acess control system activated Others

A/C duct problem A/C

A/c drain block A/C

Pole lights fused Electrical


General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
All common Area

Ac Drain water leaking. Electrician helped. AC

Ceiling water leakage.Plumber helped. Plumbing

Pole lamp fused.11 watts Electrical


Fountain lights fuse and lamp holder problem.Ac technician
helped Electrical

Booster pump fixing work.Plumber helped. Plumbing

Ceiling water leakage.Electrician helped Gym children area cabin

Basement kitchen sink leakage. Plumbing


General Checking
Taken Electrical of Common
readings area, Fire alarm
fr all mdb,water Panel, Gas
meter Electrical room
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General

Shower pipe danage in bathroom. Plumbing

Booster pump low pressure . Plumbing

FAHU A,B,C block in roof checking work. AC

Garden side pole lamp 1 no 11 watts fuse. Electrical

Tube light fuse near transformer in basement Electrical

Corridor 2 nd floor 3 watts lamps fuse. Electrical

Basement kitchen sink leakage. Plumbing

Taken Electrical readings fr all mdb,water meter Electrical


Lamp not Glowing Electrical

FCU not working HVAC

FCU drain Leakage HVAC

Lamp not glowing Electrical

A/C is not cooling HVAC

Lamp not glowing Electrical

FCU drain Leakage HVAC

Water is Checking
General leaking inofFCU
Common area, Fire alarm Panel, Gas HVAC
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments. General
Plumbing
toilet room ceiling leak.water heater safety valve problem.
Plumbing
Ground floor water heater safety valve leak.
Plumbing
Gents bath room Wash basin hose damage.
Electrical
13 watts cfl bub blinking
Electrical
3 watts LED lamp fused - 2 nos
Plumbing
Fountain motor pipeline problem.
General Checking of Common area, Fire alarm Panel, Gas AC
Ground floor Ceiling
Panel,Equipment water
Room, LVleakage
room,Roof
Equipments,Airconditioning Equipments.
General

toilet room ceiling leak.water heater safety valve problem. Plumbing

Gym room thermostat cover fixing work AC

Wall light 11 watts 1 no fuse. Electrical

Basement car parking 36 watts tubelight fuse. Electrical


General Checking of Common area, Fire alarm Panel, Gas
2nd floor garbageRoom,
Panel,Equipment door improper close
LV room,Roof Plumbing
Equipments,Airconditioning Equipments.
General

Corridor 3 watts led lamp fuse. Electrical

Booster pump 2nd pump Bush problem.water leakage. Electrical

Wall light 11 watts 1 no fuse. Electrical


General
BasementChecking of Common
acess door area,
notLVclosing Fire alarm Panel, Gas
properly Plumbing
Panel,Equipment Room, room,Roof
Equipments,Airconditioning Equipments.
General

Basement acess door not closing properly Plumbing


B block Corridor Ground floor near 007 3 watts LED lamps
fuse Electrical

Wall light 11 watts 1 no fuse. Electrical

Party hall inside 50 Watts Halogen 1 no fuse. Electrical

Ground floor thermostat problem AC


General
FCU No Checking of Common area, Fire alarm Panel, Gas
2 Drain block AC
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General

Villa side drainge checking work.Electrician Helped Plumbing


Sump pump tank all checking work Plumbing

Flush not working. Plumbing

3 watts lamps changed near Lift lobby Electrical

3 watts lamps changed near 101 Electrical

Acess door Adjustment work. B block basement. Electrical

Swimming pool Jacozzy checking work AC

General Checking of Common area, Fire alarm Panel, Gas


Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General

Jockozee checking work in swimming pool area AC

A block domestic water tank float valve checking work Plumbing

13 Watts pin type 1 no cfl lamp changing work Electrical

Garden side Coloumn light fittings inside water filled.So,


ELCB tripped.All lights connection checking work. Electrical

3 watts lamps changed near 101 Electrical

Acess door Adjustment work. B block basement. Electrical

On 14th Nov Night the non magnetic door in Basement


lift lobby in A block Has opened ,and floor scratches. This
was seen by Mr.srinivasan( Board member). He has
complained about this at 10 PM. That same day at 10.10
PM, we have rectified the door.Next day friday we came
and checked in CCTV and found the issue due to the person
A-206.Mail and photo sent to Mr.Kasper andMr. Smith. General ( Friday)

On14th Nov night at 11.30 PM ,B security called me ,that


the Magnetic access doors hinges has damaged and door is
in hanging position. I told him to keep the door in open
condition. Next day Friday carpentor came and rectified
it.In CCTV camera we found that the issue is due to B-
406person.Mail and photo sent to Mr.Kasper and
Mr.Smith. General ( Friday)

Carried out
General Glass cleaning
Checking of Common and area,
wipingFireinalarm
all 4 floors
Panel, Gas
corridor back and Room,
Panel,Equipment in all A,B
LV and C blocks.
room,Roof General ( Friday)
Equipments,Airconditioning Equipments.
General

FCU drain leakage AC

Health club shower line leakage Plumbing

Garden side fountain cleaning work. Plumbing


corridor 3 watts led lamp fuse Electrical

50 watts halogen lamp fuse -2 nos Electrical


General Checking of Common area, Fire alarm Panel, Gas
Reception 60 Watts
Panel,Equipment lamps
Room, LVchanged
room,Roof Electrical
Equipments,Airconditioning Equipments.
General

FCU drain leakage AC

FCU drain leakage AC

Basement car parking ceiling pipe water leakage . Plumbing

Garden side fountain cleaning work. Plumbing

Access door not properly close. Helped with carpentor Electrical

3 watts LED lamp fuse . Electrical

Allawai electricals carried out Heat exchanger repairing


work. others
General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General

Heat exchanger repairing co-ordination work AC

Basement common area bath room water line block. Plumbing

Garden side fountain cleaning work. Plumbing

Booster pump contactor problem. Electrical

Graden side fountainlight Transformer burn. Electrical

Allawai electricals carried out Heat exchanger repairing


work.
General Checking of Common area, Fire alarm Panel, Gas Heat exchanger
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General

Heat exchanger repairing co-ordination work AC

FCU Drain leakage in ceiling AC

Basement electric room 1 tube light fuse Electrical

3 watts lamps -3 nos fused Electrical


Allawai electricals carried out Heat exchanger repairing
work. Heat exchanger
General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General

Heat exchanger repairing co-ordination work AC

FCU Drain leakage in ceiling AC

Garbage room 1 tube light fuse Electrical

3 watts lamps -3 nos fused Electrical

Gym outside basement main drainline block. Plumbing


General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General

FAHU testing- 6 units AC

FCU Drain leakage in ceiling AC

A block booster pump pressure switch problem Electrical

3 watts lamps -3 nos fused Electrical


Basement pump room Transfer pump for A block - Air
block problem Plumbing
General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General
Heat exchanger checking work with allawai electricals AC

FCU Drain leakage in ceiling AC

A block ground and 1st floor , water low pressure problem. Electrical

3 watts lamps -3 nos fused Electrical

A block ground and 1st floor , water low pressure problem. Plumbing
Inspection carried out by Allawai electricals for not
attaining the proper temperature in Swimming pool. Heat exchanger
General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General

Gym bath room shut off problem Plumbing

FCU Drain leakage in ceiling AC

A block roof Water line checking work Electrical

3 watts lamps -3 nos fused Electrical


General Checking of Common area, Fire alarm Panel, Gas
Sump pump shortRoom,
Panel,Equipment circuit LV
problem
room,Roof Electrical
Equipments,Airconditioning Equipments.
General

13 Watts pin type cfl lamp fuse Electrical

Fire pump , Transfer pump cleaning work Electrical


FCU drain block AC

3 watts lamps -3 nos fused Electrical

Sump pump checking work Plumbing


General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General

Tube light fuse near car parking -195 Electrical

3 watts lamps fused Electrical

Exit glass screw loose Electrical

corridor FCU drain leakage AC

Deep blue came At 9 AM the filter leakage in swimming


pool pump room is arrested by providing new valve and
closed the inlet. AC

Heat exchanger checking work. The E3 water pressure


error rectified by providing valve in swimming pool filter.
Now only
General one pump
Checking is runningarea,
of Common and Fire
maintaining 1 barGas
alarm Panel,
pressure. 1 filter running.
Panel,Equipment Room, LV room,Roof Heat exchanger
Equipments,Airconditioning Equipments.
General

front fountain over flow line repairing work Plumbing

Garbage room Room Drainage block. Plumbing


General Checking
3 watts lamp of Common area, Fire alarm Panel, Gas
changed Electrical
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General ( 29.11.2013)

FCU drain block AC

3 watts lamp changed Electrical


3 watts lamp changed Electrical

Fire alarm activated due to smoke in B301 Common

General Checking of Common area, Fire alarm Panel, Gas


Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General ( 29.11.2013)

Kitchne sin Mixture hose problem Plumbing

3 watts lamp changed Electrical

3 watts lamp changed Electrical

Heat exchanger checking work AC


Carried out programming in fire panel for the smoke
detector error in Health club on 30.11.203 Vision Safety
General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General

Roof AC unit water servicing helping with AC technician Plumbing

Swimming pool Fiter cover sealant removing work Plumbing

Staircase light fuse Electrical

FCU drain block AC

Lift lamp sample checking work 7 nos Electrical

Heat exchanger checking work together with Allawai


electricals AC
General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General

Shut off hose problem Plumbing

Roof Out door unit for corridor in B block water servicing


working. Helping with AC technician Plumbing

Health club drain line block in bathroom Plumbing

Planning and scheduling for Water tank cleaning together


with Co-ordinator. Roof water tank level checking Plumbing

FCU drain block AC

60 watts lamp fuse Electrical

staircase light fuse in ground floor Electrical


Heat exchanger checking work together with Allawai
electricals
General Checking of Common area, Fire alarm Panel, Gas AC
Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. General

Shut off hose problem Plumbing

A block transfer pump airlock Plumbing

Health club drain line block in bathroom Plumbing


Basement water tank for B & C . One of the tank cleaned. Draining
started to next tank.Fire valve closed.informed to civil defense. Tank CLEANING

FCU drain block AC

staircase light fuse in ground floor Electrical

Heat exchanger checking work AC

General Checking of Common area, Fire alarm Panel, Gas


Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. General

Meeting with Mr .Saravanan( Power ) & Mr.Kasper for pending


issues Others
Basement water tank for B & C . Draining Process for2nd tank
using sump pump Plumbing

Health club drain line block in bathroom Plumbing

FCU drain block AC

Corridor LED lamp fuse Electrical

Heat exchanger checking work AC


General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. General

Combination B & C tank cleaning finished. One of the Basement


tank for A block draining started. Plumbing

Deep cleaning for removing fungus and black particles have


started. Some areas cleaned .next day also they are coming to
clean. SWIMMING POOL-DEEP BLUE

3rd corridor 2nos 3 watts led lamp fuse. Electrical

Gym room inside 1no 50 watts halogen light fuse Electrical

Corridor LED lamp fuse Electrical

corridor FCU unit drain line block. AC

General Checking of Common area, Fire alarm Panel, Gas


Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. General

A block transfer pump line NRV problem. Plumbing

Deep cleaning for removing fungus and black particles have


continued Some areas cleaned .next day also they are coming to
clean. SWIMMING POOL-DEEP BLUE

C block ground floor entrance camera not working problem Electrical

Gym room inside 1no 50 watts halogen light fuse Electrical

B block 3rd floor corridor 2nd unit fan motor burnt . AC

Tank cleaning finished for A block one of the combination tank.


Now water level lowering process started for Next tank. Tank cleaning

General Checking of Common area, Fire alarm Panel, Gas


Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. General

A block transfer pump air block releasing work. Plumbing

Carried out Deep cleaning for fungus and black parts removal. SWIMMING POOL-DEEP BLUE

Swimming pool staircase 11watts lamp fuse. Electrical

FCU drain leak. AC

Tank cleaning finished for basement tanks .Roof tank have to start. Tank cleaning
General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. General

Car parking near ceiling water leak Plumbing

Roof tank A & B cleaning finished on 13.12.2013( Friday) Tank cleaning

Bath room inside 1 no 13 watts cfl lamp fuse Electrical

Watchman room basement AC unit incoming cable problem. AC


General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General

Car parking near ceiling water leak Plumbing

3rd Floor corridor 1 no -3 watts LED lamp fuse Electrical

C block outside lights ELCB trip. Light fitting inside water


went. Electrical

Storm water pump room 1no - tube light 36 watts fuse. Electrical

Watchman room basement AC unit incoming cable


problem. AC
General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. General

C block main door handle problem.So, repair work. Plumbing

toilet flush problem. Plumbing

Corridor near 202 1 no 3 watts LED lamp fuse. Electrical

Heat exchanger checking work for low temperature problem. AC

B block 3rd floor corridor unit no 2 Condensor fan motor fixing


work. AC
General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. General

Healthclub bathroom wash basin line block Plumbing

Basement ceiling water leakage problem in Roof. Plumbing

2nd floor corridor 3 watts LED lamps fuse .So, changed the Lamp. Electrical

Allawai electricals carried out inspection for Low temperature


problem. Heat exchanger

A block 1st floor FCU drain leak. AC

General Checking of Common area, Fire alarm Panel, Gas


Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. General

Inside fountain Pipeline Broken Rework. Plumbing


4th floor lift near corridor 3 watts LED lamps fuse . Electrical

B block near fountain 1 no walk way light fuse -11 watts Electrical

A block 1st floor FCU drain leak. AC


General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. General

Rain water pipe main line block in Basement for C block.


( Complaint by C-107) Plumbing

Swimming pool outside walkway light 1 no light fitting damage. Electrical

A block ground floor corridor 1 no 3 watts LED lamps fuse.So,


changed the lamp. Electrical

A block 1st floor FCU drain leak. AC

General Checking of Common area, Fire alarm Panel, Gas


Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. General

Basement C block kitchen toilet flush Problem Plumbing

Exit light staircase near -8 watts lamp fuse Electrical

Heat exchanger Low temperature problem. Checking work. Electrical

A block 1st floor FCU drain leak. AC

General Checking of Common area, Fire alarm Panel, Gas


Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. General
A & B block roof water tank draining & cleaning work together
with Deep blue Plumbing

B block roof tank float valve cable insulation work. Electrical

Gym room inside 1 no 13 watts CFL pin type lamp fuse. Electrical

Heat exchanger Low temperature problem. Checking work AC

General Checking of Common area, Fire alarm Panel, Gas


Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. General

B block basement Access door Not closing properly Plumbing

Common error fault B block 4th floor-corridor Smoke detector in


staircase . Fire alarm Panel

Allawai electricals carried out inspection and adjusted the flow


switch controls for Water flow error and low temperature problem
in Heat exchanger. Heat exchanger

Gym bathroomn inside 2 nos 13 watts cfl lamp fuse. Electrical

Gym room inside 1 no 13 watts CFL pin type lamp fuse. Electrical

Heat exchanger Low temperature problem. Checking work & co-


ordination with Allawai. AC
General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. General

Block A,B & C booster pump pressure checking work. Plumbing

Common error fault B block 4th floor-corridor Smoke detector in


staircase . Fire alarm Panel

Heat exchanger panel reset work , for unit trip due to low flow. Heat exchanger

Gym roominside 1 nos 13 watts cfl lamp fuse. Electrical


Generalroom
Service Checking of Common
store materails area,
shifting Fire alarm Panel, Gas
work AC
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General

Gym room toilet flush problem Plumbing


Vision safety came for inspection of Common fault in
panel. Fire alarm Panel

B block basement access door not closing properly. Plumbing

Gym roominside 1 nos 13 watts cfl lamp fuse. Electrical


Heat exchanger checking work for low temperature
problem. AC

General Checking of Common area, Fire alarm Panel, Gas


Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. General

health club shower mixer handle repair work. Plumbing

C block entrance doors 2 nos and B block entrance doors 2 nos


close mechanism equipment fixing work co-ordination. Door

C- block basement kitchen room AC drain leak. AC

Service room inside 4 nos 13 watts CFL lamp changed Electrical

Heat exchanger checking work for low temperature problem. AC

General Checking of Common area, Fire alarm Panel, Gas


Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. All common Area

Health club fire hose reel water leak problem. Checking work. health club

Heat exchanger checking work for ice formation. Cappliray tube


has to flush . Allawai electricals carrying tomorrow. Heat exchanger

Lift lamp replaced from 20 W halogen lamps to 5 watts LED lamp. All lifts

Gym room inside 1 no speaker removed, so corrected. Gymroom inside


General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General
swimming pool 2nd pump removed and sent to allawai for
repairing Plumbing
Swimming pool 2nd pump terminal connection removing
work. Electrical

Lift lobby near 1no 3 watts lamps fused Electrical


Allwai electrical carreied Swimming pool old sand filter
removing work and fixed new sand filter. Plumber co-
ordinated. Filter
Swimming pool filter Multi foot valve damaged and water
leak. Plumbing

Basement A block electrical room AC unit Drain line block. AC

General Checking of Common area, Fire alarm Panel, Gas


Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. General

B block Basement door Repair work.( Carpentor work - Co-


ordination) Plumbing

Swimming Pool Main door repair work. Plumbing

Swimming pool Pump No 1 - Removing work . Hand over to Deep


blue. Plumbing

A block Basement Car parking No- 209 1 no Tube light Fuse . Electrical

Swimming pool 1st floor outer kid poolnear 1 no 20 watts CFL


lamp fuse. Electrical

Allawai Electricals carried out checking with Jackozi. Jackozi

Basement A block electrical room AC unit Drain line block. AC


General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General

C block front and back Fountain Float valve changed. Plumbing

A block outside Fountain Float Valve changed Plumbing

Health Club steam room Water line hose Damage. Plumbing


Gents steam room CFL lamp Fuse-2nos 13 watts Electrical

B block Basement Staircase near Runway light 36 watts


tubelight fuse Electrical
Max technical works proceeded for changing Garbage
Wheels. 12 wheels replaced. 8 pending. Garbage wheels

Basement A block electrical room AC unit Drain line block. AC


General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General
swimming pool no 1 fixing work , co-ordination with Deep
blue . Plumbing

A block lift near Basement Roof water leak. Plumbing

B block 2nd floor 202 near, 3rd floor 306 near 3 watts LED
lamp fuse Electrical

A block 2nd floor Emergency lamps checked 10 Nos .1 no


Lamp fuse . Electrical
A block 3rd floor Emergency light 10 nos checked. 2 nos
lamp fuse. Electrical

A block 4th floor Emergency light 10 nos checked. Electrical


General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General

Swimming pool pump room fresh water line valve handle


rusted and water leak. So changed the PPR line pipe &
valve handle. Plumbing
Jackozi checking work allawai contractor proceed the
inspection. Have to change the ELCB and wiring repairing
work Electrical

B block 2nd floor 204 near 3 watts lamp fuse Electrical

A block 4th floor Emergency light 10 nos checked. Electrical

General Checking of Common area, Fire alarm Panel, Gas


Panel,Equipment Room, LV room,Roof Equipments,Airconditioning
Equipments. General

Club house party hall, Toilet flush problem. Plumbing

Swimming pool filter air block removing work. Plumbing

B blcok basement lift near Tubelight Capacitor burn. ELCB trip. Electrical

Fire hose reel in Gym room checking and co - ordination work. Electrical

Heat exchanger checking for E3 flow error. A/C


General Checking of Common area, Fire alarm Panel, Gas
Panel,Equipment Room, LV room,Roof
Equipments,Airconditioning Equipments.
General

Irrigation pump Stainer filter cleaning work Plumbing


Storm water pump Checking and cleaning work in
Basement Plumbing
Generator Monthly maintenance by GWB intl. Co-
ordination work. Water temp- 52degc .Oil press- 5.94,
RPM- 1500,Battery volt- 23.7 Electrical

C block 3rd floor 3 watts LED lamp fuse. Electrical

Heat exchanger checking for E3 flow error. A/C


REMARKS
Lamps fused. Changed lamp.

Filter and Drain tray cleaned .

Lamps fused. Changed lamp.

Lamp change due to Blinking

Lamp change due to Blinking

Lamps fused. Changed lamp.

Float valve repaired,welded

Cleared the condensate tray and flushed

Lamps changed

Quotation sent to SNS for replacement

Lamps changed

Condensor motor Rewinded in out door units.

Filter and Drain tray cleaned .

Lamp change due to Blinking

Lamp changed due to flickering

Informed to contractor to change Union.

Handle tighten

Informed to contractor

Sample painting done.Quotation sent to SNS for apinting alla


corridors. Waiting for approval.
Strainer Cleaned

Lamp changed due to flickering

Filter and Drain tray cleaned .

Cleared the condensate tray and flushed

13 Watts Lamp Changed-8 Nos

Fused bulb Replaced

Pressure vessel changed


Fused bulb Replaced

Fused bulb Replaced

Rectified problem

Flush tank changed

Shut off valve changed

Light fixed in the fittings

Adjusted the mechanism

Drain plate flushed and washed

Finished

Fused bulb Replaced

Contactor changed

Wall clock fixed

Fused bulb Replaced

Fused bulb Replaced

Rectified the problem

M.seal provided

Drain tray flushed and washed

Motor coil grounded.Motor rewinded.

Problem Rectified

Float ball brazing done and fixed

Lights chnaged

Lights chnaged

Rectified

All Basement Lift lobby & Stairs

Rectified

Drain tray flushed and washed

Checked and changed


Duct damage.Rectified

Arrested the leakage

Changed the lights

Water removed and changed lights

Booster pump fixed

Water removed

Arrested the leakage

Shower pipe changed.

Checked but works fine.

put run for 3 hrs

Changed the lamp

Light changed

Changed the lamp

Arrested the leakage

Lamps changed

Condensor motor Rewinded in out door units.

Filter and Drain tray cleaned .

Lamp change due to Blinking

Strainer Cleaned

Lamp changed due to flickering

Filter and Drain tray cleaned .

Cleared the condensate tray and flushed

Completed
Safety valve changed

Safety valve changed

Safety valve changed

Safety valve changed

Safety valve changed

Safety valve changed

Safety valve changed

Safety valve changed

Cover fixed

Lights changed

Light changed

Rivet fixed

Changed the lamp

Arrested the water leak

Lights changed

Adjusted the doors

Adjusted the doors

Changed the Lamps

Lights changed

Lamps changed

Thermostat changed

Drain tray flushed and cleaned


Flush button repaired

Lamps changed

Lamps changed

Door adjusted

T valve have to change

T valve problem , sent to repair or replace.

Lamps changed

Rectified

Lamps changed

Door adjusted

Doors rectified

Doors rectified

Glass cleaned

Drain tray flushed and cleaned

Shower pipe changed

Cleaned
Lamps changed

Lamps changed

Lamps changed

Drain tray flushed and cleaned

Drain tray flushed and cleaned

Insulation work done

Cleaned

Rectified

Lamps changed

unit 2- heat pump, compressor removed. Unit 1 - wiring done

Block removed

Cleaned

Changed new contactor

Changed new Transformer

unit 2- new heat pump fixed ,New compressor fixed. Unit 1 -


wiring done.Gas charged.

Drain tray flushed and cleaned

tube light changed

Changed

Gas charged, commisioned.


Drain tray flushed and cleaned

tube light changed

Changed

Released the block

Drain tray flushed and cleaned

Pressure switch changed.

Changed

Released the air lock

Drain tray flushed and cleaned

Checked inside flats and roof.

Changed

Checked inside flats and roof.

Found E3 error -water pressure

Shut off valve changed

Drain tray flushed and cleaned

Changed

Lamp changed
Drain tray flushed and cleaned

Changed

Tube light changed

Lamp changed

New screw fixed

Drain tray flushed and cleaned

Filter leakage arrested

Filter leakage arrested

Rectified

Remoed the block

Lamps changed

Drain tray flushed and cleaned

Lamps changed
Lamps changed

Blanket burnt due to cigerette. Advised to tenant to respond

Hose changed

Lamps changed

Lamps changed

Completed
Removed the Sealant

Lamps changed

Drain tray flushed and cleaned

Lamps changed

Unit no 2 4 way valve problem. Sent to repair

changed the hose

Released the drainline

Drain tray flushed and cleaned

Lamps changed

Lamps changed

Unit no 2 4 way valve problem. Sent to repair

changed the hose

Released the Airlock

Released the drainline

Drain tray flushed and cleaned

Lamps changed
Released the drainline

Drain tray flushed and cleaned

Lamps changed

Lamps changed

Lamps changed

Lamps changed

Drain tray flushed and cleaned

New NRV changed

Water spread. Now water dried and it working

Lamps changed

sent for rewinding

Released the air block.

changed the lamp

Draintray flushed and cleaned


Water leak arrested

changed the lamp

Cable checked

Water leak arrested

Changed the lamp

Fittings cleaned and sealed.and arrested the holes. 4 nos.Now


lights properly glowing.

Changed the lamp

Cable checked

Adjusted the door

Repaired the flush

LED lamp changed

Asked allawai electricals to come

Fan motor fixed

Released the block

Temperorily rectified

LED lamp changed

Rectified the phase change and trip.

Drain tray flushed and cleaned


Changed the Lamp

Lamps changed

Drain tray flushed and cleaned

Released the block

Silcon applied and rectified.

Lamps changed

Drain tray flushed and cleaned

Flush valve repaired

Lamps changed

Called for Allawai electricals

Drain tray flushed and cleaned

Cleaning finished

Inulation work completed

Lamps changed

Pending. Informed to allawai

adjusted the doors

informed to vision safety

Flow switch adjusted

Changed the lamps

Lamps changed

Flow switch adjusted


Adjusted the pressure

informed to vision safety

Unit reset

Changed the lamps

materials shifted

Adjusted the flush

Have to change smoke detector in 4th floor B block

Aligned properly

Changed the lamps

Repaired

Completed

Drain tray flushed and cleaned

Changed the lamps

Temperorily drained the reel. Informed to vision safety.

Completed

Lamps changed

corrected
Sent for repairing

Completed

Lamps changed

Completed

Informed to allawai

drain tray flushed and cleaned

Repaired

Completed

Completed

Changed the Tube light

Changed the Lamps

Asked to send technician

drain tray flushed and cleaned

Changed new float valve

Changed new float valve

Changed new hose


Changed the lamps

Changed the Lamps

Changed the Wheels

drain tray flushed and cleaned


Pump fixed

Checked roof shaft.

Changed the Lamps

Changed the lamps

Changed the Lamps

Completed

Changed the PPR line pipe and valve Handle.

Have to repair

Changed the Lamps

Completed

Changed the float valve

Pump no 1 pipeline covered with plastic sheet to restict air suction.

Changed the capacitor

Completed

Filter air block removed

Stainer filter cleaned


Slightly water leaking . Taking specification. Today we inform
to sub contractor.

Completed

Changed the Lamps

Filter air block removed


AMC CONTRACTORS SERVICE SCHEDULE SEP-2013 TO AUG - 2014

S.NO COMPANY NAME CONTACT PERSON- PHONE FREQUENCY SCHEDULE

SEP OCT NOV DEC JAN FEB MAR APR MAY JUN JUL AUG
1
VISION SAFETY(FA&FF) Mr.INAM - 0502515853 QUARTERLY 8TH- DONE 8th Done 8TH- SCHE 8TH- SCHE
2
AL SABBAH (GAS) Mr.SACHIN - 0557001149 MONTHLY 7TH DONE 7TH DONE 7TH DONE 16th Done 4th Done 7TH- SCHE 7TH- SCHE
3
ETA (ELEVATORS) Mr.ISLAM - 042359595 MONTHLY 23RD DONE 25TH DONE 16th done 24th Done scheduled scheduled scheduled scheduled scheduled scheduled scheduled scheduled
4
RENTOKIL (PEST CONT) Mr.RONALD - 044547162 2 MONTHS ONCE 14th DONE scheduled scheduled scheduled scheduled
5
SPORTS LINK (GYM EQU) Mr.ALFRED - 042895558 MONTHLY 21st Done 21st Done 20th done 19th done scheduled scheduled scheduled scheduled scheduled scheduled scheduled scheduled
6
ABCL -LIFT THIRD PARTY CUSTOMER CARE - 042999785 Half yearly 26 feb-scheduled 26 - AUG scheduled

POWER GROUP SUB CONTRACTORS SERVICE SCHEDULE SEP- 2013 TO AUG - 2014

S.NO COMPANY NAME CONTACT COMPANY NAME SCHEDULE

SEP OCT NOV DEC JAN FEB MAR APR MAY JUN JUL AUG

1 GWB INTL-GENERATOR OFFICE - 044472599 MONTHLY - ANUALLY 29th Done 31 st Done 27 Done 23 Done 13th Done scheduled scheduled scheduled scheduled scheduled scheduled scheduled

3 NEW LINE SYSTEMS- CCTV Mr.SEKAR - 0508409595 MONTHLY scheduled scheduled scheduled scheduled scheduled scheduled scheduled scheduled scheduled
NEW LINE SYSTEMS-GATE BARRIER MONTHLY
4 Mr.SEKAR - 0508409595 scheduled scheduled scheduled scheduled scheduled scheduled scheduled scheduled scheduled

5 SWIMMING POOL-DEEP BLUE Mr.SUNOJ - 0557901241 WEEKLY 2 TIMES Weekly 2 timeWeekly 2 times Weekly 2 times Weekly 2 times

Done
S.NO DESCRIPTION SCOPE STATUS REMARKS UPDATE
1 Painting for All Blocks A,B & C corridors power Approved Sample painting done
Completed with sns
2 Swimming Pool Heat exchanger Repairing Completed contractor( Allawai)
Lamps in Lift room to be changed from Waiting for Board Approval
3 Hologen to LED power Pending Quotation sent on 14/9/2013
4 Gym room Ceiling water Leakage power Completed completed Quotation sent on 14/9/2013
5 Swimming pool pump no : 1 water leakage SNS Completed Completed with sns contractor
6 Corridor wooden block varnishing power Pending Waiting for Board Approval Quotation sent on 17/9/2013
7 Water Proofing power Pending Quotation sent Quotation sent on 20/12/2013
Access control implementation & activation
8 for access doors SNS Completed started on 31/10/2013

Motion sensor implementation sample work


9 in C block Garbage room ground floor lights Portdata Completed completed on 11/9/2013
Motion sensor implementation in all common
10 area corridor Lights. Portdata Pending waiting for Quotation Waiting from still 11/9/2013
11 PPM activation Power Completed PPM schedule sent to client started from 19/9/2013
12 Swimming pool Filter water leakage power Pending Waiting for Board Approval Waiting from still 24/9/2013
13
Parking lights lights energy saving in basement power Pending Looking for solution Waiting from still 19/9/2013
Water entered in Pressure vessel C block -
14 roof. Need to change pressure vessel. Power Completed Pressure vessel changed Approved on 28/10/2013
Booster pump motor in C block has to
15 rewinded power Completed Motor rewinded. finished

16 Biological test to be carried in Swimming pool. Power Pending report came Discussing with client
17 Tank cleaning. power completed Completed on 30/12/2013
18 Swimming pool Pump No 2 replacement Power Pending Quotation sent on 8/1/2014
19 Swimming pool Pump No 4 replacement Power Pending Quotation sent on 8/1/2014
S.No Description Status

1 Quotation for heat exchanger repair No 1 Waiting for approval


2 Quotation of heating and cooling unit No 2 Waiting for approval
3 Quotation of Swimming pool pump Waiting for approval
4 Quotation of Rewinding Condensor motor Approved
5 Quotation of Painting for Corridors Waiting for approval
6 Quotation of Garbage wheels Waiting for approval
7 Quotation of Motion sensor – Garbage room Waiting for approval
8 Quotation of polish of wooden beeding Waiting for approval
9 Quotation of Lift LED lamps Waiting for approval
10 Quotation of Ceiling Leakage Gym room Waiting for approval
11 Quotation For Compressor -A block lift lobby A/C Waiting for approval
12 Quotation For Door catch Mechanism Waiting for approval
13 Quotation For Pressure vessel change in Roof -C block Approved
14 Quotation For Booster pump motor rewinding Roof -C block Approved
15 Quotation For Swimming pool Filter replacement Waiting for approval
16 Quotation for Swimming pool lights Replacement Waiting for approval
17 Quotation for Swimming pool tiles replacement Waiting for approval
18 Quotation of water proofing in Fountain Area Waiting for approval
19 Quotation of Water proofing in A block near Gas filling station Waiting for approval
20 Quotation fo Water proofing in C block near Main entrance Waiting for approval
22 Quotation for Swimming pool pump No 2 Replacement Waiting for approval
Reference number Quote Date

PIFM/0913/Q6218/P 26-Sep finished with sns contractor


PIFM/0913/Q6219/P 26-Sep finished with sns contractor
PIFM/1013/Q6242/P 7-Oct finished with sns contractor
PIFM/0913/Q6213/P 24-Sep Finished Power
PIFM/0913/Q6211/P- R2 24-Sep
PIFM/0913/Q6206/P 22-Sep
PIFM/0913/Q6210/P 24-Sep
PIFM/0913/Q6204/P 17-Sep
PIFM/0913/Q6187/P 9-Sep
PIFM/0913/Q6189/P 9-Sep
PIFM/1013/Q6270/P 31-Oct
PIFM/1013/Q6250/P 13-Oct finished with sns contractor
PIFM/1013/Q6230/C 1-Oct Finished Power
PIFM/1013/Q6257/C 22-Oct Finished Power
PIFM/1113/Q6282/P 11-Nov
PIFM/1113/Q6279/P 10-Nov
PIFM/1213/Q6331/P 19-Dec
PIFM1213/Q6330/P 18-Dec
PIFM/1213/Q6329/P 18-Dec
PIFM/1213/Q6328/P 16-Dec
PIFM/0114/Q6352/P/Rev-1 8-Jan
EQUIPMENTS MONITORING
S.No ITEMS TIMING 1 2 3 4 5 6 7 8 9 10 11
1 FAHU sat,wed -2PM - 4PM
2 Garden Sprinkler timings
3 Outside lights and Garden light Eve - 5.30 PM daily
4 Swimming pool Temperature 10AM,1PM,3PM,6PM

Monitored