GENERAL NOTES FOUNDATION NOTES (CONTINUED) REINFORCING STEEL NOTES STRUCTURAL STEEL NOTES
A. BUILDING AND DESIGN CODES: A. PROVIDE DETAILING, FABRICATION, AND INSTALLATION OF REINFORCING AND ACCESSORIES IN ACCORDANCE WITH ACI
K. FORM SIDES OF BEAMS STRAIGHT AND TO SPECIFIED DIMENSIONS. EARTH FORMS WILL NOT BE A. PROVIDE STRUCTURAL STEEL OF THE FOLLOWING ASTM DESIGNATIONS UNLESS OTHERWISE NOTED:
315 AND ACI 318.
1. GOVERNING CODE: 2015 INTERNATIONAL BUILDING CODE & 2016 NEW YORK STATE UNIFORM CODE SUPPLEMENT. PERMITTED.
1. STRUCTURAL STEEL WIDE FLANGE AND WT SHAPES - ASTM A 992
B. PROVIDE STEEL REINFORCING BARS IN ACCORDANCE WITH ASTM A615, GRADE 60.
2. ASCE 7 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES, THE LATEST EDITION L. REFER TO CIVIL DRAWINGS FOR LIMITS OF EXCAVATIONS.
ADOPTED BY THE GOVERNING CODE. 2. STRUCTURAL STEEL STANDARD SHAPES, CHANNELS AND ANGLES - ASTM A 36 JE ARCHITECTS/ENGINEERS, P.C.
C. PROVIDE WELDED WIRE FABRIC IN ACCORDANCE WITH ASTM A185. LAP WELDED WIRE FABRIC TWO FULL MESH PANELS
M. THE BOTTOM OF ALL PERIMETER FOUNDATIONS MUST BE PLACED AT LEAST 4'-0" BELOW FINAL AND TIE SECURELY. PLACE WELDED WIRE FABRIC IN THE UPPER ONE-THIRD OF SLAB THICKNESS. WELDED WIRE FABRIC 2 PENN PLAZA, SUITE 0603
3. AISC MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE FACTOR DESIGN AND CODE OF GRADE (FROST DEPTH). 3. EDGE ANGLES, BENT PLATES, HANGER AND BRACES - ASTM A 36
SHOULD BE DISCONTINUED AT ANY JOINTS. CONTRACTOR MUST ATTEND CLOSELY TO ESTABLISHING AND MAINTAINING NEW YORK, NEW YORK 10121
STANDARD PRACTICE, THE LATEST EDITION ADOPTED BY THE GOVERNING CODE. ADEQUATE SUPPORT OF THE WELDED WIRE FABRIC REINFORCEMENT DURING THE CONCRETE PLACING OPERATIONS.
N. EXCAVATIONS SHALL BE MADE WITH A BACKHOE BUCKET AFFIXED WITH A SMOOTH CUTTING BLADE 4. STRUCTURAL PIPE - ASTM A 53, GRADE B
WELDED WIRE FABRIC REINFORCEMENT SHALL NOT BE LAID ON THE GROUND AND "PULLED UP" AFTER THE CONCRETE
4. ACI 318 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE, THE LATEST EDITION (RATHER THAN TEETH) SO AS NOT TO DISTURB THE SOILS BELOW BEARING LEVEL. ANY OVER- HAS BEEN PLACED, NOR SHOULD THE MATS BE "WALKED ON" AFTER PLACING THE CONCRETE. PROPER SUPPORT BAR
G ADOPTED BY GOVERNING CODE. EXCAVATION OR UNDERCUTS SHOULD BE FILLED WITH FOOTING-CLASS CONCRETE, COMPACTED SPACING MUST BE PROVIDED FOR THE WELDED WIRE FABRIC REINFORCEMENT.
5. STRUCTURAL TUBING (SQUARE OR RECTANGULAR) - ASTM A 500, GRADE B G
SELECT GRANULAR FILL OR CLSM. THERE SHALL BE A MINIMUM OF 6 INCHES OF PROPERLY
COMPACTED SELECT GRANULAR FILL OR CLSM UNDER ALL FOOTINGS AND SLABS-ON-GRADE. 6. BASE PLATES AND MISCELLANEOUS STEEL PLATES - ASTM A 36 SUB CONSULTANT:
5. ACI 530 BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES, THE LATEST EDITION ADOPTED D. PROVIDE ANCHOR RODS CONFORMING TO THE STANDARDS OF ASTM F1554 GRADE 55 (WELDABLE) UNLESS OTHERWISE
BY GOVERNING CODES. NOTED.
O. FOOTING EXCAVATION AND BEARING GRADES SHALL BE KEPT FREE OF LOOSE SOIL, MUD, WATER, 7. CONNECTION MATERIALS:
6. CRSI MANUAL OF STANDARD PRACTICE, THE LATEST EDITION ADOPTED BY THE GOVERNING CODE. FROST OR FROZEN MATERIAL. E. COORDINATE PLACEMENT OF CAST-IN-PLACE EMBEDS AND ANCHOR RODS. SET ANCHOR RODS WITH A TEMPLATE.
a. BEAM-COLUMN STIFFENER PLATES AND DOUBLER PLATES TO MATCH THE GRADE STEEL OF
SECURELY ATTACH EMBED ITEMS TO FORMWORK OR REINFORCING.
7. SDI CODE OF RECOMMENDED STANDARD PRACTICE FOR COMPOSITE DECK, FORM DECKS, AND ROOF P. ALL AREAS TO RECEIVE FILL SHALL BE PROPERLY PREPARED, THEN PROOFROLLED, INPECTED AND STRUCTURAL ELEMENT
CONSTRUCTION, THE LATEST EDITION ADOPTED BY GOVERNING CODES. APPROVED BY THE PROFESSIONAL GEOTECHNICAL ENGINEER (PGE) PRIOR TO THE PLACEMENT OF b. ALL CONNECTION MATERIALS, EXCEPT AS OTHERWISE NOTED HEREIN OR IN THE DRAWINGS,
F. PROVIDE CLASS "B" REINFORCEMENT SPLICES FOR CONTINUOUS REINFORCEMENT. PROVIDE STANDARD 90-DEGREE
FILL. INCLUDING BEARING PLATES, GUSSET PLATES, STIFFENER PLATES, ANGLES, ETC. - ASTM A 36
HOOKS IN ACCORDANCE WITH ACI 318, UNLESS OTHERWISE NOTED. STAGGER SPLICES UNLESS SPECIFICALLY NOTED. JACOBS ENGINEERING NEW YORK
JE ARCHITECTS/ENGINEERS, P.C.INC
B. DESIGN LOADS:
Q. FILL MATERIAL SHALL BE PLACED ON THE APPROVED SUBGRADE IN A MANNER TO MINIMIZE 8. HIGH STRENGTH BOLTS (SLIP CRITICAL JOINTS FOR ALL BRACES, MEMBERS SUBJECT TO AXIAL LOAD, AND 2 PENN PLAZA,
2 PENN SUITE
PLAZA, 0603
SUITE 0603
G. MAINTAIN THE FOLLOWING CONCRETE COVERAGE FOR REINFORCING STEEL UNLESS OTHERWISE NOTED:
THE FOLLOWING DESIGN LOADS WERE USED FOR THE WEST ADDITION IN SECTORS Q AND R: SEGREGATION. THE FILL SHALL BE PLACED IN NEARLY HORIZONTAL LIFTS COMMENCING AT THE WHERE SPECIFIED) - ASTM A 325 NEW
NEWYORK, NEW
YORK, NEWYORK
YORK10121
10121
LOWEST FILL AREA ELEVATION AND PROCEEDING WITH EACH LIFT UPWARD AND OUTWARD FROM 1. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH - 3 INCHES
1. RISK/OCCUPANCY CATEGORY: III THE LOWER LIFT. 9. HARDENED STEEL WASHERS - ASTM F 436
2. CONCRETE EXPOSED TO EARTH OR WEATHER
2. DEAD LOADS: R. THE MOISTURE CONTENT OF THE MATERIAL SHALL BE ADJUSTED PRIOR TO THE APPLICATION OF 10. HEAVY HEX NUTS - ASTM A 563
COMPACTION SUCH THAT IT IS WITHIN 2% OF THE OPTIMUM MOISTURE CONTENT. THIS a. NO. 6 AND LARGER - 2 INCHES
FLOOR DEAD LOADS: PROCEDURE MAY INVOLVE ADDING WATER WHEN SOIL IS TOO DRY, OR DISCING AND AERATING TO B. WELD MINIMUM SIZE AND STRENGTH
b. NO. 5 AND SMALLER - 1-1/2 INCHES
FLOOR FINISH (1/2" TERRAZO): 7 PSF REDUCE MOISTURE WHEN THE SOIL IS TOO WET.
5 1/2” SLAB ON METAL DECK: 57 PSF 1. PROVIDE MINIMUM SIZE OF FILLET WELDS AS SPECIFIED IN TABLE J2.4 OF THE AISC MANUAL.
3. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH THE GROUND:
MECH/ELEC/PLUMB: 8 PSF S. THE COMPACTED LIFT THICKNESS AND MINIMUM IN-PLACE FIELD DENSITY SHALL CONFORM TO THE
INSULATION 3 PSF FOLLOWING TABLE BELOW: 2. PROVIDE MINIMUM EFFECTIVE THROAT THICKNESS OF PARTIAL PENETRATION GROOVE WELDS AS SPECIFIED IN
a. SLABS AND WALLS
SUSPENDED CEILING: 2 PSF TABLE J2.3 OF THE AISC MANUAL.
- NO. 14 AND NO. 18 - 1-1/2 INCHES
MISC. 5 PSF STRUCTURAL FILL COMPACTION AND LIFT THICKNESS REQUIREMENTS - NO. 11 AND SMALLER - 3/4 INCH
TOTAL 82 PSF 3. DEVELOP THE FULL TENSILE STRENGTH OF THE MEMBER ELEMENT JOINED ON ALL SHOP AND FIELD WELDS
MAXIMUM UNLESS OTHERWISE NOTED ON THE DRAWINGS.
F MINIMUM
COMPACTED LIFT FILL AREA DESCRIPTION
b. BEAM STIRRUPS AND COLUMN TIES - 1-1/2 INCHES F
ROOF DEAD LOADS: IN-PLACE DENSITY*
ROOFING: 2 PSF THICKNESS (INCHES) 4. WHERE CONNECTIONS ARE NOTED ON DRAWINGS AS MOMENT CONNECTIONS, PROVIDE WELDS TO DEVELOP
H. DO NOT WELD OR BEND REINFORCEMENT IN THE FIELD UNLESS SPECIFICALLY SHOWN OR APPROVED BY STRUCTURAL
PROTECTION BOARD: 3 PSF FULL FLEXURAL CAPACITY OF THE LESSER MEMBER. 05/21/2018
ENGINEER.
METAL DECK: 3 PSF 95% 10** FILL AND SUBBASE COURSE UNDER SLABS
MECH/ELEC/PLUMB: 5 PSF 5. PROVIDE ELECTRODES FOR FIELD OR SHOP WELDING THAT CONFORM TO AWS D1.1 CLASS E70XX. IT IS A VIOLATION OF LAW FOR ANY PERSON TO ALTER A DOCUMENT IN
I. WHEN SPECIFICALLY APPROVED, PROVIDE WELDED REINFORCEMENT IN ACCORDANCE WITH ASTM A 706. USE LOW
ANY WAY, UNLESS ACTING UNDER THE DIRECTION OF A LICENSED
INSULATION 3 PSF HYDROGEN ELECTRODES FOR WELDING OF REINFORCEMENT IN CONFORMANCE WITH "WELDING REINFORCEMENT PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. IF THIS
SUSPENDED CEILING: 2 PSF CONFINED AREAS SUCH AS UTILITY TRENCHES AND C. PROVIDE MINIMUM OF TWO BOLTS PER CONNECTION. MINIMUM BOLT DIAMETER TO BE 3/4 INCH.
95% 8** STEEL, METAL INSERTS AND CONNECTIONS IN REINFORCED CONCRETE CONSTRUCTION", AMERICAN WELDING SOCIETY, DOCUMENT BEARING THE SEAL OF AN ENGINEER/ARCHITECT IS ALTERED,
SOLAR PANELS: 10 PSF FOUNDATION BACKFILL AWS D1.4.
THE ALTERING ENGINEER/ARCHITECT SHALL AFFIX TO THE DOCUMENT

TOTAL 28 PSF D. PROVIDE BOLTS, NUTS AND WASHERS THAT ARE HOT DIP GALVANIZED ACCORDING TO ASTM A 153, CLASS C WHEN USED THEIR SEAL AND THE NOTATION "ALTERED BY" FOLLOWED BY THEIR
SIGNATURE AND THE DATE OF SUCH ALTERATION, AND A SPECIFIC
TO CONNECT ELEMENTS THAT ARE HOT DIP GALVANIZED AFTER FABRICATION. DESCRIPTION OF THE ALTERATION.
* AS DETERMINED USING ASTM D1557, MODIFIED PROCTOR. J. WHERE REQUIRED, PROVIDE DOWELS TO MATCH SIZE AND SPACING OF MAIN REINFORCING.
3. LIVE LOADS: ** OR COMPACTION EQUIPMENT MANUFACTURER'S RECOMMENDATIONS, WHICHEVER IS LESS. ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE ONLY FOR
E. PROVIDE SIMPLE SHEAR CONNECTIONS FOR STEEL CONNECTIONS NOT OTHERWISE SPECIFIED UTILIZING HIGH
K. PROVIDE CONTINUOUS HORIZONTAL WALL AND GRADE BEAM REINFORCEMENT WITH 90-DEGREE BENDS AND THE PURPOSE OF AUTHENTICATING THIS DOCUMENT.
FLOOR LIVE LOADS: STRENGTH BEARING BOLTS IN SINGLE OR DOUBLE SHEAR. PROVIDE DOUBLE ANGLE OR SINGLE PLATE SHEAR TAB RESPONSIBILITY FOR ALL OTHER DOCUMENTS RELATING TO THIS
EXTENSIONS AT CORNERS AND INTERSECTIONS AS SHOWN ON TYPICAL BAR PLACING DETAILS. PROJECT IS DISCLAIMED.
DEPARTURES LEVEL (UPPER FLOOR): 100 PSF BOLTED CONNECTIONS.
ARRIVALS LEVEL (GROUND FLOOR): 100 PSF T. WHEN THE TEST RESULTS INDICATE THAT INSUFFICIENT COMPACTION HAS BEEN OBTAINED IN ANY L. PROVIDE BAR SUPPORT ACCESSORIES IN ACCORDANCE WITH THE LATEST ACI MANUAL OF STANDARD PRACTICE FOR
ELECTRICAL ROOM: 150 PSF LAYER, THE CONTRACTOR SHALL TAKE ACTION TO MODIFY OR ALTER THE MOISTURE CONTENT OF 1. UNLESS LARGER REACTION IS SHOWN ON DRAWINGS, PROVIDE MIN DESIGN FORCES AS FOLLOWS:
DETAILING REINFORCED CONCRETE STRUCTURES. SUPPORT BEAM REINFORCING ON BEAM BOLSTERS SPACED NOT
ALL OTHER AREAS: 100 PSF THE SOIL, TO PROVIDE ADDITIONAL COMPACTION OR OTHERWISE TO INCREASE THE IN-PLACE SOIL MORE THAN 4 FEET ON CENTER.
DENSITY. IF THE CONTRACTOR CANNOT OBTAIN SATISFACTORY COMPACTION DUE TO THE a. NON-COMPOSITE BEAMS: BEAM-TO-BEAM OR BEAM-TO-COLUMN CONNECTION TO DEVELOP THE
ROOF LIVE LOAD: 20 PSF MATERIAL PROPERTIES, THE CONTRACTOR SHALL REMOVE THE UNSATISFACTORY MATERIAL AND REACTION OF CONNECTED BEAM. OBTAIN END REACTION FROM UNIFORM LOAD TABLES OF THE AISC
M. PROVIDE BAR SUPPORTS WITH PLASTIC COATED LEGS OR HOT DIP GALVANIZING AFTER FABRICATION FOR CONCRETE
REPLACE WITH NEW MATERIAL. MANUAL OF STEEL CONSTRUCTION. PROVIDE MINIMUM SHEAR CAPACITY OF 12,000 POUNDS FOR BEAMS
EXPOSED TO VIEW. PROVIDE STAINLESS STEEL BAR SUPPORTS FOR CONCRETE TO RECEIVE A SANDBLAST FINISH.
4. SNOW LOADS: DEEPER THAN 8". PROVIDE MINIMUM SHEAR CAPACITY OF 8,000 POUNDS FOR BEAMS LESS
U. MATERIALS WHICH ARE FROZEN OR WHICH ARE CONTAMINATED WITH MUD, DEBRIS, ORGANICS OR THAN 8 INCHES DEEP.
GROUND SNOW LOAD - Pg: 50 PSF OTHER DELETERIOUS MATERIALS SHALL BE REMOVED AND REPLACED WITH UNCONTAMINATED
FLAT ROOF SNOW LOAD - Pf: 38 PSF SPECIFIED MATERIAL. 2. ADD TO REACTIONS LISTED ABOVE LOADS OR REACTIONS OF MEMBERS SUPPORTED BY BEAM WITHIN 3 FEET OF
BEAM END AND VERTICAL COMPONENTS OF FORCES IN BRACE MEMBERS FRAMING INTO BEAM.
SNOW EXPOSURE FACTOR - Ce:
SNOW LOAD IMPORTANCE FACTOR, Is:
1.0
1.1 V. NO FILL SHALL BE PLACED OVER AN AREA OR LIFT OF FILL THAT HAS NOT BEEN TESTED AND CONCRETE NOTES
E THERMAL FACTOR - Ct: 1.0 ACHIEVED SATISFACTORY RESULTS. F. STEEL FABRICATION E
A. PROVIDE CONCRETE AS SHOWN IN THE CONCRETE MATERIAL SCHEDULE BELOW. PROVIDE
5. WIND LOADS: W. ALL STRUCTURAL FILL AND BACKFILL SHALL CONSIST OF SELECT GRANULAR FILL OR CONTROLLED BATCH MIXING, TRANSPORTATION, PLACING AND CURING OF CONCRETE IN ACCORDANCE WITH 1. FABRICATE AND ASSEMBLE STRUCTURAL MEMBERS/ASSEMBLIES IN SHOP TO GREATEST EXTENT POSSIBLE.
LOW STRENGTH MATERIAL (CLSM). ON-SITE EXCAVATED MATERALS SHALL NOT BE RE-USED AS FILL RECOMMENDATIONS OF ACI 301, ACI 318 AND ASTM C94. USE TYPE I PORTLAND CEMENT
BASIC WIND SPEED (3 SECOND GUST): 120 MPH OR BACKFILL. CONTRACTOR SHALL PROPERLY DISPOSE OF ALL EXCAVATED MATERIALS OFF-SITE. UNLESS OTHERWISE NOTED. PROVIDE ADMIXTURES AND SPECIAL REQUIREMENTS AS SPECIFIED. 2. CAMBER OF STRUCTURAL STEEL MEMBERS IS INDICATED ON THE DRAWINGS. WHERE POSSIBLE, CAMBER OF
WIND EXPOSURE CATEGORY: C BEAMS TO BE APPLIED BY COLD BEND PROCESS. CAMBER INDICATED ON DRAWINGS ARE INTENDED TO BE FINAL
INTERNAL PRESSURE COEFFICIENTS - GCpi: +/- 0.18 X. SELECT GRANULAR FILL MATERIAL SHALL BE WELL-GRADED SAND AND GRAVEL, APPROVED B. UNLESS SPECIFIED BELOW, CONCRETE MUST REACH THE FOLLOWING PERCENTAGES OF CAMBER AT TIME OF ERECTION, AND WITHIN A TOLERANCE OF MINUS ZERO TO PLUS 1/8 INCH FOR EACH TEN FEET
COMPONENTS AND CLADDING WIND PRESSURES: REFER TO SCHEDULES ON S-005. RECYCLED PRODUCT OR CRUSHED ROCK PRODUCT WHICH IS CAPABLE OF BEING COMPACTED TO ITS 28 DAY COMPRESSIVE STRENGTH (F'c) BEFORE FORMS MAY BE REMOVED: OF MEMBER LENGTH.
THE REQUIRED DENSITY AT THE PROPER MOISTURE CONTENT AND WHICH IS FREE OF
6. SEISMIC LOADS: DELETERIOUS MATERIALS, TRASH, ROOTS, DEBRIS, FROZEN MATERIAL AND ORGANIC OR OTHER 1. WALLS, COLUMNS AND BEAM SIDES - 40 PERCENT 3. SPLICING OF STRUCTURAL STEEL MEMBERS IS PROHIBITED WITHOUT PRIOR APPROVAL BY THE A/E.
SEISMIC IMPORTANCE FACTOR - Ie: 1.25 FOREIGN MATTER. 2. BEAM BOTTOMS - 70 PERCENT
MAPPED SPECTRAL RESPONSE ACCELERATIONS: Ss = 0.212, S1 = 0.061 3. SHORING FOR FLOOR SYSTEM - 85 PERCENT 4. CONTRACTOR WILL BE RESPONSIBLE FOR ALL ERRORS OF DETAILING ON THE SHOP DRAWINGS, ERRORS IN
SITE CLASS: D Y. SELECT GRANULAR FILL MATERIAL SHALL BE ACCEPTED ON THE BASIS OF GRADATION, FABRICATION AND THE CORRECT FITTING OF STRUCTURAL STEEL MEMBERS.
SPECTRAL RESPONSE COEFFICIENTS: Sds = 0.226, Sd1 = 0.098 SOUNDNESS, PLASTICITY INDEX AND A WELL-DEFINED MOISTURE-DENSITY RELATIONSHIP CURVE. C. PROVIDE CONCRETE MIXES DESIGNED BY A QUALIFIED TESTING LABORATORY FOR REVIEW AND
SEISMIC DESIGN CATEGORY: B IMPORTED GRANULAR FILL SHALL BE PLACED WITHIN 2'-0" OF FINAL EXTERIOR GRADE SHALL BE APPROVAL BY THE STRUCTURAL ENGINEER. G. SEE ARCHITECTURAL DRAWINGS FOR FIRE RATING REQUIREMENTS.
BASIC SEISMIC-FORCE-RESISTING SYSTEM: STEEL SYSTEMS NOT SPECIFICALLY DETAILED SUBJECT TO SOUNDNESS REQUIREMENTS. SOUNDNESS SHALL BE LESS THAN 30% LOSS BASED ON
FOR SEISMIC RESISTANCE & A FOUR-CYCLE MAGNESIUM SULFATE SOUNDNESS TEST. PLASTICITY INDEX OF THAT PORTION OF D. PROVIDE CONSTRUCTION AND CONTROL JOINTS AS INDICATED ON DRAWINGS. HORIZONTAL H. NO COLUMN OR BEAM SPLICES, UNLESS CLEARLY INDICATED ON STRUCTURAL DRAWINGS ARE ALLOWED
ORDINARY MASONRY SHEAR WALLS. FILL MATERIAL PASSING THROUGH THE No. 40 MESH SIEVE SHALL NOT EXCEED 5.0. GRADATION CONSTRUCTION JOINTS ARE NOT ALLOWED UNLESS SPECIFICALLY NOTED OR APPROVED BY WITHOUT WRITTEN APPROVAL OF STRUCTURAL ENGINEER.
ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL FORCE METHOD SHALL BE AS FOLLOWS: STRUCTURAL ENGINEER. NOTIFY STRUCTURAL ENGINEER OF PROPOSED CONSTRUCTION JOINT
SEISMIC RESPONSE COEFFICIENT: Cs = 0.141 OR CONTROL JOINT LOCATIONS WHICH ARE DIFFERENT OR IN ADDITION TO JOINTS INDICATED ON I. WELDING OF GALVANIZED STEEL MUST BE IN CONFORMANCE WITH AWS APPROVED PROCEDURES FOR WELDING
RESPONSE MODIFICATION FACTOR: R=2 SIEVE SIZE PERCENT PASSING BY DRY WEIGHT DRAWINGS. PROVIDE 6,000-SQUARE FOOT MAXIMUM AREA OF CONCRETE PLACEMENT IN THE GALVANIZED STEEL, INCLUDING REMOVAL OF GALVANIZED COATING ON SURFACES TO BE WELDED OR FIELD
DESIGN BASE SHEAR: 120 kips 2 INCH 100 SLAB BETWEEN CONSTRUCTION JOINTS. PROVIDE 75-FOOT MAXIMUM SPACING OF CONSTRUCTION CERTIFICATION OF PROCEDURES TO WELD THROUGH GALVANIC COATING.
1/4 INCH* 30 TO 65 JOINTS IN GRADE BEAMS. PROVIDE GRADE BEAM CONSTRUCTION JOINTS IN MIDDLE 1/3 OF THE
7. FLOOD HAZARD INFORMATION: No. 40 5 TO 40 SPAN. WHEN A BEAM INTERSECTS A GIRDER WITHIN THE MIDDLE 1/3 OF THE GIRDER'S SPAN, J. REPAIR SURFACES WHERE GALVANIC COATING HAS BEEN DAMAGED WITH COLD GALVANIZING REPAIR PAINT PER
THIS BUILDING IS NOT DESIGNED FOR FLOOD LOADS. No. 200 0 TO 10 OFFSET THE JOINT IN THE GIRDER A DISTANCE EQUAL TO TWICE THE WIDTH OF THE BEAM. ASTM A780 OR WITH A ZINC-RICH PAINT.

*CRUSHED ROCK PRODUCTS (RUN-OF-CRUSH) MUST CONFORM TO 25 TO 60% PASSING ON THE E. WHERE CONSTRUCTION JOINTS ARE INDICATED ON STRUCTURAL DRAWINGS OR DETAILS, THE K. CONFORM TO THE AISC CODE OF STANDARD PRACTICE, FOR ERECTION TOLERANCES. FIELD MODIFICATION TO
D C. GENERAL REQUIREMENTS:
STRUCTURAL STEEL IS PROHIBITED WITHOUT PRIOR APPROVAL BY THE A/E.
D
1/4 INCH SIEVE. INTERFACE MUST BE ROUGHENED TO AN AMPLITUDE OF 1/4". CONSTRUCTION JOINTS NOT
1. SPECIFICATIONS ARE PART OF THE CONSTRUCTION DOCUMENTS AND MUST BE USED IN SHOWN MUST BE LOCATED BY THE CONTRACTOR, APPROVED BY THE A/E.
CONJUNCTION WITH THE DRAWINGS. Z. ALL GRADES TO BE COVERED WITH CONTROLLED LOW STRENGTH MATERIAL (CLSM) SHALL BE L. CLEAN STEEL OF RUST, LOOSE MILL SCALE AND OTHER FOREIGN MATERIALS WHERE REQUIRED FOR FABRICATION,
EXAMINED, TESTED AND APPROVED BY THE INSPECTING PROFESSIONAL GEOTECHNICAL ENGINEER F. PROVIDE CONSTRUCTION JOINTS IN WALLS, ELEVATED SLABS, AND ELEVATED BEAMS SPACED FITTING UP, OR WELDING.
2. ALL DIMENSIONS, ELEVATIONS AND ASSUMED EXISTING CONDITIONS ARE TO BE VERIFIED IN THE PRIOR TO POURING CLSM. LESS THAN 60 FEET APART IN ANY DIRECTION.
FIELD. SUCH VERIFICATION IS THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR MUST M. DO NOT CUT STRUCTURAL STEEL MEMBERS FOR THE WORK OF OTHER TRADES WITHOUT PRIOR REVIEW AND APPROVAL
IMMEDIATELY NOTIFY THE ARCHITECT AND ENGINEER OF RECORD OF ANY DISCREPANCIES OR AA. CLSM SHALL MEET ALL THE REQUIREMENTS OF NYSDOT STANDARD SPECIFICATIONS SECTION 204 G. CHAMFER EXPOSED EDGES 3/4 INCH UNLESS OTHERWISE NOTED. OF THE A/E.
CONFLICTS. AND EXHIBIT A COMPRESSIVE STRENGTH AT 28 DAYS OF NOT LESS THAN 120 PSI.
H. WIRE BRUSH AND CLEAN CONSTRUCTION JOINTS PRIOR TO POURING NEW CONCRETE. N. AFTER FABRICATION, HOT DIP GALVANIZE STRUCTURAL STEEL AND THEIR CONNECTIONS PERMANENTLY EXPOSED TO
3. VERIFY THE LOCATION OF CHASES, INSERTS, OPENINGS, SLEEVES, FINISHES, DEPRESSIONS, BB. PRESUMPTIVE SOIL BEARING PRESSURE OF EVERY FOOTING SHALL BE VERIFIED IN THE FIELD THE OUTSIDE. SUCH ITEMS INCLUDE BUT ARE NOT LIMITED TO:
PADS, AND WALL OPENINGS. PRIOR TO PLACEMENT OF FORMWORK AND REINFORCEMENT STEEL. REFER TO SPECIAL I. REFERENCE THE APPROPRIATE DISCIPLINE'S DRAWINGS FOR SUB SLAB PIPING, FLOOR DRAINS,
INPSPECTION TABLES FOR SOILS ON SHEET S-004. AND SLAB AND WALL PENETRATIONS. 1. SHELF ANGLES
4. DO NOT SCALE DRAWINGS FOR THE PURPOSE OF ESTABLISHING DIMENSIONS.
J. THE GENERAL CONTRACTOR MUST COORDINATE EMBEDS AND ANCHORAGES WITH OTHER 2. PARAPET WALL SUPPORTING MEMBERS
APPROPRIATE CONTRACTORS FOR WORKS TO BE ATTACHED OR ANCHORED TO CAST-IN-PLACE
5. DETAILS LABELED "TYPICAL DETAILS" ON DRAWINGS APPLY TO SITUATIONS OCCURRING ON THE
PROJECT THAT ARE THE SAME OR SIMILAR TO THOSE SPECIFICALLY DETAILED. SUCH DETAILS SUPPORT OF EXCAVATION AND PROTECTION OF EXISTING STRUCTURES. 3. SCREEN WALL SUPPORTING MEMBERS Niagara Frontier
APPLY WHETHER OR NOT DETAILS ARE REFERENCED AT EACH LOCATION. NOTIFY ENGINEER OF
CONFLICTS REGARDING APPLICABILITY OF "TYPICAL DETAILS".
FOUNDATION NOTES K. IN LOCATIONS WHERE NEW CONCRETE IS CAST AGAINST EXISTING CONCRETE OF MORE THAN 4. EMBEDDED PLATES IN CONCRETE
Transportation Authority
28 DAYS OF AGE, THE EXISTING CONCRETE MUST BE ROUGHENED TO 1/4" AMPLITUDE AND Serving the Niagara Region
A. CONTRACTOR SHALL PROVIDE SATISFACTORY SUPPORT OF EXCAVATION (SOE) AND TEMPORARY THOROUGHLY CLEANED OF ANY LAITANCE OR FOREIGN MATERIALS, THEN SATURATED WITH 5. BUILDING CLADDING SUPPORT STEEL
6. DO NOT LOAD THE SLAB ON GRADE OR SUPPORTED SLAB WITH ERECTION CRANES OR
EXCAVATION PROTECTION SYSTEMS, TO PROTECT AND PREVENT ANY VERTICAL OR HORIZONTAL MOVEMENT WATER. ALL STANDING WATER MUST BE REMOVED PRIOR TO PLACEMENT OF NEW CONCRETE.
ERECTION EQUIPMENT. THE SLABS HAVE NOT BEEN DESIGNED FOR CRANE LOADS AND WILL
OF EXISTING SLABS AND FOUNDATIONS AS WELL AS TO PROVIDE WORKER SAFETY PER OSHA AND NYCRR
REQUIRE AN INCREASE IN THICKNESS AND/OR REINFORCEMENT. OBTAIN A/E APPROVAL ON
PROPOSED CRANE SUPPORT PLAN FOR SLABS PRIOR TO COMMENCING WORK.
REGULATIONS AND LAWS. L. EVERY EFFORT MUST BE EXERCISED TO AVOID CRACKS IN CONCRETE WORK. IN THE EVENT
O. EXAMINE THE ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR OTHER ITEMS THAT REQUIRE HOT DIPPED
GALVANIZATION. BNIA - BAGGAGE CLAIM
7. DO NOT STORE OR STACK CONSTRUCTION MATERIALS ON POURED OR ERECTED
B. ALL (SOE) AND TEMPORARY EXCAVATION PROTECTION SYSTEMS SHALL BE DESIGNED BY A LICENSED
OF SHRINKAGE CRACKS, ETC. THE GENERAL CONTRACTOR MUST BE RESPONSIBLE TO
REPAIR THESE CRACKS WITH EPOXY GROUT. P. PROVIDE NON-SHRINK/NON-METALLIC GROUT FOR BASE PLATES WITH MINIMUM 28 DAY COMPRESSIVE STRENGTH OF EXPANSION
PROFESSIONAL ENGINEER IN THE STATE OF NEW YORK WITH AT LEAST 5 YEARS OF EXPERIENCE IN DESIGN 8000 PSI. COMPLETE GROUT WORK BEFORE ROOF CONCRETE POURING OF A SINGLE STORY BUILDING OR SECOND
FLOORS/ROOFS. GENERAL CONTRACTOR WILL ENSURE THAT ALL SUB-CONTRACTORS ARE
C AND INSTALLATION OF SUCH SYSTEMS HIRED BY THE CONTRACTOR. M. TOPPING CONCRETE MUST BE WET CURED FOR A MINIMUM OF 7 DAYS AND THEN A CONCRETE FLOOR CONCRETE POURING OF A MULTIPLE STORY BUILDING. C
INFORMED OF RESTRICTIONS. AVOID IMPACT WHEN PLACING MATERIALS ON POURED OR
ERECTED FLOORS OR ROOF. SEALER SHALL BE APPLIED PER THE SPECIFICATIONS.
C. (SOE) AND TEMPORARY EXCAVATION PROTECTION SYSTEM DESIGNS SHALL INCLUDE THE PROVISION FOR Q. SUBMIT CALCULATIONS FOR CONNECTION DESIGNS NOT DETAILED ON DRAWINGS. DESIGN CONNECTIONS UNDER
MONITORING THE MOVEMENT OF EXISTING STRUCTURES DURING INSTALLATION, IN-SERVICE, AND AFTER N. PROVIDE ADEQUATE STRUCTURAL FRAMING AS APPROVED BY STRUCTURAL ENGINEER FOR SUPERVISION OF REGISTERED STRUCTURAL ENGINEER WHO IS REGISTERED IN THE STATE OF NEW YORK AND
8. THE CONTRACT STRUCTURAL DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THE
EXTRACTION/REMOVAL OF (SOE). MECHANICAL OPENINGS THROUGH THE SLABS, WALLS, AND FLOOR DECK. OPENINGS WILL NOT BE EMPLOYED BY THE STEEL FABRICATOR. DESIGN CALCULATIONS TO BE SEALED BY FABRICATOR'S REGISTERED
CONTRACTOR IS RESPONSIBLE FOR THE MEANS AND METHODS OF CONSTRUCTION. PROVIDE
ALL MEASURES REQUIRED TO PROTECT THE STRUCTURE (NEW AND EXISTING), WORKMEN, AND OTHER PERSONS PERMITTED THROUGH BEAMS UNLESS SPECIFICALLY DETAILED. STRUCTURAL ENGINEER. SHOP DRAWINGS SUBMITTED WITHOUT COMPLETE DESIGN CALCULATIONS WILL NOT BE
D. MONITORING PROVISIONS SHALL INCLUDE MAXIMUM LIMITS FOR MOVEMENT, LOCATION, AND TYPE AND REVIEWED. WHERE PREDESIGNED CONNECTIONS ARE TAKEN DIRECTLY FROM TABLES IN AISC MANUAL, CALCULATIONS
DURING CONSTRUCTION; INCLUDING BRACING, SHORING FOR CONSTRUCTION EQUIPMENT,
DETAILS OF THE GEOTECHNICAL INSTRUMENTS/MONITOR POINTS AND SHALL ADDRESS MAXIMUM FUGITIVE O. FOR PIPE INSTALLED HORIZONTALLY WITHIN SLAB, PROVIDE MAXIMUM OUTSIDE DIAMETER OF 30 NEED NOT BE SUBMITTED PROVIDED JOB DESIGN CONDITIONS PRECISELY MATCH THOSE ASSUMED IN THE AISC MANUAL.
SHORING FOR THE BUILDING (NEW AND EXISTING), FORMS AND SCAFFOLDING, SHORING OF RETAINING WALLS AND
VIBRATION LIMITS SO THAT EXISTING OR NEW CONSTRUCTION IS NOT DAMAGED. PERCENT OF THE SLAB THICKNESS. PLACE CONDUIT OR PIPE BETWEEN THE TOP AND BOTTOM
OTHER TEMPORARY SUPPORTS AS REQUIRED.
LAYERS OF REINFORCEMENT WITHIN THE CENTER THIRD OF THE SLAB. DO NOT SPACE CONDUITS R. FURNISH STEEL SHOP DRAWINGS FOR ARCHITECT'S AND STRUCTURAL ENGINEER'S REVIEW PRIOR TO FABRICATION.
9. PRINCIPAL OPENINGS THROUGH THE FRAMING ARE SHOWN ON DRAWINGS. EXAMINE THE OR PIPES CLOSER THAN THREE DIAMETERS OR WIDTHS ON CENTER. INCLUDE WELDING PROCEDURES, TESTING PROGRAMS FOR WELDING AND HIGH STRENGTH BOLTING, COATING
ARCHITECTURAL, MECHANICAL, PLUMBING, ELECTRICAL, AND FIRE PROTECTION DRAWINGS FOR MATERIAL, AND ERECTION SEQUENCE ON SHOP DRAWINGS.
THE REQUIRED OPENINGS AND PROVIDE FOR REQUIRED OPENINGS WHETHER SHOWN ON THE
STRUCTURAL DRAWINGS OR NOT. VERIFY SIZE AND LOCATION OF OPENINGS WITH THE S. MILL STEEL COLUMN ENDS TO FIT FLUSH WITH BASE PLATE, CAP PLATE, AND END PLATES. FIELD ASSEMBLY OF THESE
MECHANICAL CONTRACTOR. DEVIATIONS FROM THE OPENINGS SHOWN ON THE STRUCTURAL STEEL ELEMENTS TO THE COLUMNS IS PROHIBITED.
DRAWINGS MUST BE APPROVED PRIOR TO IMPLEMENTING THE CHANGES. CONCRETE MATERIAL SCHEDULE (NORMAL WEIGHT CONCRETE)
T. HEADED STUDS (SHEAR AND ANCHOR) AND DEFORMED ANCHORS.
10. DO NOT CUT OR DRILL THROUGH EXISTING REINFORCING OR CABLE TENDONS. X-RAY TO
LOCATE REINFORCING OR CABLE TENDONS AT LOCATIONS REQUIRING CUTTING OR CORING MINIMUM 28 DAY MAXIMUM WATER/ DRY UNIT MAXIMUM AGGREGATE DESIGN AIR MAXIMUM 1. PROVIDE HEADED STUDS (SHEAR AND ANCHOR) MADE OF MATERIAL CONFORMING TO ASTM A108.
PRIOR TO START OF CONSTRUCTION. SUBMIT REINFORCEMENT AND TENDONS LOCATION IN ELEMENT CYLINDER STRENGTH CEMENTITIOUS RATIO WEIGHT AGGREGATE SIZE CLASS DESIGNATION CONTENT MAXIMUM DESIGN SLUMP CHLORIDE
CONFLICT WITH DRAWINGS FOR A/E REVIEW. (ASTM C33) CONTENT 2. PROVIDE DEFORMED ANCHORS MADE OF MATERIAL CONFORMING TO ASTM A496

FOOTINGS 4500 (PSI) 0.45 147 (PCF) 3/4" 3S 6 1/2% ±2% 4"/ 8" 0.30% 3. WELD STUDS ACCORDING TO MANUFACTURER'S RECOMMENDATIONS. MANUAL ARC (STICK) WELDING OF
HEADED STUDS AND/OR DEFORMED ANCHORS IN NOT ALLOWED.
FOUNDATION NOTES
GRADE BEAMS AND PIERS 4500 (PSI) 0.45 147 (PCF) 3/4" 3S 6 1/2% ±2% 4" / 8" 0.30% U. PRIOR TO DECK PLACEMENT, VERIFY THAT STEEL BEAMS BEARING ON MASONRY HAVE 6 INCH MINIMUM BEARING AND
A. REFER TO THE GEOTECHNICAL REPORT AND SPECIFICATIONS FOR GENERAL REQUIREMENTS OF ARE ANCHORED AS SHOWN ON DRAWINGS.
B EARTHWORK, OVER EXCAVATION, SUBGRADE PREPARATION, FILL AND COMPACTION, B
WATERPROOFING AND OTHER PERTINENT REQUIREMENTS AND INFORMATION. V. ULTRASONICALLY TEST FULL AND PARTIAL PENETRATION WELDS AND COLUMN BASE PLATE DETAILS AT MOMENT
CAST IN PLACE CONCRETE FRAMING
ABOVE GRADE AND EXPOSED TO CONNECTED WELDED FRAMES.
B. FOUNDATION DESIGN IS BASED UPON THE SOILS EXPLORATION REPORT ENTITLED 3/4"
"BNIA - BAGGAGE CLAIM EXPANSION, BUFFALO, NEW YORK ", DATED APRIL 28, 2017 REPORT WEATHER, 4500 (PSI) 0.45 147 (PCF) 4S 6 1/2% ±2% 4" / 8" 0.30%
FREEZE AND THAW, AND DE-ICING W. PROVIDE TEMPORARY SHORING OR BRACING DURING CONSTRUCTION PHASE PRIOR TO COMPLETING CONNECTIONS
NUMBER 27216B-01-0417, BY CME ASSOCIATES INC.
AGENT (*) AND POURING OF FLOOR SLAB. 0 05/21/18 ISSUED FOR BIDS
C. SPREAD FOOTINGS ARE DESIGNED FOR AN ALLOWABLE NET BEARING PRESSURE
OF 4000 PSF. MARK DATE DESCRIPTION
D. PROTECT PIPES AND CONDUITS RUNNING THRU WALLS AND SLABS WITH 1/2 INCH
COLUMNS AND BEAMS WITHIN THE
ELEVATOR CORE 4000 (PSI) 0.50 147 (PCF) 3/4" 1S N/A 4" / 8" 0.30% METAL DECK NOTES NFTA PROJECT NO: 10BT1516
EXPANSION MATERIAL. LOWER CONTINUOUS FOOTINGS AND GRADE BEAMS A. METAL ROOF DECK AND FLOOR DECK AS INDICATED IN THE DRAWINGS, GALVANIZED, AND CONTINUOUS OVER 3 OR MORE
PERPENDICULAR TO PIPE RUNS, TO ALLOW PIPES TO PASS ABOVE THE FOOTINGS OR DESIGNER PROJECT NO: F8Z94900
SPANS. FURNISH IN SINGLE SHEETS.
THROUGH THE GRADE BEAMS. ALTERNATIVELY, PROVIDE A CONCRETE JACKET IF PIPES FILE NAME: F8Z94900_BUF_STRUCT_A360.rvt
ARE LOW ENOUGH TO BE PLACED BELOW THE FOOTINGS AND GRADE BEAMS. LOWER SLAB ON GRADE/SLAB ON METAL DECK 3000 (PSI) 0.52 147 (PCF) 3/4" 1S N/A 4" / 8" 0.30% B. METAL ROOF DECK IS DESIGNED FOR DIAPHRAGM ACTION AND MUST BE FASTENED USING 5/8" PUDDLE WELDS TO ALL
FOOTINGS AND GRADE BEAMS PARALLEL TO PIPE RUNS TO AVOID SURCHARGE ONTO SUPPORTS PER STEEL DECK INSTITUTE 36/7 PATTERN AS FOLLOWS:36/7 - END LAP MUST BE FASTENED THROUGH BOTH DRAWN BY: VH
ADJACENT TRENCH EXCAVATIONS. PIECES, AT EACH SIDE LAP AND ALL FLUTES BETWEEN. AT INTERMEDIATE SUPPORTS, FASTENERS MUST OCCUR AT EACH CHECKED BY: MT
SIDE LAP AND AT ALL FLUTES BETWEEN. SIDE LAPS MUST BE (10) #10 SCREW FASTENERS BETWEEN SUPPORTS. AT
E. MAINTAIN SUBGRADE AND FILL MOISTURE CONTENT UNTIL FOUNDATIONS ARE PLACED. (*) CORROSION INHIBITOR ADMIXTURE SHALL BE ADDED TO CONCRETE MIX. CORNER CONDITIONS, DENOTED AS ZONES 3 AND 3O ON SHEET S-005, SUPPORT DECK WITH (2) WELDS IN EACH RIB. COPYRIGHT:
F. ARRANGE FOR OWNER'S INDEPENDENT TESTING AGENCY TO MONITOR CUT AND FILL 1. THICKNESS: 0.0474 IN
OPERATIONS, AND PERFORM FIELD DENSITY AND MOISTURE CONTENT TESTS TO VERIFY
COMPACTION AND APPROVE FOOTING SUBGRADE PRIOR TO PLACING CONCRETE.
2. SECTION MODULUS (Sp): 0.318 IN3/FT SHEET TITLE:
3. MOMENT OF INERTIA (Ip): 0.289 IN4
G. DO NOT PLACE FOUNDATION ELEMENTS OR SLABS AGAINST SUBGRADE CONTAINING C. METAL FLOOR DECK IS DESIGNED FOR DIAPHRAGM ACTION AND MUST BE FASTENED USING 5/8" PUDDLE WELDS TO ALL
STRUCTURAL NOTES -
FREE WATER, FROST, SNOW OR ICE.
A
SUPPORTS PER STEEL DECK INSTITUTE 36/4 PATTERN AS FOLLOWS: 36/4 - END LAP MUST BE FASTENED THROUGH BOTH
PIECES, AT EACH SIDE LAP AND ALL FLUTES BETWEEN. AT INTERMEDIATE SUPPORTS, FASTENERS MUST OCCUR AT EACH
WEST A
H. MAINTAIN PROPER SITE DRAINAGE DURING CONSTRUCTION TO ENSURE SURFACE RUNOFF AWAY SIDE LAP AND AT ALL FLUTES BETWEEN. SIDE LAPS MUST BE (5) PUDDLE WELDS BETWEEN SUPPORTS.
FROM STRUCTURES AND TO PREVENT PONDING OF SURFACE RUNOFF NEAR THE STRUCTURES.
1. THICKNESS: 0.0474 IN WEST ADDITION CONTRACTOR NOTE
I. KEEP OPEN EXCAVATIONS AROUND BUILDING DRY. BACKFILL AGAINST FOUNDATIONS AND 2. SECTION MODULUS (Sp): 0.311 IN3
GRADE BEAMS AS SOON AS PRACTICAL. PUMP WATER OUT OF OPEN EXCAVATIONS IF ALL STRUCTURAL WORK FOR THE WEST ADDITION, SECTORS Q & R,
3. MOMENT OF INERTIA (Ip): 0.272 IN4
FLOODING OCCURS PRIOR TO BACKFILLING. IS BEING DESIGNED BY JACOBS ENGINEERING NEW YORK INC.
ONLY GENERAL NOTES SHEETS, PLAN SHEETS AND DETAIL SHEETS
J. DO NOT BACKFILL AGAINST WALLS, WHEREVER FEASIBLE, UNTIL BASEMENT AND PREPARED BY JACOBS ENGINEERING NEW YORK INC. SHALL BE
GROUND FLOOR SLABS HAVE ATTAINED 75 PERCENT OF THE SPECIFIED 28-DAY REFERENCED FOR ALL SCOPE IN THE WEST ADDITION. THE DRAWING#
COMPRESSIVE STRENGTH. IF THE WALLS ARE BACKFILLED PRIOR TO COMPLETION OF APPLICABLE SHEETS ARE LISTED BELOW:
GROUND AND BASEMENT FLOORS BEFORE THE SPECIFIED PERCENT STRENGTH CAN BE
ATTAINED, BRACE THE WALLS FOR THE SPECIFIED DESIGN PRESSURE. OBTAIN THE S-002, S-003, S-004, S-005, S-012, S-013, S-132, S-133, S-172, S-192, S-003
5/10/2018 9:58:06 AM

APPROVAL OF THE ENGINEER FOR THE ADEQUACY OF SUCH BRACE. S-221, S-421, S-422, S-721, S-722, S-723, S-731, S-732, S-733, S-741
SHEET# 107 OF 725