GENERAL NOTES

PRAXIS3
STRUCTURAL STEEL STRENGTHS DESIGN NOTES
STEEL SHAPE ASTM Fy (ksi) Fu (ksi) REFERENCE CODES
CONCRETE NOTES STRUCTURAL STEEL NOTES REPAIR, PROTECT, AND STRENGTHENING NOTES ANGLES,PLATES, S SHAPE, AND INTERNATIONAL BUILDING CODE IBC 2021 & CITY OF FORT WORTH AMENDMENTS
MISC. MINIMUM DESIGN LOADS ASCE 7-16
1. REINFORCING STEEL FOR ALL MEMBERS SHALL HAVE A YIELD STRENGTH OF 60,000 PSI 1. FABRICATION AND ERECTION OF ALL STEEL SHALL BE IN ACCORDANCE WITH THE AISC THE BELOW PRODUCTS ARE THE DESIGN BASIS FOR THIS PROJECT. CONTRACTOR SHALL FOLLOW
CHANNELS MC15 AND MASONRY STRUCTURES TMS 402-16 100 Peachtree St NW 404-875-4500 tel
MINIMUM, EXCEPT FOR STIRRUPS, TIES AND HOOPS, WHICH SHALL HAVE A YIELD. STRENGTH OF SPECIFICATIONS. MANUFACTURER'S INSTALLATION INSTRUCTIONS AND CONTACT MANUFACTURER'S REPRESENTATIVE
2. ALL BOLTS SHALL BE ASTM A-325 HIGH STRENGTH BOLTS U.N.O. (T.C. BOLTS)
SMALLER, AND A36 36 58
40,000 PSI MINIMUM. (800-999-5099) WITH PRODUCT RELATED QUESTIONS. SUBSTITUTION REQUESTS FOR PRODUCTS OTHER STRUCTURAL CONCRETE ACI 318-19 Suite 1450 404-876-8884 fax
CHANNELS C8 AND
2. UNLESS SHOWN OTHERWISE, FRAMED CONCRETE SLABS SHALL BE 4" THICK REINFORCED WITH 3. WHERE BEAMS REST ON MASONRY OR CONCRETE WALLS THEY SHALL BEAR A MINIMUM OF 8" THAN THOSE LISTED BELOW MAY BE SUBMITTED BY THE CONTRACTOR TO THE ENGINEER-OF-RECORD STRUCTURAL STEEL AISC 360-16
#4 @ 8" o.c. EACH WAY. AND SHALL HAVE BEARING PLATES AND ANCHORS. (EOR) FOR REVIEW AND APPROVAL. SUBSTITUTIONS WILL ONLY BE CONSIDERED FOR PRODUCTS
SMALLER Atlanta, GA 30303 www.praxis3.com
3. WHERE MAIN REINFORCING IN A SOLID SLAB IS ONE DIRECTION, PROVIDE #3 BARS AT 12" o.c. IN 4. WHERE NOT SHOWN OTHERWISE, ALL COLUMNS SHALL HAVE BASE PLATES AND (4) 3/4" HAVING INDEPENDENT TEST RESULTS OR OTHER DOCUMENTATION INDICATING THE PRODUCT IS COLD-FORMED STEEL AISI S100-16
W SHAPES, MISC CHANNELS A992 50 65
THE OTHER DIRECTION, UNLESS SHOWN OTHERWISE. DIAMETER x 1'-2" LONG ANCHOR BOLTS. APPROPRIATE FOR THE INTENDED APPLICATION. MC18 AND LARGER,
4. BACKFILL SHALL NOT BE PLACED AGAINST BASEMENT WALLS UNTIL THE BASEMENT FLOOR SLAB 5. UNLESS SHOWN OTHERWISE, PROVIDE 5/8"x12"x7-1/2" BEARING PLATES ON 1" GROUT WITH (2) LIVE LOADS
CHANNELS C10 AND LARGER
AND THAT PORTION OF THE FIRST SLAB OVER THE BASEMENT ARE IN PLACE. 3/4" DIAMETER ANCHOR BOLTS UNDER ALL STEEL BEAMS THAT BEAR ON MASONRY WALLS. A. REBAR PRIMER: REBAR PRIMER SHALL BE USED TO PROTECT EXISTING STEEL REINFORCING UNIFORM CONC. UNIFORM CONC.
5. UNLESS SHOWN OTHERWISE, CONCRETE WALLS 8" THICK OR LESS SHALL BE REINFORCED WITH 6. COLUMN BASES ARE DESIGNED AS UNRESTRAINED, THEREFORE COLUMNS MUST BE BRACED AND ENCOURAGE POSITIVE BOND FROM EXISTING STEEL REINFORCING TO NEW REPAIR OCCUPANCY OR USE OCCUPANCY OR USE
HSS RECTANGULAR AND A500 GRADE C 50 62 (PSF) (LBS) (PSF) (LBS)
#4 @ 8" o.c. EACH WAY. WALLS OVER 8" THICK SHALL BE REINFORCED WITH #4 @ 12" o.c. EACH DURING ERECTION. MATERIAL. PRE-APPROVED PRODUCTS INCLUDE: SQUARE
WAY, EACH FACE. 7. AS ERECTION PROGRESSES, FRAMING SHALL BE ADEQUATELY GUYED AND BRACED AND ROOF 20 300 OFFICES & CORRIDORS 80 2,000
6. WHERE THE LENGTH OF A BAR IS GIVEN, AND IT IS TO BE HOOKED, THE HOOK SHALL BE IN CONNECTIONS SHALL BE SECURELY BOLTED OR WELDED. 1. SIMPSON STRONG TIE "FX-406" HSS ROUND A500 GRADE C 46 62 LIGHT STORAGE 125 HANDRAILS AND GUARDS 200
ADDITION TO THE LENGTH GIVEN. 8. NO SHOP SPLICE OR OTHER CONNECTION WILL BE PERMITTED UNLESS THIS SPLICE OR DETAIL STAIRS AND EXIT WAYS 100 300 GRAB BARS 250
7. WHERE OPENINGS OCCUR IN SLABS, PLACE THE REINFORCING THAT WOULD OCCUR IN LINE IS SHOWN ON SHOP DRAWINGS AND REVIEWED BY THE ENGINEERS. B. BONDING AGENTS: BONDING AGENTS SHALL BE USED TO ENCOURAGE POSITIVE BOND OF NEW SHEAR STUDS A108 65 PASSENGER VEHCILES 40 3,000
WITH THE OPENING EQUALLY TO EITHER SIDE OF THE OPENING. CUT NO STEEL IN THE FIELD. 9. ALL FASTENERS SHALL CONSIST OF ONE NUT, ONE BOLT, AND ONE WASHER. REPAIR MATERIAL TO EXISTING CONCRETE. PRE-APPROVED PRODUCTS INCLUDE:
8. REINFORCING BARS THAT ARE TO BE WELDED SHALL BE OF A WELDABLE GRADE AND WELDED 10. ALL WELDING SHALL CONFORM TO THE "STRUCTURAL WELDING CODE - AMERICAN WELDING
ANCHOR BOLTS/RODS F1554 36 58 ROOF RAIN LOAD
IN ACCORDANCE WITH A.W.S. RECOMMENDATIONS. SOCIETY." FOR WELD TESTING REQUIREMENTS, SEE SPECIFICATIONS. 1. SIMPSON STRONG TIE "FX-762" HIGH STRENGTH BOLTS
9. PROTECTIVE COVERING OF REINFORCEMENT (SEE DETAILS) SHALL BE AS FOLLOWS: 11. NO SLOTTED HOLES ARE PERMITTED UNLESS SPECIFICALLY DETAILED BY THE ENGINEER OF DESIGN RAIN INTENSITY (i): 6 IN/HR
3/4" TO 1" DIAM. INCLUSIVE A325 120
A. FOOTINGS AND GRADE BEAMS 3" CLEAR BOTTOM AND SIDES, 1 1/2" CLEAR SIDES. RECORD. C. REPAIR MORTARS: REPAIR MATERIAL SHALL BE USED TO REPAIR AREAS OF DAMAGED SECONDARY DRAINAGE: INTERNAL DRAINS
1-1/8" TO 1-1/2" DIAM. INCL. A325 105
B. BEAMS 1 1/2" CLEAR TO STIRRUPS. 12. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO SECURE STEEL AGAINST CONCRETE. PRE-APPROVED PRODUCTS INCLUDE: 1-1/8" TO 1-1/2" DIAM. INCL. A490 150
C. CONCRETE COLUMNS AND PIERS 1 1/2" CLEAR TO TIES DISPLACEMENT DURING ERECTION AND TO MAINTAIN IT AGAINST DISPLACEMENT UNTIL THE ROOF SNOW LOAD
D. 3/4" CLEAR FOR CONCRETE JOIST TOP BARS ERECTION OF ALL STEEL IS COMPLETED, ALL FLOOR AND ROOF DECKS ARE IN PLACE, AND ALL 1. SIMPSON STRONG TIE "FX-263" (FOR USE IN OVERHEAD AND VERTICAL APPLICATIONS) WELDED WIRE FABRIC A185
10. ALL CONCRETE FOR TOPPING SLAB SHALL BE REGULAR WEIGHT CONCRETE. EXTERIOR MASONRY IS COMPLETED. ALL STRUCTURAL METAL WORK SHALL HAVE TEMPORARY 2. SIMPSON STRONG TIE "FX-261" (FOR USE IN HORIZONTAL AND FORM & POUR 6x6-W.9xW2.9 FLAT-ROOF SNOW LOAD (pf): 4 PSF SNOW IMPORTANCE FACTOR (Is): 1.0
GUYS, BRACES AND STAYS TO HOLD IT IN POSITION UNTIL IT IS PERMANENTLY SECURE. APPLICATIONS) SNOW EXPOSURE FACTOR (Ce): 0.9 THERMAL FACTOR (Ct): 1.0
13. ALL GROUT UNDER BASE PLATES AND BEAM BEARING PLATES SHALL BE NON SHRINK GROUT. REINFORCING STEEL A615 60
CONTRACTOR'S NOTES (5,000 PSI) D. CRACK REPAIR SYSTEM: CRACK REPAIR SYSTEM SHALL CONSIST OF CRACK INJECTION DESIGN FROST DEPTH 12"
1. SEE ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL DRAWING. AND 14. WHERE ROOF DECKS FRAME ONTO A ROOF MEMBER, AND DECK IS IN A DIFFERENT PLANE THAN MATERIAL AND PASTE OVER ADHESIVE AND SHALL BE USED TO PRESSURE INJECT CRACKS.
SPECIFICATIONS FOR SIZE AND LOCATION OF DRIPS, CHAMFERS, SLEEVES, ANCHORS, INSERTS THE ROOF MEMBER, PROVIDE A 3/16" CONTINUOUS BENT PLATE WELDED ACROSS THE TOP OF PRE-APPROVED SYSTEMS INCLUDE: MINIMUM REINFORCED CONCRETE STRENGTHS WIND DESIGN CRITERIA SIGNED & SEALED 10.03.2022
AND OPENINGS REQUIRED. THE LOCATION AND SIZE OF SLEEVES OR OPENINGS NOT SHOWN THE ROOF MEMBER SLOPED TO MATCH PLANE OF ROOF DECK. f'c AT 28 DAYS (U.N.O. ON SCHEDULES)
15. FILL ALL CMU CELLS WITH GROUT WHERE REINFORCING AND/OR ANCHORS OCCUR. 1. SIMPSON STRONG TIE "FX-751 LV" INJECTION MATERIAL WITH "FX-763" PASTE OVER DESIGN WIND SPEED INTERNAL PRESSURE COEFFICIENT ±0.18 Copyright (c) 2022 Praxis3, LLC
ON THE DRAWINGS IN STRUCTURAL MEMBERS SHALL BE SUBJECT TO THE APPROVAL OF THE (TYPE 1 CEMENT ONLY. DO NOT SUBSTITUTE FLYASH OR SLAG FOR CEMENT)
ARCHITECT. ANY CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT 16. HEADED CONCRETE ANCHORS SHALL BE NELSON OR K.S.M. HEADED CONCRETE ANCHORS (OR ADHESIVE ULTIMATE (V): 106 MPH All reports, plans, specifications, computer files, field data, notes and other documents

BEFORE PROCEEDING WITH THE WORK AFFECTED. PRINCIPAL OPENINGS IN THE STRUCTURE APPROVED EQUAL), AND SHALL CONFORM TO ASTM A-108. NOMINAL (Vasd): 82 MPH and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.
LOCATION DENSITY STRENGTH RISK CATEGORY 2
ARE INDICATED ON THE CONTRACT DRAWINGS. ANY SUBSTITUTIONS RESULTING IN REVISIONS 17. ANCHORS SHALL BE AUTOMATICALLY END WELDED WITH SUITABLE STUD WELDING EQUIPMENT E. NON-SHRINK GROUT MATERIAL: NON-SHRINK GROUT MATERIAL SHALL BE USED TO GROUT COMPONENTS AND CLADDING WIND This drawing may not be reproduced in whole or in part without written permission of
TO THE STRUCTURE SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE MANUFACTURER. BENEATH BASEPLATES, BEARING PLATES AND EQUIPMENT BASES. PRE-APPROVED PRODUCTS WIND EXPOSURE (X-X) C PRESSURES: SEE TABLES, THIS SHEET Praxis3. It is to be returned upon request. Scales as stated are valid on the original
SLAB SUPPORTED ON GRADE 145 P.C.F. 3000 PSI
WITH THE ARCHITECT. 18. WHERE A ROOF FRAMING MEMBER DOES NOT FRAME OVER A COLUMN, PROVIDE A 1/2" THICK INCLUDE: drawings.

CAP PLATE (i.e. TUBES AND PIPES) WIND EXPOSURE (Y-Y) C


2. THE CONTRACTOR SHALL NOT SCALE THE CONTRACT DRAWINGS FOR THE PURPOSE OF FOOTINGS SUPPORTING WOOD,
ESTABLISHING CORRECT DIMENSIONS. 19. FABRICATOR SHALL SUBMIT COMPLETE CALCULATIONS OF ALL CONNECTIONS, STRUCTURAL 1. SIMPSON STRONG TIE "FX-228"
MASONRY, AND STEEL STRUCTURES
145 P.C.F. 3000 PSI Rev Date Comments
3. U.N.O. DENOTES: "UNLESS NOTED OTHERWISE". STEEL, AND JOIST SEALED BY THE REGISTERED DESIGN ENGINEER SEISMIC DESIGN CRITERIA 10.03.22 Permit / Bid Set
4. GENERAL CONTRACTOR SHALL FIELD VERIFY EXISTING SIZES, DIMENSIONS, NOTES OR 20. WHERE HSS OUTLOOKERS OCCUR PROVIDE 1/4" CAP PLATE AT END.
21. AT CAR WASH STRUCTURE, ALL STRUCTURAL STEEL, MISC. STEEL, EMBED PLATES AND ROOF
STEEL STAIR AND ALL RAILING NOTES CONCRETE PIERS SUPPORTING RISK CATEGORY 2
CONDITIONS PRIOR TO ANY DETAILING, OR FABRICATION OF MATERIALS. 145 P.C.F. 3000 PSI
DECK SHALL BE GALVANIZED G90. 1. SUBMIT COMPLETE ERECTION, FABRICATION DRAWINGS AND CALCULATIONS SIGNED AND STEEL OR MASONRY COLUMNS
5. WHERE THE CONTRACTOR ELECTS TO POUR THE SLAB ON GRADE PRIOR TO ERECTING THE
SUPERSTRUCTURE, THE CONTRACTOR SHALL TAKE INTO CONSIDERATION THAT THE SLAB ON 22. ALL EXTERIOR EXPOSED STEEL SHALL BE GALVANIZED G90 UNLESS NOTED OTHERWISE BY THE SEALED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE IN WHICH THIS PROJECT IS SEISMIC IMPORTANCE FACTOR Ie = 1.0
GRADE IS NOT DESIGNED FOR SUPPORT OF ANY CRANES OR SIMILAR DEVICES USED TO ERECT ARCHITECT. BUILT WHICH ADDRESSES THE DESIGN FOR ALL STEEL STAIRS, GUARD RAILS AND HANDRAILS. SLAB ON GRADE AT BIN-SUPPORTED
145 P.C.F. 5000 PSI
THE STRUCTURAL FRAME. DO NOT PLACE THIS EQUIPMENT ON THE SLAB. 23. ALL BEAM SHOP CONNECTIONS SHALL BE WELDED. BEAM SHOP CONNECTIONS MAY BE DETAILS SHALL BE FURNISHED OF ALL STEEL STAIRS. STAIRS SHALL MEET THE SPECIFICATIONS MEZZANINE MAPPED SPECTRAL RESPONSE ACCELERATIONS Ss = 0.096 (GEOTECH REPORT)
6. WHERE OVERHEAD LIFTS OCCUR ON THE PROJECT, NO KEYED OR SAW CUT JOINT SHALL BE BOLTED IN LIEU OF WELDING PROVIDED THAT THE CONTRACTOR ASKS AND RECEIVES AN FOR ARCHITECTURALLY EXPOSED STRUCTURAL STEEL (AESS) OF THE AISC CODE OF STANDARD S1 = 0.05 (GEOTECH REPORT)
PLACED WITHIN 6" OF THE LIFT SUPPORT ANCHORAGE AS PER THE LIFT MANUFACTURER AFFIRMATIVE ANSWER BY THE ENGINEER OF RECORD IN WRITING. FURTHERMORE, PRACTICE. ALLOW TEN (10) BUSINESS DAYS FOR REVIEW OF SUBMITTED STRUCTURAL FRAMED SLABS IN COMPOSITE
115 P.C.F. 4000 PSI
RECOMMENDATIONS. GENERAL CONTRACTOR COORDINATE WITH FINAL LIFT PLACEMENT PLAN ACCEPTANCE OF A BOLTED CONNECTION WILL ONLY OCCUR IF THE FABRICATOR FOLLOWS THE DRAWINGS. STEEL CONSTRUCTION SITE CLASS C (GEOTECH REPORT)
PRIOR TO POURING THE SLAB. ECCENTRIC LOAD TABLES PROVIDED ON PAGES 7-30 THROUGH 7-53 OF THE AISC MANUAL. 2. TREADS AND RISERS SHALL BE PREFORMED OF 14 GAUGE METAL. LANDING PAN SHALL BE 12
STAIR TREADS AND LANDINGS 145 P.C.F. 3000 PSI MAPPED SPECTRAL RESPONSE ACCELERATIONS SDS = 0.076 (GEOTECH REPORT)
7. GENERAL CONTRACTOR SHALL ENGAGE A SURVEYOR TO PROVIDE LOCATIONS OF ALL EXISTING e GAUGE MINIMUM.
UTILITES, TRENCHES, ETC. TO ENSURE THAT NEW FOUNDATIONS WILL NOT INTERFERE, FACE OF 3. STRINGERS, LANDING BEAMS, CLOSURE PLATES, STIFFENERS AND CONNECTION ANGLES SHALL SD1 = 0.057 (GEOTECH REPORT)
e = ECCENTRICITY
UNDERMINE, OR BEAR ON EXISTING UTILITIES. FRAMING BE OF SIZES DESIGNED BY THE STAIR PROVIDER AND SHALL RESIST A MINIMUM OF SELF NON-SHRINK GROUT AT STEEL SEISMIC DESIGN CATEGORY : A
(SEE 7-30 - 7-53, AISC 145 P.C.F. 5000 PSI
MEMBER WEIGHT OF STEEL, CONCRETE, ARCHITECTURAL FINISHES AND 100 PSF LIVE LOAD. COLUMN BASEPLATES NOT REQUIRED FOR SEISMIC
FOURTEENTH EDITION)
4. AT LOWEST LEVEL, STAIRS MAY BE SUPPORTED FROM POST BEARING ON A FOOTING, DESIGN CATEGORY A.
DECKING NOTES THICKENED SLAB, OR CONCRETE WALL PROVIDED SUPPORT BASE PLATE CAN REMAIN 4000 PSI (SEE ANALYSIS PROCEDURE:
DRILLED SHAFTS 145 P.C.F. STRUCTURE DESIGNED TO
1. NO PIPING, DUCTWORK, OR CONDUIT LARGER THAN 3/4" DIAMETER OR STUD WALLS SHALL BE CONCEALED WITHIN ARCHITECTURAL ELEMENTS WITHOUT BEING EXPOSED. SPECIFICATIONS) COMPLY WITH ASCE 7-16 § 1.4.
SUPPORTED DIRECTLY FROM METAL DECK OR PERMANENT METAL FORM. 5. WHERE STAIR LANDINGS ARE SUSPENDED FROM FLOORS ABOVE, USE A MINIMUM OF DOUBLE
2. ALL METAL ROOF DECKS SHALL BE WIDE RIB AND GALVANIZED TYPE "B" DECKS UNLESS NOTED
CONCRETE MASONRY NOTES ANGLE 3x3x1/4" HANGERS. HANG CONCENTRICALLY FROM FLOOR BEAM. CONTRACTOR SHALL GRADE BEAMS OR TIE STRAPS 145 P.C.F. 4000 PSI
OTHERWISE. 1. MORTAR SHALL COMPLY WITH ASTM C 270, TYPE S, UNLESS GREATER STRENGTH IS SPECIFIED COORDINATE WITH THE ARCHITECTURAL PARTITION SCHEDULE TO ENSURE HANGERS ARE
ELSEWHERE. CONCEALED WITHIN PARTITIONS. DO NOT USE ROD HANGERS.
2. MASONRY GROUT SHALL BE COMPLYING WITH ASTM C 476, MINIMUM REQUIRED GROUT 6. INTERMEDIATE LANDINGS SHALL BE COMPRISED OF CHANNELS SPANNING BETWEEN SUPPORT
FOUNDATION NOTES
COMPRESSIVE STRENGTH f'g = 2250 PSI, U.N.O. STRINGERS SPACED AT A MAXIMUM OF 2'-0" o.c. MAX. MINIMUM LAP SPLICE LENGTH SCHEDULE
1. NO PIPES OR CONDUIT SHALL BE PLACED IN FOUNDATIONS, GRADE BEAMS, OR THE SLABS-ON- 3. REQUIRED MASONRY NET AREA COMPRESSIVE STRENGTH f'm = 2250 PSI, U.N.O. 7. AT ORNAMENTAL STAIRS, STRINGERS SHALL BE COMPRISED OF TUBE STEEL OR CHANNELS

4' - 10"
GRADE. 4. CONCRETE GROUT, CONFORMING TO ASTM C476, NOT MORTAR, SHALL BE USED AT CELLS AND WITH CONTINUOUS COVER PLATES TO FORM A TUBE. IN THIS CASE WELDS SHALL BE 3000 PSI CONC. 14' - 5" 14' - 5"
2. SITE SHALL BE PREPARED IN ACCORDANCE TO THE GEOTECHNICAL REPORT PREPARED BY BOND BEAMS CONTAINING REINFORCING BARS. DO NOT FILL CELLS NOT CONTAINING CONTINUOUS AND GROUND SMOOTH. BAR TYPE
"ECS SOUTHWEST, LLP" DATED 15 APRIL 2022. PROJECT NO. 63:1624. 8. SEE ARCHITECTURAL DRAWINGS FOR ALL STAIR LAYOUTS, DIMENSIONS AND SECTIONS. #3 #4 #5 #6 #7 #8 #9 #10 #11 3' - 2"
REINFORCING BARS, EXCEPT BELOW GRADE, UNLESS SO INDICATED.
3. BUILDING FOUNDATIONS ARE DRILLED AND UNDERREAMED SHAFTS DESIGNED USING THE 5. UNLESS NOTED OTHERWISE, MAXIMUM CONTROL JOINT SPACING SHALL BE 32'-0", 16'-0" FROM TOP BARS 29" h = 24'
38" 47" 56" 82" 94" 105" 118" 131" = ZONE 1'

9' - 5"
FOLLOWING PARAMETERS: CORNERS, COORDINATE WITH ARCHITECTURAL. ALL HORIZONTAL REINFORCING SHALL BE
A. AXIAL DESIGN PARAMETERS
SUBMITTAL NOTES = ZONE 1
DISCONTINUED AT WALL CONTROL JOINTS. OTHER BARS 22" 29" 36" 43" 62" 72" 81" 91" 101"
• ACCEPTABLE BEARING MATERIAL: CLAY SOILS 6. LOAD BEARING MASONRY WALLS SHALL BE LATERALLY BRACED UNTIL ALL FLOOR / ROOF 1. THE GENERAL CONTRACTOR SHALL SUBMIT A SCHEDULE OF SUBMITTALS PRIOR TO = ZONE 2
• MINIMUM EMBEDMENT DEPTH: 18 FEET BELOW FINISHED GRADE DIAPHRAGM IS IN PLACE. CONSTRUCTION BEGINNING ON THE PROJECT. THE SCHEDULE SHOULD DESCRIBE WHAT EACH 4000 PSI CONC.
BAR TYPE = ZONE 3 h = 15' - 8"
• NET ALLOWABLE END BEARING: 7,000 PSF 7. AT ALL NON-LOAD BEARING MASONRY WALLS (INTERIOR AND EXTERIOR), PROVIDE A 3/4" SUBMITTAL IS, WHETHER IT IS THE ENTIRE PACKAGE, OR BROKEN INTO PHASES FOR REVIEW.
• MINIMUM SHAFT Ø: 18 INCHES 2. THE GENERAL CONTRACTOR SHALL ALLOW FOR 10 BUSINESS DAYS OF ALL STRUCTURAL #3 #4 #5 #6 #7 #8 #9 #10 #11
CAULKED JOINT BETWEEN UNDERSIDE OF BEAM, JOIST, DECK, OR STRUCTURE AND TOP OF
• MINIMUM BELL Ø: 30 INCHES LARGER THAN SHAFT MASONRY WALL. SUBMITTALS. IF THE CONTRACTOR WISHES TO EXPEDITE OR REDUCE THE REVIEW TIME, IT TOP BARS 25" 33" 40" 48" 70" 81" 91" 103" 113"
• BELL-TO-SHAFT Ø RATIO: 2:1 TO 3:1 8. PROVIDE MASONRY HORIZONTAL JOINT REINFORCEMENT 16" o.c. VERTICAL IN ALL CONCRETE SHALL BE DONE FOR AN ADDITIONAL CHARGE AND MUST BE NEGOTIATED WITH THE ARCHITECT
• SOIL-INDUCED UPLIFT: 1,500 PSF ACTING OVER SHAFT PERIMETER BLOCK WALLS. REINFORCEMENT SHALL BE FOR TOTAL WIDTH OF CAVITY WALLS. AND ENGINEER PRIOR TO THE SUBMISSION OF THE PACKAGE. OTHER BARS 20" 25" 31" 38" 55" 62" 70" 79" 87"
B. LATERAL DESIGN PARAMETERS: SEE GEOTECHNICAL REPORT 9. PROVIDE A 2 SQUARE INCH INSPECTION HOLE AT THE BOTTOM CELL FOR EACH LIFT TO ALLOW 3. IN THE EVENT THE CONTRACTOR ATTEMPTS TO SUBMIT THE ENTIRE PROJECT AT THE SAME
C. VOID SPACE BENEATH GRADE BEAMS AND PIER CAPS: VISUAL INSPECTION AND TO REMOVE MORTAR DROPPING PRIOR TO GROUTING. TIME FOR SUBMISSION, ADDITIONAL TIME WILL BE REQUIRED BEYOND THE STANDARD 10 DAY h = 21' 12' - 8" 12' - 8"
• 6 INCHES MINIMUM IF THE SUBGRADE IS MOISTURE CONDITIONED 10. ALL MASONRY SHALL BE RUNNING BOND UNLESS NOTED OTHERWISE. REVIEW TIME.
• 8 INCHES OTHERWISE 11. SLEEVE ALL PLUMBING OR FIRE PROTECTION PIPING THROUGH CMU WALL. 4. WHERE GLASS REQUIRES ADDITIONAL DESIGN OF MISCELLANEOUS STEEL AND MULLIONS, MINIMUM PRETENSION OF BOLTS (KIPS)
12. SEE ARCHITECT DRAWINGS AND SPECIFICATIONS FOR MASONRY FINISHES. CONTRACTOR SHALL FURNISH DETAILED DESIGN CALCULATIONS SEALED BY A REGISTERED
13. AT LOAD-BEARING MASONRY WHERE JOISTS OR BEAMS BEAR ON MASONRY WALLS, GROUT ENGINEER IN THE STATE IN WHICH THE PROJECT IS BUILT. BOLT DIAMETER A325 BOLTS A490 BOLTS
SLAB-ON-GRADE NOTES POCKET SOLID WITH GROUT TO THE SAME FINISH FACE AS MASONRY ABOVE AND BELOW. DO 5. STRUCTURAL STEEL SUPPLIER SHALL PROVIDE COMPLETE SHOP DRAWINGS INCLUDING AN
1. WHERE SLABS REST ON FILL, FILL SHALL BE COMPACTED IN ACCORDANCE WITH THE THIS ONLY AFTER JOIST SEAT CONNECTION HAS BEEN INSPECTED. ANCHOR SETTING PLAN, ERECTION DRAWINGS WITH ALL PIECE MARKS, AND ASSOCIATED 3/4" DIAMETER 28 35
SPECIFICATIONS. FABRICATION DRAWINGS SHOWING ALL MATERIAL AND CONNECTIONS. CONNECTIONS SHALL 24' - 0" h = 40'
BE DESIGNED BASED UPON THE END SHEAR TABLES PROVIDED IN THE AISC UNLESS NOTED 7/8" DIAMETER 39 49
2. SLABS ON GROUND MAY BE PLACED IN LANE FASHION USING GALVANIZED STEEL, PREFORMED FOR ADDITIONAL
KEYED FORMS AT FLOOR JOINT LOCATION INDICATED. REINFORCING SHALL NOT CROSS
POST-INSTALLED ANCHOR NOTES OTHERWISE.
1" DIAMETER 51 64 INFORMATION ON 8' - 0"
CONSTRUCTION OR KEYED JOINTS. THE BELOW PRODUCTS ARE THE DESIGN BASIS FOR THIS PROJECT. PRODUCT DIAMETER AND 6. REBAR SUPPLIER SHALL PROVIDE COMPLETE SHOP DRAWINGS INCLUDING PLAN VIEWS WITH
ZONES, REFERENCE
3. SLABS-ON-GRADE REQUIRE CONTROL JOINTS PER THE TYPICAL DETAILS UNLESS NOTED EMBEDMENT SHALL BE AS SHOWN IN THE DETAILS. INSTALL PRODUCTS IN ACCORDANCE WITH MARKS ILLUSTRATING BAR SIZES AND BAR BENDING DETAILS. INCLUDE ALL LOCATION OF STEPS
ASCE 7-16, FIG. 30.3-2A.
OTHERWISE. LOCATE CONSTRUCTION AND CONTROL JOINTS IN SUCH A WAY TO MINIMIZE THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS (MPII). SUBSTITUTION REQUESTS FOR NOTED IN THE GENERAL NOTES FOR PLUMBING AND CIVIL LINES WHERE APPLICABLE. WHERE
EFFECTS OF SHRINKAGE AND CURLING OF THE CONCRETE SLAB SECTIONS. SUBMIT TO THE PRODUCTS OTHER THAN THOSE LISTED BELOW MAY BE SUBMITTED BY THE CONTRACTOR TO THE CONCRETE PIER AND STEM WALLS OCCUR PROVIDE SECTION CUTS, AND ELEVATIONS
ARCHITECT/ENGINEER/EQUIPMENT VENDOR THE SEQUENCE AND METHOD OF CASTING ENGINEER-OF-RECORD (EOR) FOR REVIEW. SUBSTITUTIONS WILL ONLY BE CONSIDERED FOR ILLUSTRATING THE MATERIAL SPECIFIED ROOF PLAN
7. REBAR SUPPLIER SHALL PROVIDE COMPLETE SHOP DRAWINGS FOR LOAD BEARING MASONRY.
CONCRETE SLABS-ON-GRADE PRIOR TO PLACING THESE ELEMENTS.
A. JOINT SPACING SHALL NOT EXCEED 15 FEET, AND THE RESULTING PLAN ASPECT RATIO
PRODUCTS HAVING A CODE REPORT RECOGNIZING THE PRODUCT FOR THE APPROPRIATE
APPLICATION. SUBSTITUTION REQUESTS SHALL INCLUDE CALCULATIONS THAT DEMONSTRATE THE PROVIDE ALL WALLS INCLUDING NON LOAD BEARING PARTITIONS IN ELEVATIONS DEPICTING THE COMPONENTS AND CLADDING ROOF (ENCLOSED) 106 MPH EXP. "C" 'ULT' Mark W. Nannis, P.E.
(PANEL LENGTH TO PANEL WIDTH) OF ANY GIVEN SECTION OF SLAB SHALL NOT EXCEED SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE EQUIVALENT PERFORMANCE VALUES OF THE VERTICAL WALL REINFORCEMENT/ LAPS, ALL LINTELS AT OPENINGS , REINFORCING AND BOND Texas Design Firm #21364
BEAMS AS DESCRIBED IN TYPICAL DETAILS AND WALL SECTIONS INCLUDING MASONRY
EXTERNAL PRESSURES (PSF) 1591 Riverside Drive
1.5. DESIGN BASIS PRODUCT. CONTRACTOR SHALL CONTACT MANUFACTURER'S REPRESENTATIVE
B. WHERE POSSIBLE, CONTROL JOINT LAYOUT SHALL BE SUCH THAT JOINTS ALIGN WITH (800-999-5099) FOR PRODUCT INSTALLATION TRAINING AND A LETTER SHALL BE SUBMITTED TO THE EOR CONTROL JOINT LOCATIONS. A e (EFFECTIVE AREA) ZONE 1' ZONE 1 ZONE 2 ZONE 3 Gainesville, GA 30501
THE VERTICES OF COLUMN ISOLATION BLOCKOUTS AND SHALL BE ARRANGED IN A INDICATING TRAINING HAS TAKEN PLACE. SPECIAL INSPECTIONS ARE REQUIRED PER THE IBC AND ICC- 8. JOIST AND DECK SUPPLIER SHALL PROVIDE COMPLETE SHOP DRAWINGS INCLUDING ERECTION 770-614-6114 tel
GENERALLY ORTHOGONAL MANNER. ES REPORTS. DRAWINGS, SECTIONS INCLUDING MATERIALS PROVIDED, ALL ASSOCIATED CONNECTIONS AS A e = 10 SQ. FT. +16.0, -27.6 +16.0, -48.0 +16.0, -63.3 +16.0, -86.2
C. IN AREAS WHERE NON-STRUCTURAL BONDED OVERLAY MATERIAL OR GROUT-BEDDED OUTLINED IN THE CONTRACT DOCUMENTS AND SPECIFICATIONS. SHOP DRAWINGS SHALL All drawings, specifications, and other work product
INCLUDE ALL EDGE OF DECK DIMENSIONS, EDGE OF JOIST DIMENSIONS . A e = 20 SQ. FT. +16.0, -27.6 +16.0, -45.4 +16.0, -59.5 +16.0, -78.6
FLOORING ARE TO BE INSTALLED, FEATURES SUCH AS CRACK-SUPPRESSION A. FOR ANCHORING INTO CONCRETE: of Mark W. Nannis, P.E. (henceforth referred to as "The
MEMBRANES AND FLOORING DIVIDER STRIPS ALIGNED WITH SLAB CONTROL JOINTS 9. SEE DISCIPLINE SPECIFIC NOTES AND SPECIFICATIONS FOR ALL ADDITIONAL SUBMITTAL A e = 50 SQ. FT. +16.0, -27.6 +16.0, -40.3 +16.0, -53.1 +16.0, -67.9 Engineer") for this project are instruments of service for
1. MECHANICAL ANCHORS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN REQUIREMENTS. this project only and shall remain the property of The
SHALL BE DESIGNED AND INSTALLED BY OTHERS AS PART OF THE NON-STRUCTURAL
10. FOR THIRD-PARTY DESIGN SUBMITTALS INCLUDING, BUT NOT LIMITED TO, METAL STUDS, STAIRS A e = 100 SQ. FT. +16.0, -27.6 +16.0, -37.8 +16.0, -50.5 +16.0, -60.0 Engineer whether the project is complete or not. Reuse
FLOORING ASSEMBLY IN ORDER TO MITIGATE SUBSTRATE-INDUCED CRACKING. ACCORDANCE WITH ACI 355.2 AND ICC-ES AC193 FOR CRACKED CONCRETE AND SEISMIC of any of the instruments of service of The Engineer by
4. SEE CIVIL AND ARCH. DRAWINGS AND SPECIFICATIONS FOR EXTERIOR SLAB WORK AND APPLICATIONS. PRE-APPROVED ANCHORS INCLUDE: & HANDRAILS, AND GLASS DESIGN, PLEASE SUBMIT MANUFACTURER'S DRAWINGS WITH the owner or extensions of this project without the written
JOINTING. HORIZONTAL RUNS OF CONDUIT AND PIPE SHALL NOT BE PLACED IN SLABS ON ACCOMPANYING CALCULATIONS SEALED BY A REGISTERED ENGINEER IN THE STATE IN WHICH permission of The Engineer shall be at the owner's risk
• SIMPSON STRONG TIE "STRONG-BOLT 2" (IAPMO-UES ESR ER-240) THE PROJECT IS BUILT. "a" and the owner agrees to defend, indemnify, and hold
GROUND, PLACE IN SUB-GRADE.
harmless The Engineer from all claims, damages, and
expenses including attorney's fees arising out of such
2. ADHESIVE FOR REBAR AND ANCHORS SHALL HAVE BEEN TESTED AND QUALIFIED FOR 5 4 5 unauthorized reuse of The Engineer's instruments of
COLD-FORMED STEEL NOTES USE IN ACCORDANCE WITH ACI 355.4 AND ICC-ES AC308 FOR CRACKED CONCRETE AND service by the owner or others acting through the owner.
SEISMIC APPLICATIONS. ADHESIVE ANCHORS SHALL BE INSTALLED BY A CERTIFIED © 2022
1. ALL EXTERIOR METAL STUDS ARE TO BE C.S.J. (U.N.O.) ADHESIVE ANCHOR INSTALLER PER ACI 318-11 D.9.2.2 WHERE INDICATED ON THE
2. ALL EXTERIOR METAL STUDS SHALL BE DESIGNED FOR LATERAL WIND PRESSURE BASED UPON CONTRACT DOCUMENTS. INSTALLATIONS REQUIRING CERTIFIED INSTALLERS SHALL BE Client:
ULTIMATE DESIGN WIND SPEED AS SHOWN ON DESIGN NOTES AND SHOULD BE LIMITED TO INSPECTED PER ACI 318-11 D.9.2.4. PRE-APPROVED ANCHORS INCLUDE: WALL ELEVATION
LATERAL DEFLECTION OF L/600 WHEN BACKING MASONRY, AND L/360 WHEN BACKING E.I.F.S.,

3.
AND METAL PANELS
ALL EXTERIOR FLANGES OF STUD WALLS SHALL BE BRACED BY SHEATHING PROPERLY


SIMPSON STRONG TIE "SET-XP" (ICC-ES ESR-2508)
SIMPSON STRONG TIE "AT-XP" (IAPMO-UES ESR-263)
COMPONENTS AND CLADDING WALL (ENCLOSED) 106 MPH Automotive
EXP. "C" 'ULT' EXTERNAL PRESSURES (PSF)
4.
ATTACHED TO THEM.
CONTRACTOR SHALL FURNISH DETAILED DESIGN CALCULATIONS INCLUDING CONNECTION AND 3. POWDER-ACTUATED FASTENERS SHALL HAVE BEEN TESTED IN ACCORDANCE WITH ICC- A e (EFFECTIVE AREA) ZONE 4 ZONE 5
Managment
GAUGE OF ALL EXTERIOR METAL STUDS, METAL STUD TRUSSES AND METAL STUD TRUSS ES AC70. PRE-APPROVED ANCHORS INCLUDE:

5.
GIRDERS SEALED BY A REGISTERED ENGINEER IN THE STATE IN WHICH THE PROJECT IS BUILT.
THE TOP COMPRESSION FLANGES OF JOISTS & TRUSSES ARE TO BE LATERALLY BRACED BY • SIMPSON STRONG TIE "GAS ACTUATED PINS" (ICC-ES ESR-2811)
A e = 10 SQ. FT. +27.6, -29.9 +27.6, -36.7 Services, Inc.
PROPER ATTACHMENT OF THE DECKING. A e = 20 SQ. FT. +26.3, -28.6 +26.3, -34.3 505 S. Flagler Dr., Suite 1400
• SIMPSON STRONG TIE "POWDER ACTUATED PINS" (ICC-ES ESR-2138)
6. THE TOP FLANGES OF BOTTOM CHORDS OF TRUSSES, SHALL BE BRACED LATERALLY AT A e = 50 SQ. FT. +24.7, -27.0 +24.7, -31.1 West Palm Beach, FL 33401
INTERVALS NOT EXCEEDING 3'-0" o.c. BY CONTINUOUS C STUDS WELDED TO TOP FLANGES OR B. FOR ANCHORING INTO MASONRY:
BY SHEATHING ATTACHED DIRECTLY TO BOTTOM FLANGE. STRUCTURAL SUBMITTALS A e = 100 SQ. FT. +23.5, -25.8 +23.5, -28.6 Project Number: 22008
7. TOP FLANGE OF CEILING STUD SHALL BE BRACED LATERALLY BY CONTINUOUS C STUDS 1. ANCHORAGE TO SOLID-GROUTED CONCRETE MASONRY SUBMITTAL TYPE DESIGN BY CONTRACTOR'S NOTES: Project Name:
WELDED TO EACH JOIST. EACH BRACE SHALL BE CAPABLE OF TRANSMITTING A MINIMUM OF 200
SPECIFICATION SECTION SUBMITTAL ACTION INFORMATIONAL LICENSED ENGINEER 1. INTERPOLATION MAY BE UTILIZED FOR EFFECTIVE AREAS THAT
POUNDS IN TENSION OR COMPRESSION. BOTTOM FLANGE OF CEILING SHALL BE BRACED BY a. MECHANICAL ANCHORS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN

8.
SHEATHING PROPERLY ATTACHED TO BOTTOM FLANGE.
ALL INTERIOR FLANGES OF STUD WALLS SHALL BE BRACED EITHER BY SHEATHING OR BY
ACCORDANCE WITH ICC ES AC01 OR ICC-ES AC106 PRE-APPROVED ANCHORS
INCLUDE: 03 1000 - CONCRETE FORMING AND ACCESSORIES
PRODUCT DATA
FORMWORK SHOP DRAWINGS (ELEVATED

2.
OCCUR BETWEEN VALUES SHOWN ON THE TABLE.
PLUS AND MINUS SIGN INDICATES THE PRESSURE ACTING Alliance Hyundai
CONTINUOUS CHANNELS WELDED TO FLANGE AT INTERVALS NOT EXCEEDING 2'-0" o.c. OR AS ● ● TOWARD AND AWAY FROM THE SURFACES, RESPECTIVELY.
DETERMINED BY DETAIL DESIGN DOCUMENTS FURNISHED BY A REGISTERED ENGINEER IN THE CONCRETE ONLY) 3. FORCES AND DIAGRAMS ARE BASED ON IBC / ASCE 7.
• SIMPSON STRONG TIE "TITEN-HD" (ICC-ES ESR-1056)
STATE IN WHICH THE PROJECT IS BUILT. • SIMPSON STRONG TIE "STRONG-BOLT 2" (IAPMO-ES ER-240) PRODUCT DATA ● End zone width, a = 16' - 0"
9. ALL NON-LOAD-BEARING METAL STUD WALLS (INTERIOR AND EXTERIOR) SHALL BE CONNECTED REINFORCING SHOP DRAWINGS ●
TO ALLOW FOR 3/4" VERTICAL MOVEMENT BETWEEN STUD WALL AND STRUCTURE. b. ADHESIVE FOR REBAR AND ANCHORS SHALL HAVE BEEN TESTED AND QUALIFIED
10. ALL OTHER INTERIOR METAL STUD PARTITIONS, BULKHEADS, CEILING STUDS AND ECT. SHALL BE FOR USE IN ACCORDANCE WITH ICC-ES AC58. PRE-APPROVED ANCHORS 03 2000 - CONCRETE REINFORCING CONSTRUCTION JOINT LAYOUT ●
FURNISHED UNDER THE DIRECTION OF THE ARCHITECTURAL DOCUMENTS . ANY ADDITIONAL INCLUDE: REINFORCING MATERIAL CERTIFICATES ●
STUD DESIGN REQUIREMENTS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR'S METAL 11001 North Fwy
STUD DESIGN ENGINEER. REINFORCING MATERIAL TEST REPORTS ●
• SIMPSON STRONG TIE "TITEN-HD" (ICC-ES ESR-1056) Fort Worth, TX 76177
11. METAL STUD WALLS SHALL NOT BE ERECTED UNTIL AFTER DEAD LOADS AND ALL CONCRETE • SIMPSON STRONG TIE "STRONG-BOLT 2" (IAPMO-ES ER-240) PRODUCT DATA ●
FLOORS ON FRAMING ABOVE ABOVE ARE IN PLACE.
CONCRETE DESIGN MIXTURES ●
c. POWDER-ACTUATED FASTENERS SHALL HAVE BEEN TESTED IN ACCORDANCE
STEEL BAR JOIST NOTES WITH ICC-ES AC70. PRE-APPROVED ANCHORS INCLUDE: 03 3000 - CAST-IN-PLACE CONCRETE SLAB-ON-GRADE JOINT LAYOUT ●
MATERIAL CERTIFICATES ●
1. JOIST BRIDGING SHALL NOT BE USED TO SUPPORT CONDUIT, PIPING, DUCTWORK, ETC. • SIMPSON STRONG TIE "GAS ACTUATED PINS" (ICC-ES ESR-2811)
2. JOISTS SHALL NOT BE FIELD MODIFIED EXCEPT AS SHOWN. • SIMPSON STRONG TIE "POWDER ACTUATED PINS" (ICC-ES ESR-2138) MATERIAL TEST REPORTS ●
3. WHERE JOISTS CANNOT ACHIEVE THE REQUIRED BEARING ON STEEL BEAMS, STAGGER JOISTS PRODUCT DATA ●
TO PROVIDE ADEQUATE BEARING. 2. ANCHORAGE TO HOLLOW CONCRETE MASONRY
4. STEEL JOISTS SHALL BE OPEN WEB STEEL JOISTS OF THE SIZES AND SERIES SHOWN ON THE SHOP DRAWINGS ●
DRAWINGS. JOISTS, BRIDGING AND SPACING OF BRIDGING SHALL MEET THE REQUIREMENTS OF a. MECHANICAL ANCHORS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN MATERIAL CERTIFICATES ●
THE LATEST EDITION OF THE "STANDARD SPECIFICATIONS" OF THE STEEL JOIST INSTITUTE, 04 2200 - CONCRETE UNIT MASONRY
ACCORDANCE WITH ICC-ES AC106 PRE-APPROVED ANCHORS INCLUDE:
EXCEPT WHERE OTHERWISE INDICATED BY THE DRAWINGS OR SPECIFICATIONS. MIX DESIGNS FOR MORTAR AND GROUT ●
5. WHERE ANGLE BRACES ARE SHOWN ON STRUCTURAL SECTIONS, JOIST MANUFACTURER SHALL • SIMPSON STRONG TIE "TITEN-HD" STATEMENT OF COMPRESSIVE STRENGTH
RESOLVE AN AXIAL LOAD OF 2000 POUNDS FROM THE BRACE INTO THE JOIST - TYPICAL UNLESS ●
FOR MASONRY
NOTED OTHERWISE. b. ADHESIVE FOR REBAR AND ANCHORS WITH SCREEN TUBES SHALL HAVE BEEN PRODUCT DATA ●
6. IN ADDITION TO WHAT IS CALLED FOR ON PLAN, BAR JOISTS SHALL BE DESIGNED TO SUPPORT TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC58. THE
AN ADDITIONAL CONCENTRATED LOAD OF 300 POUNDS AT TOP OR BOTTOM CHORD AT ANY ONE APPROPRIATE SCREEN TUBE SHALL BE USED AS RECOMMENDED BY THE SHOP DRAWINGS ●
LOCATION ALONG THE SPAN. ADHESIVE MANUFACTURER. PRE-APPROVED ANCHORS WITH SCREEN TUBES CONNECTION DESIGN CALCULATIONS ● ●
7. AT THE END OF EACH ROOF JOIST, PROVIDE A CONTINUOUS ROW OF BRIDGING AT THE LAST INCLUDE: 05 1200 - STRUCTURAL STEEL FRAMING
BOTTOM CHORD PANEL POINT FOR UPLIFT. TYPICAL AT EACH END OF JOIST. PAINT COMPATIBILITY CERTIFICATES ●
8. NET WIND UPLIFT SHALL BE CONSIDERED USING THE ASD COMPONENTS AND CLADDING • SIMPSON STRONG TIE "SET" (ICC-ES ESR-1772) MILL TEST REPORTS ● Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


PRESSURES (THIS SHEET) AND A DEAD LOAD OF 8 P.S.F. USE LOAD COMBINATION 16-15 IBC
PRODUCT TEST REPORTS ●

COMPOSITE FLOOR NOTES


c. POWDER-ACTUATED FASTENERS SHALL HAVE BEEN TESTED IN ACCORDANCE
WITH ICC-ES AC70. PRE-APPROVED ANCHORS INCLUDE: 05 2100 - STEEL JOIST FRAMING STEEL JOIST SHOP DRAWINGS
STEEL DECKING PRODUCT DATA & SHOP
● General Notes
1. ALL SHEAR STUDS SHALL BE 3/4" DIAMETER x 3-1/2" LONG. SHEAR STUDS SHALL BE FIELD • SIMPSON STRONG TIE "GAS ACTUATED PINS" (ICC-ES ESR-2811) 05 3100 - STEEL DECKING ●
DRAWINGS
WELDED TO TOP FLANGE OF BEAMS AND TESTED IN ACCORDANCE TO THE PROJECT • SIMPSON STRONG TIE "POWDER ACTUATED PINS" (ICC-ES ESR-2138)
SPECIFICATIONS. PRODUCT DATA ●
2. NO CONDUIT SHALL BE PLACED OR RUN IN THE CONCRETE SLAB. ALL CONDUIT SHALL BE C. FOR ANCHORING INTO STEEL POWDER-ACTUATED FASTENERS SHALL HAVE BEEN TESTED IN SHOP DRAWINGS ●
SUPPORTED FROM BELOW THE SLAB. ACCORDANCE WITH ICC-ES AC70. PRE-APPROVED ANCHORS INCLUDE:
EXTERIOR METAL STUD DESIGN
3. ALL DECK SIDE LAPS SHALL BE EITHER WELDED OR FASTENED WITH A SELF TAPPING FASTENER. 05 4000 - COLD-FORMED METAL FRAMING ● ●
1. SIMPSON STRONG TIE "GAS ACTUATED PINS" (ICC-ES ESR-2811) CALCULATIONS
BUTTON PUNCHING, OR CRIMPING IS NOT PERMITTED. SEE SPECIFICATIONS FOR SPACING.
4. METAL STUD WALLS SHALL NOT BE ERECTED UNTIL AFTER DEAD LOADS AND ALL CONCRETE 2. SIMPSON STRONG TIE "POWDER-ACTUATED PINS" (ICC-ES ESR-2138) PRODUCT CERTIFICATES ●
FLOORS ON FRAMING ABOVE ABOVE ARE IN PLACE. PRODUCT TEST REPORTS ● Sheet Number:
PRODUCT DATA ●

05 5113 - METAL STAIRS, HAND RAILS, & GUARDS


SHOP DRAWINGS
DESIGN CALCULATIONS
PAINT COMPATIBILITY CERTIFICATES



● S001
STEEL COLUMN SCHEDULE SLAB AND DECK SCHEDULE
Showroom
Roof
40' - 0"
Showroom
Roof
40' - 0"
MARK
TOTAL THICKNESS: 5-1/2"
CONCRETE 28-DAY STRENGTH: 4,000 PSI
CONCRETE DENSITY: 115 PCF
DESCRIPTION
PRAXIS3
100 Peachtree St NW 404-875-4500 tel
CONCRETE REINFORCEMENT: #4 @ 12" o.c. EACH WAY, 3/4" CLEAR FROM TOP Suite 1450 404-876-8884 fax

HSS8X8X1/4
DECK: 2" COMPOSITE (VULCRAFT 2VLI OR EQUIVALENT) Atlanta, GA 30303 www.praxis3.com
GAUGE: 20 (t = 0.0358")
FINISH: GALVANIZED (G90)

HSS6X6X1/4
CF-5.5 GRADE: 50 ksi
FASTENER TYPE AT SUPPORT: 5/8" Ø PUDDLE WELDS
END SUPPORT ATTACHMENT PATTERN: 36/4
Level 2 Level 2 INTERMEDIATE SUPPORT ATTACHMENT PATTERN: 36/4
PERIMETER SUPPORT ATTACHMENT PATTERN: 12" o.c. MAX.
24' - 0" 24' - 0"

HSS8X8X5/16
HSS10.750X0.375

HSS10.750X0.500
HSS12.750X0.500

HSS8X8X1/4
Low Roof Low Roof SIDE LAP FASTENER: #10 TEK SCREWS @ 18" o.c. MAX.

HSS10X10X1/2
HSS8X8X5/16
MINIMUM END LAP = 4" (AT SUPPORTS ONLY)

HSS8X8X5/16
21' - 0" 21' - 0"

HSS8X8X3/8
6" ELEVATED CONCRETE CAST-IN-PLACE SLAB

HSS8X8X1/4
Service Drive Service Drive 28-DAY CONCRETE STRENGTH = 4,000 PSI
Vestibule Vestibule CIP-6 NORMAL-WEIGHT CONCRETE

HSS6X6X1/4

HSS6X6X1/2

HSS6X6X3/8
REINFORCEMENT: #3 @ 10" o.c. EACH WAY BOTTOM

HSS8X8X5/16
HSS6X6X1/4

HSS8X8X1/2

HSS8X8X1/4
14' - 0" 14' - 0"
2 2

HSS8X8X1/4
CLEAR COVER = 1-1/2"

HSS8X8X1/4
HSS4X4X5/16
HSS8X8X1/4
DECK: 1-1/2" WIDE RIB TYPE B
GAUGE: 22 (t = 0.0295")
HSS8X8X1/2

HSS4X4X5/16
FINISH: GALVANIZED (G90)

HSS5X5X1/4
GRADE: 50 ksi SIGNED & SEALED 03.30.2023
FASTENER TYPE AT SUPPORT: 5/8" Ø PUDDLE WELDS WITH WELDING WASHERS
RD-1.5 END SUPPORT ATTACHMENT PATTERN: 36/4 Copyright (c) 2023 Praxis3, LLC

Level 1 Level 1 All reports, plans, specifications, computer files, field data, notes and other documents
INTERMEDIATE SUPPORT ATTACHMENT PATTERN: 36/4 and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.
0' - 0" 0' - 0" PERIMETER SUPPORT ATTACHMENT PATTERN: 12" o.c. MAX.
This drawing may not be reproduced in whole or in part without written permission of
SIDE LAP FASTENER: #10 TEK SCREWS @ 18" o.c. MAX. Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.
Column C.6-4.6, C.8-4.6, MS1-MSA, MINIMUM END LAP = 4" (AT SUPPORTS ONLY)
B-1, B-1.2, B-1.1, B-1.3, MS4-MSA,
Locations A-3.4, A-3.6 A.2-2 A.2-3, A.2-4 A.2-5 A.4-3.3, A.4-3.5 B-1.9 C-1 C-1.9 C-3 C-4 C-5 C.4-6, C.6-6 E-4.6, E.3-4.6, D-1 D-1.8 D-1.9 D-3 D-4 D-5 E-6 E.2-3.8, E.6-3.8 F-6 MS2-MSA, Rev Date Comments
B-1.5, C.5-1 B-1.6, B-1.8
E.5-4.6 MS3-MSA
MS5-MSA 5" CONCRETE SLAB ON A VAPOR RETARDER ON A GRAVEL BED OR SAND
CUSHION AS RECOMMENDED BY THE GEOTECHNICAL REPORT. REINFORCE 10.03.2022 Permit / Bid Set
SOG-5
SLAB WITH WELDED WIRE FABRIC 6/6-W2.9xW2.9 IN FLAT SHEETS. FINISH FLOOR 2 04.18.2023
03.31.2023 ASI 01
SLAB ELEVATION SEE CIVIL FOR DATUM
STEEL COLUMN MASONRY COLUMN SCHEDULE ANCHOR BOLT SCHEDULE (F1554 GRADE 36) 6" CONCRETE SLAB ON A VAPOR RETARDER ON A GRAVEL BED OR SAND
CUSHION AS RECOMMENDED BY THE GEOTECHNICAL REPORT. REINFORCE
MARK SIZE VERTICAL REINF. SHEAR REINF. ANCHOR BOLT ANCHOR BOLT PROJECTION GROUT MIN. WASHER MIN. WASHER SOG-6
SCHEDULE MC1216A 11-5/8" x 16" A (4) #5 - DIAMETER ABOVE TOP OF FOUNDATION THICKNESS WIDTH THICKNESS COUNT
SLAB WITH WELDED WIRE FABRIC 6/6-W2.9xW2.9 IN FLAT SHEETS. FINISH FLOOR
SLAB ELEVATION SEE CIVIL FOR DATUM
Showroom Showroom MC1232A 11-5/8" x 32" A (8) #5 - 3/4" 8" 2" 2" 1/4" 152 8" CONCRETE SLAB ON A VAPOR RETARDER ON NON-EXPANSIVE FILL AS
Roof Roof MC1248A 11-5/8" x 48" A (12) #5 - RECOMMENDED IN SECTION 4.2 OF THE GEOTECHNICAL REPORT. REINFORCE
SOG-8
40' - 0" 40' - 0" SLAB WITH #4 @ 12" O.C. EACH WAY BOTTOM (3" CLEAR). 5,000 PSI CONCRETE.
"L"
BASE PLATE SCHEDULE (36 KSI) SEE CIVIL FOR DATUM.
PLATE PLATE PLATE ANCHOR BOLT
MARK WIDTH LENGTH THICKNESS ANCHOR BOLT DIAMETER EMBEDMENT COUNT
"D"

BP10 10" 10" 3/4" HEADED ANCHOR BOLT : 3/4" Ø 1' - 0" 7
BP12 12" 12" 3/4" HEADED ANCHOR BOLT : 3/4" Ø 1' - 0" 6
MC 0816A MC 1216A
BP14 14" 14" 3/4" HEADED ANCHOR BOLT : 3/4" Ø 1' - 0" 15
Level 2 Level 2
BP14a 14" 14" 3/4" HEADED ANCHOR BOLT : 3/4" Ø 1' - 0" 4
"L" BP14b 14" 14" 7/8" HEADED ANCHOR BOLT : 3/4" Ø 1' - 0" 1
24' - 0" 24' - 0"
Low Roof Low Roof BP14c 14" 14" 1" HEADED ANCHOR BOLT : 3/4" Ø 1' - 0" 2
21' - 0" 21' - 0" BP16 16" 16" 1" HEADED ANCHOR BOLT : 3/4" Ø 1' - 0" 1
"D"

BP16a 16" 16" 1" HEADED ANCHOR BOLT : 3/4" Ø 1' - 0" 2
Service Drive Service Drive
Vestibule Vestibule MC 0832A MC 1232A
5 1/2" 5 1/2"
14' - 0" 14' - 0" 3 1/2" 3 1/2" 4 1/2" 4 1/2" 1 1/2" 1 1/2" 2" 6" 6" 2"

1 1/2"
1 1/2"
1 1/2"
"L" 1 1/2" 1 1/2" 1 1/2" 1 1/2"
HSS8X8X1/4

5 1/2"
3 1/2"

4 1/2"

6" 2"
CENTERLINE CENTERLINE CENTERLINE CENTERLINE
"D"

OF COLUMN OF COLUMN OF COLUMN OF COLUMN

2" 6"
3 1/2"

4 1/2"

5 1/2"
1 1/2"

1 1/2"
MC 0848A MC 1248A

1 1/2"
Level 1 Level 1
0' - 0" 0' - 0" "L" = WALL COL. BP10 BP12 BP14 BP16
LENGTH

THICKNESS
WASHER

WASHER
Column
Locations
MS4-MSB,
MS5-MSB
WALL TYPE KEY: MC 0848A WIDTH

1 1/2" 5 1/2"5 1/2" 1 1/2" 2" 6" 6" 2"

5 1/2"5 1/2" 1 1/2"


INDICATES COLUMN IS
"D" = WALL COL. Mark W. Nannis, P.E.

PROJECTION
REINFORCED IN EACH FACE

6" 2"
EMBEDMENT
DEPTH LEVELING NUT Texas Design Firm #21364
AND WASHER CENTERLINE CENTERLINE 1591 Riverside Drive
NOTE: SEE MASONRY COLUMN SCHEDULE FOR VERTICAL OF COLUMN OF COLUMN Gainesville, GA 30501
HEAVY HEX
REINFORCEMENT AND SHEAR REINFORCEMENT. MINIMUM 770-614-6114 tel

2" 6"
HEAD OR NUT
REINFORCEMENT SHALL BE #5 VERTICAL. All drawings, specifications, and other work product

1 1/2"
NOTE: SQUARE OR CIRCULAR of Mark W. Nannis, P.E. (henceforth referred to as "The
Engineer") for this project are instruments of service for
WASHERS ARE ACCEPTABLE. this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
HEADED ANCHOR BP14a BP16a of any of the instruments of service of The Engineer by
BOLT & WASHER the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk
and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
expenses including attorney's fees arising out of such
unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
© 2023
MINIMUM ANCHOR BOLT WASHER DIMENSIONS
ANCHOR BOLT MINIMUM WASHER MINIMUM WASHER
STEEL BEAM AND BAR JOIST Client:

DIAMETER "B" DIMENSION THICKNESS


BEARING PLATE SCHEDULE Automotive
3/4" 2" 1/4"

7/8" 2-1/2" 5/16" MEMBER


BEARING
THICKNESS
NUMBER OF HEADED Managment
PLATE STUDS X 5" LONG
1" 3" 3/8" Services, Inc.
1-1/8" OR 1-1/4" 3" 1/2" WF BEAM 7" x 12" 3/4" THICK (2) - 3/4"DIAM 505 S. Flagler Dr., Suite 1400
West Palm Beach, FL 33401
1-3/8" OR 1-1/2" 3-1/2" 1/2"
LH SERIES JOIST 6" x 12" 5/8" THICK (2) - 5/8" DIAM
1-5/8" OR 1-3/4" 4" 5/8" Project Number: 22008
1-7/8" OR 2" 5" 3/4"
K SERIES JOIST 5" x 9" 5/8" THICK (2) - 5/8" DIAM Project Name:

2-1/4" OR 2-1/2" 5-1/2" 7/8"


1' - 0" 1' - 0"
Alliance Hyundai
"B" "B" 9"

1 1/2" 1 1/2" 3" 3" 3" 3" 11001 North Fwy


Fort Worth, TX 76177
CIRCULAR WASHER SQUARE WASHER K SERIES JOIST LH SERIES JOIST WF BEAM

EXTERIOR SCHEDULE OF METAL STUD SIZES MASONRY LINTEL SCHEDULE


115 MPH, EXPOSURE C, Fy = 33 ksi 8" CMU LINTEL
WALL HEIGHT 6" STUD 8" STUD
WIND ZONE 4 L/360 L/600 L/360 L/600 SPAN SIZE REINFORCEMENT
Up to 11'-0" 600S 162-43 @ 16" o/c 600S 162-43 @ 16" o/c 800S 162-43 @ 16" o/c 800S 162-43 @ 16" o/c 0 to 4'-0" 8" x 8" 2 #5 BOTT.
4'-1" to 8'-0" 8" x 16" 2 #5 BOTT.
Over 11'-0" to 12'-6" 600S 162-43 @ 16" o/c 600S 162-68 @ 16" o/c 800S 162-54 @ 16" o/c 800S 162-54 @ 16" o/c
8'-1" to 10'-0" 8" x 24" 2 #5 BOTT. & 2 #4 TOP
Over 12'-6" to 15'-6" 600S 162-68 @ 16" o/c 600S 200-97 @ 16" o/c 800S 162-54 @ 16" o/c 800S 162-54 @ 16" o/c 10'-1" to 12'-0" 8" x 32" 2 #6 BOTT. & 2 #5 TOP Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


Over 15'-6" to 16'-6" 600S 162-97 @ 16" o/c 600S 200-97 @ 12" o/c 800S 162-54 @ 16" o/c 800S 162-68 @ 16" o/c 12'-1" to 14'-0" 8" x 40" 2 #6 BOTT. & 2 #5 TOP
Over 16'-6" to 20'-0" 600S 200-97 @ 12" o/c N/A 800S 162-68 @ 16" o/c 800S 250-97 @ 16" o/c Schedules
Over 20'-0" to 21'-0" 600S 250-97 @ 12" o/c N/A 800S 162-97 @ 16" o/c 800S 200-97 @ 12" o/c 12" CMU LINTEL
WIND ZONE 5 L/360 L/600 L/360 L/600 SPAN SIZE REINFORCEMENT
Up to 11'-0" 600S 162-43 @ 16" o/c 600S 162-54 @ 16" o/c 800S 162-54 @ 16" o/c 800S 162-54 @ 16" o/c 0 to 4'-0" 12" x 8" 2 #5 BOTT.
4'-1" to 8'-0" 12" x 16" 2 #5 BOTT. & 2 #5 TOP
Over 11'-0" to 12'-6" 600S 162-54 @ 16" o/c 600S 162-68 @ 16" o/c 800S 162-54 @ 16" o/c 800S 162-54 @ 16" o/c
8'-1" to 10'-0" 12" x 24" 2 #5 BOTT. & 2 #5 TOP
Over 12'-6" to 15'-6" 600S 162-97 @ 16" o/c 600S 250-97 @ 16" o/c 800S 162-54 @ 16" o/c 800S 162-68 @ 16" o/c 10'-1" to 12'-0" 12" x 32" 2 #6 BOTT. & 2 #5 TOP
Over 15'-6" to 16'-6" 600S 162-97 @ 16" o/c 600S 200-97 @ 12" o/c 800S 162-54 @ 16" o/c 800S 162-97 @ 16" o/c 12'-1" to 15'-4" (12" x 48") 2 #8 BOTT. & 2 #6 TOP Sheet Number:
Over 16'-6" to 20'-0" 600S 200-97 @ 12" o/c N/A 800S 162-97 @ 16" o/c 800S 250-97 @ 16" o/c
NOTE: LINTEL SIZE IN PARENTHESIS ( ) SHALL HAVE #3
Over 20'-0" to 21'-0" N/A
NOTE: WHERE EXTERIOR FINISH IS EXTERIOR FINISHES, EFIS OR METAL PANEL USE DEFLECTION LIMITATION
OF L/360.
N/A 800S 162-97 @ 16" o/c 800S 200-97 @ 12" o/c DOUBLE TIES VERTICAL AT 8" o.c. MAX.
NOTE: BEAR LINTELS A MINIMUM OF 8" AT EACH END OF
OPENING.
S002
SPECIAL INSPECTIONS SCHEDULES PRAXIS3
1704.2.5 Inspection of Fabricators 1705.4 Masonry Construction (in accordance with TMS 402/ACI 530/ASCE 5 AND TMS 602/ACI 530.1/ASCE 6)
APPLICABLE TO THIS PROJECT DATE APPLICABLE TO THIS PROJECT DATE 100 Peachtree St NW 404-875-4500 tel
Suite 1450 404-876-8884 fax
MATERIAL / ACTIVITY SERVICE Y/N EXTENT AGENT* COMPLETED MATERIAL / ACTIVITY SERVICE Y/N EXTENT AGENT* COMPLETED
In-plant review (3) Y 1 (A) Levels A, B, and C Quality Assurance:
Atlanta, GA 30303 www.praxis3.com
Verify fabrication/quality control procedures Periodic - If fabricator is not AISC certified, (structural steel) or
certified by the standard code/spec. for the fabricated assembly or 1. Verify compliance with approved submittals Field inspection Y Periodic 1, 2, & 3
material, special inspection required as indicated within structural (B) Level B Quality Assurance:
steel welding portion of this document or applicable 1. Verification of f'm and f'acc prior to construction Testing by unit strength method or prism test method Y Periodic 1
code/specification. If fabricator is approved as specified in section
(C) Level C Quality Assurance:
1704.2.5.1, fabricator inspection is not required. At completion of
fabrication, fabricator shall submit certificate of compliance to 1. Verification of f'm and f'acc prior to construction and for every 5,000 SF during construction Testing by unit strength method or prism test method N Periodic 1
building official in accordance with Section 1704.2.5.1. 2. Verification of proportions of materials in premixed or preblended mortar, prestressing grout, Field inspection N Continuous 1
and grout other than self-consolidating grout, as delivered to the project site
1705.1.1 Special Cases 3. Verify placement of masonry units Field inspection N Periodic 1
(D) Levels B and C Quality Assurance:
APPLICABLE TO THIS PROJECT DATE 1. Verification of Slump Flow and Visual Stability Index (VSI) of self-consolidating grout as Field testing Y Continuous 1
MATERIAL / ACTIVITY SERVICE Y/N EXTENT AGENT* COMPLETED delivered to the project
The special inspector must record product description Y Continuous during the first 36-hour period of anchor installation for 1 2. Verify compliance with approved submittals Field inspection Y Periodic 1
HY-150 (or equal epoxy system/anchor) (including product name), adhesive expiration date, concrete each anchor type (special inspector must be on site and observing 3. Verify proportions of site-mixed mortar, grout and prestressing grout for bonded tendons Field inspection Y Periodic - test one prior to construction of each building 1
or masonry type and strength, anchor diameter and steel installation of operations while installations are taking place).
4. Verify grade, type, and size of reinforcement and anchor bolts, and prestressing tendons Field inspection Y Periodic - 1) for reinforcement and anchor bolts perform one 1
grade, complience of drill bit with this report, hole diameter Remaining anchor installations: periodic - random 25% of anchor
and anchorages inspection per day or every 5,000 square feet of wall area, whichever
and location, cleanliness of hole and anchor adhesive installation inspected. If any installations do not meet specifications,
is more restrictive 2) for prestressing tendons and anchorages verify
application, and anchor embedment. Additionally, the special all anchors/installations will be inspected (anchors installed and
one time at start of prestressing and one additional verification every 2
inspector must state in the report supplied to the building remaining anchors to be installed). Inspections may require
weeks during prestressing
official whether the anchor installation is in accordance with continuous inspection if required by building official - special
the manufacturer's published instructions and this evaluation inspector to confirm prior to inspections. 5. Verify construction of mortar joints Field inspection Y Periodic - inspect at same intervals as mortar samples are taken for 1
SIGNED & SEALED 10.03.2022
report. mortar testing
Kwik Bolt 3 (or equal wedge/expansion anchor system/anchor) The special inspector must record product description Y 1 6. Verify placement of reinforcement, connectors, and prestressing tendons and Field inspection Y Level B - Periodic - one inspection per day or every 5,000 square 1 Copyright (c) 2022 Praxis3, LLC
Continuous during the first 36-hour period of anchor installation for
(including product name), masonry type and condition, anchor anchorages feet of wall area, whichever is most restrictive
each anchor type (special inspector must be on site and observing All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
type, diameter and steel grade, compliance of the drill bit with installation of operations while installations are taking place). N Level C - Continuous 1 reserved rights, including copyright thereto.
this report, hole diameter and location; and anchor Remaining anchor installations: periodic - random 25% of anchor 7. Verify grout space prior to grouting Field inspection Y Level B - Periodic 1 This drawing may not be reproduced in whole or in part without written permission of
embedment. Additionally, the special inspector must state in installation inspected. If any installations do not meet specifications, all Praxis3. It is to be returned upon request. Scales as stated are valid on the original
the report supplied to the building official whether the anchor
N Level C - Continuous 1
anchors/installations will be inspected (anchors installed and remaining drawings.
installation is in accordance with the manufacturer's published anchors to be installed). Inspections may require continuous inspection 8. Verify placement of grout and prestressing grout for bonded tendons Field inspection Y Continuous 1
instructions and this evaluation report. if required by building official - special inspector to confirm prior to 9. Verify size and location of structural masonry elements Field inspection Y Periodic - one inspection per day or every 5,000 square feet of wall 1 Rev Date Comments
inspections. area, whichever is more restrictive
10.03.22 Permit / Bid Set
10. Verify type, size, and location of anchors, including details of anchorage of masonry to Field inspection Y Level B - Periodic - one inspection per day or every 5,000 square 1
structural members, frames, or other construction. feet of wall area, whichever is most restrictive
1705.2 Steel Construction
N Level C - Continuous 1
APPLICABLE TO THIS PROJECT DATE 11. Verify welding of reinforcement (see 1705.2.2) Field inspection N Continuous 1
MATERIAL / ACTIVITY SERVICE Y/N EXTENT AGENT* COMPLETED 12. Verify preparation, construction, and protection of masonry during cold weather Field inspection Y Periodic - one inspection per day or every 5,000 square feet of wall 1
1. Fabricator and erector documents (Verify reports and certificates as listed in AISC 360, chapter Submittal Review Y Each submittal 1&2 (temperature below 40 degrees F) or hot weather (temperature above 90 degrees F) area, whichever is more restrictive
N, paragraph 3.2 for compliance with construction documents) 13. Verify application and measurement of prestressing force Field inspection N Continuous 1
2. Material verification of structural steel Shop (3) and field inspection Y Periodic 14. Verify placement of AAC masonry units and construction of thin-bed mortar joints (first Field inspection N Continuous 1
3. Embedments (Verify diameter, grade, type, length, embedment. See 1705.3 for anchors) Field inspection Y Periodic 1 5000 SF of AAC masonry)
4. Verify member locations, braces, stiffeners, and application of joint details at each connection Field inspection Y Periodic - random selection of 25% of all frame joints. 1 15. Verify placement of AAC masonry units and construction of thin-bed mortar joints (after Field inspection N Level B - Periodic 1
comply with construction documents the first 5000 SF of AAC masonry) N Level C - Continuous
5. Structural steel welding: 16. Verify properties of thin-bed mortar for AAC masonry (first 5000 SF of AAC masonry) Field inspection N Continuous 1
a. Inspection tasks Prior to Welding (Observe, or perform for each welded joint or member, the Shop (3) and field inspection Y Observe or Perform as noted (4) 1 17. Verify properties of thin-bed mortar for AAC masonry (after the first 5000 SF of AAC Field inspection N Level B - Periodic 1
QA tasks listed in AISC 360, Table N5.4-1) masonry) N Level C - Continuous
b. Inspection tasks During Welding (Observe, or perform for each welded joint or member, the Shop (3) and field inspection Y Observe (4) 1 18. Prepare grout and mortar specimens Field testing N Level B - Periodic 1
QA tasks listed in AISC 360, Table N5.4-2) N Level C - Continuous
c. Inspection tasks After Welding (Observe, or perform for each welded joint or member, the Shop (3) and field inspection Y Observe or Perform as noted (4) 1 19. Observe preparation of prisms Field inspection N Level B - Periodic 1
QA tasks listed in AISC 360, Table N5.4-3) N Level C - Continuous
d. Nondestructive testing (NDT) of welded joints: see Commentary
1) Complete penetration groove welds 5/16" or greater in risk category III or IV Shop (3) or field ultrasonic testing - 100% N Periodic 1 1705.8 Cast-in-Place Deep Foundations
2) Complete penetration groove welds 5/16" or greater in risk category II Shop (3) or field ultrasonic testing - 10% of welds minimum Y Periodic 1
3) Thermally cut surfaces of access holes when material t > 2" Shop (3) or field magnetic Partical or Penetrant testing N Periodic 1 APPLICABLE TO THIS PROJECT DATE
Shop (3) or field radiographic or Ultrasonic testing N Periodic 1 MATERIAL / ACTIVITY SERVICE Y/N EXTENT AGENT* COMPLETED
4) Welded joints subject to fatigue when required by AISC 360, Appendix 3, Table A-3.1
1.Observe drilling operations and maintain complete and accurate records for each element Field inspection Y Continuous 1
5) Fabricator's NDT reports when fabricator performs NDT Verify reports N Each submittal (5) 1 2. Verify placement locations and plumbness, confirm element diameters, bell diameters (if Field inspection Y Continuous 1
6. Structural steel bolting: applicable), lengths, embedment into bedrock (if applicable) and adequate end-bearing strata
Shop (3) and field inspection capacity. Record concrete or grout volumes
a. Inspection tasks Prior to Bolting (Observe, or perform tasks for each bolted connection, in N Observe or Perform as noted (4) 1
accordance with QA tasks listed in AISC 360, Table N5.6-1) 3. For concrete elements, perform additional inspections in accordance with Section 1705.3 See Section 1705.3 Y See Section 1705.3 1
b.Inspection tasks during bolting (observe the QA tasks listed in AISC 360, Table N5.6-2) Shop (3) and field inspection Y Observe (4) 1 4. Verify placement locations and plumbness, confirm type and size of hammer, record number of Field Inspection and testing Y In accordance with construction documents
1) Pre-tensioned and slip-critical joints blows per foot of penetration, determine required penetrations to achieve design capacity, record 1
a) Turn-of-nut with matching markings Shop (3) and field inspection N Periodic 1 tip and butt elevations and document any damage to foundation element
b) Direct tension indicator Shop (3) and field inspection Y Periodic - observe all connections; measure 10% of connections 1
c) Twist-off type tension control bolt Shop (3) and field inspection Y Periodic - observe all connections 1 1705.6 Soils
d) Turn-of-nut without matching markings Shop (3) and field inspection N Continuous 1
e) Calibrated wrench Shop (3) and field inspection Y Continuous 1 APPLICABLE TO THIS PROJECT DATE
2) Snug-tight joints Shop (3) and field inspection N Periodic 1 MATERIAL / ACTIVITY SERVICE Y/N EXTENT AGENT* COMPLETED
c. Inspection tasks After Bolting (Perform tasks for each bolted connection in accordance with Shop (3) and field inspection Y Perform (4) 1 Field inspection Y Periodic 1
1. Verify materials below shallow foundations are adequate to achieve the design bearing capacity.
QA tasks listed in AISC 360, Table N5.6-3)
7. Inspection of steel elements of composite construction prior to concrete placement in Shop (3) and field inspection and testing N Observe or Perform as noted (4) 1 2. Verify excavations are extended to proper depth and have reached proper material. Field inspection Y Periodic 1
accordance with QA tasks listed in AISC 360, Table N6.1 3. Perform classification and testing of controlled fill materials. Field inspection Y Periodic 1
4. Verify use of proper materials, densities, and lift thicknesses during placement and compaction Field inspection Y Continuous 1
1705.2.2 Steel Construction Other Than Structural Steel of controlled fill
5. Prior to placement of controlled fill, observe subgrade and verify that site has been prepared Field inspection Y Periodic 1
APPLICABLE TO THIS PROJECT DATE properly Mark W. Nannis, P.E.
MATERIAL / ACTIVITY SERVICE Y/N EXTENT AGENT* COMPLETED Texas Design Firm #21364
1591 Riverside Drive
1. Material verification of cold-formed steel deck: *Inspection Agents Gainesville, GA 30501
a. Identification markings Field inspection Y Periodic 1
b. Manufacturer's certified test reports Submittal Review Y Each submittal 1
FIRM 770-614-6114 tel
2. Connection of cold-formed steel deck to supporting structure: 1. Special Inspector
Y 1 All drawings, specifications, and other work product
2. Structural Engineer
a. Welding Shop (3) and field inspection Y Periodic - inspect all deck welds & side laps 1 of Mark W. Nannis, P.E. (henceforth referred to as "The
3. Architect Engineer") for this project are instruments of service for
b. Other fasteners (in accordance with AISC 360,Section N6) this project only and shall remain the property of The
1) Verify fasteners are in conformance with approved submittal Y Periodic 1 4. Mech. & Plumbing
Shop (3) and field inspection Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by
2) Verify fastener installation is in conformance with approved submittal and Shop (3) and field inspection Y Periodic 1 Notes: the owner or extensions of this project without the written
manufacturer's recommendations 1. The inspection and testing agent(s) shall be engaged by the Owner or the Owner's Agent, and not by the Contractor or Subcontractor whose work is to be inspected or permission of The Engineer shall be at the owner's risk
tested. Any conflict of interest must be disclosed to the Building Official prior to commencing work. The qualifications of the Special Inspector(s) and/or testing agencies and the owner agrees to defend, indemnify, and hold
3. Reinforcing steel
may be subject to the approval of the Building Official and/or the Design Professional. harmless The Engineer from all claims, damages, and
a. Verification of weldability of steel other than ASTM A706 Shop (3) and field inspection Y Periodic - verify correct, specified weld electrodes and reinforcing 1 2. The list of Special Inspectors may be submitted as a separate document, if noted so above. expenses including attorney's fees arising out of such
steel for each material shipment. Verify compliance with specified 3. Special Inspections as required by Section 1704.2.5 are not required where the fabricator is approved in accordance with IBC Section 1704.2.5.2 unauthorized reuse of The Engineer's instruments of
connection, construction for each connection type at the start of service by the owner or others acting through the owner.
4. Observe on a random basis, operations need not be delayed pending these inspections. Perform these tasks for each welded joint, bolted connection, or steel element. © 2022
construction for that connection type. 5. NDT of welds completed in an approved fabricator's shop may be performed by that fabricator when approved by the AHJ. Refer to AISC 360, N7.
6. For all other disciplines refer to relevant documents provided by the design professional. Client:
b. Reinforcing steel resisting flexural and axial forces in intermediate and special moment Shop (3) and field inspection N Continuous 1
frames, boundary elements of special concrete structural walls and shear reinforcement
c. Shear reinforcement Shop (3) and field inspection N Continuous 1 Automotive
d. Other reinforcing steel Shop (3) and field inspection N Periodic - verify correct, specified weld electrodes and reinforcing 1
steel for each material shipment. Verify compliance with specified
connection, construction for each connection type at the start of
Managment
construction for that connection type.

4. Cold-formed steel trusses spanning 60 feet or greater


Services, Inc.
505 S. Flagler Dr., Suite 1400
a. Verify temporary and permanent restraint/bracing are installed in accordance with the Field inspection N Periodic 1 West Palm Beach, FL 33401
approved truss submittal package
Project Number: 22008
1705.3 Concrete Construction Project Name:
APPLICABLE TO THIS PROJECT
MATERIAL / ACTIVITY SERVICE Y/N EXTENT AGENT*
DATE
COMPLETED Alliance Hyundai
1. Inspection of reinforcing steel installation (see 1705.3.1 for welding) Shop (3) and field inspection Y Periodic - before each concrete pour of ftgs., walls, columns, and 1
elevated slabs with sufficient time allowed for inspection of
completed installed reinforcing prior to pour.
2. Inspection of prestressing steel installation Shop (3) and field inspection N Periodic - before each concrete pour of ftgs., walls, columns, and
elevated slabs with sufficient time allowed for inspection of
completed installed reinforcing prior to pour.
3. Inspection of anchors cast in concrete where allowable loads have been increased per Section Shop (3) and field inspection N Periodic 11001 North Fwy
1901.3/ACI 318:17.8.2 or where strength design is used
Fort Worth, TX 76177
4. Inspection of anchors and reinforcing steel post-installed in hardened concrete: Per research Field inspection Y Periodic or as required by the research report issued by an 1
reports including verification of anchor type, anchor dimensions, hole dimensions, hole cleaning approved source
procedures, anchor spacing, edge distances, concrete minimum thickness, anchor embedment and
tightening torque
5. Verify use of approved design mix Shop (3) and field inspection Y Periodic 1&2
6. Fresh concrete sampling, perform slump and air content tests and determine temperature of Shop (3) and field inspection Y Continuous - sample every 75 cubic yds or each day (whichever is 1
concrete more stringent) and each change in concrete strength.
7. Inspection of concrete and shotcrete placement for proper application techniques Shop (3) and field inspection Y Continuous 1
8. Inspection for maintenance of specified curing temperature and techniques Shop (3) and field inspection Y Periodic 1
9. Inspection of prestressed concrete:
a. Application of prestressing force Shop (3) and field inspection N Continuous 1
b. Grouting of bonded prestressing tendons in the seismic-force-resisting system Shop (3) and field inspection N Continuous 1
10. Erection of precast concrete members
a. Inspect in accordance with construction documents Field inspection N In accordance with construction documents - 1) Sample grout: (3) 1
test samples every day of masonry construction for first three days
of masonry construction with additional (3) samples every 30 cubic
yards placed/once per week/every 5000 SF of wall, whichever is
most stringent. 2) Inspect erection, bearing conditions and general
conformance to erection drawings (2) times per week minimum. Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


b. Perform inspections of welding and bolting in accordance with Table 1705.3
11. Verification of in-situ concrete strength, prior to stressing of tendons in post tensioned concrete
and prior to removal of shores and forms from beams and structural slabs
Field inspection
Review field testing and laboratory reports
N
Y
In accordance with Section 1705.2 - (1) time per week minimum
Periodic - additional cylinder for 3-day/7-day tests (contractor's
option) on time of testing with same sampling frequency as typical
1
1 Special
Inspections
fresh concrete sampling. Verify that adequate concrete strength has
been obtained on concrete test cylinders.

12. Inspection of formwork for shape, lines, location, and dimensions Field inspection Y Periodic - inspect prior to each concrete placement. 1
13. Concrete strength testing and verification of compliance with construction documents Field testing and review of laboratory reports Y Periodic 1&2
Schedules
Sheet Number:

S003
FOUNDATION PLAN NOTES GRADE BEAM & WALL FOOTING SCHEDULE Gridline Type Legend
:

[0'-0"]
INDICATES TO SLOPE SLAB. SEE
ARCHITECTURAL FOR AMOUNT OF SLOPE AND
EXACT LOCATION.

INDICATES ELEVATION OF FINISH FLOOR SLAB.


NOTE:

NOTE:
AT THE BASE OF ALL STAIRS, PROVIDE A
THICKENED SLAB 10" THICK & 20" WIDE REINF.
WITH 2 #5 CONT.
GB24 2' - 0" 2' - 0"
BOTTOM

4 #5
TOP
MARK WIDTH THICKNESS REINFORCEMENT REINFORCEMENT
4 #5
STIRRUPS
#3 @ 10" o.c.
NEW GRIDLINE

F.O. MASONRY GRIDLINE


PRAXIS3
UNLESS NOTED OTHERWISE ON PLANS, TOP GB24a 2' - 0" 2' - 0" 4 #6 4 #6 #3 @ 10" o.c. 100 Peachtree St NW 404-875-4500 tel
SEE CIVIL DRAWINGS FOR DATUM. OF FOOTINGS AT ALL EXTERIOR FOOTINGS
SHALL BE [-2'-0"] BELOW FINISH FLOOR SLAB. GB24b 2' - 0" 2' - 0" 6 #5 6 #5 #3 @ 10" o.c. Suite 1450 404-876-8884 fax
[ ]: NUMBER INSIDE OF BRACKETS INDICATES TOP Atlanta, GA 30303 www.praxis3.com
OF FOOTING ELEVATION
GB24c 2' - 0" 2' - 0" 4 #7 4 #7 #3 @ 10" o.c.
NOTE: UNLESS NOTED OTHERWISE ON PLANS, TOP
OF FOOTINGS AT ALL INTERIOR FOOTINGS GB24e 2' - 0" 2' - 0" 4 #8 4 #8 #3 @ 10" o.c.
S

INDICATES A STEP IN FOOTING. SEE GENERAL SHALL BE [-2'-0"] BELOW FINISH FLOOR SLAB.
NOTES FOR CRITERIA. SEE DETAIL 5 / S680 GB24f 2' - 0" 2' - 0" 6 #7 6 #7 #3 DOUBLE STIRRUPS @ 10" o.c.
NOTE: MAXIMUM SPACING OF VERTICAL CONTROL GB24g 2' - 0" 2' - 0" 6 #8 6 #8 #3 DOUBLE STIRRUPS @ 10" o.c.
D.J. : INDICATES A DUMMY JOINT IN THE SLAB ON JOINTS IN EXTERIOR MASONRY VENEER IS
GRADE. SEE TYPICAL DUMMY JOINT 16'-0" FROM CORNERS AND 32'-0" FOR GB24h 2' - 0" 2' - 0" 6 #8 6 #8 #3 DOUBLE STIRRUPS @ 8" o.c.
DETAIL 3 / S680
. INTERMEDIATE VERTICAL JOINTS. SEE GB2418 2' - 0" 1' - 6" 4 #6 4 #5 #3 @ 16" o.c.
2
ARCHITECT FOR EXACT LOCATIONS.
F.J. : INDICATES A FLOOR JOINT. USE 24 GAUGE WF01 2' - 0" SEE TYP.
KEYED TYPE. DISCONTINUE MESH AT JOINT. NOTE: FOR ISOLATION JOINT AT COLUMN BASES, SEE THICKENED SLAB
SEE TYPICAL CONTROL JOINT DETAIL AND TYPICAL DETAIL: 11 / S680
SPECIFICATIONS. SEE DETAIL 2 / S680
DETAIL
NOTE: MAXIMUM EARTH DIFFERENTIAL WHEN
C.J. : INDICATES A VERTICAL CONTROL JOINT IN BACKFILLING SHOULD NOT EXCEED 2'-0"
CONCRETE WALL. PROVIDE AT LOCATIONS
NOTED ON FOUNDATION PLAN. DO NOT
EXCEED 30'-0" ON CENTER. SEE DETAIL - / ---
NOTE: SLABS-ON-GRADE REQUIRE CONTROL JOINTS DRILLED SHAFT SCHEDULE
PER THE TYPICAL DETAILS UNLESS NOTED
M.C.J. : INDICATES A MASONRY CONTROL JOINT.
OTHERWISE. LOCATE CONSTRUCTION AND
CONTROL JOINTS IN SUCH A WAY TO MINIMIZE
(MINIMUM EMBEDMENT DEPTH = 18'-0")
COORDINATE EXACT LOCATION WITH
ARCHITECT. JOINT SHALL EXTEND TO TOP OF
THE EFFECTS OF SHRINKAGE AND CURLING OF SHAFT Ø BELL Ø VERT. REINF. HOOPS COUNT
THE CONCRETE SLAB SECTIONS. SUBMIT TO
PARAPET AND SHALL NOT BE LOCATED WITHIN THE ARCHITECT/ENGINEER/EQUIPMENT 18" 48" (8) #5 #3 @ 12" o.c. 12
1'-0" OF A JOIST BEARING SEAT ABOVE, 2'-0" OF VENDOR THE SEQUENCE AND METHOD OF SIGNED & SEALED 02.16.2024
A BEAM BEARING, OR WITHIN 2'-0" OF JAMB OF 24" 54" (8) #5 #3 @ 12" o.c. 127
CASTING CONCRETE SLABS-ON-GRADE PRIOR
ANY OPENING. SEE DETAIL 7 / S687 TO PLACING THESE ELEMENTS. 24" 66" (8) #7 #3 @ 12" o.c. 15 Copyright (c) 2023 Praxis3, LLC

JOINT SPACING SHALL NOT EXCEED 15 FEET, All reports, plans, specifications, computer files, field data, notes and other documents
R.B.: INDICATES TO PROVIDE 2#4 X 3'-0" LONG. AND THE RESULTING PLAN ASPECT RATIO
24" 72" (8) #7 #3 @ 12" o.c. 2 and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.
CENTER AT INTERSECTION OF DUMMY JOINT (PANEL LENGTH TO PANEL WIDTH) OF ANY 30" 60" (12) #8 #3 @ 12" o.c. 2
WHERE JOINT IS NOT CONTINUOUS NOR GIVEN SECTION OF SLAB SHALL NOT EXCEED This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
ALIGNED. PLACE 1 BAR 1" CLEAR TOP, AND A 1.5. drawings.
SECOND BAR 3" CLEAR TOP OF SLAB. WHERE POSSIBLE, CONTROL JOINT LAYOUT
SHALL BE SUCH THAT JOINTS ALIGN WITH THE 13 Rev Date Comments
NOTE: ALL ELEVATIONS SHOWN ARE TOP OF FOOTING VERTICES OF COLUMN ISOLATION BLOCKOUTS
ELEVATION. S208 10.03.2022 Permit / Bid Set
AND SHALL BE ARRANGED IN A GENERALLY
ORTHOGONAL MANNER. 2 04.17.2023 ASI 01
NOTE: GENERAL CONTRACTOR SHALL ENGAGE A 3
SURVEYOR TO PROVIDE LOCATIONS OF ALL S207 54 02.16.2024 Foundation Coor.
EXISTING UTILITES, TRENCHES, ETC. TO M6 M5 R3 R2 M3.2 R1 M3 MS5 MS4 MS3 MS2 MS1
ENSURE THAT NEW FOUNDATIONS WILL NOT
INTERFERE, UNDERMINE, OR BEAR ON 8' - 8" 31' - 6" 14' - 0" 5' - 4"
EXISTING UTILITIES. 1' - 10"
MATCHLINE MATCHLINE
NOTE: CONTRACTOR SHALL COORDINATE EXACT
4" 8' - 4" 6" 16' - 0" 22' - 0" GB24
LOCATIONS OF ALL FLOOR JOINTS AND DUMMY
[-2' - 0"]
JOINTS WITH THE ARCHITECTURAL JOINTS IN MD.2
FINISHES. ALL FLOOR JOINTS SHOULD

[-2' - 0"]
Sim

[-2' - 0"]
GB24f
GB24
1' - 11"
4' - 9"

COINCIDE 15
DIRECTLY UNDER A JOINT IN THE RA S680 24" / 54" 24" / 54" 24" / 54" 24" / 54" 24" / 66" 24" / 54" 24" / 54" 24" / 54" 24" / 54" 24" / 54" 24" / 54"
ARCHITECTURAL FINISH ABOVE. SEE 24" / 54" GB24a 24" / 54" 24" / 54" [-2' - 0"] [-2' - 0"] [-4' - 0"] [-4' - 0"] [-4' - 0"] [-4' - 0"] [-4' - 0"] GB24h [-4' - 0"] [-4' - 0"] [-4' - 0"] [-4' - 0"] 24" / 54"

5 5/8"
ARCHITECTURAL DRAWINGS. [-4' - 0"] [-2' - 0"] [-4' - 0"] [-4' - 0"] [-2' - 0"] [-4' - 0"]
MD MD
NOTE: WHERE ROOF DRAIN PIPES ARE LOCATED
6"

OVER A COLUMN OR A WALL FOOTING, DROP GB24a


[-2' - 0"]
GB24

24" / 66"
7' - 2"

TOP OF FOOTING TO [-2'-0"] BELOW FINISH [-2' - 0"] 24" / 54" WF01 Sim

[0' - 0"]
D.J. WF01
FLOOR SLAB ELEVATION [0'-0"] AND PROVIDE A [-4' - 0"] [-4' - 0"] 13
13' - 11 7/8"

GB24 [0' - 0"]


F.J.

[0' - 0"]
15' - 7 5/8"

15' - 7 5/8"
CONCRETE PIER S680

WF01
[-2' - 0"]

D.J.

D.J.

D.J.
4"

14' - 0"
[0' - 0"]
GB2418

[0' - 0"]

[0' - 0"]

WF01
[-2' - 0"]

WF01

WF01
AT COLUMN.
D.J.

D.J.

F.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.
4' - 7 5/8"

[0' - 0"]
WF01
NOTE: FOOTINGS HAVE NOT BEEN DROPPED FOR 24" / 54" 4" 5' - 2" Sim

[0' - 0"]
WF01
BP14 17 SOG-5
CIVIL,PLUMBING, OR ELECTRICAL LINES. SEE [-4' - 0"] D.J. D.J. D.J. D.J.
24" / 54" S680 Sim
GENERAL NOTES FOR CRITERIA. 24" / 54"
[-2' - 0"] GB2418 13
D.J. D.J. D.J. [-4' - 0"] [-2' - 0"] S680
F

4"
SHAFT Ø / BELL Ø
24" / 54" D.J. D.J.
6' - 1 7/8"

D.J.

D.J.

D.J.
[ELEVATION] BASE PLATE MARK
Sim MC
[-4' - 0"] SOG-5 24" / 54"
10 5' - 6" 18" / 48" 18" / 48" 18" / 48" 18" / 48" 18" / 48" 18" / 48" 18" / 48"
12' - 6"

S682 BP10 [-4' - 0"]


18" / 48" [-3' - 6"] [-3' - 6"] [-3' - 6"] [-3' - 6"] [-3' - 6"] [-3' - 6"] [-3' - 6"]
D.J.

D.J.

F.J.
E.6 [-2' - 0"] 5
D.J. D.J. D.J. Sim D.J.
Sim

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.
8

F.J.
1' - 4 1/4" 1' - 6 1/8"

17' - 0"

17' - 4"
15
E.5 S686 SOG-8 SOG-6

[-2' - 0"]
GB24c
S680
9' - 11"

CL. OF PIER TUBE OR

D.J.
AND COLUMN W-SECTION 22' - 3 3/8" 9' - 3 3/4" 26' - 3"

D.J.

D.J.
D.J. D.J. D.J.
24" / 66" BP10
DRILLED PIER KEY 5 18" / 48"
E.3 [-4' - 0"] 24" / 54" 24" / 54" 24" / 54"
GB24e
24" / 54"
GB24e
24" / 54"
GB24e
24" / 54" 24" / 54"
[-2' - 0"]
12' - 6"

[-4' - 0"] [-4' - 0"] [-4' - 0"] [-2' - 0"] [-4' - 0"] [-2' - 0"] [-4' - 0"] [-2' - 0"] [-4' - 0"] [-4' - 0"]
F.J. F.J. F.J. F.J.

4"

4"
[-2' - 0"]

E.2 MB
GB24g

D.J.

D.J.

F.J.
SOG-6 Sim
4" 15' - 1 1/8" 15' - 2" 26' - 8" 6"
8' - 6 3/4"

[-2' - 0"]

[-2' - 0"]
Sim

GB24

GB24
D.J.
S686 13 Sim
BP14b BP10 10

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.
F.J.
5 S680
24" / 66" 18" / 48" S680
24" / 54" [-2' - 0"] [-2' - 0"] 24" / 54" 24" / 54"

R.B.
D.J. D.J. D.J. [-4' - 0"] [-4' - 0"]
E

21' - 1 1/4"
[-4' - 0"]
D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J.
12' - 6"

SOG-5
Mark W. Nannis, P.E.
9' - 11"

D.J.
D.J.

D.J.

F.J.

Sim Sim Texas Design Firm #21364


13 13

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.
1591 Riverside Drive

F.J.

10' - 9"
BP10 S680 S680
18" / 48" Gainesville, GA 30501
[-2' - 0"] BP14 BP14 BP14 BP12 770-614-6114 tel
D.J. D.J. D.J.
C.8 24" / 66" 24" / 54" 24" / 54" GB24 24" / 54" 24" / 54" 24" / 54"
24" / 54" [-2' - 0"] [-2' - 0"] [-4' - 0"] [-2' - 0"] [-4' - 0"] [-2' - 0"] [-2' - 0"] All drawings, specifications, and other work product
[-4' - 0"] D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. 2 D.J. D.J. D.J. D.J. of Mark W. Nannis, P.E. (henceforth referred to as "The
D Engineer") for this project are instruments of service for
9' - 11"

12' - 6"

D.J.

D.J.

F.J.

4"
D.J.
this project only and shall remain the property of The
Sim Engineer whether the project is complete or not. Reuse
12 BP14 BP10 Sim
13 of any of the instruments of service of The Engineer by
S680 24" / 66" 18" / 48" the owner or extensions of this project without the written
S680

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.
F.J.
[-4' - 0"] [-2' - 0"] permission of The Engineer shall be at the owner's risk
R.B.

D.J. D.J. D.J. and the owner agrees to defend, indemnify, and hold
C.6 SOG-5 SOG-5
harmless The Engineer from all claims, damages, and

19' - 9"
expenses including attorney's fees arising out of such
unauthorized reuse of The Engineer's instruments of
D.J.

24" / 54" D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. service by the owner or others acting through the owner.
[-4' - 0"] © 2023
12' - 9"

GB24
D.J.

D.J.

F.J.
12' - 6"

13
Sim Client:
S680 BP12
24" / 54"
Automotive
D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.
F.J.
C.4 BP14 [-2' - 0"]

R.B.
R.B.

C.5
Managment
6"

MA
GB24
1' - 6 3/4"

24" / 54"
[-4' - 0"]
24" / 54"
[-4' - 0"]
[-2' - 0"] 24" / 54"
[-4' - 0"] 15
Sim
13
24" / 54"
Sim
[-4' - 0"]
D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J.
4 S401
Services, Inc.
505 S. Flagler Dr., Suite 1400

15' - 9 1/4"
13' - 11 1/2"

S680 S680
West Palm Beach, FL 33401
D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.
F.J.
6" 16' - 0" 15' - 0" 21' - 7 5/8" Project Number: 22008
BP16 BP14a BP14a BP14 BP12 Project Name:
24" / 66" 24" / 66" 24" / 54" 24" / 66" 24" / 54"

C
[-2' - 0"]
F.J. F.J. F.J.
[-2' - 0"]
F.J. F.J. F.J.
[-2' - 0"]
F.J. F.J. F.J.
[-2' - 0"]
F.J. F.J.
[-2' - 0"]
F.J.
C Alliance Hyundai
2 2

D.J.

D.J.
S401 1
D.J.

D.J.

D.J.

D.J.

D.J.
F.J.

F.J.
23' - 7 1/2"

23' - 7 1/2"
11001 North Fwy
D.J. D.J. D.J. Fort Worth, TX 76177
D.J. D.J. D.J. D.J. D.J. D.J. D.J. SOG-5

D.J.

D.J.
F.J.
BP14 BP12 BP12 BP12
D.J.

D.J.

D.J.

D.J.

D.J.
F.J.
Sim 24" / 54" 24" / 54" 24" / 54" 24" / 54"
10 [-2' - 0"] [-2' - 0"] [-2' - 0"] [-2' - 0"]
S680 SOG-5 SOG-5
B B
3
10' - 2 3/4"

10' - 2 3/4"
D.J. D.J. D.J. D.J. D.J. D.J. D.J. Sim
Sim 15
10
S680
D.J.

D.J.

S680 S401
BP10 BP10
D.J.

D.J.

D.J.
24" / 54"
R.B.
24" / 54"
R.B. F.J. 1 S402
[-2' - 0"] [-2' - 0"]
R.B.

R.B.

A.4 A.4
4' - 5 3/4"

4' - 5 3/4"
BP14a BP16a BP16a BP14a
24" / 54" 24" / 66" R.B. R.B. 24" / 66" 24" / 54"
[-2' - 0"] [-2' - 0"] BP14c BP14c [-2' - 0"] [-2' - 0"]
Sheet Title:
A.2 30" / 60" 30" / 60" A.2

RELEASED FOR CONSTRUCTION AND PERMIT


1 [-2' - 0"] [-2' - 0"]

A
SK-3
A
Foundation Plan
2' - 7 7/8"

2' - 7 7/8"
Sim POUR 2' - 0" THICK CONCRETE AT ENTRANCE
5
S686
BUMPOUTS WITH ISOLATION JOINT POURBACKS.
PROVIDE SAME WELDED WIRE FABRIC AS FOR
10
S680
Sim
- Showroom
THE SLAB-ON-GRADE IN SHOWROOM.
5 5/8" 2' - 5 1/2" 8 1/4" 1' - 9 3/4" 1' - 9 3/4" 2' - 6 7/8" 2' - 6 5/8" 2' - 4 3/4" 2' - 4 3/4" 1' - 5 3/4"
52' - 8" 12' - 2" 23' - 1" 14' - 11 1/8" 10' - 9 1/4" 14' - 11 1/8" 35' - 3" 12' - 7 1/4" 12' - 7 1/4" 12' - 7 1/4"
2
Sheet Number:
M6 M5 M3 6 5 4.6 4 3.8 3.5 3.6 3.4 3.3 3 2 1.9 1.8 1.6 1.5 1.3 1.2 1.1 1
S401

1
S201a
Foundation Plan - Showrrom & Service Drive
1/8" = 1'-0"
S201a
Gridline Type Legend
NEW GRIDLINE

F.O. MASONRY GRIDLINE


PRAXIS3
100 Peachtree St NW 404-875-4500 tel
Suite 1450 404-876-8884 fax
Atlanta, GA 30303 www.praxis3.com

R3 R2 R1 M3 MS5 MS4 MS3 MS2 MS1 M2 M1.7 M1


14' - 0" 5' - 9" 18' - 5 5/8" 28' - 0" 33' - 0" 26' - 0" 30' - 4" 31' - 5 5/8" 16' - 8" 24' - 8 3/4"

1' - 5" SIGNED & SEALED 02.16.2024


6" 6"
6" 17' - 6" 14' - 8" 14' - 8" 17' - 4" 27' - 0" 10' - 8" 24' - 8" 16' - 0" 16' - 0" 16' - 0" 16' - 0" 16' - 2" 6" Copyright (c) 2023 Praxis3, LLC
24" / 54" 24" / 54"
GB24 All reports, plans, specifications, computer files, field data, notes and other documents
Sim Sim [-4' - 0"] [-2' - 0"] [-4' - 0"] Sim Sim and instruments prepared by Praxis3 shall retain all common law, statutory and other

6"
14 13 13 15 reserved rights, including copyright thereto.

S680 S680 S680 S680 This drawing may not be reproduced in whole or in part without written permission of

[-2' - 0"]
[-2' - 0"]

GB24c
GB24e
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
24" / 54" 24" / 54" 24" / 54" 24" / 54" 24" / 54" 24" / 54" 24" / 54" 24" / 54" 24" / 54" 24" / 54" 24" / 54" drawings.
GB24b GB24a
[-4' - 0"] [-4' - 0"] [-2' - 0"] [-4' - 0"] [-4' - 0"] [-4' - 0"] [-4' - 0"] [-4' - 0"] [-2' - 0"] [-4' - 0"] [-4' - 0"] [-4' - 0"] [-4' - 0"]

6"
2 Sim
15 Rev Date Comments
MH

D.J.
S680 10.03.2022 Permit / Bid Set

6"
2

18' - 8"
2 04.17.2023 ASI 01
54 02.16.2024 Foundation Coor.

D.J.

D.J.
D.J. D.J.

15' - 10"
D.J.

D.J.

D.J.

D.J.

D.J.
24" / 54" 24" / 54" 24" / 54"

SLOPE

SLOPE

SLOPE

SLOPE

SLOPE

SLOPE
D.J. D.J. D.J.
22' - 8"

[-2' - 0"]
GB24
[-4' - 0"] [-4' - 0"] [-4' - 0"]

D.J.
D.J. 24" / 54"

[-2' - 0"]
SOG-6

GB24
[-4' - 0"]
Sim

32' - 2"
[-2' - 0"]

[-2' - 0"]
D.J.

D.J.

GB24c

GB24
13 D.J. SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE

[-2' - 0"]
GB24e
S680 SOG-6

D.J. D.J.
24" / 54" (TYPICAL AT Sim

SLOPE

SLOPE

SLOPE

SLOPE

SLOPE

SLOPE
Sim
IN-GROUND LIFTS)
17
[-4' - 0"] 2 D.J. D.J. D.J. Sim Sim
S680

D.J.

D.J.

D.J.

D.J.

D.J.
13 13
S686

15' - 10"
F.J.
24" / 54" S680 WF01 S680
GB24

D.J.
[-4' - 0"] [0' - 0"]
[-2' - 0"]

D.J.

D.J.
3 25' - 0" 25' - 0" 20' - 9"
S207 13 BP14 BP14
24" / 54" 24" / 54"
S208 24" / 54" 24" / 66" 24" / 54" 24" / 66" 24" / 54" 24" / 54" 24" / 54" MSB

F.J.
[-2' - 0"] [-2' - 0"] GB24g GB24g
[-4' - 0"] [-4' - 0"] [-4' - 0"] [-2' - 0"] [-4' - 0"] [-4' - 0"] [-4' - 0"] [-2' - 0"] [-4' - 0"]

6"
F.J. F.J. F.J. F.J. F.J. F.J.
MG
22' - 8"

RE 20' - 7 3/4"
12
S208 Sim 6"

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.
F.J.
Sim 13

SLOPE

SLOPE

SLOPE

SLOPE
8
Sim S680
14 S680
S680 (TYPICAL AT HIGH-
24" / 54" Sim
SPEED DOORS)
19' - 8"

D.J. SLOPE SLOPE D.J. SLOPE SLOPE D.J. 14


[-4' - 0"]

25' - 6"

25' - 0"
S680
2
S207

[-2' - 0"]
GB24f
SLOPE

SLOPE

SLOPE

SLOPE
D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.
F.J.
Sim
16
S680
RD 4"
24" / 54" GB24 24" / 54"
D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. [-4' - 0"] 2 [-2' - 0"] [-4' - 0"]
6" 17' - 8" SOG-6 SOG-6 MF
14' - 6 1/8"

4"
D.J.

D.J.

D.J.

F.J.
Sim
15

D.J.

9' - 8"
D.J.

S680
24" / 54" 24" / 54"

D.J.

D.J.

D.J.

D.J.

D.J.
24" / 54" 24" / 54" 24" / 54" D.J. D.J. D.J. D.J. [-4' - 0"] GB24 [-4' - 0"]
GB24 [-2' - 0"]
[-4' - 0"] [-4' - 0"] [-2' - 0"] [-4' - 0"]
Mark W. Nannis, P.E.
6"

ME.8 Texas Design Firm #21364


D.J.

D.J.

D.J.

24' - 8"
F.J.
D.J. D.J. 1591 Riverside Drive

F.J.
2 Gainesville, GA 30501
(TYPICAL AT Sim
Sim
IN-GROUND LIFTS) 13 770-614-6114 tel
[-2' - 0"]

2
D.J.

GB24f

D.J.
S680

14' - 8"
S686 D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. All drawings, specifications, and other work product
15' - 6"

D.J.

of Mark W. Nannis, P.E. (henceforth referred to as "The


BP14 BP14 BP14 BP14 BP14 Engineer") for this project are instruments of service for
D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.
F.J.
D.J.

D.J. D.J. 24" / 54" 24" / 54" 24" / 54" 24" / 54" 24" / 54" this project only and shall remain the property of The
24" / 54" [-2' - 0"] [-2' - 0"] [-2' - 0"] [-2' - 0"] [-2' - 0"] 24" / 54" Engineer whether the project is complete or not. Reuse
SOG-5 of any of the instruments of service of The Engineer by
24" / 54" [-4' - 0"] [-4' - 0"]
D.J. D.J. the owner or extensions of this project without the written
[-4' - 0"] F.J. F.J. F.J. F.J. F.J. F.J. F.J. F.J. F.J. F.J. F.J. permission of The Engineer shall be at the owner's risk
MSA
32' - 0"

and the owner agrees to defend, indemnify, and hold


D.J.

SOG-6 harmless The Engineer from all claims, damages, and


expenses including attorney's fees arising out of such

[-2' - 0"]
GB24a
unauthorized reuse of The Engineer's instruments of

[-2' - 0"]
D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.
F.J.

D.J.
GB24f
[-2' - 0"]

service by the owner or others acting through the owner.


GB24

12' - 8"
© 2023
14' - 0"

D.J. D.J.
D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J.
(TYPICAL AT Client:
15' - 6"

Sim
IN-GROUND LIFTS) 24" / 54" 24" / 54"

21' - 8"
2 GB24
24" / 54" [-4' - 0"]
[-2' - 0"]
[-4' - 0"]
Automotive
D.J.

S686
D.J.

[-4' - 0"]
24" / 54" GB24a 24" / 54"
Managment
D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.
F.J.
[-4' - 0"] [-2' - 0"] [-4' - 0"]

8' - 8"
D.J.
Services, Inc.

D.J.
ME.2 24" / 54" 24" / 54"
(TYPICAL AT
6"

2 [-4' - 0"] [-4' - 0"] 505 S. Flagler Dr., Suite 1400

4"
Sim
IN-GROUND LIFTS) 2
D.J.

2 West Palm Beach, FL 33401


16' - 0"

RC Sim S686 ME
15
GB24
S680 Project Number: 22008
3' - 7 3/8"

[-2' - 0"]

8' - 4"
D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. Project Name:
26' - 0" 24" / 54" 24" / 54"
6"
[-4' - 0"]

16
Sim
[-4' - 0"]
Alliance Hyundai
S680
D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.
F.J.

Sim
SLOPE

SLOPE

SLOPE

SLOPE
8
27' - 5"

S680

SOG-6 SOG-6 Sim


Sim SLOPE SLOPE SLOPE SLOPE 14

17' - 4"
14 D.J.
S680
S680 11001 North Fwy
Fort Worth, TX 76177
SLOPE

SLOPE

SLOPE

SLOPE
26' - 0"

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.
F.J.

24" / 54"
[-4' - 0"]

53' - 0 3/8"
D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J.
RB
5 5
D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

[-2' - 0"]
F.J.

GB24f
S207 WF01 (TYPICAL AT CMU
Sim

12' - 8"
24" / 54" [0' - 0"]
13 AND GRADE BEAM)
[-4' - 0"]
S680
D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J. D.J.
24" / 54"
19' - 4"

[-4' - 0"]
Sim
13
S680

[0' - 0"]
WF01
24" / 54"
D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.

D.J.
F.J.

[-4' - 0"]
MATCHLINE MATCHLINE
19' - 2"

14' - 8 3/8"
1' - 0"
3' - 0"

MD.2 Sheet Title:


[-2' - 0"]

20' - 5" 20' - 3" 16' - 0" 16' - 0" 16' - 0" 15' - 0" 15' - 4" 15' - 0" 15' - 11 5/8"

RELEASED FOR CONSTRUCTION AND PERMIT


GB24

1' - 8"
Foundation Plan
4' - 9"

GB24
24" / 54" 24" / 54" [-2' - 0"] 24" / 66" 24" / 54" 24" / 54" 24" / 66" 24" / 54" 24" / 54" 24" / 54" 24" / 54" 24" / 54" 24" / 54" 5
RA 24" / 54" 24" / 54"
GB24a [-2' - 0"] [-2' - 0"] [-4' - 0"] [-4' - 0"] [-4' - 0"] [-4' - 0"] [-4' - 0"] [-4' - 0"] GB24h [-4' - 0"] [-4' - 0"] [-4' - 0"] [-4' - 0"]

5 5/8"
[-4' - 0"] [-4' - 0"]
MD
[-2' - 0"] [-2' - 0"]
MD - Service Shop
1' - 11"

5
5 13' - 4" 34' - 0" 5' - 4" 5 5/8"
Sim
13
S680
M5 M4 M3.2 M3 6 4.6 4 3 2 1.8 1.5 1.2 1 M2 Sheet Number:

1
S201b
Foundation Plan - Service Shop
1/8" = 1'-0" SEE ALSO "FOUNDATION PLAN NOTES" ON SHEET S201a.
S201b
ROOF FRAMING PLAN NOTES Gridline Type Legend
: INDICATES CONTINUOUS HORIZONTAL RIGID
BRACING AT TOP AND BOTTOM CHORD OF
JOIST. ADD "X" TYPE BRIDGING IN FIRST PANEL
AND AT EVERY SIXTH PANEL. WELD TO JOIST,
FRAMING, AND AT CROSSOVER POINTS. SEE
NOTE :

NOTE:
WHERE TUBE FRAME MEMBERS CONNECT TO
COLUMNS, PROVIDE A WELDED CONNECTION
ALL AROUND FROM TUBE TO COLUMN, TYP.

STEEL REINF. TO BE WELDED SHALL CONFORM


NEW GRIDLINE

F.O. MASONRY GRIDLINE


PRAXIS3
SPECIFICATIONS. TO THE REQUIREMENTS OF ASTM A-706 AND
100 Peachtree St NW 404-875-4500 tel
THAT WELDING SHALL BE IN ACCORDANCE Suite 1450 404-876-8884 fax
: INDICATES A LOAD-BEARING CMU WALL WITH AWS D1.4, STRUCTURAL WELDING CODE - Atlanta, GA 30303 www.praxis3.com
BELOW. SEE WALL ELEVATIONS AND TYPICAL REINFORCING STEEL BY AMERICAN WELDING
DETAILS FOR SIZE AND REINFORCEMENT. SOCIETY FOR COMPLIANCE WITH ACI 318.

: INDICATES A NON-LOAD-BEARING CMU WALL NOTE: FOR FRAMING AROUND ROOF HATCH, PROVIDE
BELOW. SEE WALL ELEVATIONS AND TYPICAL CHANNEL FRAMING AS SHOWN ON THE
DETAILS FOR SIZE AND REINFORCEMENT. TYPICAL DETAIL FOR FRAMING AROUND
MECHANICAL UNITS. (UNLESS NOTED
: INDICATES THE DIRECTION THE DECK IS OTHERWISE)
SPANNING.
NOTE: KEEP STRUCTURE GUYED AND BRACED UNTIL
INDICATES A MOMENT CONNECTION AT EACH ALL MASONRY/CONCRETE SHEAR WALLS,
END OF BEAM TO COLUMN. SEE TYPICAL DIAGONAL BRACES, MOMENT FRAMES,
DETAIL FOR FULL PENETRATION WELD OF FRAMED FLOORS AND ROOF DECKS ARE IN
FLANGES AT EACH END. SEE DETAIL 10 / S681 PLACE.

(H) : INDICATES HIGH BEAM. NOTE: SEE ARCHITECT AND PLUMBING DRAWINGS
FOR LOCATIONS OF ROOF DRAINS. ROOF IS
(L) : INDICATES LOW BEAM. DESIGNED FOR A MAXIMUM DEPTH OF 4" OF
WATER AT ANY LOCATION OF THE ROOF.
WATER SHALL BE RELIEVED BY EITHER 0
Key Plan
H.B. : INDICATES ANGLE 3"x3"x1/4" HORIZONTAL
BRACE EXTENDING FROM TOP CHORD OF SCUPPERS OR AN INDEPENDENT EMERGENCY
OVERFLOW DRAIN AT THE 4" LEVEL. S202
JOIST OR BEAM TO FACE OF COLUMN. WELD
ALL AROUND EACH END WITH A 3/16" FILLET
WELD. NOTE: FOR FRAMING AROUND THE PERIMETER OF SIGNED & SEALED 02.16.2024
A MECHANICAL UNIT, SEE TYPICAL
A.X. : DETAIL: 3 / S681
. Copyright (c) 2023 Praxis3, LLC
INDICATES ADDITIONAL "X" TYPE BRIDGING.
USE 2"x2"x1/4" ANGLE All reports, plans, specifications, computer files, field data, notes and other documents
NOTE: FOR FRAMING AROUND ROOF OPENINGS and instruments prepared by Praxis3 shall retain all common law, statutory and other
INCLUDING EXHAUST FANS, ROOF DRAINS AND reserved rights, including copyright thereto.
S.P. : INDICATES A BEAM SPLICE POINT, SEE TYPICAL
ANY PENETRATIONS LARGER THAN 12", SEE This drawing may not be reproduced in whole or in part without written permission of
SPLICE POINT DETAIL.4 / S681 Praxis3. It is to be returned upon request. Scales as stated are valid on the original
TYPICAL DETAIL: 12 / S681
drawings.

T/S : INDICATES TOP OF STEEL BEAM REFERENCED


NOTE: FOR SUPPORT OF ROOF PIPING
FROM ELEVATION [0'-0"].
PERPENDICULAR TO JOIST, AND PARALLEL TO Rev Date Comments
M.C.J. : INDICATES A MASONRY CONTROL JOINT.
JOIST, SEE DETAIL 11 / S681 10.03.2022 Permit / Bid Set
COORDINATE EXACT LOCATION WITH 2 04.17.2023 ASI 01
ARCHITECT. JOINT SHALL EXTEND TO TOP OF
PARAPET AND SHALL NOT BE LOCATED WITHIN 54 02.16.2024 Foundation Coor.
1'-0" OF A JOIST BEARING SEAT ABOVE, 2'-0" OF
A BEAM BEARING, OR WITHIN 2'-0" OF JAMB OF
ANY OPENING. SEE DETAIL 7 / S687 . 13
S208
NOTE: AFTER ALL ROOF DEAD LOAD HAS BEEN
INSTALLED, PROVIDE ANGLE BRACES, OR M3.2 M3
TENSION RODS AS NOTED IN "TYPICAL BAR
M6 M5 R3 R2 R1 MS5 MS4 MS3 MS2 MS1
3
JOIST ROOF CONSTRUCTION" SEE DETAIL 1 / S681
S207
3
NOTE: WHERE CONDENSING UNITS BEAR ON ROOF S605
STRUCTURE, PROVIDE A SUPPORT FRAME 6
SIMILAR TO A ROOF OPENING SUPPORT AT THE 3 S606
PERIMETER OF THE UNIT. PROVIDE ANGLES AS
MD.2 1 2
S604 S605 S605
SHOWN IN DETAIL 12 / S681
NOTE: WHERE FANS ARE TO BE SUPPORTED FROM RA
ROOF JOIST FRAMING, PROVIDE ADDITIONAL
STEEL SUPPORT PER DETAIL 3 / S682
MD MD
NOTE: CONTRACTOR COORDINATE LOCATION OF
OPENINGS AND WEIGHTS OF MECHANICAL
UNITS, WITH THE MECHANICAL DRAWINGS. IF
WEIGHTS EXCEED WHAT IS SHOWN ON THE 2 MAX. HP WEIGHT = 200 LBS
STRUCTURAL PLAN, THEN NOTIFY THE 1' - 9 7/8" 7 5/8" 3' - 6 1/2" 7
S604
STRUCTURAL ENGINEER OF THE CHANGE DSSC-2 S606
PRIOR TO ANY DETAILING OR FABRICATION OF
JOIST, DECK OR STEEL.
2' - 5 1/2"
Sim
NOTE: WHERE A K SERIES JOIST BEARS ON THE SAME 5' - 11" 5' - 11" 5' - 10" 5' - 11" 5' - 11" 5' - 11" 6' - 0" 6' - 0" 5
STEEL BEAM OR MASONRY WALL AS AN LH F S687
JOIST, PROVIDE A 5" SEAT AT THAT END TO Sim MC

24K5

24K5

24K5

24K5

24K5

24K5

24K5

24K5

24K5

24K5

24K5

24K5

24K5

24K5

24K5

24K5

24K5

24K5

24K5
MATCH THE BEARING DEPTH OF THE LH JOIST. 1 8
S604 S686
NOTE: AT PERIMETER OF ALL ROOFS, EXPANSION
JOINTS, AND TRANSITIONS FROM HIGH TO LOW E.6
ROOFS, PROVIDE ROOF CLOSURE ANGLES AS 5 RD-1.5
PER SECTIONS DETAILED. WHERE NOT 3' - 3 1/2"

44LH11

44LH11
SHOWN, PROVIDE A 4" x 3" x 1/4" CONT. ANGLE 5' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 5' - 8"
LONG LEG VERTICAL. WHERE ANGLE BEARS
ON JOIST SEATS, FIELD WELD TO EACH JOIST

44LH10

44LH10

44LH11

44LH10

44LH10

44LH10

44LH10
WITH A 3/16" FILLET WELD. WHERE ANGLE RTU-8 Sim
BEARS ON A ROOF BEAM, FIELD WELD WITH A 6 1/4" 6 4
3/16" FILLET WELD 2" at 12" o.c. MAX. BEAMS FOR SUPPORT OF STAIR MAX. RTU WEIGHT = 1500 LBS S605 2 MAX. DSSC WEIGHT = 200 LBS S682

E.2 3 MB

t/s 20' - 4 7/8"

t/s 20' - 4 7/8"


t/s 20' - 4 7/8"

t/s 20' - 4 7/8"


S603 MAX. RTU WEIGHT = 1500 LBS MAX. RTU WEIGHT = 1500 LBS
Sim RTU-4

16KCS2
8
13 S686
S208 MAX. RTU WEIGHT = 1500 LBS
RTU-7 RTU-6 RTU-5 Mark W. Nannis, P.E.

W14X22

W14X22

W14X22
8
DSSC-1 Texas Design Firm #21364
S606

W12X14
E 2 2 1591 Riverside Drive

16KCS2

16KCS2

16KCS2

16KCS2

16KCS2

16KCS2

16KCS2
16K2

16K2

16K2

16K2

16K2
3 S606 Gainesville, GA 30501
MAX. RTU WEIGHT = 4200 LBS t/s 20' - 8 1/8"
S605 W8X18 W8X18 770-614-6114 tel
MATCHLINE
6k 6k 6k 6k

8' - 6" (COORD.


3' - 0 3/8"

t/s 20' - 10 1/4"


5' - 4" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 4' - 4 3/8" 6' - 0"

t/s 20' - 10 1/4"

t/s 20' - 10 1/4"

t/s 20' - 10 1/4"


WITH STAIR)
All drawings, specifications, and other work product
5' - 4" EF-2 of Mark W. Nannis, P.E. (henceforth referred to as "The

16KCS2
1 1' - 0"
MD.2

5" SEAT
Engineer") for this project are instruments of service for

5" SEAT

5" SEAT
S606 this project only and shall remain the property of The
2
3' - 0" MAX. HP OR IH WEIGHT = 200 LBS Engineer whether the project is complete or not. Reuse
6' - 8"

of any of the instruments of service of The Engineer by

6k
W8X10

6k

6k

6k
RA 4 24 k W24X62 22 k 20 k W24X76 17 k 6 k W12X16 W8X10 W30X108 29 k the owner or extensions of this project without the written
RD-1.5

3' - 0"

S605 t/s 20' - 5 1/4" t/s 20' - 5 1/4" t/s 20' - 7 3/4" 6k t/s 20' - 7 3/4"
D permission of The Engineer shall be at the owner's risk
and the owner agrees to defend, indemnify, and hold

t/s 20' - 10 1/4"

t/s 20' - 10 1/4"


6k

6k
MD MAX. EF WEIGHT = 50 LBS 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 5' - 10 3/8" harmless The Engineer from all claims, damages, and
t/s 20' - 7 3/4" expenses including attorney's fees arising out of such
HP-3 HP-4
5 unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
S603 5 © 2023
t/s 10' - 9 1/2"
HSS8X8X1/4

C.6 S605 IH-4


Client:

W12X14
IH-3 Sim
Automotive

24KCS4

24KCS4
3 7

t/s 21' - 3 1/8"


S606 RTU-2 S682
2 Managment

W12X14
F

24KCS2

24KCS4

24KCS4

24KCS2

24KCS2
S603

24K4
Services, Inc.

6k
RTU-1 H.B.
C.4 C.5 505 S. Flagler Dr., Suite 1400
A.X.

t/s 21' - 7 1/8" t/s 21' - 3 1/8"


6k
MA 6 West Palm Beach, FL 33401
S603
HSS4X4X1/4 4' - 7 5/8" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 5' - 0" 6' - 0"
E.5 4 S401 Project Number: 22008
10' - 9 1/2" 1' - 0"
Project Name:

W12X14
HSS4X4X1/4

1
10' - 9 1/2"
t/s 10' - 9 1/2"
HSS8X8X1/4

4 S603
Alliance Hyundai

t/s 21' - 7 1/8"


S603
MAX. RTU WEIGHT = 4200 LBS

HSS4X4X1/4 MAX. RTU WEIGHT = 2600 LBS

6k
E.3 10' - 9 1/2"
3 34 k W30X90 36 k
C C
HSS4X4X1/4

S603 t/s 21' - 4 5/8"


10' - 9 1/2"

t/s 21' - 7 1/8"


6k
2 2
Sim
6
S682 11001 North Fwy
S401 1 Fort Worth, TX 76177
HSS4X4X1/4
E 10' - 9 1/2"
3.1

W12X14
HSS4X4X1/4

18K3

18K3

18K3

18K3

18K3

18K3

18K3

18K3

18K3
S606
10' - 9 1/2"

5
t/s 10' - 9 1/2"
HSS8X8X1/4

5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 5' - 0" 4' - 8" 4' - 9" 4' - 8"
HSS4X4X1/4
C.8

t/s 22' - 1"


10' - 9 1/2"
HSS4X4X1/4
10' - 9 1/2"

10k-ft 9k-ft

6k
13k-ft 14k-ft 13k-ft 11k-ft
6k W8X18 6k 6k W8X13 6k 6k W8X13 6k
B t/s 21' - 10 1/2" t/s 21' - 10 1/2" t/s 21' - 10 1/2"
B
3
HSS4X4X1/4
C.6 5
10' - 9 1/2" 4 4
S606 S401
S602 S606
Sim 1 S402
Sheet Title:
t/s 10' - 9 1/2"

4
HSS8X8X1/4

RELEASED FOR CONSTRUCTION AND PERMIT


S686 6k HSS4X4X1/4 6k
A.4 A.4
2
t/s 9' - 11 1/2"
Framing Plan -
S603 A.2 A.2
C.4
A
HSS8X8X1/4 (H)
6 k t/s 11' - 10 1/2"6 k
A
Low Roof
HSS8X8X1/4 (L)
MA t/s 10' - 3 1/2"

R2 M3.2 R1 M3 6 5 4.6 3 2 1
Sheet Number:
M6 M5 M3 6 5 4 3.8 3.5 3.6 S602 3.4 3.3 3 S602 S602 2 1.9 1.8 1.6 1.5 1.3 1.2 1.1 1

2
S202
Service Drive Vestibule Roof
1/8" = 1'-0"
1
S202
Low Roof Framing Plan
1/8" = 1'-0"
2

S401
S202
FLOOR FRAMING PLAN NOTES Gridline Type Legend
E.5
(Fy=50 KSI) (U.N.O.) THUS:
NUMBER OF
SHEAR STUDS
NOTE: UNLESS SHOWN OTHERWISE, PROVIDE 3/4"
DIAM. x 4" LONG SHEAR STUDS FIELD WELDED
TO TOP FLANGE OF FLOOR BEAMS AT 1'-0" o.c.
MAX.
NEW GRIDLINE

F.O. MASONRY GRIDLINE


PRAXIS3
##k BEAM SIZE (##) ##k 100 Peachtree St NW 404-875-4500 tel
NOTE: CONTRACTOR COORDINATE LOCATION OF
c = CAMBER OPENINGS AND WEIGHTS OF MECHANICAL Suite 1450 404-876-8884 fax
UNITS, AND KITCHEN HOOD EQUIPMENT WITH Atlanta, GA 30303 www.praxis3.com
REACTION IN KIPS THE MECHANICAL AND KITCHEN DRAWINGS. IF
WEIGHTS EXCEED WHAT IS SHOWN ON THE

6k

"
"
7/8
3/4
STRUCTURAL PLAN, THEN NOTIFY THE

6k
FRAMING KEY

-3
-3
STRUCTURAL ENGINEER OF THE CHANGE

22'
22'
(6)
E.3 PRIOR TO ANY DETAILING OR FABRICATION OF

t/s
t/s

(6)
0
JOIST, DECK OR STEEL.

1/4 8X1
- 0"
(H) : INDICATES HIGH BEAM.

X31
E.2

W
NOTE: U.N.O., AT ALL COMPOSITE FLOORS PROVIDE A

"

"
20'

3/8

W8
t/s
22' (L) : INDICATES LOW BEAM.
5-1/2" MIN. SEMI-LIGHTWEIGHT CONCRETE

-3

-3
6 k - 3 1/2"

22'

22'
6k
W8 t/s
22' U.N.O. : SLAB (4000 psi MAX. DENSITY = 115 pcf) ON 20
INDICATES "UNLESS NOTED OTHERWISE"

t/s

t/s

6k
X31 - 4"
GAUGE, 2" GALVANIZED (3 SPAN CONT.)
(
6k 6 k4) COMPOSITE STEEL DECK. SEE
"

"
1/4
E.O.S. : INDICATES EDGE OF SLAB
3/8

6k
SPECIFICATIONS. FOR SLAB REINFORCING SEE
-3

-3
DETAIL: 5 / S683
22'

22'

F.O.S.: INDICATES FACE OF STUD


t/s

t/s
X10

X31

NOTE: KEEP STRUCTURE GUYED AND BRACED UNTIL


W8

E.F.O.B. : INDICATES EXTERIOR FACE OF BRICK ALL MASONRY/CONCRETE SHEAR WALLS,


W8

E
"
7/8

DIAGONAL BRACES, MOMENT FRAMES,


Key Plan
- 3"
-2

t/s S.E. : INDICATES A SPECIAL END MOMENT FRAMED FLOORS AND ROOF DECKS ARE IN 0
22'

22'
6k

22'
-3 PLACE.
CONNECTION, SEE DETAIL - / ---
t/s

t/s

1/8
6k
0"

"
S203a
1' -

W8
6k
6 k W8X31 6 k
6k X31 NOTE: AT ALL OPENINGS, PROVIDE A BENT PLATE 1/4"
S.P. : INDICATES A SPLICE POINT, SEE DETAIL 4 / S681
t/s (4) THICK HIGH EXTENDING FROM CENTERLINE OF
22' W8
t/s 22' - 4"
-2 t/s
7/8
" X 10 22'
- 4" BEAM TO EDGE OF SLAB. WHERE BENT PLATE SIGNED & SEALED 02.16.2024
1' - (4) : INDICATES THE DIRECTION THE DECK IS
6k BEARS ON BEAM, SHOP WELD ON BOTH SIDES
0 " 6k SPANNING.
WITH A 3/16" FILLET WELD 3"@12"o.c. COPE Copyright (c) 2023 Praxis3, LLC
9' - VERTICAL LEG OF BENT PLATE FOR CHANNEL
37 : INDICATES A TYPICAL MOMENT CONNECTION All reports, plans, specifications, computer files, field data, notes and other documents
/8 " STRINGER TO FRAME TO FLOOR BEAM AT
-3 6 k

and instruments prepared by Praxis3 shall retain all common law, statutory and other
SEE DETAIL: 10 / S681
"

t/s
6k
"
3/4

22' STAIRS.
7/8

- 4" reserved rights, including copyright thereto.


C.8
'-3
" t/s 0
22'

This drawing may not be reproduced in whole or in part without written permission of
X31

INDICATES A LOAD-BEARING CMU WALL


1/2 X1

" 22

NOTE: FOR FRAMING AROUND FLOOR OPENINGS, SEE Praxis3. It is to be returned upon request. Scales as stated are valid on the original
5/8t/s
W8

BELOW. SEE WALL ELEVATIONS AND TYPICAL drawings.


W8

"TYPICAL DETAIL OF FRAMING AROUND A


DETAILS FOR SIZE AND REINFORCEMENT.
-3

FLOOR OPENING". COORDINATE WITH


-3
22'
t/s k

Rev Date Comments


22'

ARCHITECT AND MECHANICAL / PLUMBING


6

t/s

6k

INDICATES A NON-LOAD-BEARING CMU WALL ENGINEER FOR EXACT DIMENSION AND 10.03.2022 Permit / Bid Set
- 0"

2' - 6 k
/2"

"

LOCATION. SEE DETAILS 7 / S683 AND 6 / S683


5/8

BELOW. SEE WALL ELEVATIONS AND TYPICAL


31

6k
20'

2 04.17.2023 ASI 01
-3

DETAILS FOR SIZE AND REINFORCEMENT.


" t 0

22'
1/8 X1
/s 2

NOTE: AT THE PERIMETER OF ALL COMPOSITE


54
X31

02.16.2024 Foundation Coor.


" t/s
- 3 W8

NOTE: EDGE OF SLAB FOR ALL CORE ELEMENTS FLOORS, A STEEL FLOOR CLOSURE ANGLE
1/4
W8

SHALL BE PROVIDED. SEE DETAILS 8 / S685


-3

INCLUDING ELEVATOR SHAFTS, STAIR WELLS, 13


6k

22'
22'

AND MECHANICAL OPENINGS SHALL BE


6k

S208
t/s
t/s

C.6 COORDINATE BY THE GENERAL CONTRACTOR


6k
"
X31 - 3 1/4"
1/8

WITH THE ARCHITECT AND MECHANICAL


6k
-3

ENGINEER PRIOR TO FABRICATION.


" t/ 0
22'

22'
3/4 X1

DIMENSIONS SHALL BE NOTED AND MARKED R3 R2 M3.2 R1 M3 MS5 MS4 MS3 MS2 MS1
s

t/s
W8

ON SHOP DRAWING PACKAGES.


"
7/8
W8
-2

-2

t/s
22'
22'

22'
6k

6k -3
3 3 6
1/8
M6 M5
0"

t/s

t/s

6k

"
S207 S605 S606
1' -

t/s W8
6 k 22' - 2 W8 X
1' -
7/8
" X10 31 (4 3 1 2
(4) )t/s 6 k S604 S605 S605
0 " 22'
- 4"
9' -
9 1' - 6"
3' - 1 3/4"

1/2 t/s RA
" 22 9' - 3 3/8" 9' - 3 3/8" 9' - 3 3/8"
6 k' - 4"
C.4
MD t/s 22' - 10 1/2"
MD
6 17 k
t/s 22' - 3 7/8" W30X90 (18)
W8X31 (8)

W8X31 (8)
MA
6k

6k

W8X31 (8)

1' - 6"
CF-5.5

t/s 22' - 5 1/4"

t/s 22' - 6 3/8"


S603

6k
t/s 22' - 7 1/2"
6k

6k 6k
W8X31
t/s 22' - 4"

6' - 3"

t/s 22' - 10 1/2"

W8X31 (8)
t/s 22' - 10 3/8"
2

W30X90
6k

6k

6k
M6 M5
6k

S604 27 k 7
t/s 22' - 3 7/8" W30X90 (28) c = 3/4" t/s 22' - 10 1/2" S606

6' - 2 7/8"
6k
W8X31
t/s 22' - 4"

Callout at Cantilever Vehicle Display

17 k
3
6k

F W30X90 (32) c = 1" 30 k


S203a

48 k
3/16" = 1'-0" t/s 22' - 3 7/8" t/s 22' - 10 1/2"
MC
7' - 6 3/4"
W8X31
t/s 22' - 4"

1
S604
5 t/s 22' - 10 1/2" 33 k
E.6 t/s 22' - 3 7/8" W30X90 (36) c = 1" t/s 22' - 9 7/8"
t/s 22' - 10 1/2"
6 k W8X31 6 k

1' - 6" W8X18 (8)

6k
W8X18 (10)
6k 6k
t/s 22' - 4"

t/s 22' - 10 1/2"


7' - 6"

t/s 22' - 9 7/8"

W30X90
Sim 1' - 2 1/8"

6k
4 Sim
W30X116 34 k 6 4
S682 t/s 22' - 10 1/2" S605 S682
t/s 22' - 3 3/4"

6k
W8X18 (10)
t/s 22' - 9 7/8" W8X18 (8)
7' - 6"

t/s 22' - 9 7/8"


MB E.2 4' - 8 1/4" 3 MB
6k 6k
S603
6' - 11 1/4"
2"

6' - 11 1/4"
34 k t/s 22' - 10 1/2"
6 kt/s 22' - 9 7/8" 6 k 6 k

2"
W30X116 t/s 22' - 10 1/2"
t/s 22' - 9 7/8"
t/s 22' - 3 1/4" t/s 22' - 10 1/2"
Mark W. Nannis, P.E.
W8X18 (10)
7' - 8 1/2"
CF-5.5

81 k 58 k 8
Texas Design Firm #21364

t/s 23' - 7 1/2"


6k 6k S606

MC8X18.7
5 1591 Riverside Drive

t/s 23' - 6 1/2"


6' - 9"

W8X18 (8) BACK FACE OF CHANNEL & EDGE OF DECK 2 Gainesville, GA 30501

6' - 9"
1' - 0" S605
t/s 22' - 2 7/8" W30X116 32 k C12X20.7 S606 770-614-6114 tel
W8X316 k

W8X18
t/s 22' - 10 1/2" t/s 23' - 6 1/2"
5' - 7 1/4"

t/s 23' - 6 1/2"


t/s 23' - 6 1/2"
t/s 23' - 6 1/2"

t/s 23' - 6 1/2"


All drawings, specifications, and other work product
t/s 22' - 4"

t/s 22' - 10 1/2"

t/s 23' - 6 1/2"


t/s 23' - 6 1/2"
Sim W8X18 (10) of Mark W. Nannis, P.E. (henceforth referred to as "The
28 k 6
8' - 4 3/8" t/s 23' - 6 1/2" Engineer") for this project are instruments of service for
6k
6' - 9"

W30X116 t/s 22' - 10 1/2" 1

W8X18
S681

6' - 9"
W8X18

W8X18

W8X18

W8X18

W8X18
this project only and shall remain the property of The
S606

4' - 9"
CF-5.5
Engineer whether the project is complete or not. Reuse
W30X90

t/s 22' - 3 3/4" W8X18 (6)


5' - 8 3/4"

t/s 23' - 6 1/2" of any of the instruments of service of The Engineer by


6"

6"
the owner or extensions of this project without the written
D 3' - 3 1/8" 69 k W27X84 (12) 33 k 15 k W21X44 (14) 19 k 7k W18X35 (12) 7k 6k 6k permission of The Engineer shall be at the owner's risk
D
5' - 5 1/4"

W30X116 27 k t/s 23' - 6 1/2" t/s 23' - 6 1/2" t/s 23' - 6 1/2" and the owner agrees to defend, indemnify, and hold

5' - 5 1/4"
6k

6k
17 k

17 k

13 k

6k

6k

6k

6k

6k
6k

28 k
12 k

16 k

24 k
harmless The Engineer from all claims, damages, and

5' - 5"
t/s 22' - 3 1/2" t/s 22' - 10 1/2"
5' - 8 3/4"

expenses including attorney's fees arising out of such

6k
t/s
22'
W8 unauthorized reuse of The Engineer's instruments of

6k

6k

6k

6k

6k

6k

6k
6k -
X31 3 1/2" W8X18 (6)
92 k

t/s 5 6k 6k 10 k W21X44 (14) 10 k 10 k W21X44 (14) 16 k service by the owner or others acting through the owner.
6k 22' © 2023
-4
5/8 W30X116 27 k S603 t/s 23' - 6 1/2" t/s 23' - 6 1/2" t/s 23' - 6 1/2"

6k

9k
5' - 11"

"

t/s 23' - 7 1/2"


C.6

5' - 11"
Client:

MC8X18.7
t/s 22' - 3 1/8" t/s 22' - 10 1/2" 9' - 0" 8' - 9" 8' - 9" 8' - 9" 9' - 0" 7' - 3 1/8" 7' - 5" 7' - 5" 9' - 4 1/4" 6' - 4 1/2"
6' - 1 1/2"

t/s 22' - 10 1/2"


18 k
W30X90 (20)

t/s 23' - 6 1/2"


W8X18
5' - 11 1/4"

W30X116
29 k
3
Automotive
5' - 11"

t/s 22' - 2 3/4" t/s 22' - 10 1/2"

5' - 11"
S606
Managment
W18X35 (18) c = 1"

W18X35 (18) c = 1"


6k
W8X31 (8)

6k
6k
6k

6k

W8X31 (8)
6k
W8X31 (8)

W8X31 (8)

W8X31 (8)

W8X31 (8)

W8X31 (8)
6k

t/s 22' - 10 3/8"


6' - 7 1/2"

t/s 23' - 6 1/2"

t/s 23' - 6 1/2"

t/s 23' - 6 1/2"


t/s 22' - 4 3/4"

t/s 22' - 7 1/4"

t/s 22' - 9 3/4"

W21X44 (20)
t/s 23' - 6 1/2"

t/s 23' - 6 1/2"

t/s 23' - 6 1/2"


W18X35 (18)
t/s 22' - 8 1/2"
6 k t/s 22' - 4"

2
t/s 22' - 6"

Sim

W21X48

W21X55
1' - 6 3/4"

Sim
7
8' - 9 1/2"
S603 7
Services, Inc.
16 k

t/s 23' - 6 1/2"

t/s 23' - 6 1/2"


6k
6k

W18X35 (18)
S682 C.4
6k

6k
5' - 11"

S682
t/s 23' - 6 1/2"
6k

6k

W12X30

5' - 11"
C.5 W30X90 (20) 19 k 505 S. Flagler Dr., Suite 1400
W18X35 (20) c = 0.75"

C.5
6 West Palm Beach, FL 33401
MA
S603 t/s 22' - 3 7/8" t/s 22' - 10 1/2"
4 Project Number: 22008
5' - 11"

4 S401

t/s 23' - 7 1/2"


S603

5' - 11"
t/s 23' - 6 1/2"

Project Name:
W8X18 (10)

MC8X8.5
3 1

6
Sim
S203a S603
6
Sim Alliance Hyundai
6' - 4 1/2"
5' - 11"

HSS4X4X1/4 (TYP.) S682 5' - 2" 10' - 0" 10' - 0" 10' - 0" 10' - 0" HSS4X4X1/4 (TYP.)

5' - 11"
S682
t/s 29' - 6" t/s 23' - 8"
17 k

1' - 6" 6' - 5 5/8" 2' - 8"


15 k

17 k
17 k

10 k

10k-ft
6k

6k
6"

6k

6k

9k

6"
6k 51 k W30X90 44 k 6k W21X44 14 k
C C C
t/s 23' - 6 1/2" t/s 23' - 6 1/2"
6k

19 k

12 k

6k

6k
W27X84 (CANT.)
14 k

22 k

13 k
2 2
18 k

REINFORCE TOPPING SLAB WITH


77k-ft

19 k

6' - 0" 6' - 0" 6' - 0" 6' - 0" 5' - 0" WELDED WIRE FABRIC 6/6-W2.9xW2.9 t/s 23' - 6 1/2"
IN FLAT SHEETS. PROVIDE SAWCUT 10' - 1 5/8" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 5' - 0" 7' - 6" 11001 North Fwy
JOINTS MEETING THE SAME CRITERIA Fort Worth, TX 76177
AS FOR SLAB-ON-GRADE. S401 1
1.5 1.2

t/s 23' - 6 1/2"

t/s 23' - 6 1/2"


W18X35 (14)

t/s 23' - 7 1/2"


W8X18

t/s 23' - 6 1/2"


W24X68 (20)

MC8X18.7
3.1

2
Top of Screen Framing Plan S606

t/s 23' - 6 1/2"


5
t/s 23' - 6 1/2"

t/s 23' - 6 1/2"


W21X44 (24)

S203a

W27X84
1/8" = 1'-0"
W21X44 (22) c = 3/4"

W21X44 (22) c = 3/4"

W24X76
t/s 23' - 6 1/2"

t/s 23' - 6 1/2"

t/s 23' - 6 1/2"


W30X99
t/s 23' - 6 1/2"

6k

6k
W18X35

W18X35 (6) 19 k W24X55 (22) c = 1" 19 k 18 k W24X55 (12) 22 k


3' - 3 1/2"

W18X35 (4)

28 k
t/s 23' - 6 1/2" t/s 23' - 6 1/2" t/s 23' - 6 1/2" t/s 23' - 6 1/2"
9k

9k

9k

9k

8k

8k

8k

9k
6k 6k 6k C8X11.5 C8X11.5 C8X11.5
6k
B t/s 23' - 7 1/2" t/s 23' - 7 1/2" t/s 23' - 7 1/2"
B

6k
6k
3
t/s 23' - 6 1/2"

t/s 23' - 6 1/2"

t/s 23' - 6 1/2"

t/s 23' - 6 1/2"

t/s 23' - 6 1/2"

t/s 23' - 6 1/2"

t/s 23' - 6 1/2"

t/s 23' - 6 1/2"


W10X22 (12)

W10X22 (12)

W10X22 (12)

W10X22 (12)

W10X22 (12)

W10X22 (12)

W10X22 (12)

W18X35 (18)
CF-5.5

t/s 23' - 6 1/2"


5

W8X18 (10)

t/s 23' - 6 1/2"


4 4
S606

W18X35
S602 Sim S401 S606
6 1 S402 Sheet Title:
S686

RELEASED FOR CONSTRUCTION AND PERMIT


3' - 9 5/8"
Framing Plan -
19 k
69k-ft

1' - 10" 8' - 9 3/4" 8' - 9 3/4" 8' - 9 3/4" 8' - 9 3/4" 8' - 10" 8' - 10" 8' - 11" 8' - 10" 8' - 10" 7' - 4" 7' - 4 1/8" 7' - 5" 9' - 4 1/4" 1' - 10"
24 k

32 k
17 k

19 k

17 k

6k
8k 43k-ft 289k-ft 263k-ft 182k-ft 181k-ft
9k

9k

9k

9k

8k

8k

8k

7k
6k

Level 2
13k-ft 29 k W30X108 42 k 28 k W30X108 25 k 25 k W30X108 18 k
A.2 10k-ft A.2
W30X90 (CANT.) 6k t/s 23' - 6 1/2" 6k 6k t/s 23' - 6 1/2" 6k 6k t/s 23' - 6 1/2" 30k-ft 6 k
W30X90 (CANT.)
t/s 23' - 6 1/2" W18X35 (12) W18X35 (14) W18X35 (12) t/s 23' - 6 1/2"

1' - 10"
A A
W30X90 (CANT.)

W30X90 (CANT.)

t/s 23' - 6 1/2" t/s 23' - 6 1/2" t/s 23' - 6 1/2"


8k
t/s 23' - 6 1/2"

t/s 23' - 6 1/2"

WHERE SLOPED ARCHITECTURAL 8k


13k-ft 13k-ft
COLUMNS PENETRATE THROUGH
COMPOSITE SLAB, PROVIDE A 1' - 0"
Sim
SQUARE BLOCKOUT PER 1 3 2 1 Sheet Number:
M6 M5 DETAIL 6 / S683. M3 6 5 4.6 4 S602 S602 3 S602 S602 2 1.9 1.8 1.6 1.5 1.3 1.2 1.1 1
COORDINATE EXACT LOCATIONS

1
S203a
Level 2 Framing Plan
1/8" = 1'-0"
WITH ARCHITECTURAL DRAWINGS.

S203a
3

ROOF FRAMING PLAN NOTES M4 R3 8


S207
R2 R1 M3

: INDICATES CONTINUOUS HORIZONTAL RIGID


BRACING AT TOP AND BOTTOM CHORD OF
JOIST. ADD "X" TYPE BRIDGING IN FIRST PANEL
AND AT EVERY SIXTH PANEL. WELD TO JOIST,
FRAMING, AND AT CROSSOVER POINTS. SEE
NOTE :

NOTE:
WHERE TUBE FRAME MEMBERS CONNECT TO
COLUMNS, PROVIDE A WELDED CONNECTION
ALL AROUND FROM TUBE TO COLUMN, TYP.

STEEL REINF. TO BE WELDED SHALL CONFORM


ME.8
S608

PRAXIS3
RD 13 100 Peachtree St NW 404-875-4500 tel
SPECIFICATIONS. TO THE REQUIREMENTS OF ASTM A-706 AND S208
THAT WELDING SHALL BE IN ACCORDANCE Suite 1450 404-876-8884 fax
: INDICATES A LOAD-BEARING CMU WALL WITH AWS D1.4, STRUCTURAL WELDING CODE - Atlanta, GA 30303 www.praxis3.com
BELOW. SEE WALL ELEVATIONS AND TYPICAL REINFORCING STEEL BY AMERICAN WELDING ERD
DETAILS FOR SIZE AND REINFORCEMENT. SOCIETY FOR COMPLIANCE WITH ACI 318.

: INDICATES A NON-LOAD-BEARING CMU WALL NOTE: FOR FRAMING AROUND ROOF HATCH, PROVIDE

24K4

24K4

24K4

24K4

24K4

24K4
RD-1.5

RB
BELOW. SEE WALL ELEVATIONS AND TYPICAL CHANNEL FRAMING AS SHOWN ON THE
DETAILS FOR SIZE AND REINFORCEMENT. TYPICAL DETAIL FOR FRAMING AROUND MSA
MECHANICAL UNITS. (UNLESS NOTED 7
: INDICATES THE DIRECTION THE DECK IS OTHERWISE) S608
SPANNING.
NOTE: KEEP STRUCTURE GUYED AND BRACED UNTIL 5' - 6" 5' - 6" 5' - 6" 5' - 6" 5' - 6" 5' - 5" 5' - 5 3/8"
INDICATES A MOMENT CONNECTION AT EACH ALL MASONRY/CONCRETE SHEAR WALLS,
END OF BEAM TO COLUMN. SEE TYPICAL DIAGONAL BRACES, MOMENT FRAMES, 4
DETAIL FOR FULL PENETRATION WELD OF FRAMED FLOORS AND ROOF DECKS ARE IN S608
FLANGES AT EACH END. SEE DETAIL 10 / S681 PLACE.

(H) : INDICATES HIGH BEAM. NOTE: SEE ARCHITECT AND PLUMBING DRAWINGS
FOR LOCATIONS OF ROOF DRAINS. ROOF IS
(L) : INDICATES LOW BEAM. DESIGNED FOR A MAXIMUM DEPTH OF 4" OF
WATER AT ANY LOCATION OF THE ROOF.
H.B. : INDICATES ANGLE 3"x3"x1/4" HORIZONTAL WATER SHALL BE RELIEVED BY EITHER
SCUPPERS OR AN INDEPENDENT EMERGENCY ME.2
BRACE EXTENDING FROM TOP CHORD OF
JOIST OR BEAM TO FACE OF COLUMN. WELD OVERFLOW DRAIN AT THE 4" LEVEL.
ALL AROUND EACH END WITH A 3/16" FILLET
WELD. NOTE: FOR FRAMING AROUND THE PERIMETER OF 6 SIGNED & SEALED 03.30.2023
A MECHANICAL UNIT, SEE TYPICAL MS3 MS2 MS1 M2 M1.7 M1
A.X. : INDICATES ADDITIONAL "X" TYPE BRIDGING.
DETAIL: 3 / S681
.
2
Express Drive Roof Framing Plan S608
Copyright (c) 2023 Praxis3, LLC

USE 2"x2"x1/4" ANGLE All reports, plans, specifications, computer files, field data, notes and other documents
NOTE: FOR FRAMING AROUND ROOF OPENINGS S203b 1/8" = 1'-0" 3
and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.
INCLUDING EXHAUST FANS, ROOF DRAINS AND
S.P. : INDICATES A BEAM SPLICE POINT, SEE TYPICAL S607
ANY PENETRATIONS LARGER THAN 12", SEE This drawing may not be reproduced in whole or in part without written permission of
SPLICE POINT DETAIL.4 / S681 Sim Praxis3. It is to be returned upon request. Scales as stated are valid on the original
TYPICAL DETAIL: 12 / S681 1 1 drawings.

T/S : INDICATES TOP OF STEEL BEAM REFERENCED


NOTE: FOR SUPPORT OF ROOF PIPING M3 S607 MS5 MS4 2
Sim S607
FROM ELEVATION [0'-0"].
PERPENDICULAR TO JOIST, AND PARALLEL TO M Rev Date Comments
S607
INDICATES A MASONRY CONTROL JOINT.
JOIST, SEE DETAIL 11 / S681 2 10.03.2022 Permit / Bid Set
M.C.J. : 2' - 0 3/4"
COORDINATE EXACT LOCATION WITH S607
MH 2 04.18.2023
03.31.2023 ASI 01
ARCHITECT. JOINT SHALL EXTEND TO TOP OF
PARAPET AND SHALL NOT BE LOCATED WITHIN
1'-0" OF A JOIST BEARING SEAT ABOVE, 2'-0" OF
A BEAM BEARING, OR WITHIN 2'-0" OF JAMB OF
ANY OPENING. SEE DETAIL 7 / S687 .

NOTE: AFTER ALL ROOF DEAD LOAD HAS BEEN 4


INSTALLED, PROVIDE ANGLE BRACES, OR S607
TENSION RODS AS NOTED IN "TYPICAL BAR MAX. HP WEIGHT = 200 LBS
JOIST ROOF CONSTRUCTION" SEE DETAIL 1 / S681
HP-2
NOTE: WHERE CONDENSING UNITS BEAR ON ROOF
STRUCTURE, PROVIDE A SUPPORT FRAME 24K5 @ 6' - 0" 26K7 @ 6' - 0" 24K5 @ 6' - 0"
SIMILAR TO A ROOF OPENING SUPPORT AT THE 4' - 8" 5' - 0 3/8" 6' - 0" 6' - 0"
MAX. HP WEIGHT = 100 LBS
PERIMETER OF THE UNIT. PROVIDE ANGLES AS Sim EF-9
SHOWN IN DETAIL 12 / S681 4 4' - 0 3/4"
S607
NOTE: WHERE FANS ARE TO BE SUPPORTED FROM
ROOF JOIST FRAMING, PROVIDE ADDITIONAL
STEEL SUPPORT PER DETAIL 3 / S682 Sim
R3 R2 R1 8
3
NOTE: CONTRACTOR COORDINATE LOCATION OF S689 EF-4
S207 13
OPENINGS AND WEIGHTS OF MECHANICAL
UNITS, WITH THE MECHANICAL DRAWINGS. IF S208 MSB
WEIGHTS EXCEED WHAT IS SHOWN ON THE
S.P. S.P.
STRUCTURAL PLAN, THEN NOTIFY THE W12X16 14 k W18X65 11 k W12X14
STRUCTURAL ENGINEER OF THE CHANGE MG
t/s 21' - 2 1/8" 4' - 0" t/s 21' - 2 1/8" 6' - 0" t/s 21' - 2 1/8"
PRIOR TO ANY DETAILING OR FABRICATION OF RE
JOIST, DECK OR STEEL. 12
S208 Sim
NOTE: WHERE A K SERIES JOIST BEARS ON THE SAME 6 5
STEEL BEAM OR MASONRY WALL AS AN LH MAX. HP WEIGHT = 200 LBS MAX. HP WEIGHT = 200 LBS S688 6 S607
JOIST, PROVIDE A 5" SEAT AT THAT END TO S607
MATCH THE BEARING DEPTH OF THE LH JOIST. 5
S608
NOTE: AT PERIMETER OF ALL ROOFS, EXPANSION FAN FAN FAN
JOINTS, AND TRANSITIONS FROM HIGH TO LOW
2
ROOFS, PROVIDE ROOF CLOSURE ANGLES AS
PER SECTIONS DETAILED. WHERE NOT S207
EF-7 EF-8
SHOWN, PROVIDE A 4" x 3" x 1/4" CONT. ANGLE
LONG LEG VERTICAL. WHERE ANGLE BEARS
ON JOIST SEATS, FIELD WELD TO EACH JOIST
WITH A 3/16" FILLET WELD. WHERE ANGLE 7
40LH09

40LH09

40LH09

40LH09

40LH09

40LH09

40LH09

40LH09

40LH09

40LH09

40LH09

32LH09

32LH09

40LH09

40LH09

40LH09

40LH09

40LH09

40LH09

40LH09

40LH09

40LH09

40LH09

40LH09

40LH09

40LH09

40LH09

40LH09

40LH09

40LH09
BEARS ON A ROOF BEAM, FIELD WELD WITH A S607
3/16" FILLET WELD 2" at 12" o.c. MAX.
RD

MF
8
S608
5' - 8" 6' - 0" 5' - 10" 4' - 2" 6' - 0" 6' - 0" 6' - 0" 5' - 10" 5' - 6" 5' - 6" 5' - 6" 5' - 6" 5' - 6" 5' - 6" 3' - 2" 6' - 0" 6' - 0" 6' - 0" 4' - 10" 4' - 7" 4' - 7" 6' - 0" 6' - 0" 6' - 0" 3' - 2" 5' - 0" 5' - 0" 4' - 10" 6' - 0" 4' - 0" 5' - 8" Mark W. Nannis, P.E.
RTU-12 Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
ME.8 MAX. RTU WEIGHT = 4200 LBS 770-614-6114 tel
M M IH-1 Sim
RTU-11 8 8
MAX. HP WEIGHT = 100 LBS All drawings, specifications, and other work product
S689 S607 of Mark W. Nannis, P.E. (henceforth referred to as "The
EF-10
Engineer") for this project are instruments of service for
this project only and shall remain the property of The
RD-1.5 MAX. HP WEIGHT = 200 LBS Engineer whether the project is complete or not. Reuse
MAX. RTU WEIGHT = 4200 LBS HP-1 of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written

32LH07

32LH07
permission of The Engineer shall be at the owner's risk
and the owner agrees to defend, indemnify, and hold
S.P. S.P. S.P. S.P. S.P. harmless The Engineer from all claims, damages, and
W14X22 21 k W18X86 31 k W18X35 30 k W18X76 25 k W18X76 36 k W18X50 expenses including attorney's fees arising out of such
t/s 22' - 2 3/4" t/s 22' - 2 3/4" t/s 22' - 2 3/4" t/s 22' - 2 3/4" t/s 22' - 2 3/4" t/s 22' - 2 3/4"
MSA unauthorized reuse of The Engineer's instruments of
4' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" service by the owner or others acting through the owner.
© 2023
DSSC-4
Client:
5' - 4" 5' - 4" 5' - 4 3/8"
4
S608
RD-1.5
2
MAX. DSSC WEIGHT = 200 LBS Automotive
Managment
M M
Services, Inc.
505 S. Flagler Dr., Suite 1400
ME.2 West Palm Beach, FL 33401

Project Number: 22008


RC ME Project Name:

1
S608
Alliance Hyundai
Sim
MAX. HP WEIGHT = 200 LBS MAX. HP WEIGHT = 200 LBS 6
EF-5 EF-6 S607

11001 North Fwy


4' - 8" FAN FAN FAN 4' - 8"
Fort Worth, TX 76177
3
S608

48LH13 @ 6' - 0"

RB
5
S207 MAX. RTU WEIGHT = 4200 LBS

RTU-10

DSSC-3

2
3 6
S605 S606
MATCHLINE MATCHLINE Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


MD.2 2
S605
MAX. DSSC WEIGHT = 200 LBS

Key Plan
Framing Plan -
0
RA S203b Service Shop
MD MD
Gridline Type Legend
Roof
Sheet Number:
NEW GRIDLINE

1
S203b
Service Shop Roof Framing Plan
1/8" = 1'-0"
M3.2 M3 6 5 4.6 3.8 1.9 1
F.O. MASONRY GRIDLINE
S203b
1
S601 4 5
ROOF FRAMING PLAN NOTES S601 S601

: INDICATES CONTINUOUS HORIZONTAL RIGID


BRACING AT TOP AND BOTTOM CHORD OF
JOIST. ADD "X" TYPE BRIDGING IN FIRST PANEL
AND AT EVERY SIXTH PANEL. WELD TO JOIST,
FRAMING, AND AT CROSSOVER POINTS. SEE
NOTE :

NOTE:
WHERE TUBE FRAME MEMBERS CONNECT TO
COLUMNS, PROVIDE A WELDED CONNECTION
ALL AROUND FROM TUBE TO COLUMN, TYP.

STEEL REINF. TO BE WELDED SHALL CONFORM


6
S600
2
S601 PRAXIS3
D 100 Peachtree St NW 404-875-4500 tel
SPECIFICATIONS. TO THE REQUIREMENTS OF ASTM A-706 AND
THAT WELDING SHALL BE IN ACCORDANCE HSS8X8X1/4 (CANT.) Suite 1450 404-876-8884 fax
: INDICATES A LOAD-BEARING CMU WALL WITH AWS D1.4, STRUCTURAL WELDING CODE - t/s 33' - 9 1/2" Atlanta, GA 30303 www.praxis3.com
BELOW. SEE WALL ELEVATIONS AND TYPICAL REINFORCING STEEL BY AMERICAN WELDING 2
DETAILS FOR SIZE AND REINFORCEMENT. SOCIETY FOR COMPLIANCE WITH ACI 318.

: INDICATES A NON-LOAD-BEARING CMU WALL NOTE: FOR FRAMING AROUND ROOF HATCH, PROVIDE
BELOW. SEE WALL ELEVATIONS AND TYPICAL CHANNEL FRAMING AS SHOWN ON THE
DETAILS FOR SIZE AND REINFORCEMENT. 6
TYPICAL DETAIL FOR FRAMING AROUND
MECHANICAL UNITS. (UNLESS NOTED S601
: INDICATES THE DIRECTION THE DECK IS OTHERWISE)
2

HSS12X12X5/16
SPANNING.

t/s 33' - 1 1/2"


NOTE: KEEP STRUCTURE GUYED AND BRACED UNTIL
INDICATES A MOMENT CONNECTION AT EACH ALL MASONRY/CONCRETE SHEAR WALLS,
END OF BEAM TO COLUMN. SEE TYPICAL DIAGONAL BRACES, MOMENT FRAMES,
DETAIL FOR FULL PENETRATION WELD OF FRAMED FLOORS AND ROOF DECKS ARE IN
FLANGES AT EACH END. SEE DETAIL 10 / S681 PLACE.

(H) : INDICATES HIGH BEAM. NOTE: SEE ARCHITECT AND PLUMBING DRAWINGS
FOR LOCATIONS OF ROOF DRAINS. ROOF IS
(L) : INDICATES LOW BEAM. DESIGNED FOR A MAXIMUM DEPTH OF 4" OF
WATER AT ANY LOCATION OF THE ROOF.
H.B. : INDICATES ANGLE 3"x3"x1/4" HORIZONTAL WATER SHALL BE RELIEVED BY EITHER
BRACE EXTENDING FROM TOP CHORD OF SCUPPERS OR AN INDEPENDENT EMERGENCY
JOIST OR BEAM TO FACE OF COLUMN. WELD OVERFLOW DRAIN AT THE 4" LEVEL.
ALL AROUND EACH END WITH A 3/16" FILLET
WELD. NOTE: FOR FRAMING AROUND THE PERIMETER OF SIGNED & SEALED 02.16.2024
A MECHANICAL UNIT, SEE TYPICAL
A.X. : DETAIL: 3 / S681
. Copyright (c) 2023 Praxis3, LLC
INDICATES ADDITIONAL "X" TYPE BRIDGING. C
USE 2"x2"x1/4" ANGLE 2 2 All reports, plans, specifications, computer files, field data, notes and other documents
NOTE: FOR FRAMING AROUND ROOF OPENINGS HSS8X8X1/4 (CANT.) and instruments prepared by Praxis3 shall retain all common law, statutory and other
INCLUDING EXHAUST FANS, ROOF DRAINS AND reserved rights, including copyright thereto.
S.P. : INDICATES A BEAM SPLICE POINT, SEE TYPICAL t/s 33' - 9 1/2"
ANY PENETRATIONS LARGER THAN 12", SEE 2 This drawing may not be reproduced in whole or in part without written permission of
SPLICE POINT DETAIL.4 / S681 Praxis3. It is to be returned upon request. Scales as stated are valid on the original
TYPICAL DETAIL: 12 / S681 drawings.
S401 1
T/S : INDICATES TOP OF STEEL BEAM REFERENCED
NOTE: FOR SUPPORT OF ROOF PIPING
FROM ELEVATION [0'-0"].
PERPENDICULAR TO JOIST, AND PARALLEL TO
Rev Date Comments
INDICATES A MASONRY CONTROL JOINT.
JOIST, SEE DETAIL 11 / S681 10.03.2022 Permit / Bid Set
M.C.J. :
COORDINATE EXACT LOCATION WITH 2 04.17.2023 ASI 01
ARCHITECT. JOINT SHALL EXTEND TO TOP OF
PARAPET AND SHALL NOT BE LOCATED WITHIN
Gridline Type Legend 54 02.16.2024 Foundation Coor.
1'-0" OF A JOIST BEARING SEAT ABOVE, 2'-0" OF
A BEAM BEARING, OR WITHIN 2'-0" OF JAMB OF 2

HSS12X12X5/16
t/s 33' - 1 1/2"
ANY OPENING. SEE DETAIL 7 / S687 . NEW GRIDLINE

NOTE: AFTER ALL ROOF DEAD LOAD HAS BEEN


INSTALLED, PROVIDE ANGLE BRACES, OR F.O. MASONRY GRIDLINE
TENSION RODS AS NOTED IN "TYPICAL BAR
JOIST ROOF CONSTRUCTION" SEE DETAIL 1 / S681 B

NOTE: WHERE CONDENSING UNITS BEAR ON ROOF 2


STRUCTURE, PROVIDE A SUPPORT FRAME

HSS8X8X1/4 (CANT.)

HSS8X8X1/4 (CANT.)

HSS12X12X5/16
SIMILAR TO A ROOF OPENING SUPPORT AT THE 2

t/s 33' - 1 1/2"


PERIMETER OF THE UNIT. PROVIDE ANGLES AS 2' - 9 1/2"
Sim 1 S402
SHOWN IN DETAIL 12 / S681 2 2

t/s 33' - 9 1/2"

t/s 33' - 9 1/2"


4

CENTERLINE
NOTE: WHERE FANS ARE TO BE SUPPORTED FROM 5 S686

2" HSS
ROOF JOIST FRAMING, PROVIDE ADDITIONAL S600 HSS8X8X1/4 (CANT.)
HSS8X8X1/4 (CANT.) t/s 33' - 9 1/2"
STEEL SUPPORT PER DETAIL 3 / S682 t/s 33' - 9 1/2" 2
2 A.2
NOTE: CONTRACTOR COORDINATE LOCATION OF
OPENINGS AND WEIGHTS OF MECHANICAL HSS12X12X5/16 HSS12X12X1/2 HSS12X12X3/8
UNITS, WITH THE MECHANICAL DRAWINGS. IF
t/s 33' - 1 1/2" t/s 33' - 1 1/2" t/s 33' - 1 1/2"
A
WEIGHTS EXCEED WHAT IS SHOWN ON THE 2 2 2 1 1/8"
STRUCTURAL PLAN, THEN NOTIFY THE
STRUCTURAL ENGINEER OF THE CHANGE
PRIOR TO ANY DETAILING OR FABRICATION OF
JOIST, DECK OR STEEL.

NOTE: WHERE A K SERIES JOIST BEARS ON THE SAME 3 1


STEEL BEAM OR MASONRY WALL AS AN LH 6 5 4.6 4 3.8 4 3 S600 2 2 1.9 S600
JOIST, PROVIDE A 5" SEAT AT THAT END TO 2 S600 S600
MATCH THE BEARING DEPTH OF THE LH JOIST.
0
Key Plan 2
Showroom Top of Glass Framing Plan S401
NOTE: AT PERIMETER OF ALL ROOFS, EXPANSION
JOINTS, AND TRANSITIONS FROM HIGH TO LOW S204 4 S204
ROOFS, PROVIDE ROOF CLOSURE ANGLES AS 1/8" = 1'-0"
S601 4
PER SECTIONS DETAILED. WHERE NOT
SHOWN, PROVIDE A 4" x 3" x 1/4" CONT. ANGLE S601
LONG LEG VERTICAL. WHERE ANGLE BEARS
ON JOIST SEATS, FIELD WELD TO EACH JOIST
MB MB

t/s 37' - 10 1/4"


WITH A 3/16" FILLET WELD. WHERE ANGLE
BEARS ON A ROOF BEAM, FIELD WELD WITH A
3/16" FILLET WELD 2" at 12" o.c. MAX.

3 3

t/s 37' - 8 1/2"


W10X12
S601 S601
1
1 5 S601 5
S601 S601 S601 Mark W. Nannis, P.E.
2 4' - 0" 4' - 8 1/2" Texas Design Firm #21364
3' - 3" 3' - 3" 7"
S601 1591 Riverside Drive

t/s 38' - 3 5/8"


2 Gainesville, GA 30501

HSS2-1/2X2-1/2X1/4
S601

4' - 10"
770-614-6114 tel

4' - 7"
6 6 37k-ft
S600 S600 6k
C8X11.5 C8X11.5 C8X11.5 W24X55 W24X55 W24X55 W18X35 All drawings, specifications, and other work product
11 k 12 k 18 k 18 k 9k 6k
t/s 41' - 4" t/s 41' - 4" t/s 41' - 4"
D t/s 38' - 1 1/8" t/s 38' - 1 1/8" t/s 38' - 1 1/8"
D of Mark W. Nannis, P.E. (henceforth referred to as "The

5' - 3 1/4"

5' - 3 1/4"
t/s 38' - 1 1/8" Engineer") for this project are instruments of service for

15 k
W8X10 this project only and shall remain the property of The
t/s 37' - 9 5/8" Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by

t/s 37' - 9 5/8"


the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk

5' - 10"

5' - 10"
and the owner agrees to defend, indemnify, and hold
Sim harmless The Engineer from all claims, damages, and
3 expenses including attorney's fees arising out of such
6 S681 6 unauthorized reuse of The Engineer's instruments of
S601 S601 service by the owner or others acting through the owner.
© 2023

5' - 10"

5' - 10"
MAX. RTU WEIGHT = 4200 LBS
Client:

26KCS2

26KCS2

26KCS2

26KCS2

26KCS2

26KCS2

26KCS2

26KCS2

W24X55
W24X55
RTU-9
Automotive

26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7
5' - 10"

5' - 10"
Sim
7
4' - 9" 5' - 11 7/8" Managment
5' - 8"

5' - 8"
S682
1' - 0"

5' - 10" Services, Inc.

5' - 10"
Sim 505 S. Flagler Dr., Suite 1400
5' - 8"

5' - 8"
1' - 0" 7
West Palm Beach, FL 33401
S682

t/s 38' - 6 1/2"

t/s 38' - 6 1/2"


Sim Sim
2 Project Number: 22008
5' - 10"

5' - 10"
6
1' - 1"

S681

1' - 1"
Project Name:
5' - 2"

5' - 2"
HSS4X4X1/4 (TYP.) 6" S682 8"
20 k

17 k
t/s 40' - 6"
S.P. S.P.
C
18 k W27X84 36 k W27X84 35 k W27X84 35 k
C Alliance Hyundai
5' - 10"

5' - 10"
t/s 38' - 10" t/s 38' - 10" t/s 38' - 10"

t/s 38' - 6 1/2"


6k

24 k
6"

6"
2 2
52k-ft
20 k

3' - 0" 3' - 0"

6k
t/s 38' - 6 1/2"

6" (TYPICAL)

S401 1
5' - 10"

5' - 10"
RD-1.5

RD-1.5
RD-1.5
11001 North Fwy
5 4.6 4 3.8 3 2 1.9 Fort Worth, TX 76177
5' - 10"

5' - 10"
3
Showroom Roof Parapet and Screen Framing
W24X68

W24X68
W24X76

W24X76
5' - 10"

5' - 10"
26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7

26K7
S204 1/8" = 1'-0"

B
5' - 10"

5' - 10"
5' - 11" 5' - 11" 5' - 11" 5' - 10" 5' - 11" 5' - 9" 5' - 8" 5' - 6" 5' - 6" 5' - 6" 5' - 5" 5' - 6" 5' - 6" 5' - 8" 5' - 9" 5' - 11" 5' - 10" 4' - 7" 5' - 0" 4' - 3" 3' - 11"
Sim
7
5' - 10"

5' - 10"
S682

t/s 39' - 4 1/8"


1 S402 1 S402
t/s 39' - 4 1/8"

126k-ft
86k-ft

95k-ft
5
Sim
9k

9k
S600
89k-ft

7
5' - 10"

5' - 10"
22 k

30 k
S682 35k-ft 158k-ft 162k-ft 161k-ft 156k-ft 27k-ft
7k W24X146 21 k 23 k W24X146 23 k 20 k W24X146 7k Sheet Title:
A.2

RELEASED FOR CONSTRUCTION AND PERMIT


103k-ft
t/s 39' - 7 5/8" t/s 39' - 7 5/8" t/s 39' - 7 5/8"
95k-ft

84k-ft
17 k

18 k
Framing Plan -

21 k
70k-ft
17 k

6' - 10"

6' - 10"
W24X68

W24X76

W24X76
6' - 6"

6' - 6"
1' - 5"

HSS4X4X1/4 (TYP.)

W24X68
5' - 5"

5' - 5"
t/s 45' - 2" A
5 5
C 5 6k W18X35
t/s 39' - 9 1/4"
6k 9k W24X55
t/s 39' - 9 3/8"
9k 8k W18X35
t/s 39' - 9 1/4"
8k 5
Showroom Roof
Sim
t/s 39' - 5 7/8"

t/s 39' - 11 7/8"


t/s 39' - 10 1/8"

t/s 39' - 4"


6
t/s 39' - 4 1/8"

t/s 39' - 11 7/8"

t/s 39' - 5 7/8"


t/s 39' - 10 1/8"
S682 4 3 2 1
S600 S600 S600 S600
2
4 3.8 3 Sheet Number:
6 5 4.6 4 3.8 3 2 1.9
S401

4
S204
Screen Framing
1/8" = 1'-0"
1
S204
Showroom Roof Framing Plan
1/8" = 1'-0"
S204
11 4 13
MC1 R5 R6 MC2 MCA MCB MCC

PRAXIS3
MC2 R6 R5 MC1 12
S205 S207 S205
S205

12W 12W 100 Peachtree St NW 404-875-4500 tel


5/48 5/48 Suite 1450 404-876-8884 fax
Atlanta, GA 30303 www.praxis3.com

12W
12W 5/48
5/48 40" DEEP MASONRY LINTEL REINFORCED
WITH (2) #8 BOTTOM AND (2) #4 TOP

3
Car Wash Rear 4
Car Wash Front 5
Car Wash Entrance
SIGNED & SEALED 02.16.2024
S205 3/16" = 1'-0"
S205 3/16" = 1'-0"
S205 3/16" = 1'-0"
Copyright (c) 2023 Praxis3, LLC

All reports, plans, specifications, computer files, field data, notes and other documents

MCA 10 MCB MCB MCA and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.
14
MCB MCC
S205 This drawing may not be reproduced in whole or in part without written permission of
S205 Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.

Rev Date Comments


12W 10.03.2022 Permit / Bid Set
5/48 2 04.17.2023 ASI 01
54 02.16.2024 Foundation Coor.

12W
MC1216A

5/48 12W
5/48

6
Car Wash Exit 7
Car Wash Interior 8
EV Storage 1 9
EV Storage 2
5
S205 3/16" = 1'-0" S205 3/16" = 1'-0" S205 3/16" = 1'-0" S205 3/16" = 1'-0"

ANCHOR TO BOND BEAM WITH


MC2 MCA 5/8" Ø EXPANSION ANCHORS
1' - 0" FROM EACH END OF
MCB WALL AND AT 2' - 0" o.c. MAX.
Sim 4" x 3" x 1/4" CONT. ANGLE. WELD TO EACH
2 ROOF JOIST WITH A 3/16" FILLET WELD IN
1 1/2" EDGE OF STEEL Sim
S688 THE FIELD. ANCHOR WOOD BLOCKING TO
2
VERTICAL LEG WITH A "TB1460S" SCREW AT EACH Sim
S688 11
BY "SIMPSON" AT 12" o.c. MAX BEAM
3/16 S205
AT EACH 4" MC2 MC1
INFILL 12" CMU BETWEEN BEAMS.
PROVIDE FACE SHELL AT BEAM 3/16 BEAM
Sim LOCATIONS. 4' - 6 3/4" 5' - 6"
12
S688 MCC

t/s 15' - 9 1/8"


FOR BEARING PLATE SIZE AND HEADED
STUDS, SEE BEARING PLATE SCHEDULE. W10X12
BEAM BEARING 15' - 7 3/8" 5

W10X12
W10X12 NOTE: ALL STEEL IN CAR WASH, INCLUDING

t/s 15' - 11 7/8"


Sim BEARING PLATES, SHALL BE GALVANIZED.
BEAM BEARING 15' - 1 7/8" 4"x3"x1/4" CONTINUOUS ANGLE 11
2 Sim
S689 (LONG LEG VERTICAL) S205 13
12" CONT. BOND BEAM REINFORCED S205
WITH (2) #5 CONTINUOUS MCB Mark W. Nannis, P.E.

t/s 15' - 11 7/8"

t/s 15' - 11 7/8"

t/s 15' - 11 7/8"

t/s 15' - 11 7/8"

t/s 15' - 11 7/8"

t/s 15' - 11 7/8"

t/s 15' - 11 7/8"

t/s 15' - 11 7/8"

t/s 15' - 11 7/8"

t/s 15' - 11 7/8"


Texas Design Firm #21364
HOOK VERTICAL WALL REINFORCEMENT
1591 Riverside Drive
2'-0" HORIZONTALLY INTO BOND BEAM.
Gainesville, GA 30501
RD-1.5 770-614-6114 tel
14 13 All drawings, specifications, and other work product
S205 S205 of Mark W. Nannis, P.E. (henceforth referred to as "The

W10X12

W10X12

W10X12

W10X12

W10X12

W10X12

W10X12

W10X12

W10X12

W10X12
Engineer") for this project are instruments of service for
10 this project only and shall remain the property of The
S205 5 Engineer whether the project is complete or not. Reuse
LINTEL (SEE WALL ELEVATIONS of any of the instruments of service of The Engineer by
5' - 10" 5' - 10" 5' - 10" 5' - 10" 5' - 10" 5' - 10" 5' - 10" 5' - 10 3/4" 4' - 4" 5' - 0" 5' - 6" 4' - 6" the owner or extensions of this project without the written
AND LINTEL SCHEDULE)
VERTICAL WALL REINFORCEMENT permission of The Engineer shall be at the owner's risk

t/s 16' - 5 1/4"

t/s 16' - 5 1/4"

t/s 16' - 5 1/4"

t/s 16' - 5 1/4"

t/s 16' - 5 1/4"

t/s 16' - 5 1/4"

t/s 16' - 5 1/4"

t/s 16' - 5 1/4"

t/s 16' - 5 1/4"

t/s 16' - 5 1/4"


CENTERED IN MASONRY WALL. FILL and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
ALL CELLS WITH GROUT WHERE expenses including attorney's fees arising out of such
REINFORCING OCCURS. SEE WALL unauthorized reuse of The Engineer's instruments of
ELEVATIONS, TYPICAL DETAILS AND service by the owner or others acting through the owner.
WALL SCHEDULE FOR SIZE AND © 2023
VEHICLE DOOR LOCATION OF REINFORCING. MCA
(SEE ARCHITECTURAL DRAWINGS) Client:

4
S207
12
S205 Automotive
Roof - Car Wash (exit) Roof - Car Wash (bearing, low) Roof - Car Wash (bearing, high) Car Wash Roof Managment
10 11 12 2
S205 3/4" = 1'-0" S205 3/4" = 1'-0" S205 3/4" = 1'-0" S205 1/8" = 1'-0"
Services, Inc.
505 S. Flagler Dr., Suite 1400
West Palm Beach, FL 33401

Project Number: 22008


Project Name:

MC1 Alliance Hyundai


R5
Sim
2
S688 MC2 MC1
68' - 0" 5
WELD DECK TO CLOSURE ANGLE PER
DECK SPECIFICATION. 6" 23' - 10" 23' - 10" 8' - 4" 10' - 6" 1' - 0" 11001 North Fwy
GB24 1' - 0" Fort Worth, TX 76177
[-2' - 0"]

6"
Sim MCC
12
S688 24" / 54" 24" / 54"
[-4' - 0"] 9 [-4' - 0"]
12" CONT. BOND BEAM REINFORCED

11' - 0"
10' - 6"
[-2' - 0"]
WITH (2) #4 CONT. HORIZONTAL. SLOPE

GB24
8 S205

[-2' - 0"]
BOND BEAM WITH SLOPE OF ROOF DECK.

GB24
4" CUT BLOCK BELOW AS REQUIRED. 24" / 54" 24" / 54" 24" / 54"
[-4' - 0"] [-4' - 0"] GB24c [-4' - 0"]
[-2' - 0"]

6"
5"x3"x1/4" CONTINUOUS ANGLE
(LONG LEG VERTICAL) MCB

6' - 0"
ANCHOR TO BOND BEAM WITH 5/8" Ø 24" / 54"
EXPANSION ANCHORS 1' - 0" FROM [-4' - 0"]
EACH END OF WALL AND AT 2' - 0" o.c.
MAX. SOG-6 SOG-6

[-2' - 0"]
3

GB24

21' - 8"
22' - 8"
[-2' - 0"]
12' - 0"

GB24
6 7 5 S205
S205
Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


LINTEL (SEE WALL ELEVATIONS LINTEL (SEE WALL ELEVATIONS Sim

Car Wash Plan,


4 8
AND LINTEL SCHEDULE) AND LINTEL SCHEDULE)
S680
24" / 54" 24" / 54" 24" / 54" 24" / 54"

Elevations, and
4' - 8"

[-4' - 0"] [-4' - 0"] [-4' - 0"] [-4' - 0"]

MCA
GB24c
Details

6"
[-2' - 0"]
4
S207
Sheet Number:

13
S205
Roof - Car Wash (entrance)
3/4" = 1'-0"
14
S205
Roof - Car Wash (interior)
3/4" = 1'-0"
1
S205
Car Wash Foundation
1/8" = 1'-0"
S205
CONCRETE WALL
DRILLED SHAFT SCHEDULE R6 (SEE RAMP DETAILS)

PRAXIS3
RE 12
S208
R6 (MINIMUM EMBEDMENT DEPTH = 18'-0")
SHAFT Ø BELL Ø VERT. REINF. HOOPS COUNT
_22"
18" 48" (8) #5 #3 @ 12" o.c. 5 100 Peachtree St NW 404-875-4500 tel

2" CLEAR
1' - 0" 4" 8"
24" 54" (8) #5 #3 @ 12" o.c. 125 DRILLED SHAFT BELOW CLASS A LAP Suite 1450 404-876-8884 fax

6"
24" 66" (8) #7 #3 @ 12" o.c. 15 Atlanta, GA 30303 www.praxis3.com
(8) #8 VERTICAL
24" 72" (8) #7 #3 @ 12" o.c. 2 #3 HOOPS @ 14" o.c.
CABLE RAIL POST 2"
30" 60" (12) #8 #3 @ 12" o.c. 2

2' - 0"
(SEE CABLE RAIL DETAILS) 5' - 7 3/8" CLEAR
#3 HOOPS @ 16" o.c.
RE (8) #7 VERTICAL

3"

2' - 0"
2" CLEAR
CLEAR

STAGGER LAPS 180

6"
8" 1' - 5" RAMP ELEVATION VARIES DEGREES OPPOSITE
ALTERNATING.

CLEAR
45.
12 00° 00°
45.

3"
S208
(1) #4 CONTINUOUS 1' - 4" 8" (1) #4 CONTINUOUS
AT TOP AND BOTTOM
OF STEM WALL Ramp Column at Concrete Wall Typical Ramp Column
1' - 4"
1:1
4 5
(2) #5 CONTINUOUS S206 S206
3/4" = 1'-0" 1/2" = 1'-0"
(1) #4 CONTINUOUS
AT TOP AND BOTTOM
OF STEM WALL NOTE: KEEP STEM WALL
SHORED UNTIL BEAM
#4 HORIZONTAL AT NOTE: KEEP STEM WALL SHORED UNTIL HAS BEEN POURED. #4 HORIZONTAL AT MC2 R6 R5 MC1 R4 M4 R3 R2 R1 M3 SIGNED & SEALED 10.03.2022
12" o.c. MAX. UPPER SLAB HAS BEEN POURED. 12" o.c. MAX.
31' - 6" 31' - 6" 22' - 10" 19' - 9" Copyright (c) 2022 Praxis3, LLC
#4 VERTICAL AT 18" o.c.
MAX. + STANDARD #4 VERTICAL AT 18" o.c. 1' - 5"
All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
HOOKS AT EACH END MAX. + STANDARD 5' - 9" reserved rights, including copyright thereto.
HOOKS AT EACH END MH
This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
M drawings.

1 1/2" CLEAR
Rev Date Comments
MCB
10.03.22 Permit / Bid Set
1 1/2" CLEAR

8" 8" 8"

M
M
8" 8" 8"
T/FTG -2' - 0" T/FTG -2' - 0"
1' - 0"

1' - 0"
FD FD FD
CLEAR

CLEAR
3"

3"
(3) #6 CONTINUOUS (3) #6 CONTINUOUS
3
S207

FE
2
Ramp - Stem Wall at On-Grade Portion 3 Ramp - Transition to Framed Slab 10
Sim
2
13
8 S208 MCA
S680 S206

5' - 1 7/8"
S206 S206 S207 FD
3/4" = 1'-0" 3/4" = 1'-0"

RE
12 24" / 54" 24" / 54" 24" / 54" 24" / 54" 24" / 54"
S208 [-2' - 0"] [-2' - 0"] [-2' - 0"] [-2' - 0"] [-2' - 0"]
4
S206

3 7

19' - 8"
S206 S207
SOG-6 SOG-6 SOG-6
2
S207
Sim
Sim 5
10 24" / 54" S206

M
S680 [-2' - 0"]
RD
24" / 54" 24" / 54" 24" / 72" 24" / 66"
[-2' - 0"] [-2' - 0"] [-2' - 0"] [-2' - 0"]
Sim Sim
10 2
S680 S206
4
10' - 0" 10' - 0" 24' - 8" S207

R6
ME.8
M M

Mark W. Nannis, P.E.


Texas Design Firm #21364
1591 Riverside Drive

FE

50' - 1 1/2"
Gainesville, GA 30501
770-614-6114 tel

All drawings, specifications, and other work product

RB
of Mark W. Nannis, P.E. (henceforth referred to as "The
MSA Engineer") for this project are instruments of service for
this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk
and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
expenses including attorney's fees arising out of such
unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
© 2022

Client:
M M
ME.2 Automotive
RC
Managment
24" / 72"
[-2' - 0"]
24" / 66"
[-2' - 0"]
Services, Inc.
505 S. Flagler Dr., Suite 1400
FD West Palm Beach, FL 33401

Project Number: 22008

M
Project Name:

Alliance Hyundai

27' - 5"
24" / 54" 24" / 54" 11001 North Fwy
[-2' - 0"] [-2' - 0"]
Fort Worth, TX 76177
RB
5
S207

24' - 1 1/128"
MATCHLINE

24" / 54" 24" / 54" MD.2


[-2' - 0"] [-2' - 0"]

RA Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


1' - 10 127/128"
M M M
MD Ramp
Foundation Plan
M6 M5 M3.2 6

1
Ramp Foundation
S206 1/8" = 1'-0" Sheet Number:

S206
PRAXIS3
R6 R5 R4 M4 R3 R2 R1 M3 MSB MG RE RD ME.8 ME.2 RC RB MD.2 RA MD
5
2' - 0" S207
3 13 12 2 1" 14' - 8 1/2" 1' - 6" 14' - 7 1/2" 1' - 6" 14' - 8 1/2" 2' - 0" 12' - 0" 1' - 4" 12' - 1" 2' - 0" 10' - 9" 1' - 4" 10' - 0 1/128" 2' - 0"
S207 S208 S208 S207
24' - 0"

10' - 0" 10' - 0" 24' - 8" 31' - 6" 31' - 6" 22' - 10" 19' - 9"
1' - 5" 100 Peachtree St NW 404-875-4500 tel
20' - 0" Suite 1450 404-876-8884 fax
20' - 0"
4 19' - 6" Atlanta, GA 30303 www.praxis3.com
S207 18' - 6"

8
S608
1' - 0"

0' - 0"
-0' - 6"
16' - 3" 15' - 3" 15' - 9" 15' - 9" 10' - 0" 10' - 0" 2' - 10" 19' - 9"

2
Ramp Profile Lower 3
Ramp Profile Upper
SIGNED & SEALED 10.03.2022
S207 1/8" = 1'-0" S207 1/8" = 1'-0"
Copyright (c) 2022 Praxis3, LLC

All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.
MCA RE 12 2 RD
S208 S207
MC2 R6 R5 MC1 R4 M4 R3 R2 R1 M3 This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.

MH Rev Date Comments


10.03.22 Permit / Bid Set

MCB
8" 22' - 6" 8"

7
S207

8
S207 3 13
S207 S208

FE
Sim 1' - 0" 1' - 2"
10 2 1' - 2" 1' - 0" 1' - 4" 1' - 0"
8 MCA
S680 S206 8" 8' - 2" 8' - 3"

2' - 0"
S207
24 x 24 24 x 24 24 x 24 24 x 24

RE
12

1"
S208

2' - 0" 19' - 10" 2' - 0"


5
3 7 S608

42 x 24

20 x 16

42 x 24
24 x 24

20 x 16

24 x 24

20 x 16

24 x 24

16 x 18

20 x 16

19' - 8"
S206 S207
SOG-6 SOG-6 SOG-6 CIP-6 CIP-6
2
S207

Sim
10
S680

1"
24 x 24 24 x 24 24 x 24 42 x 24
RD

2' - 0"
14' - 7" 13' - 7" 14' - 1" 14' - 1" 8' - 4" 8' - 8"
Sim Sim
10 2 2' - 0" 1' - 4" 1' - 0" 1' - 0" 1' - 4" 1' - 0" 1' - 0" 8" 8"
S680 S206
4 8

14' - 8 1/2"
S207 S608

4
Ramp Cross-Section Lower Mark W. Nannis, P.E.
ME.8
S207 20 x 18 Texas Design Firm #21364
3/8" = 1'-0" 1591 Riverside Drive
CONCRETE BEAM SCHEDULE RD Gainesville, GA 30501

1' - 6"
770-614-6114 tel
R3 R2 R1 M3 TOP BOTTOM
All drawings, specifications, and other work product
MARK WIDTH HEIGHT REINFORCEMENT REINFORCEMENT STIRRUPS FROM EACH END ERD of Mark W. Nannis, P.E. (henceforth referred to as "The
3 13

14' - 7 1/2"
Engineer") for this project are instruments of service for
S207 S208 20 x 16 16" 20" 2 #8 4 #8 #3 Stirrups 1 at 2, R at 8" o.c. this project only and shall remain the property of The
20 x 18 18" 20" 3 #8 6 #8 #3 Stirrups 1 at 2, R at 8" o.c. Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by

RB
8" 22' - 3" 11" 24 x 24 24" 24" 4 #8 4 #8 #3 Stirrups 1 at 2, R at 10" o.c. MSA the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk
40 x 40 40" 40" 7 #8 7 #8 #3 Double Stirrups 1 at 2, R at 12" o.c. 7

1' - 6"
and the owner agrees to defend, indemnify, and hold
S608 harmless The Engineer from all claims, damages, and
42 x 24 24" 42" 4 #8 4 #8 #3 Stirrups 1 at 2, R at 18" o.c. 20 x 18 expenses including attorney's fees arising out of such
unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
© 2022
4
12 S608 Client:
RE S208

14' - 8 1/2"
Automotive
CABLE RAIL (SEE CABLE RAIL DETAILS) Managment
ME.2
Services, Inc.

1' - 0"
4 42 x 24
505 S. Flagler Dr., Suite 1400
S207 RC

40 x 40
2' - 9 3/4" 6 1/4" 16' - 10 3/4" 2' - 4" 1' - 3" West Palm Beach, FL 33401

40 x 40
6

CIP-6
0" S608

1' - 0"
GAP Project Number: 22008
(SEE SCHEDULE)

8 SHIFT LONGITUDINAL BARS Project Name:


BEAM DEPTH

FD

12' - 0"
S207
2" CLEAR

HORIZONTALLY TO AVOID CLASHES


Sim
WITH STUDS AT POSTS 6
Alliance Hyundai
6"

S207

1' - 4"
20 x 16
(SEE SCHEDULE)
BEAM DEPTH

2" CLEAR
3
11001 North Fwy

12' - 1"
S608
Fort Worth, TX 76177
BEAM WIDTH

1' - 0"
(SEE SCHEDULE)
CLEAR

42 x 24
2"

BEAM WIDTH
(SEE SCHEDULE)
RB
5

1' - 0"
S207
Ramp - Transverse Beam Ramp - Edge

10' - 9"
7 8
S207 3/4" = 1'-0" S207 3/4" = 1'-0"

1' - 4"
20 x 16

MATCHLINE

10' - 0 1/128"
TOP LONGITUDINAL BARS
(SEE SCHEDULE)
MD.2 Sheet Title:

1' - 0"

RELEASED FOR CONSTRUCTION AND PERMIT


BEAM DEPTHS > 36"

3
S604
42 x 24
RA
Ramp Plan,
ADDITIONAL #3 BAR EACH SIDE
Profiles, and

1' - 0"
9"

MD
ADDITIONAL #3 BAR EACH SIDE
Cross-Sections
9"

BOTTOM LONGITUDINAL BARS 1 2 3


(SEE SCHEDULE) S605 S605 S605 Sheet Number:

5
S207
Ramp Cross Section Upper
3/8" = 1'-0"
6
S207
Typical Skin Reinforcement at Ramp Beams Deeper than 36"
3/4" = 1'-0"
1
S207
Ramp Plan
1/8" = 1'-0"
M6 M5 M3.2 6 5 S207
3' - 0"

PRAXIS3
SLEEVE ALL THE CABLE TO POST.
REFER TO ARCHITECTURAL DETAILS.
Sim
3
1/2" CAP PLATE TYP. 1/2" CAP PLATE TYP.
S208
ALL EXPOSED STEEL SHALL BE GALVANIZED 1/2" CAP PLATE TYP.
POST POST
(4) - HSS3X2X1/4 KICKER BRACES BUILDING COLUMN 100 Peachtree St NW 404-875-4500 tel
WT6x26.5 CUT TO FIT. AT CORNERS. WELD AT EACH END SLEEVE ALL THE CABLE TO Suite 1450 404-876-8884 fax
SEE SECTION CUT. TO TUBE AND PLATE WITH A 3/16" POST. REFER TO
FILLET WELD. ARCHITECTURAL DETAILS.
Atlanta, GA 30303 www.praxis3.com

HSS8X8X1/2 INTERMEDIATE POST OR 3"

4' - 0"

4' - 0"
BUILDING COLUMN. GALVANIZED

HS
INTERMEDIATE RAIL POST.

S
3X
PT CABLES WITH PLASTIC SLEEVE (4) - HSS3X2X1/4 KICKER BRACES

2X
PAINTED BLACK. SEE ARCHITECT. AT CORNERS. WELD AT EACH END

1/
3' - 0"

2" 2" TYP. @ EA.

4
BR
TO TUBE AND PLATE WITH A 3/16" BASE

AC
FILLET WELD.

ES
1' - 0"
Sim CONCRETE FLOOR
3 SEE PLAN.
S208

2"

2"
Sim
3
2" Sim WT6X26.5 GALVANIZED CUT TO
5
S208 FIT. PROVIDE 1/2" END PLATES TYP. @ EA.
S208 AS SHOWN ON THE ENDS OF BASE
3' - 0" THE TEE. WELD TO TOP
HSS8X8X5/8 OR BUILDING HSS8X8X5/8 OR BUILDING
COLUMN. SEE PLAN. COLUMN. SEE PLAN. FLANGE OF BEAM WITH A 5/16"
TERMINATION POST. TERMINATION POST. FILLET WELD ALL AROUND.
SIGNED & SEALED 10.03.2022

Copyright (c) 2022 Praxis3, LLC


WT4X17.5 CUT TO FIT AT (4) 3/8" STIFF. PLATES AT EACH BASE SUPPORT BEAM WT4X17.5 CUT TO FIT AT SUPPORT BEAM
CORNER POST INTERMEDIATE POST TERMINATION POST EACH SIDE OF SUPPORT BRACE. 2 ON EACH SIDE. EACH SIDE OF SUPPORT
All reports, plans, specifications, computer files, field data, notes and other documents
FLOOR BEAM FLOOR BEAM and instruments prepared by Praxis3 shall retain all common law, statutory and other
BEAM AT TERMINATION POST. BEAM AT TERMINATION POST. reserved rights, including copyright thereto.

This drawing may not be reproduced in whole or in part without written permission of

2
Typical Cable Rail & Post Layout 3
Typical Cable Rail Termination Post 4
Typical Cable Rail Intermediate Post 5
Typical Cable Rail at Building Column Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.

S208 3/4" = 1'-0"


S208 3/4" = 1'-0"
S208 3/4" = 1'-0"
S208 3/4" = 1'-0" Rev Date Comments
10.03.22 Permit / Bid Set

ALL POST-TENSIONING SHALL BE GRADE 270 SEVEN-WIRE


3' - 0"
STRAND 1/2" Ø. SEE SPECIFICATIONS. SLEEVE ALL THE CABLE TO POST.
REFER TO ARCHITECTURAL DETAILS.

NOTE: FORCES SHOWN ARE EFFECTIVE POST-TENSIONING 1/2" CAP PLATE TYP. 1/2" CAP PLATE TYP.
FORCES (Fe) AFTER LOSSES DUE TO MEANS AND METHODS
HAVE BEEN ACCOUNTED FOR BY THE CONTRACTOR. POST POST

Fe = 3 KIPS SLEEVE ALL THE CABLE TO


POST. REFER TO
ARCHITECTURAL DETAILS.
4"

Fe = 3 KIPS
3' - 6" MIN. HEIGHT PER IBC 2021, SECTION 1015.3

4"

4' - 0"
4' - 0"
Fe = 3 KIPS 3"
4"

HS
Fe = 3 KIPS

S
3X
4"

2X
Fe = 3 KIPS TYP. @ EA.

1/
4B
11 CABLES

BASE

RA
4"

Fe = 5 KIPS

C ES
CONCRETE SLAB AND
4"

Fe = 5 KIPS BEAMS (SEE PLAN)


4"

Fe = 5 KIPS
12"X12"X1" EMBED PLATE 12"X12"X1" EMBED PLATE 12"X12"X1" EMBED PLATE
4"

11"
Fe = 3 KIPS WITH (8) 5/8" Ø HEADED WITH (8) 5/8" Ø HEADED WITH (8) 5/8" Ø HEADED
STUDS EMBEDDED 11" STUDS EMBEDDED 11" STUDS EMBEDDED 11"
4"

Fe = 3 KIPS TYP. @ EA.


BASE
4"

Fe = 3 KIPS 1 1/2" 1 1/2"


4 1/2" 4 1/2"
4"

FLOOR

SUPPORT BEAM

6
Typical Cable Rail Spacing & Tension 8
Typical Cable Rail Termination Post 9
Typical Cable Rail Intermediate Post
S208 1" = 1'-0" S208 3/4" = 1'-0" S208 3/4" = 1'-0"
13
S208

M6 M5 R3 R2 M3.2 R1 M3

3 3
1' - 6" 27' - 10 1/8"
S207 S605 Mark W. Nannis, P.E.
Texas Design Firm #21364
1 2 1591 Riverside Drive
S605 S605 Gainesville, GA 30501
1' - 6 5/8"
RA 770-614-6114 tel
3
9' - 3 3/8" 9' - 3 3/8" 9' - 3 3/8"
S604

1' - 6"
All drawings, specifications, and other work product
MC2 R6 R5 MC1 R4 M4 R3 R2 R1 M3 of Mark W. Nannis, P.E. (henceforth referred to as "The
Engineer") for this project are instruments of service for
MD MD this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse

6' - 2 1/4"
12' - 5" 12' - 6" 16' - 0" 15' - 3" 15' - 9" 15' - 9" 10' - 0" 10' - 0" 12' - 8" 9' - 11" of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk
3 13 2 and the owner agrees to defend, indemnify, and hold

10' - 0"
harmless The Engineer from all claims, damages, and
S207 S208 S604
expenses including attorney's fees arising out of such
PROVIDE 1-1/2" Ø GALVANIZED PIPE unauthorized reuse of The Engineer's instruments of
BETWEEN THESE (2) POSTS IN LIEU OF service by the owner or others acting through the owner.
10' - 0 1/8" © 2022
4 10' - 0 5/8" CABLES. SEE ARCHITECTURAL DRAWINGS
3/4" FOR FINISH.
S207 1 6' - 0 Client:
F

16' - 11"
1 6' - 0
3/4"
Automotive

10' - 0"
8 1
S207 S604
1 5' - 6
5/8"
Managment
3/4"
2
S206
1 6' - 3 Services, Inc.
" 505 S. Flagler Dr., Suite 1400
1 2' - 9
West Palm Beach, FL 33401

10' - 0"
1' - 1"
"
1 2' - 8
Project Number: 22008
Project Name:
E.2 3
S603 Alliance Hyundai

- 0"

10' - 0"
10'
1' -
6 "
9' -
3 7/8
Cable Rail Profile at Ramp - Lower E "

90.0
12


S208

- 0"
1/8" = 1'-0" 11001 North Fwy
Fort Worth, TX 76177

10'
45' - 2 7/8"

45' - 2 7/8"

10' - 0"
6"

1' - 2 5/8"
1' -
°
MSB MG RE RD ME.8 MSA ME.2 RC RB MD.2 RA MD .00
C.8 65

- 6"
12 5 2 4 3 5 D

10'
S208 S608 S207 S608 S608 S207
12' - 5 1/8" 12' - 5 1/8"
13' - 9 1/8" 1' -
13' - 8 1/8" 6 "
11' - 3" 11' - 3" 16' - 5 5/8" 5
16' - 1 5/8"
16' - 1 5/8" S603
C.6

- 6"
10'
90.0
°
4 5 .00


6

3' - 1 3/4"

6"
S605 PROVIDE 1-1/2" Ø GALVANIZED PIPE

1' -
BETWEEN THESE (2) POSTS IN LIEU OF 2
9' - CABLES. SEE ARCHITECTURAL DRAWINGS
91 S603
/2" FOR FINISH. Sheet Title:
HSS8X2X1/4

RELEASED FOR CONSTRUCTION AND PERMIT


C.4
6
S603
Cable Rail Plan
1' - 6 3/4"
MA 4
16' - 1 1/2" 16' - 1 1/2" 16' - 5 1/2" 13' - 8" 13' - 9" 12' - 5" 11' - 8 1/128"

5' - 2" 10' - 0" 10' - 0" 10' - 0"


S603

10' - 0" 5' - 4"


and Details
1' - 6"

M6 M5 M3 6 5 Sheet Number:

13
S208
Cable Rail Profile at Ramp - Upper
1/8" = 1'-0"
1
S208
Cable Rail Plan - Vehicle Display
1/8" = 1'-0"
S208
PRAXIS3
6 5
MD F E.6 E.5 E.3 E.2 E C.8 S600 D C.6 C.4 MA C B A.4 S600 A.2 A

100 Peachtree St NW 404-875-4500 tel


Suite 1450 404-876-8884 fax
W24X68 Atlanta, GA 30303 www.praxis3.com
W24X55
1
S601

HSS8X8X1/4
2
3 2 1 4
S603 S603 S603 S602

W30X99

W30X90 W30X90 W30X90 W30X90 (20)

HSS10.750X0.500
HSS10X10X1/2
SIGNED & SEALED 03.30.2023

Copyright (c) 2023 Praxis3, LLC

All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.

TOP OF STEEL 10' - 9 1/2" This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.

HSS8X8X1/2

HSS8X8X1/2
HSS8X8X1/4 HSS8X8X1/4 HSS8X8X1/4 HSS8X8X1/4
Rev Date Comments

HSS8X8X5/16
HSS8X8X1/4

10.03.2022 Permit / Bid Set


2 04.18.2023
03.31.2023 ASI 01

1
Showroom Left
S401 3/16" = 1'-0"

M3 6 5 4.6 4 3.8 3.5 3.6 3.4 3.3 3 2


2 1.9
4 3 1
S600 S600 S600 S600

W18X35 W24X55 W18X35

HSS12X12X5/16 HSS12X12X1/2 HSS12X12X3/8

2 3 2 1
S602 S602 S602

4
1.8 2 1.9 1.8 1.6 1.5 1.3 1.2 S606 1.1 1
W30X108 W30X108 W30X108 C8X11.5 C8X11.5 C8X11.5 Mark W. Nannis, P.E.
Texas Design Firm #21364
W8X18 W8X13 W8X13 1591 Riverside Drive
HSS10.750X0.500

HSS12.750X0.500

HSS12.750X0.500

HSS10.750X0.375
Gainesville, GA 30501
770-614-6114 tel
VERTICALLY SLOTTED
SHEAR CONNECTION FROM All drawings, specifications, and other work product
of Mark W. Nannis, P.E. (henceforth referred to as "The
JAMB POSTS TO BOTTOM OF

HSS8X8X1/4
Engineer") for this project are instruments of service for
BEAMS TO ALLOW FOR 3/4" this project only and shall remain the property of The
VERTICAL LIVE LOAD Engineer whether the project is complete or not. Reuse
MOVEMENT. DESIGN of any of the instruments of service of The Engineer by
HORIZONTAL SHEAR = 1.2 the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk
kips (ASD)
and the owner agrees to defend, indemnify, and hold

HSS6X6X1/4

HSS6X6X1/4

HSS6X6X1/4
harmless The Engineer from all claims, damages, and

HSS6X6X1/4

HSS6X6X1/4

HSS6X6X1/4

HSS6X6X1/4
expenses including attorney's fees arising out of such
HSS8X8X1/4 (H) unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
HSS8X8X1/4 (L) © 2023

Client:

Automotive
HSS8X8X1/2

HSS8X8X1/2

18
Sim
18
Sim
18
Sim
18
Sim Managment
S680 S680 S680 S680
Services, Inc.
505 S. Flagler Dr., Suite 1400
West Palm Beach, FL 33401

Project Number: 22008


Project Name:

2
Showroom Front 3
Elevation at NVD Entrance Alliance Hyundai
S401 3/16" = 1'-0"
S401 3/16" = 1'-0"

B C C.5 D MB
8 11001 North Fwy
S606
Fort Worth, TX 76177
MC8X18.7 MC8X8.5 MC8X18.7 MC8X18.7

W12X14
W12X14
W12X14
W12X14
HSS6X6X1/4

HSS6X6X1/2

HSS6X6X1/4

HSS6X6X3/8

Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


Elevations -
Steel Frames

Sheet Number:

4
S401
Elevation at NVD Side
3/16" = 1'-0"
S401
PRAXIS3
A A.2 B C 6 D
S601

100 Peachtree St NW 404-875-4500 tel


W24X68
W24X68 Suite 1450 404-876-8884 fax
W24X55
Atlanta, GA 30303 www.praxis3.com

HSS12X12X5/16

2
1

HSS6X6X1/4
5
S606 S606
3
S606

W8X18 (10)

HSS8X8X5/16
SIGNED & SEALED 03.30.2023
HSS8X8X1/4
Copyright (c) 2023 Praxis3, LLC

All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.
TOP OF STEEL 10' - 9 1/2"
This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.
HSS8X8X1/4

Rev Date Comments

HSS8X8X1/4
10.03.2022 Permit / Bid Set
2 04.18.2023
03.31.2023 ASI 01

1
Showroom Right
S402 3/16" = 1'-0"

Mark W. Nannis, P.E.


Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel

All drawings, specifications, and other work product


of Mark W. Nannis, P.E. (henceforth referred to as "The
Engineer") for this project are instruments of service for
this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk
and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
expenses including attorney's fees arising out of such
unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
© 2023

Client:

Automotive
Managment
Services, Inc.
505 S. Flagler Dr., Suite 1400
West Palm Beach, FL 33401

Project Number: 22008


Project Name:

Alliance Hyundai

11001 North Fwy


Fort Worth, TX 76177

Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


Elevations -
Steel Frames

Sheet Number:

S402
R1 M3.2
13

PRAXIS3
4 MA C.4 C.6 C.8 E E.2 E.3 E.5 E.6 1 F 2 MD 2 MD MD.2 RA MD
5 6 M3 M5 M6 3 M5 S208
S603 S604 S604 S604
S604

3
M3 S605

100 Peachtree St NW 404-875-4500 tel


Suite 1450 404-876-8884 fax
Atlanta, GA 30303 www.praxis3.com

M.C.J.

M.C.J.
12W 4

M.C.J.
5/8 S605
12W
5/8
12" x 48" MASONRY LINTEL REINFORCED 12" x 24" MASONRY LINTEL REINFORCED
WITH (2) #8 BOTTOM AND (2) #5 TOP. WITH (2) #6 BOTTOM AND (2) #5 TOP
PROVIDE STIRRUPS AT 12" o.c. MAX.
MC1216A

MC1216A

MC1216A

MC1216A

MC1216A

MC1216A

MC1216A
8W 8W
5/48 5/48
8W
5/48
8W
5/48

SIGNED & SEALED 03.30.2023

Copyright (c) 2023 Praxis3, LLC

All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.

This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.

Rev Date Comments

1
Service Drive Front 2
Service Drive Side 3
Janitor 1 4
Janitor 2 5
Service Drive 1 6
Service Drive 2 10.03.2022 Permit / Bid Set
2 04.18.2023
03.31.2023 ASI 01
S403 3/16" = 1'-0"
S403 3/16" = 1'-0"
S403 3/16" = 1'-0"
S403 3/16" = 1'-0"
S403 3/16" = 1'-0"
S403 3/16" = 1'-0"

4
S601

13
S208
1 2 6
M6 3 M5 S605
R3 S605
R2 M3.2 R1 M3 6 S605
S604
3 3
S207 S605
1 1.2 1.5 1.8 1.9 2 3

8W
5/48

12W
5/8
M.C.J.

M.C.J.

M.C.J.

M.C.J.

M.C.J.
12" x 24" MASONRY LINTEL REINFORCED
WITH (2) #6 BOTTOM AND (2) #5 TOP
MC1216A
MC1216A
MC1216A
MC1216A
MC1216A
MC1216A
MC1216A

8W
5/48
8W 8W
5/48 5/48

Mark W. Nannis, P.E.


Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel

All drawings, specifications, and other work product


of Mark W. Nannis, P.E. (henceforth referred to as "The
Engineer") for this project are instruments of service for
this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk
and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
7
Service Drive Rear 8
Stair Tower and Parts expenses including attorney's fees arising out of such
unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
S403 3/16" = 1'-0"
S403 3/16" = 1'-0" © 2023

Client:
2 1.9 MB 3 D
D
3
S601 MB
4
S601
5
S601
Automotive
S601
Managment
Services, Inc.
505 S. Flagler Dr., Suite 1400
West Palm Beach, FL 33401

Project Number: 22008


Project Name:

Alliance Hyundai
1 6 2 1
S606 S605 S606 S606
MB MC

11001 North Fwy


M3.2
Fort Worth, TX 76177

S403 CMU WALL TYPE KEY


NOMINAL WALL
MD.2 6 8W THICKNESS (IN INCHES)
5 5/48 8W
S403 8W 8W VERTICAL 5/48 VERTICAL
MD MD 5/48 5/48 REINFORCEMENT EF REINFORCEMENT
4 S403 S404 BAR SIZE SPACING (IN INCHES)
7 1
2 S404 VERTICAL
3 3 REINFORCEMENT
S403 S404 8W IN EACH FACE
S404 4 MC
S403 5/48
S403 IN ADDITION TO THE VERTICAL SPACING INDICATED,
12 S403 PROVIDE VERTICAL REINFORCEMENT AT EACH SIDE OF
A MASONRY CONTROL JOINT, AT ENDS OF WALLS, AT
8 CORNERS, INTERSECTIONS, AND JAMBS OF ALL
2
MB OPENINGS. REINFORCEMENT SHALL BE CENTERED IN
S403 MASONRY WALL AND EXTENDED FROM FOUNDATION TO
HIGHEST EXTENT OF WALL/PARAPET. SEE TYPICAL
S403 11 9 S403 2 MASONRY WALL DETAILS FOR ADDITIONAL HORIZONTAL Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


REINFORCEMENT.
WALLS NOT IDENTIFIED ON PLAN OR ELEVATION SHALL
BE REINFORCED AS NOTED ABOVE AND AT 48" o.c. MAX.
SEE MASONRY PIER SCHEDULE FOR ADDITIONAL
Elevations -
S403
10
REINFORCEMENT AT JAMBS FOR LARGER OPENINGS.
UNLESS NOTED OTHERWISE, MAXIMUM CONTROL JOINT
SPACING SHALL BE 32'-0" o.c. AND 16'-0" FROM CORNERS.
Masonry Walls
S403 ALL HORIZONTAL REINFORCING SHALL BE
1 DISCONTINUED AT WALL CONTROL JOINTS. VERTICAL
MA 2 WALL CONTROL JOINTS SHALL BE LOCATED AT EACH
FLOOR JOINT (MINIMUM). COORDINATE LOCATIONS WITH
ARCHITECTURAL DRAWINGS.
M6 M5 M3 UNLESS NOTED OTHERWISE, PROVIDE LINTELS AT ALL Sheet Number:
MASONRY OPENINGS PER MASONRY LINTEL SCHEDULE.
UNLESS NOTED OTHERWISE, PROVIDE (2) CELLS

0
S403
Masonry Key Plan
3/64" = 1'-0"
9
S403
Stair Tower Side 1
3/16" = 1'-0"
10
S403
Stair Tower Front
3/16" = 1'-0"
11
S403
Stair Tower Side 2
3/16" = 1'-0"
12
S403
Retail
3/16" = 1'-0"
GROUTED AND REINFORCED WITH (1) #5 VERTICAL AT
ALL OPENINGS IN EXTERIOR WALLS GREATER THAN
10'-0" WIDE. HOOK REINFORCEMENT INTO PARAPET
BOND BEAM.
S403
M3 6 5 4.6MS5 6 4 3.8 MS4 3.5 3.6 3.4 3.3 MS3 3 MS2 2 1.9 1.8 1.6 MS1 1.5 1.3 1.2 1.1 1 MC MD
S606

PRAXIS3
100 Peachtree St NW 404-875-4500 tel
Suite 1450 404-876-8884 fax
Atlanta, GA 30303 www.praxis3.com

12" x 24" MASONRY LINTEL REINFORCED 12" x 48" MASONRY LINTEL REINFORCED 12" x 48" MASONRY LINTEL REINFORCED
WITH (2) #6 BOTTOM AND (2) #5 TOP WITH (2) #8 BOTTOM AND (2) #5 TOP WITH (2) #8 BOTTOM AND (2) #5 TOP

M.C.J.

M.C.J.

M.C.J.

M.C.J.

M.C.J.

M.C.J.
12W
5/48

8W
5/48

8W 8W
5/48 5/48

SIGNED & SEALED 02.16.2024

Copyright (c) 2023 Praxis3, LLC

All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.

This drawing may not be reproduced in whole or in part without written permission of

1
Parts and Service Shop 2
Parts 1 Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.

S404 3/16" = 1'-0" S404 3/16" = 1'-0"


Rev Date Comments
10.03.2022 Permit / Bid Set
54 02.16.2024 Foundation Coor.
MD 7 MC MB 3 2 1.9 1.8 1.5 1.2 1
S606

12W
5/32

8W 8W
5/48 5/48

3
Parts 2 4
Parts Receiving 5
Elevation 1 - a
S404 3/16" = 1'-0" S404 3/16" = 1'-0" S404 3/16" = 1'-0"
5

Mark W. Nannis, P.E.


Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel

All drawings, specifications, and other work product


of Mark W. Nannis, P.E. (henceforth referred to as "The
Engineer") for this project are instruments of service for
this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk
and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
expenses including attorney's fees arising out of such
unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
© 2023

Client:

Automotive
Managment
Services, Inc.
505 S. Flagler Dr., Suite 1400
West Palm Beach, FL 33401

Project Number: 22008


Project Name:

Alliance Hyundai

11001 North Fwy


M3.2 Fort Worth, TX 76177

S403
CMU WALL TYPE KEY
NOMINAL WALL
MD.2 6 THICKNESS (IN INCHES)
8W
S403 5 VERTICAL 5/48 VERTICAL
REINFORCEMENT EF REINFORCEMENT
MD MD BAR SIZE SPACING (IN INCHES)
S404
7 1 VERTICAL
2 S404 REINFORCEMENT
3 3
S404 IN EACH FACE
S403 MC
S404 4
S403 5 IN ADDITION TO THE VERTICAL SPACING INDICATED,
S403 PROVIDE VERTICAL REINFORCEMENT AT EACH SIDE OF
12 S403
A MASONRY CONTROL JOINT, AT ENDS OF WALLS, AT
S404
8 CORNERS, INTERSECTIONS, AND JAMBS OF ALL
OPENINGS. REINFORCEMENT SHALL BE CENTERED IN
2
MB MASONRY WALL AND EXTENDED FROM FOUNDATION TO
S403
HIGHEST EXTENT OF WALL/PARAPET. SEE TYPICAL
MASONRY WALL DETAILS FOR ADDITIONAL HORIZONTAL Sheet Title:
S403 11 9 S403

RELEASED FOR CONSTRUCTION AND PERMIT


REINFORCEMENT.
WALLS NOT IDENTIFIED ON PLAN OR ELEVATION SHALL
BE REINFORCED AS NOTED ABOVE AND AT 48" o.c. MAX.
SEE MASONRY PIER SCHEDULE FOR ADDITIONAL
Elevations -
S403
10
REINFORCEMENT AT JAMBS FOR LARGER OPENINGS.
UNLESS NOTED OTHERWISE, MAXIMUM CONTROL JOINT
SPACING SHALL BE 32'-0" o.c. AND 16'-0" FROM CORNERS.
Masonry Walls
ALL HORIZONTAL REINFORCING SHALL BE
S403
1 DISCONTINUED AT WALL CONTROL JOINTS. VERTICAL
WALL CONTROL JOINTS SHALL BE LOCATED AT EACH
MA FLOOR JOINT (MINIMUM). COORDINATE LOCATIONS WITH
ARCHITECTURAL DRAWINGS.
M5 M3 UNLESS NOTED OTHERWISE, PROVIDE LINTELS AT ALL Sheet Number:
MASONRY OPENINGS PER MASONRY LINTEL SCHEDULE.
UNLESS NOTED OTHERWISE, PROVIDE (2) CELLS

0
S404
Masonry Key Plan
3/64" = 1'-0"
GROUTED AND REINFORCED WITH (1) #5 VERTICAL AT
ALL OPENINGS IN EXTERIOR WALLS GREATER THAN
10'-0" WIDE. HOOK REINFORCEMENT INTO PARAPET
BOND BEAM.
S404
MD RA MD.2 RB RC ME.2 MSA ME.8 RD RE MG MSB MH
5 3 4 2 5 12

PRAXIS3
S207 S608 S608 S207 S608 S208

100 Peachtree St NW 404-875-4500 tel


Suite 1450 404-876-8884 fax
4 Atlanta, GA 30303 www.praxis3.com
S605

M.C.J.

M.C.J.

M.C.J.

M.C.J.

M.C.J.
12W
5/8

SIGNED & SEALED 04.17.2023

Copyright (c) 2023 Praxis3, LLC

All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.

1
Service Shop Side 1 This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.

S405 3/16" = 1'-0"


Rev Date Comments
10.03.2022 Permit / Bid Set
2 04.18.2023
04.17.2023 ASI 01
M3 R1 R2 R3 M4 M4 R3 R2 R1 M3 M3 1 MS5 MS4
S607

13 3 3 13
S208 S207 ME.2 ME.8 S207 S208

7 8
S608 S608
6
S608

12W 12W
5/24 5/8
12W
5/24

M.C.J.

M.C.J.
MC1216A

MC1216A
MC1216A

MC1216A
MC1216A

MC1216A
2 12W 2
5/48

2
Express Drive Front 3
Express Drive Side 4
Express Drive Rear 5
Service Shop Rear
S405 3/16" = 1'-0"
S405 3/16" = 1'-0"
S405 3/16" = 1'-0"
S405 3/16" = 1'-0"

2 3 MS3
MG MSB MH S607 S607
MH MSB MG
Mark W. Nannis, P.E.
Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel

All drawings, specifications, and other work product

M.C.J.
of Mark W. Nannis, P.E. (henceforth referred to as "The
Engineer") for this project are instruments of service for

M.C.J.
this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk
and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
expenses including attorney's fees arising out of such
12W
unauthorized reuse of The Engineer's instruments of
5/48 12W 12W 12W service by the owner or others acting through the owner.
5/48 5/48 5/48 © 2023

M3 Client:

M4 M2 M1.7 M1 Automotive
MH Managment
5 7
1 Services, Inc.
6 S405 8 505 S. Flagler Dr., Suite 1400
S405 S406 2
S406 West Palm Beach, FL 33401

Project Number: 22008


Project Name:
MG
3
6
Photo Booth Side 1 7
Photo Booth Rear 8
Photo Booth Side 2 Alliance Hyundai
S406
S405 3/16" = 1'-0"
S405 3/16" = 1'-0"
S405 3/16" = 1'-0"

MF
7
11001 North Fwy
ME.8 S406 Fort Worth, TX 76177
4
4
1 S405
S406 9
CMU WALL TYPE KEY
3 S405 NOMINAL WALL
5 THICKNESS (IN INCHES)
2 8W
S406 VERTICAL 5/48 VERTICAL
S406 6
REINFORCEMENT EF REINFORCEMENT
ME.2 8 BAR SIZE SPACING (IN INCHES)
ME VERTICAL
REINFORCEMENT
IN EACH FACE

IN ADDITION TO THE VERTICAL SPACING INDICATED,


PROVIDE VERTICAL REINFORCEMENT AT EACH SIDE OF
A MASONRY CONTROL JOINT, AT ENDS OF WALLS, AT
M3.2 CORNERS, INTERSECTIONS, AND JAMBS OF ALL
OPENINGS. REINFORCEMENT SHALL BE CENTERED IN
MASONRY WALL AND EXTENDED FROM FOUNDATION TO
HIGHEST EXTENT OF WALL/PARAPET. SEE TYPICAL
S403 MASONRY WALL DETAILS FOR ADDITIONAL HORIZONTAL Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


REINFORCEMENT.
MD.2
S403 5
6 WALLS NOT IDENTIFIED ON PLAN OR ELEVATION SHALL
BE REINFORCED AS NOTED ABOVE AND AT 48" o.c. MAX.
SEE MASONRY PIER SCHEDULE FOR ADDITIONAL
Elevations -
MD
7 1
MD REINFORCEMENT AT JAMBS FOR LARGER OPENINGS.
UNLESS NOTED OTHERWISE, MAXIMUM CONTROL JOINT
SPACING SHALL BE 32'-0" o.c. AND 16'-0" FROM CORNERS.
Masonry Walls
2 S404 ALL HORIZONTAL REINFORCING SHALL BE
DISCONTINUED AT WALL CONTROL JOINTS. VERTICAL
S403 S404 WALL CONTROL JOINTS SHALL BE LOCATED AT EACH
S404 4
FLOOR JOINT (MINIMUM). COORDINATE LOCATIONS WITH
ARCHITECTURAL DRAWINGS.
M3 M2 UNLESS NOTED OTHERWISE, PROVIDE LINTELS AT ALL Sheet Number:
MASONRY OPENINGS PER MASONRY LINTEL SCHEDULE.
UNLESS NOTED OTHERWISE, PROVIDE (2) CELLS

0
S405
Masonry Key Plan
3/64" = 1'-0"
GROUTED AND REINFORCED WITH (1) #5 VERTICAL AT
ALL OPENINGS IN EXTERIOR WALLS GREATER THAN
10'-0" WIDE. HOOK REINFORCEMENT INTO PARAPET
BOND BEAM.
S405
MH MSB MG

PRAXIS3
MS2 MS1 M2 M1.7 M1 4
S607

100 Peachtree St NW 404-875-4500 tel


Suite 1450 404-876-8884 fax

M.C.J.
Atlanta, GA 30303 www.praxis3.com

M.C.J.

M.C.J.

M.C.J.

M.C.J.
12W
5/8

12W
5/40

MC1216A

MC1248A

MC1248A

MC1248A

MC1248A

MC1248A

MC1216A
SIGNED & SEALED 02.16.2024
2
Copyright (c) 2023 Praxis3, LLC

All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.

This drawing may not be reproduced in whole or in part without written permission of

1
Detail Bays Rear 2
Detail Bays Side Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.

S406 3/16" = 1'-0" S406 3/16" = 1'-0"


Rev Date Comments
10.03.2022 Permit / Bid Set
2 04.17.2023 ASI 01
MS3 MS2 MS1 M2 M1.7 M1 M2 M1.7 M1.7 M2 54 02.16.2024 Foundation Coor.
Sim Sim
5 5 5
S607 S687 S687
M.C.J.

M.C.J.

M.C.J.

M.C.J.

M.C.J.
12W
12W 5/48
8W
5/48 5/48
8W
5/48

3
Detail Bay sand Service Shop 4
Tech Breakroom Rear 5
Tech Breakroom Front
S406 3/16" = 1'-0" S406 3/16" = 1'-0" S406 3/16" = 1'-0"

MSB MG RE RD MF MSA RC ME RB RA MD
6
S607

Mark W. Nannis, P.E.


Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel

M.C.J.

M.C.J.

M.C.J.

M.C.J.
12W
All drawings, specifications, and other work product
5/8 of Mark W. Nannis, P.E. (henceforth referred to as "The
12W Engineer") for this project are instruments of service for
5/48 this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk

MC1232A
and the owner agrees to defend, indemnify, and hold
5 harmless The Engineer from all claims, damages, and
12W expenses including attorney's fees arising out of such
unauthorized reuse of The Engineer's instruments of
5/48
service by the owner or others acting through the owner.
© 2023

Client:

Automotive
M3

M2 M1.7 M1
Managment
Services, Inc.
MH 505 S. Flagler Dr., Suite 1400
7
West Palm Beach, FL 33401
5 1
6 S405 8 Project Number: 22008
S405 S406 2
S406 Project Name:

6
Service Shop Side 2 Alliance Hyundai
MG S406 3/16" = 1'-0"
3

S406
M2 M1.7 M1.7 1 M2 MF MSA ME
7 8
S608
S607 S607 11001 North Fwy
MF Fort Worth, TX 76177
7

ME.8 CMU WALL TYPE KEY


S406
4 NOMINAL WALL
THICKNESS (IN INCHES)
1 S405 8W
S406 9 VERTICAL 5/48 VERTICAL
REINFORCEMENT EF REINFORCEMENT
5 BAR SIZE SPACING (IN INCHES)
S406 VERTICAL
S406 6 REINFORCEMENT
ME.2 8 IN EACH FACE
ME IN ADDITION TO THE VERTICAL SPACING INDICATED,
8W 8W 8W PROVIDE VERTICAL REINFORCEMENT AT EACH SIDE OF
5/48 5/48 5/8 A MASONRY CONTROL JOINT, AT ENDS OF WALLS, AT
CORNERS, INTERSECTIONS, AND JAMBS OF ALL
OPENINGS. REINFORCEMENT SHALL BE CENTERED IN
MASONRY WALL AND EXTENDED FROM FOUNDATION TO
HIGHEST EXTENT OF WALL/PARAPET. SEE TYPICAL
MASONRY WALL DETAILS FOR ADDITIONAL HORIZONTAL Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


REINFORCEMENT.
WALLS NOT IDENTIFIED ON PLAN OR ELEVATION SHALL
BE REINFORCED AS NOTED ABOVE AND AT 48" o.c. MAX.
SEE MASONRY PIER SCHEDULE FOR ADDITIONAL
Elevations -
MD.2
REINFORCEMENT AT JAMBS FOR LARGER OPENINGS.
UNLESS NOTED OTHERWISE, MAXIMUM CONTROL JOINT
SPACING SHALL BE 32'-0" o.c. AND 16'-0" FROM CORNERS.
Masonry Walls
ALL HORIZONTAL REINFORCING SHALL BE
MD MD DISCONTINUED AT WALL CONTROL JOINTS. VERTICAL
2 2 WALL CONTROL JOINTS SHALL BE LOCATED AT EACH
7 1 FLOOR JOINT (MINIMUM). COORDINATE LOCATIONS WITH
2 S404 ARCHITECTURAL DRAWINGS.
S404
UNLESS NOTED OTHERWISE, PROVIDE LINTELS AT ALL Sheet Number:
S403 M3 M2 MASONRY OPENINGS PER MASONRY LINTEL SCHEDULE.
UNLESS NOTED OTHERWISE, PROVIDE (2) CELLS

0
S406
Masonry Key Plan
3/64" = 1'-0"
7
S406
Grid MF
3/16" = 1'-0"
8
S406
Grid ME
3/16" = 1'-0"
9
S406
Tech Breakroom Side
3/16" = 1'-0"
GROUTED AND REINFORCED WITH (1) #5 VERTICAL AT
ALL OPENINGS IN EXTERIOR WALLS GREATER THAN
10'-0" WIDE. HOOK REINFORCEMENT INTO PARAPET
BOND BEAM.
S406
PRAXIS3
100 Peachtree St NW 404-875-4500 tel
Suite 1450 404-876-8884 fax
Atlanta, GA 30303 www.praxis3.com

SIGNED & SEALED 03.30.2023

Copyright (c) 2023 Praxis3, LLC

All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.

This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.

Rev Date Comments


10.03.2022 Permit / Bid Set
2 04.18.2023
03.31.2023 ASI 01

1
Axonometric 1 2
Axonometric 2
S410 S410

Mark W. Nannis, P.E.


Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel

All drawings, specifications, and other work product


of Mark W. Nannis, P.E. (henceforth referred to as "The
Engineer") for this project are instruments of service for
this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk
and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
expenses including attorney's fees arising out of such
unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
© 2023

Client:

Automotive
Managment
Services, Inc.
505 S. Flagler Dr., Suite 1400
West Palm Beach, FL 33401

Project Number: 22008


Project Name:

Alliance Hyundai

11001 North Fwy


Fort Worth, TX 76177

Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


Exterior
Axonometrics

Sheet Number:
NOTE: AXONOMETRIC VIEWS ARE SHOWN

3
S410
Axonometric 3 4
S410
Axonometric 4 FOR VISUAL REFERENCE ONLY AND MAY NOT
ACCURATELY REPRESENT ACTUAL DESIGN
OR DIMENSIONS. USE ONLY IN CONJUNCTION
WITH PLANS, DETAILS, AND SECTIONS.
S410
A A.2 A A.2

4" INSIDE FACE OF STUD


5' - 7" 1' - 5" 4' - 5"

10" INSIDE FACE OF STUD


6' - 6"

10" INSIDE FACE OF STUD


6' - 6"
A A.2

PRAXIS3
3 1/2" EDGE OF STEEL 9 1/2" EDGE OF STEEL 9 1/2" EDGE OF STEEL 100 Peachtree St NW 404-875-4500 tel
3" END OF HSS 9" END OF HSS 9" END OF BEAM Suite 1450 404-876-8884 fax
5 5
Atlanta, GA 30303 www.praxis3.com
Sim Sim Sim
9 11 11
S684 S684 S684
HSS2-1/2X2-1/2X1/4

HSS (SEE PLAN FOR SPACING) HSS (SEE PLAN FOR SPACING)

6" EXTERIOR METAL STUDS AT 16"


o.c. MAX. SEE COLD-FORMED STEEL
6" EXTERIOR METAL STUDS AT 16" 6" EXTERIOR METAL STUDS AT 16" NOTES.
o.c. MAX. SEE COLD-FORMED STEEL o.c. MAX. SEE COLD-FORMED STEEL
NOTES. Sim NOTES.
3 5/8" DIAM. ROD OR ANGLE BOTTOM
S683 CHORD EXTENSIONS AT JOIST CLOSEST
TO BEAM MIDSPAN - SEE DETAIL 1 / S681

SIGNED & SEALED 02.16.2024

Copyright (c) 2023 Praxis3, LLC

All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.

This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.

Sim
1 Rev Date Comments
S683 10.03.2022 Permit / Bid Set
HSS8X8X1/4 (CANT.)
2 04.17.2023 ASI 01
54 02.16.2024 Foundation Coor.

BOTTOM OF STEEL 32' - 2"

2 2

GLASS SYSTEM (SEE ARCHITECTURAL DRAWINGS) GLASS SYSTEM (SEE ARCHITECTURAL DRAWINGS) GLASS SYSTEM (SEE ARCHITECTURAL DRAWINGS)

1
Roof - Showroom - Front Corner 2
Roof - Showroom - Front 3
Roof - Showroom - Front at Column
S600 3/4" = 1'-0"
S600 3/4" = 1'-0"
S600 3/4" = 1'-0"

Mark W. Nannis, P.E.


Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel

All drawings, specifications, and other work product


of Mark W. Nannis, P.E. (henceforth referred to as "The
1 Engineer") for this project are instruments of service for
S601 this project only and shall remain the property of The
A A.2 6 5 Engineer whether the project is complete or not. Reuse
6 5 of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk
6' - 10" and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
6" INSIDE FACE OF STUD 6x4x5/16 CONTINUOUS ANGLE BETWEEN EACH HSS expenses including attorney's fees arising out of such
7' - 4" INSIDE FACE OF STUD unauthorized reuse of The Engineer's instruments of
5 1/2" EDGE OF STEEL service by the owner or others acting through the owner.
5" END OF HSS 7' - 3 1/2" EDGE OF STEEL 5" INSIDE FACE OF STUD © 2023

7' - 3" END OF HSS Client:


3/16 3 @ 12 7' - 4" INSIDE FACE OF STUD
Sim
11
S684
HSS2-1/2X2-1/2X1/4 Sim
5 1/2" EDGE OF STEEL Automotive
11
S684 HSS6X6X3/8 Managment
7' - 3 1/2" EDGE OF STEEL
HSS (SEE PLAN FOR SPACING) Services, Inc.
505 S. Flagler Dr., Suite 1400
HSS (SEE PLAN FOR SPACING) Sim Sim West Palm Beach, FL 33401
9 9
S684 S684
Project Number: 22008
3' - 3" 3' - 3" 7" Project Name:

Alliance Hyundai
5/8" DIAM. ROD OR ANGLE BOTTOM
CHORD EXTENSIONS AT JOIST CLOSEST
TO BEAM MIDSPAN - SEE DETAIL 1 / S681 6" EXTERIOR METAL STUDS AT 16"
6" EXTERIOR METAL STUDS AT 16" o.c. MAX. SEE COLD-FORMED STEEL
o.c. MAX. SEE COLD-FORMED STEEL 6" EXTERIOR METAL STUDS AT 16"
NOTES.
NOTES. o.c. MAX. SEE COLD-FORMED STEEL
NOTES.
11001 North Fwy
Fort Worth, TX 76177

2
2" HSS CENTERLINE

2
2

BOTTOM OF STEEL 32' - 1 1/2"


GLASS SYSTEM (SEE ARCHITECTURAL DRAWINGS)

Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


Wall Sections

GLASS SYSTEM (SEE ARCHITECTURAL DRAWINGS)

Sheet Number:

4
S600
Roof - Showroom - Front (soffit step)
3/4" = 1'-0"
5
S600
Roof - Showroom - Side (grid 5)
3/4" = 1'-0"
6
S600
Roof - Showroom - Rear Corner Return (grid 5)
3/4" = 1'-0"
S600
6
D

4
S601
PRAXIS3
D 100 Peachtree St NW 404-875-4500 tel
S600
Sim Suite 1450 404-876-8884 fax
14
S684 Sim Sim Atlanta, GA 30303 www.praxis3.com
1 1
S688 S688
8" EXTERIOR METAL STUDS AT 16"
o.c. MAX. SEE COLD-FORMED STEEL
NOTES.
4' - 11" INSIDE FACE OF STUD
4' - 10 1/2" EDGE OF STEEL 4" EXTERIOR FACE OF STUD
4' - 10" END OF HSS 3 1/2" EDGE OF STEEL
3" END OF JOIST

Sim
11
S684 HSS2-1/2X2-1/2X1/4 Sim
5
Sim Sim
S684 10 10
S688 S688
HSS (SEE PLAN FOR SPACING)

4' - 0" 4' - 8 1/2"

6" EXTERIOR METAL STUDS AT 16" Sim SIGNED & SEALED 03.30.2023
3
o.c. MAX. SEE COLD-FORMED STEEL
S684 Copyright (c) 2023 Praxis3, LLC
NOTES.
All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.

This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.

Rev Date Comments


10.03.2022 Permit / Bid Set
2 04.18.2023
03.31.2023 ASI 01
HSS8X8X1/4 (CANT.)

8" EXTERIOR METAL STUDS AT 16"


o.c. MAX. SEE COLD-FORMED STEEL
NOTES.

2 HSS12X12X5/16

C.8 C.6

1
Roof - Showroom - Rear Corner 2
Roof - Showroom - Rear 3
Roof - Showroom - Stairs (deck bearing)
S601 3/4" = 1'-0" S601 3/4" = 1'-0"
S601 3/4" = 1'-0"

Mark W. Nannis, P.E.


Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel

All drawings, specifications, and other work product


of Mark W. Nannis, P.E. (henceforth referred to as "The
Engineer") for this project are instruments of service for
this project only and shall remain the property of The
MB D Engineer whether the project is complete or not. Reuse
D of any of the instruments of service of The Engineer by
1.9 2 the owner or extensions of this project without the written
3 permission of The Engineer shall be at the owner's risk
Sim S601 and the owner agrees to defend, indemnify, and hold
1 harmless The Engineer from all claims, damages, and
S688 expenses including attorney's fees arising out of such
unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
© 2023

4' - 9 1/8" INSIDE FACE OF STUD 6x4x5/16 CONTINUOUS ANGLE BETWEEN EACH HSS Client:
4"x3"x1/4" CONTINUOUS ANGLE (LONG LEG VERTICAL)
PROVIDE A 3/4" Ø EXPANSION ANCHOR INTO A 4' - 8 5/8" EDGE OF STEEL
GROUTED CELL AT 2' - 0" o.c. MAX WITH 5" MINIMUM
EMBEDMENT.
4' - 11" INSIDE FACE OF STUD
4' - 8 1/8" END OF HSS Automotive
4' - 10 1/2" EDGE OF STEEL

Sim
3/16 3 @ 12
Managment
3/16
Sim
11
S684 Services, Inc.
9 HSS6X6X3/8 505 S. Flagler Dr., Suite 1400
S684 West Palm Beach, FL 33401

Project Number: 22008


Sim HSS (SEE PLAN FOR SPACING) Project Name:
3

BEAM BEARING 37' - 0 3/8" W10X12 BEAM BEARING 37' - 5 7/8" S684
Alliance Hyundai
4' - 7"
Sim AT
SimJOIST Sim
1 SimBEAM
AT 3 3
S689 1 S688 S684
S689

11001 North Fwy


Fort Worth, TX 76177
6" EXTERIOR METAL STUDS AT 16"
6" EXTERIOR METAL STUDS AT 16"
o.c. MAX. SEE COLD-FORMED STEEL
o.c. MAX. SEE COLD-FORMED STEEL
NOTES.
NOTES.

10" EXTERIOR METAL STUDS AT 16"


o.c. MAX. SEE COLD-FORMED STEEL
NOTES.

Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


Wall Sections
8" EXTERIOR METAL STUDS AT 16"
o.c. MAX. SEE COLD-FORMED STEEL
NOTES.

Sheet Number:
Roof - Showroom - Stairs (beam/joist bearing) Roof - Showroom - Rear Return Corner Roof - Showroom - Side (grid 1.9)
S601
4 5 6
S601 3/4" = 1'-0"
S601 3/4" = 1'-0"
S601 3/4" = 1'-0"
PRAXIS3
A A.2 A.4 M3 6 5
A A.2 A A.2 A.4

100 Peachtree St NW 404-875-4500 tel


Suite 1450 404-876-8884 fax
Atlanta, GA 30303 www.praxis3.com

3 1/4" EDGE OF STEEL


3 1/4" EDGE OF STEEL 1' - 10" 3 1/4" EDGE OF STEEL 3 1/4" EDGE OF STEEL
1' - 10" 1' - 10" 1' - 10"

Sim Sim Sim


8 8 Sim
8 8
S685 S685 S685
S685

SIGNED & SEALED 10.03.2022

Copyright (c) 2022 Praxis3, LLC

All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.

This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.

GLASS SYSTEM GLASS SYSTEM GLASS SYSTEM GLASS SYSTEM


(SEE ARCHITECTURAL DRAWINGS) (SEE ARCHITECTURAL DRAWINGS) (SEE ARCHITECTURAL DRAWINGS) (SEE ARCHITECTURAL DRAWINGS) Rev Date Comments
10.03.22 Permit / Bid Set

SLOPED ARCHITECTURAL COLUMNS


(SEE ARCHITECTURAL DRAWINGS)

ENTRANCE PORTAL
(SEE ARCHITECTURAL DRAWINGS)

BOTTOM OF STEEL 9' - 7 1/2" BOTTOM OF STEEL 9' - 7 1/2"


Mark W. Nannis, P.E.
Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel

1
Level 2 - Showroom - Full-Height Glass at Front 2 Level 2 - Showroom - Full-Height Glass at Front at Column 3 Level 2 - Showroom - Full-Height Glass at Front at Vestibule 4 Level 2 - Showroom - Full-Height Glass at Side (grid 5) All drawings, specifications, and other work product
of Mark W. Nannis, P.E. (henceforth referred to as "The
S602 3/4" = 1'-0"
S602 3/4" = 1'-0"
S602 3/4" = 1'-0"
S602 3/4" = 1'-0" Engineer") for this project are instruments of service for
this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk
and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
expenses including attorney's fees arising out of such
unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
© 2022

Client:

Automotive
Managment
Services, Inc.
505 S. Flagler Dr., Suite 1400
West Palm Beach, FL 33401

Project Number: 22008


Project Name:

Alliance Hyundai

11001 North Fwy


Fort Worth, TX 76177

Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


Wall Sections

Sheet Number:

S602
M3 6 5 M3 6 5 M3 6 5 MA C.4

PRAXIS3
HSS8X2X1/4 HSS8X2X1/4
28' - 0" 28' - 0"

CABLE RAIL & POST (SEE TYPICAL DETAILS)


100 Peachtree St NW 404-875-4500 tel
DOOR (SEE ARCHITECTURAL DRAWINGS) STEEL POST FOR CABLE RAIL BARRIER
Suite 1450 404-876-8884 fax
GLASS SYSTEM 5-1/2" x 4-1/2" x 3/8" CONTINUOUS ANGLE
(SEE CABLE RAIL DETAILS) ANCHOR TO BOND BEAM WITH A 3/4" DIAM.
Atlanta, GA 30303 www.praxis3.com
(SEE ARCHITECTURAL DRAWINGS)
EXPANSION ANCHOR 1' - 0" FROM EACH END
AND AT 2' - 0" o.c. MAX.
12" x 8" CONT. BOND BEAM REINFORCED
WITH (2) #4 CONT. BOTTOM

Sim TOPPING SLAB OVER INSULATION


3 3/8" EDGE OF STEEL 2' - 8" 3/16" THICK STIFFENER PLATES AT EACH END 3/16" 2" at 12 (SEE ARCHITECTURAL DRAWINGS FOR SLOPE)
5" EDGE OF STEEL 9
L8X4X7/16 CONTINUOUS AND AT 4' - 0" o.c. MAX. S685

Sim
8 Sim
9
S685
S685

5-1/2X4X1/4 CONTINUOUS
Sim 3/16"
3 WT5X6 IN WEB OF FLOOR BEAM WHERE ROOF DECK IS ABOVE

4"
S684 BOTTOM FLANGE OF BEAM. MAXIMUM SPACING = 6' - 0" o.c.
INFILL STUD AT WEB OF BEAM BETWEEN WTs

2' - 11 7/8" EXTERIOR 3/16" 2" at 12 SIGNED & SEALED 03.30.2023


FACE OF STUD STEEL FLOOR BEAMS (SEE PLAN) Copyright (c) 2023 Praxis3, LLC

Sim 3/16"
All reports, plans, specifications, computer files, field data, notes and other documents
3 and instruments prepared by Praxis3 shall retain all common law, statutory and other
S684 reserved rights, including copyright thereto.

Sim This drawing may not be reproduced in whole or in part without written permission of
3 Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.
S684
Rev Date Comments
3/16" 2" at 12
10.03.2022 Permit / Bid Set
2 04.18.2023
03.31.2023 ASI 01
VERTICAL WALL REINFORCEMENT
CENTERED IN MASONRY WALL. FILL ALL
3/16" STIFFENER PLATES AT EACH END OF ANGLE CELLS WITH GROUT WHERE REINFORCING
AND AT 4' - 0" o.c. MAX. OCCURS. SEE WALL ELEVATIONS, TYPICAL
DETAILS AND WALL SCHEDULE FOR SIZE
AND LOCATION OF REINFORCING.

10" EXTERIOR METAL STUDS AT 16"


o.c. MAX. SEE COLD-FORMED STEEL
NOTES.

L4X3X1/4 CONTINUOUS. SLOPE WITH ROOF.

L8X4X1/2 CONTINOUS WHERE ROOF DECK IS BELOW BOTTOM


FLANGE OF BEAM

LINTEL (SEE WALL ELEVATIONS


AND LINTEL SCHEDULE)
Sim Sim
13 13
S684 S684

VEHICLE DOOR
(SEE ARCHITECTURAL DRAWINGS)

GLASS SYSTEM GLASS SYSTEM Mark W. Nannis, P.E.


(SEE ARCHITECTURAL DRAWINGS) (SEE ARCHITECTURAL DRAWINGS) Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel

1
Level 2 - Showroom - Stud and Glass at Side 2
Level 2 - Showroom - Transition to Vehicle Display 3
Level 2 - Service Drive - Transition to Low Roof 4
Level 2 - Service Drive - Front All drawings, specifications, and other work product
of Mark W. Nannis, P.E. (henceforth referred to as "The
Engineer") for this project are instruments of service for
S603 3/4" = 1'-0"
S603 3/4" = 1'-0"
S603 3/4" = 1'-0"
S603 3/4" = 1'-0" this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written
D C.8 permission of The Engineer shall be at the owner's risk
and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
expenses including attorney's fees arising out of such
unauthorized reuse of The Engineer's instruments of
HSS8X2X1/4 service by the owner or others acting through the owner.
© 2023
28' - 0"
Client:

Automotive
Managment
CABLE RAIL BARRIER
Services, Inc.
4" EXTERIOR FACE OF STUD 505 S. Flagler Dr., Suite 1400
(SEE CABLE RAIL
3 1/2" EDGE OF STEEL DETAILS) West Palm Beach, FL 33401

Sim Project Number: 22008


8
S685
Project Name:
L8X4X7/16

Alliance Hyundai
Sim
9
S685

Sim
W27X84 (12) 8
SHEAR CONNECTION FROM S685
FLOOR BEAM TO W30X90 BEAM 11001 North Fwy
Fort Worth, TX 76177
6" EXTERIOR METAL STUDS AT 16"
L4X3X1/4 o.c. MAX. SEE COLD-FORMED STEEL
NOTES. 1' - 0"

6" EDGE OF STEEL


3" EDGE OF STEEL & FACE OF STUD

W30X90
Sim
5
S684
SHEAR CONNECTION FROM
LOWER ROOF BEAM TO BOTTOM 2
W24X62
FLANGE OF W30X90 BEAM

Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


Wall Sections

Sheet Number:
Level 2 - Showroom - High-Low Beam Connection Level 2 - Service Drive - Edge Condition at
5
S603
at Corner
3/4" = 1'-0"
6
S603
Cantilever
3/4" = 1'-0"
S603
M6 M5 M6 M5

PRAXIS3
HSS8X2X1/4
28' - 0"
3
S604 MD 2
S604

100 Peachtree St NW 404-875-4500 tel


HAND RAIL BY OTHERS HAND RAIL BY OTHERS Suite 1450 404-876-8884 fax
Atlanta, GA 30303 www.praxis3.com
STAIR DESIGN BY GENERAL CONTRACTOR'S CABLE RAIL & POST (SEE TYPICAL DETAILS)
LICENSED ENGINEER. SEE ARCHITECTURAL
DRAWINGS FOR DIMENSIONS AND REQUIREMENTS.
5-1/2" x 4-1/2" x 3/8" CONTINUOUS ANGLE 5-1/2" x 4-1/2" x 3/8" CONTINUOUS ANGLE 5-1/2" x 4-1/2" x 3/8" CONTINUOUS ANGLE 5-1/2" x 4-1/2" x 3/8" CONTINUOUS ANGLE
ANCHOR TO BOND BEAM WITH A 3/4" DIAM. ANCHOR TO BOND BEAM WITH A 3/4" DIAM. ANCHOR TO BOND BEAM WITH A 3/4" DIAM. ANCHOR TO BOND BEAM WITH A 3/4" DIAM.
EXPANSION ANCHOR 1' - 0" FROM EACH END EXPANSION ANCHOR 1' - 0" FROM EACH END EXPANSION ANCHOR 1' - 0" FROM EACH END EXPANSION ANCHOR 1' - 0" FROM EACH END
AND AT 2' - 0" o.c. MAX. AND AT 2' - 0" o.c. MAX. Sim AND AT 2' - 0" o.c. MAX. AND AT 2' - 0" o.c. MAX.
2 9
Sim Sim
Sim S685 9 9
12" x 8" CONT. BOND BEAM REINFORCED 8" x 8" CONT. BOND BEAM REINFORCED 12" x 8" CONT. BOND BEAM REINFORCED 8" x 8" CONT. BOND BEAM REINFORCED
9 S685 S685
WITH (2) #4 CONT. BOTTOM WITH (2) #4 CONT. BOTTOM WITH (2) #4 CONT. BOTTOM WITH (2) #4 CONT. BOTTOM
S685

Sim
9
S685

SIGNED & SEALED 03.30.2023

Copyright (c) 2023 Praxis3, LLC


STEEL FLOOR BEAM (SEE PLAN)
All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.

This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.

Rev Date Comments


10.03.2022 Permit / Bid Set
STEEL FLOOR BEAM (SEE PLAN) 2 04.18.2023
03.31.2023 ASI 01
Sim
2
S689

VERTICAL WALL REINFORCEMENT VERTICAL WALL REINFORCEMENT VERTICAL WALL REINFORCEMENT VERTICAL WALL REINFORCEMENT
CENTERED IN MASONRY WALL. FILL ALL CENTERED IN MASONRY WALL. FILL ALL CENTERED IN MASONRY WALL. FILL ALL CENTERED IN MASONRY WALL. FILL ALL
CELLS WITH GROUT WHERE REINFORCING CELLS WITH GROUT WHERE REINFORCING CELLS WITH GROUT WHERE REINFORCING CELLS WITH GROUT WHERE REINFORCING
OCCURS. SEE WALL ELEVATIONS, TYPICAL OCCURS. SEE WALL ELEVATIONS, TYPICAL OCCURS. SEE WALL ELEVATIONS, TYPICAL OCCURS. SEE WALL ELEVATIONS, TYPICAL
DETAILS AND WALL SCHEDULE FOR SIZE DETAILS AND WALL SCHEDULE FOR SIZE DETAILS AND WALL SCHEDULE FOR SIZE DETAILS AND WALL SCHEDULE FOR SIZE
AND LOCATION OF REINFORCING. AND LOCATION OF REINFORCING. AND LOCATION OF REINFORCING. AND LOCATION OF REINFORCING.

Mark W. Nannis, P.E.


Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel

1
Level 2 - Service Drive - Side 2
Level 2 - Service Drive - Side at Stair Bumpout 3
Level 2 - Service Drive - Rear at Stair Bumpout All drawings, specifications, and other work product
of Mark W. Nannis, P.E. (henceforth referred to as "The
Engineer") for this project are instruments of service for
S604 3/4" = 1'-0" S604 3/4" = 1'-0" S604 3/4" = 1'-0" this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk
and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
expenses including attorney's fees arising out of such
unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
© 2023

Client:

Automotive
Managment
Services, Inc.
505 S. Flagler Dr., Suite 1400
West Palm Beach, FL 33401

Project Number: 22008


Project Name:

Alliance Hyundai

11001 North Fwy


Fort Worth, TX 76177

Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


Wall Sections

Sheet Number:

S604
HSS8X2X1/4
MD RA MD MD.2 RA MD

PRAXIS3
28' - 0"

CABLE RAIL & POST (SEE TYPICAL DETAILS)


100 Peachtree St NW 404-875-4500 tel
5-1/2" x 4-1/2" x 3/8" CONTINUOUS ANGLE 5-1/2" x 4-1/2" x 3/8" CONTINUOUS ANGLE Suite 1450 404-876-8884 fax
5-1/2" x 4-1/2" x 3/8" CONTINUOUS ANGLE ANCHOR TO BOND BEAM WITH A 3/4" DIAM. ANCHOR TO BOND BEAM WITH A 3/4" DIAM. Atlanta, GA 30303 www.praxis3.com
ANCHOR TO BOND BEAM WITH A 3/4" DIAM. EXPANSION ANCHOR 1' - 0" FROM EACH END EXPANSION ANCHOR 1' - 0" FROM EACH END
EXPANSION ANCHOR 1' - 0" FROM EACH END AND AT 2' - 0" o.c. MAX. AND AT 2' - 0" o.c. MAX.
AND AT 2' - 0" o.c. MAX. Sim Sim
12" x 8" CONT. BOND BEAM REINFORCED 12" x 8" CONT. BOND BEAM REINFORCED
9 WITH (2) #4 CONT. BOTTOM 9 WITH (2) #4 CONT. BOTTOM
12" x 8" CONT. BOND BEAM REINFORCED S685 S685
WITH (2) #4 CONT. BOTTOM
2" EXPANSION JOINT 2" EXPANSION JOINT
(SEE ARCH) (SEE ARCH)
Sim
9
S685

SIGNED & SEALED 10.03.2022


STEEL FLOOR BEAMS (SEE PLAN) STEEL FLOOR BEAM (SEE PLAN) STEEL FLOOR BEAM (SEE PLAN) Copyright (c) 2022 Praxis3, LLC

All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.

This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.

Rev Date Comments


10.03.22 Permit / Bid Set
VERTICAL WALL REINFORCEMENT VERTICAL WALL REINFORCEMENT VERTICAL WALL REINFORCEMENT
CENTERED IN MASONRY WALL. FILL ALL CENTERED IN MASONRY WALL. FILL ALL CENTERED IN MASONRY WALL. FILL ALL
CELLS WITH GROUT WHERE REINFORCING CELLS WITH GROUT WHERE REINFORCING CELLS WITH GROUT WHERE REINFORCING
OCCURS. SEE WALL ELEVATIONS, TYPICAL OCCURS. SEE WALL ELEVATIONS, TYPICAL OCCURS. SEE WALL ELEVATIONS, TYPICAL
DETAILS AND WALL SCHEDULE FOR SIZE DETAILS AND WALL SCHEDULE FOR SIZE DETAILS AND WALL SCHEDULE FOR SIZE
13
AND LOCATION OF REINFORCING. AND LOCATION OF REINFORCING. AND LOCATION OF REINFORCING.
S208

3
4 S605
S605 M3.2 R1 M3
ANCHOR TO BOND BEAM WITH
Sim Sim 5/8" Ø EXPANSION ANCHORS
1 1 1' - 0" FROM EACH END OF
S688 S688 WALL AND AT 2' - 0" o.c. MAX.

AT EACH
4" 3/16 BEAM 4"

Sim t/s 14' - 0"


Sim 12 Sim
10 1
S688 S688 W8X10
S689 Sim
2
S689
3' - 0 3/8" 3' - 0" 4"x3"x1/4" CONTINUOUS ANGLE
(LONG LEG VERTICAL)

LINTEL (SEE WALL ELEVATIONS LINTEL (SEE WALL ELEVATIONS


AND LINTEL SCHEDULE) AND LINTEL SCHEDULE)

VEHICLE DOOR VEHICLE DOOR


(SEE ARCHITECTURAL DRAWINGS) (SEE ARCHITECTURAL DRAWINGS)

1
Level 2 - Service Drive - Rear 2
Level 2 - Service Drive - Rear at Ramp 3
Roof - Service Drive Vestibule 4
Roof - Service Drive Vestibule (beam bearing)
S605 3/4" = 1'-0"
S605 3/4" = 1'-0"
S605 3/4" = 1'-0"
S605 3/4" = 1'-0"
Mark W. Nannis, P.E.
Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel

All drawings, specifications, and other work product


of Mark W. Nannis, P.E. (henceforth referred to as "The
Engineer") for this project are instruments of service for
this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk
and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
expenses including attorney's fees arising out of such
unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
© 2022

Client:
D MB D
1
S606 Automotive
Managment
Services, Inc.
8" EXTERIOR METAL STUDS AT 16"
505 S. Flagler Dr., Suite 1400
o.c. MAX. SEE COLD-FORMED STEEL West Palm Beach, FL 33401
NOTES.
Project Number: 22008
Project Name:

4" EXTERIOR FACE OF STUD 8


Sim Alliance Hyundai
3 1/2" EDGE OF STEEL 6 7/8" EDGE OF STEEL S685

Sim
Sim 8
8 S685
S685
Sim Sim
11001 North Fwy
2 1 Fort Worth, TX 76177
S685 S685

Sim
3
4" INSIDE FACE OF STUD
S684
3" EDGE OF STEEL
4' - 8 3/8" 4' - 9"
Sim
5
S684 STEEL STAIRS BY OTHERS
JOIST BEARING 20' - 2 1/2"

Sim
4
S688
3" END OF JOIST

Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


Wall Sections
5/8" DIAM. ROD OR ANGLE BOTTOM
CHORD EXTENSIONS AT JOIST CLOSEST
TO BEAM MIDSPAN - SEE DETAIL 1 / S681

Sheet Number:

5
S605
Level 2 - Showroom - Low Roof
3/4" = 1'-0"
6
S605
Level 2 - Showroom - Stairs (beam parallel)
3/4" = 1'-0"
S605
PRAXIS3
6
D 1.8 1.9 2
S605 2 1.9

100 Peachtree St NW 404-875-4500 tel


Suite 1450 404-876-8884 fax
8" EXTERIOR METAL STUDS AT 16" 10" EXTERIOR METAL STUDS AT 16" Atlanta, GA 30303 www.praxis3.com
o.c. MAX. SEE COLD-FORMED STEEL o.c. MAX. SEE COLD-FORMED STEEL
NOTES. NOTES.

4" EXTERIOR FACE OF STUD


5" EXTERIOR FACE OF STUD
3 1/2" EDGE OF STEEL 4 1/2" EDGE OF STEEL 3" EDGE OF STEEL
TOP OF STEEL 23' - 6 1/2"

Sim Sim
Sim 8 8
8 S685 S685
BETWEEN
Sim BEAMS BETWEEN
Sim BEAMS S685
1 1
S685 S685
Sim
3
AT
SimBEAMS AT
SimBEAMS S684
1 1
S689 S689 8" EXTERIOR METAL STUDS AT 16"
o.c. MAX. SEE COLD-FORMED STEEL Sim
3
NOTES. S684 8" EXTERIOR METAL STUDS AT 16" SIGNED & SEALED 02.16.2024
4" INSIDE FACE OF STUD o.c. MAX. SEE COLD-FORMED STEEL
Copyright (c) 2023 Praxis3, LLC
3" EDGE OF STEEL NOTES.
Sim All reports, plans, specifications, computer files, field data, notes and other documents
Sim 6 and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.
Sim Sim 5 S684
10 10 S684 This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
S688 S688 drawings.

2 1/2" END OF JOIST


Sim Sim Rev Date Comments
9 9
S688 S688
10.03.2022 Permit / Bid Set
5/8" DIAM. ROD OR ANGLE BOTTOM 54 02.16.2024 Foundation Coor.
CHORD EXTENSIONS AT JOIST CLOSEST JOIST BRIDGING (SEE PLAN)
TO BEAM MIDSPAN - SEE DETAIL 1 / S681

Level 2 - Showroom - Stairs (beam bearing) Level 2 - Showroom - Low Roof at Corner 3
Level 2 - Showroom - Low Roof NVD Side
1 2
S606 S606 S606 3/4" = 1'-0"
3/4" = 1'-0" 3/4" = 1'-0"

1.8 1.9 2
1 1.1

Sim
10" EXTERIOR METAL STUDS AT 16" 2
o.c. MAX. SEE COLD-FORMED STEEL S688
NOTES.
5" EXTERIOR FACE OF STUD
4 1/2" EDGE OF STEEL
Sim
8
S685 Sim
8
S685

MD
WT5X6 IN WEB OF FLOOR BEAM WHERE ROOF DECK
3/16"
IS ABOVE BOTTOM FLANGE OF BEAM. MAXIMUM
SPACING = 6' - 0" o.c.
L4X3X1/4 CONTINUOUS. SLOPE WITH ROOF.
INFILL STUD AT WEB OF BEAM BETWEEN WTs

Sim
Sim 2
3 S688
S684

JOIST BEARING 23' - 9 1/2" Sim


12
S688
Sim
5
S688

9
Sim Mark W. Nannis, P.E.
Texas Design Firm #21364
3.1
Level 2 - Showroom - Low Roof NVD Side at W24 S688 1591 Riverside Drive
Gainesville, GA 30501
S606 3/4" = 1'-0" 770-614-6114 tel

All drawings, specifications, and other work product


5 B of Mark W. Nannis, P.E. (henceforth referred to as "The
Engineer") for this project are instruments of service for
this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by
Sim Sim the owner or extensions of this project without the written
14 5
permission of The Engineer shall be at the owner's risk
S684 S688 and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
4" EXTERIOR FACE OF STUD JOIST BEARING 19' - 3 3/4" expenses including attorney's fees arising out of such
3 1/2" EDGE OF STEEL unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
3" END OF JOIST © 2023

Sim Client:
5
S684
Automotive
Sim 7
Roof - Parts - Joist Parallel (CMU) Managment
3
S684 1.9 2
S606 3/4" = 1'-0"
Services, Inc.
505 S. Flagler Dr., Suite 1400
1 1.1 West Palm Beach, FL 33401

Project Number: 22008


5/8" DIAM. ROD OR ANGLE BOTTOM
CHORD EXTENSIONS AT JOIST CLOSEST
TOP OF STEEL 23' - 7 1/2" Project Name:
TO BEAM MIDSPAN - SEE DETAIL 1 / S681 Sim
14
S684
Alliance Hyundai
8" EXTERIOR METAL STUDS AT 16"
o.c. MAX. SEE COLD-FORMED STEEL
3 1/4" EDGE OF STEEL NOTES.
8" EXTERIOR METAL STUDS AT 16" 1' - 10" 4" EXTERIOR FACE OF STUD
o.c. MAX. SEE COLD-FORMED STEEL 3 1/2" EDGE OF STEEL
NOTES. 11001 North Fwy
Sim Fort Worth, TX 76177
8 Sim
S685 6
S684

LINTEL (SEE WALL ELEVATIONS


AND LINTEL SCHEDULE)

GLASS SYSTEM
COLD-FORMED STEEL HEADER
(SEE ARCHITECTURAL DRAWINGS) Sheet Title:
BEAM BY COLD-FORMED STEEL 8" EXTERIOR METAL STUDS AT 16"

RELEASED FOR CONSTRUCTION AND PERMIT


DESIGNER GLASS
o.c. MAX. SEE COLD-FORMED STEEL
(SEE ARCHITECTURAL DRAWINGS)
NOTES.
Wall Sections
VEHICLE DOOR
(SEE ARCHITECTURAL DRAWINGS)

Sheet Number:

4
S606
Roof - Showroom Low Roof - Joist Bearing
3/4" = 1'-0"
5
S606
Level 2 - Showroom - Full-Height Glass at Side (grid 2)
3/4" = 1'-0"
6
S606
Roof - Shop - Joist Bearing (roof transition)
3/4" = 1'-0"
8
S606
Roof - Showroom Low Roof - Joist Parallel
3/4" = 1'-0"
S606
M1

2
S688
Sim

PRAXIS3
100 Peachtree St NW 404-875-4500 tel
Suite 1450 404-876-8884 fax
Atlanta, GA 30303 www.praxis3.com

MH
MH
4"x4"x5/16" CONTINUOUS ANGLE (LONG LEG WELD DECK TO CLOSURE ANGLE
VERTICAL) ANCHORED TO BOND BEAM WITH AS PER DECK SPECIFICATION.
A 3/4" DIAM. EXPANSION ANCHOR AT 2' - 6" o.c.
MAX. PROVIDE 5" MINIMUM EMBEDMENT.
Sim
12
S688
JOIST BEARING 20' - 8 5/8" JOIST BEARING 20' - 8 3/4"
12" CONT. BOND BEAM REINFORCED WITH (2)
Sim #4 CONTINUOUS HORIZONTAL. SLOPE TO Sim
8 MATCH SLOPE OF ROOF DECK. 8
S688 S688
Sim
9
Sim S688
9
S688
SIGNED & SEALED 10.03.2022

Copyright (c) 2022 Praxis3, LLC

All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.

LINTEL (SEE WALL ELEVATIONS This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
AND LINTEL SCHEDULE) drawings.

Rev Date Comments


10.03.22 Permit / Bid Set
LINTEL (SEE WALL ELEVATIONS
GLASS AND LINTEL SCHEDULE)
(SEE ARCHITECTURAL DRAWINGS) VERTICAL WALL REINFORCEMENT CENTERED
IN MASONRY WALL. FILL ALL CELLS WITH
GROUT WHERE REINFORCING OCCURS. SEE
WALL ELEVATIONS, TYPICAL DETAILS AND
WALL SCHEDULE FOR SIZE AND LOCATION
OF REINFORCING.
GLASS
(SEE ARCHITECTURAL DRAWINGS)

LINTEL (SEE WALL ELEVATIONS


AND LINTEL SCHEDULE)

LINTEL (SEE WALL ELEVATIONS


AND LINTEL SCHEDULE)

VEHICLE DOOR VEHICLE DOOR


(SEE ARCHITECTURAL DRAWINGS) (SEE ARCHITECTURAL DRAWINGS)

1
Roof - Shop - Joist Bearing (no parapet) 2
Roof - Shop - Joist Parallel (no parapet) 3
Roof - Shop - Joist Bearing (no parapet at bumpout) 4
Roof - Shop - Joist Parallel (grid M1)
S607 3/4" = 1'-0" S607 3/4" = 1'-0" S607 3/4" = 1'-0" S607 3/4" = 1'-0"

M1.7
MG MSB M2 MF

Sim
2 Sim Sim
2 1 Sim
S688 1
S688 S688
S688
Mark W. Nannis, P.E.
Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel

All drawings, specifications, and other work product


of Mark W. Nannis, P.E. (henceforth referred to as "The
Engineer") for this project are instruments of service for
this project only and shall remain the property of The
Sim Engineer whether the project is complete or not. Reuse
Sim 10
4 of any of the instruments of service of The Engineer by
S688 the owner or extensions of this project without the written
Sim S688
5 permission of The Engineer shall be at the owner's risk
Sim and the owner agrees to defend, indemnify, and hold
S688 12 JOIST BEARING 21' - 8 1/2" harmless The Engineer from all claims, damages, and
S688 expenses including attorney's fees arising out of such
JOIST BEARING 21' - 4 5/8" unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
© 2022

Client:
Sim
9
S688
Automotive
Managment
9
Sim Services, Inc.
505 S. Flagler Dr., Suite 1400
S688
West Palm Beach, FL 33401

Project Number: 22008


Project Name:

Alliance Hyundai

11001 North Fwy


Fort Worth, TX 76177

LINTEL (SEE WALL ELEVATIONS


AND LINTEL SCHEDULE)

Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


VEHICLE DOOR
Wall Sections
(SEE ARCHITECTURAL DRAWINGS)

Sheet Number:

5
S607
Roof - Shop - Joist Bearing (parapet, grid MG)
3/4" = 1'-0"
6
S607
Roof - Shop - Joist Parallel (grid M2)
3/4" = 1'-0"
7
S607
Roof - Shop - Joist Bearing (parapet, grid MF)
3/4" = 1'-0"
8
S607
Roof - Shop - Joist Parallel (grid M1.7)
3/4" = 1'-0"
S607
ME R1 M3

PRAXIS3
R1 M3
13
Sim Sim S208
1 8 Sim Sim
S688 S207 2 2
S688 S688
13 100 Peachtree St NW 404-875-4500 tel
S208 Suite 1450 404-876-8884 fax
Atlanta, GA 30303 www.praxis3.com

Sim EXPANSION JOINT BETWEEN RAMP AND CMU


4
(SEE ARCHITECTURAL DRAWINGS)
S688 2"
Sim
JOIST BEARING 22' - 8 1/8" 12
S688 Sim
8
S207 Sim
12
S688

Sim
9
S688
Sim
9
S688 SIGNED & SEALED 10.03.2022

Copyright (c) 2022 Praxis3, LLC

All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.

5" This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.

Rev Date Comments


10.03.22 Permit / Bid Set

Sim
12
S688

Sim
9
S688

LINTEL (SEE WALL ELEVATIONS


AND LINTEL SCHEDULE)

VEHICLE DOOR
(SEE ARCHITECTURAL DRAWINGS)

1
Roof - Shop - Joist Bearing (parapet, grid ME) 3
Roof - Shop - Joist Parallel at Ramp (Grid M3) 4 Roof - Shop - Joist Parallel at Ramp and Express Drive
S608 3/4" = 1'-0" S608 3/4" = 1'-0" S608 3/4" = 1'-0"

R1 M3

ME.2
Sim
2 M4
S688
13
S208
2
Sim
2
Sim Mark W. Nannis, P.E.
S688 S688 Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel
JOIST BEARING 15' - 5 1/4" Sim
12 All drawings, specifications, and other work product
Sim S688 of Mark W. Nannis, P.E. (henceforth referred to as "The
5
Engineer") for this project are instruments of service for
S688 LINTEL (SEE WALL ELEVATIONS this project only and shall remain the property of The
Sim AND LINTEL SCHEDULE) Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by
8
the owner or extensions of this project without the written
S207 permission of The Engineer shall be at the owner's risk
and the owner agrees to defend, indemnify, and hold
MECHANICAL LOUVER harmless The Engineer from all claims, damages, and
Sim (SEE ARCHITECTURAL & expenses including attorney's fees arising out of such
EXPANSION JOINT BETWEEN RAMP AND CMU 12 MECHANICAL DRAWINGS) unauthorized reuse of The Engineer's instruments of
S688 service by the owner or others acting through the owner.
(SEE ARCHITECTURAL DRAWINGS) © 2022
3"
Client:

9
Sim Automotive
9
Sim
LINTEL (SEE WALL ELEVATIONS
S688
Managment
S688 AND LINTEL SCHEDULE)

IF BRIDGING ALIGNS WITH


Services, Inc.
505 S. Flagler Dr., Suite 1400
LOUVER, ATTACH BELOW LOUVER
VEHICLE DOOR AS SHOWN HERE West Palm Beach, FL 33401
(SEE ARCHITECTURAL DRAWINGS)
Project Number: 22008
Project Name:
Roof - Express Drive - Joist Bearing (high side) Roof - Express Drive - Joist Parallel
6
S608
7
S608
Alliance Hyundai
3/4" = 1'-0" 3/4" = 1'-0"

5"
ME.8
11001 North Fwy
Fort Worth, TX 76177

Sim
2
S688

Sim
5
S688
JOIST BEARING 14' - 9 3/8"

LINTEL (SEE WALL ELEVATIONS


AND LINTEL SCHEDULE)

VEHICLE DOOR
(SEE ARCHITECTURAL DRAWINGS) Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


Wall Sections
LINTEL (SEE WALL ELEVATIONS
AND LINTEL SCHEDULE)

VEHICLE DOOR
(SEE ARCHITECTURAL DRAWINGS)
Sheet Number:

5
S608
Roof - Shop - Joist Parallel at Ramp Landing (grid M3)
3/4" = 1'-0"
8
S608
Roof - Express Drive - Joist Bearing (low side)
3/4" = 1'-0"
S608
SEE PLAN FOR REINF.

PRAXIS3
(DISCONTINUE AT FLOOR JOINT)
1/2" Ø SMOOTH ROD x 2'-0" @ 1'-6" o.c.
(GREASE ONE END TO PREVENT BOND)

1" CLR.
SAWCUT OR TOOLED JOINT 1/8" AT EXPOSED FLOOR
WITH JOINT FILLER AND

1/4 "T"
SEALANT AT EXPOSED FLOORS
100 Peachtree St NW 404-875-4500 tel
Suite 1450 404-876-8884 fax

"T"
GRADE BEAMS ALWAYS POURS OVER THE TOP

1 1/2"
OF THE DRILLED PIERS. PLAN ELEVATION NOTED Atlanta, GA 30303 www.praxis3.com

SEE PLAN
FOR TOP OF DRILLED SHAFT IS TOP OF GRADE
BEAM. TOP OF DRILLED SHAFT IS TO BE POURED NOTE: ALL SAWCUT JOINTS ARE
MONOLITHICIALLY WITH THE GRADE BEAMS. TO BE CUT WITHIN 12 - 24 HOURS
OF SLAB ON GRADE POUR.

2
Typical Detail of Floor Joint (F.J.) 3
Typical Detail of Dummy Joint (D.J.)
DRILLED SHAFT - SEE PLANS. EXTEND S680 1" = 1'-0"
S680 1" = 1'-0"
REINFORCEMENT UP INTO GRADE BEAM
AND HOOK AT TOP.

BASEPLATE
THICKNESS
LESS THAN SLOPE TOP OF SLAB AWAY FROM
AT GRADE BEAMS 3/4"
1/4"
FOR WALL TYPE, SEE
FOUNDATION PLAN
BUILDING FACE. SEE ARCHITECT FOR
SLOPE AMOUNT AND EXTENTS.
BASEPLATE AND SECTION 5" EXTERIOR APRON SLAB REINFORCED
ELEVATION, WITH WELDED WIRE FABRIC 6x6-
THICKNESS BASE BASE PLATE SEE SCHEDULE SEE PLAN
LESS THAN PLATE W2.9xW2.9 IN FLAT SHEETS. (3000 PSI
1/4" CONCRTE)
3/4" THICKNESS ISOLATION JOINT TENSION LAP
5/16" REINFORCING (LAP WITH EXTERIOR GRADE/PAVING/CONCRETE
GREATER
BOTTOM WALL REINFORCING) SLAB. SEE CIVIL AND ARCHITECTURAL
BASE THAN 3/4" SIGNED & SEALED 10.03.2022
SEE SECTION FOR SIZE AND DRAWINGS.
PLATE NUMBER COLUMN OR WALL
THICKNESS FOOTING, SEE ARCH. Copyright (c) 2022 Praxis3, LLC
GREATER 5/16" NOTE: SEE ARCHITECT FOR JOINT
ISOLATION JOINT FOOTING All reports, plans, specifications, computer files, field data, notes and other documents
THAN 3/4" CLASS C LOCATION AND SPACING IN

SEE PLAN
and instruments prepared by Praxis3 shall retain all common law, statutory and other
ELEVATION, APRON SLAB. JOINTING SHALL

T
reserved rights, including copyright thereto.
TENSION LAP SEE PLAN NOT EXCEED A 2 TO 1 RATIO

2' - 0"
This drawing may not be reproduced in whole or in part without written permission of
BASED UPON DIMENISON OF

T
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
1/4" SLAB. drawings.

3" CLR

°
.00
Rev Date Comments

60
2
FINISH FLOOR SLAB
ELEVATION, 1 AT OPENINGS IN EXTERIOR WALL OF 10.03.22 Permit / Bid Set
BUILDING, THICKEN THE APRON SLAB

3" CLR
2"

SEE ARCH. DO NOT TRENCH OR PLACE


GROUT BED (5000 PSI)

GROUT BED (5000 PSI)


SEE ARCHITECT TO THE REQUIRED FROST DEPTH. SEE
T
1 1/2" NON SHRINK

1 1/2" NON SHRINK


PIPING AFTER COLUMN OR DESIGN CRITERIA.
FOR SIZE & WALL FOOTINGS ARE IN PLACE
(3) HOOPS IN THE TOP 5" 4000 PSI REINFORCEMENT OF
2' - 0"

GRADE BEAM, SEE


FOUNDATION PLAN 5
Typical Step in Footing 6
Typical Detail of Trenches Near Footings 7
Typical Detail at Apron Slab at Building Perimeter
S680 3/4" = 1'-0"
S680 1" = 1'-0"
S680 3/4" = 1'-0"
A A E.O.S., SEE PLAN
SEE FOUNDATION NOTES AND PLAN FOR DEPTH OF SHAFT

#3 HOOPS @ 12"o.c. MAX. G.C. COORD WITH CAR WASH DESIGNER FOR WHEN GRATING OCCURS
ROUGHEN (3) HOOPS IN THE TOP 5" 2' - 0" COORD. WITH ANY CONCRETE PROJECTIONS IN TRENCH. 2' - 0" COORD. WITH PROVIDE EMBED ANGLE WITH FOR ANY SLOPE AT
SURFACE MANUFACTURER 3/8" DIA. HEADED STUDS x 4" EXTERIOR SLAB, SEE
MANUFACTURER WHEN GRATING OCCURS PROVIDE EMBED
2" CL. LONG @ 24" o.c. MAX COORD. EXTERIOR SLAB SEE ARCHITECT.
ANGLE WITH 3/8" DIA. HEADED STUDS x 4" #4 @ 12" o.c
2" CL. EXACT BLOCK SIZE WITH THE CIVIL DRAWINGS.
LONG @ 24" o.c. MAX COORD. (1) #4 CONT.

4000 PSI
MAX. MANUF.

3' - 0"
#4 AT 18" o.c. MAX EXACT BLOCK SIZE WITH THE MANUF.
VERTICAL REINF. SEE
SCHEDULE + HK'S 3" CLR.

2'-0" MAX
VARIES
SEE FOUNDATION NOTES & PLAN FOR DEPTH OF SHAFT
#3 HOOPS @ 12"o.c. MAX.

6"

1' - 4"
6"

G.C. COORD. WITH


TRENCH.MANUF.
3'-0" MAX.
8" 8"

3"
CONT. PLASTIC #4 HORIZ. AT 12" o.c. MAX.
3000 PSI

SHAFT DIAMETER SEE SCHEDULE PROVIDE CORNER BARS AT


WATERSTOP.
48 x TIES DIAM. VERTICAL REINF. SEE TYPICAL. CORNERS. TYPICAL (4) SIDES.
#4 HORIZ. AT TOP AND BOTTOM OF
SCHEDULE + HK'S 3" CLR. ROUGHEN TURNDOWN AND AT 12" o.c. MAX.
SURFACE 6" (2) #5 CONT.
TYPICAL AT EACH FACE OF TRENCH CONT. PLASTIC WATERSTOP. 1' - 0"

10"

3" CL.
DRAIN. TYPICAL (4) SIDES.
#4 HORIZ. AT CORNERS
8" AND AT 8" o.c. #4 AT CORNERS & AT 8" o.c.

3" CL.
10"
SHAFT DIAMETER SEE SCHEDULE
°
60

.00

Typical Detail at Trench Drain Section at Catch Basin Typical Turndown (1'-4" x 1'-0")
.00

3000 PSI
60

8 9 10
°

S680 S680 S680


1' - 0"

3/4" = 1'-0" 3/4" = 1'-0" 3/4" = 1'-0"

INTERIOR SLAB ISOLATION JOINT SLAB ISOLATION JOINT AT CORNER SLAB ISOLATION JOINT AT EDGE
3"

SECTION A-A
SEE PLAN
EDGE OF SLAB
°
60

.00

BELL DIAMETER
.00

60
°

(1) #4 CONT.
+ 8" HOOKS
PROVIDE (2) #4 X 4'-0" COLUMN BASE PLATE AT CORNERS

2"

SEE PLAN
1' - 0"

SEE PLAN
TOP AT ISOLATION
EDGE OF SLAB
JOINT CORNERS
WHERE CONTROL OR
ISOLATION JOINT BY
"NOMAFLEX" OR
EQUIPMENT FRAME
COORDINATE FRAME DEPTH WITH
Mark W. Nannis, P.E.
4" . CONSTRUCTION JOINT EQUIPMENT MANUFACTURER
Texas Design Firm #21364
IN APPROVED EQUAL 1591 Riverside Drive
M IS NOT LOCATED AS

4"
SHOWN 1/2" Ø F1554 A36 ANCHOR BOLTS Gainesville, GA 30501

1' - 0"
MIN.
BELL DIAMETER x 6" LONG, (2) PER SIDE OF PIT 770-614-6114 tel
CONSTRUCTION OR 8" 3"
ISOLATION JOINT BY CONTROL JOINT W.W.F. SAME AS FLOOR SLAB
ISOLATION JOINT BY "NOMAFLEX" OR All drawings, specifications, and other work product
"NOMAFLEX" OR APPROVED EQUAL. of Mark W. Nannis, P.E. (henceforth referred to as "The

4" N.
PROVIDE (2) #4 X 4'-0" TOP

4" N.

M
Engineer") for this project are instruments of service for

M
APPROVED EQUAL.

6"
DETAIL OF DRILLED SHAFT DETAIL OF DRILLED SHAFT

I
I
AT ISOLATION JOINT this project only and shall remain the property of The

2"
COLUMN BASE PLATE CORNERS WHERE Engineer whether the project is complete or not. Reuse
COLUMN BASE PLATE

CLEAR
CONTROL OR of any of the instruments of service of The Engineer by
#4 DOWELS + 8" HOOKS
AT COLUMN AT GRADE BEAM the owner or extensions of this project without the written

3"
EDGE OF SLAB CONSTRUCTION JOINT IS AT 18" o.c. MAX.
CONTROL JOINT permission of The Engineer shall be at the owner's risk
NOT LOCATED AS SHOWN and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
expenses including attorney's fees arising out of such
1
Typical Steel Column Connection to Drilled Pier 11
Typical Detail of Slab Isolation Joints 12
Typical Detail at Quick Tread Pit unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
© 2022
S680 3/4" = 1'-0" S680 3/4" = 1'-0" S680 3/4" = 1'-0"
Client:
1#4 CONT. TOP AND
BOTTOM.
GALVANIZED CONT. ANGLE 2x2x3/8" W/
5/8" dia. HEADED STUDS x 4" LONG, 6"
FROM END AND @ 18" o.c. MAX.
Automotive
#4 DOWEL x 2'-0" LONG PLUS
9" HOOK. PROVIDE AT 18" COORDINATE WITH
SUPPLIER FOR EXACT
Managment
o.c. MAX.

W.W.F.
DIMENSIONS OF PIT, AND
FOR AMOUNT OF DROP. Services, Inc.

1/2"
505 S. Flagler Dr., Suite 1400
West Palm Beach, FL 33401
1/2" PROUD FROM

MANUFAC.
VERIFY W/
CONCRETE Project Number: 22008
2#5 CONT. Project Name:

Alliance Hyundai

6"
3"
8"
#4 DOWEL x 1'-4" LONG PLUS
1'-4" HOOK. PROVIDE AT 18" 2' - 0" W.W.F.
o.c. MAX. 11001 North Fwy
REINFORCE MASONRY WALLS PER Fort Worth, TX 76177
MASONRY WALL ELEVATIONS, WALL
SCHEDULE, AND TYPICAL DETAILS. BARS ARE IN SAME PLANE
16
Typical Section at Pit Drop
CENTER IN WALL. (MINIMUM AT ENDS INSIDE FACE OF WALL BEYOND.
OF WALLS, CORNERS, JAMBS OF
ALIGN SLAB WITH INT. FACE OF WALL
S680 3/4" = 1'-0"
OPENINGS, EACH SIDE OF CONTROL GROUT ALL CELLS SOLID UP OVERHEAD DOOR JAMB BEYOND
JOINTS, AND AT 4'-0" o.c. MAX.) TO BOND BEAM CONCRETE APRON SLAB TO POUR UP TO CONCRETE APRON SLAB TO POUR UP TO
SEE MIN. LAP SPLICE SCHED.

EDGE OF SLAB. SEE ARCHITECT EDGE OF SLAB. SEE ARCHITECT REINFORCE WALL AT ENDS OF AT TOP OF PARTITION PROVIDE A
CONT. BOND BEAM REINFORCED DRAWING FOR ELEVATION AND SLOPES PARTITIONS, CORNERS, JAMBS OF CONT. BOND BEAM REINFORCED HSS COLUMN SEE PLAN AND CHARGEPOINT EXPRESS 250
DRAWING FOR ELEVATION AND SLOPES
WITH (1) #5 CONT. OF SLAB. OPENINGS. MASONRY CONTROL JOINT WITH 2 #4 CONT. AND GROUTED ELEVATION AT DOORS ELECTRIC VEHICLE
SEE ARCH. OF SLAB.
LOCATIONS AND AT SPACING NOTED ON FULLY CHARGER (BY OTHERS)
L5X3X1/2 (LLH) GALVANIZED STEEL ANGLE. L3X3X1/2 (LLH) GALVANIZED STEEL ANGLE. SCHEDULE. NOT TO EXCEED 4'-0" o.c. MAX
PROVIDE RETURN ANGLES AT END. SEE PROVIDE RETURN ANGLES AT END. SEE
ARCH FOR EXACT LOCATION. ANCHOR TO FILL ALL CELLS WITH GROUT (6) 5/8" DIAMETER HEX HEAD
ARCH FOR EXACT LOCATION. ANCHOR TO ASTM F1554 GRADE 36
TURNDOWN WITH 1/2" DIAM HEADED WHERE REINFORCING OCCURS
TURNDOWN WITH 1/2" DIAM HEADED ANCHOR BOLTS (SEE

EMBEDEMENT
STUDS x 4" LONG, 6" FROM EACH END OF STUDS x 4" LONG, 6" FROM EACH END OF

9" MINIMUM
OPENING AND AT 2'-0" o.c. MAX. FILLET WELD ON (3) MANUFACTURER FOR FROST DEPTH
OPENING AND AT 2'-0" o.c. MAX. 2#5 CONT. MAXIMUM HEIGHT OF SIDES. BUTT WELD PLACEMENT PATTERN) (GC TO CONSULT
FOR TOP ELEVATION OF WELDED WIRE FABRIC IN FLAT SHEETS WALL SHALL NOT
WELDED WIRE FABRIC IN FLAT SHEETS ON FRONT FACE 3/16
GRADE BEAM, SEE PLAN. LOCAL JURISDICTION
"d"- SEE PLAN

EXCEED 14'-0" SEE CIVIL FOR AREA OR GEOTECHNICAL


1/2"

1/2"

1/2"

SURROUNDING BASE
1/2"

ENGINEER)
8" x 6" x 7/16" x 10" LONG
3"
SCHEDULED DEPTH

BUILDING SUBGRADE TO B W.W.F. GALVANIZED ANGLE AT EACH


E PREPARED IN POST WITH (4) - 3/4" DIAM Sheet Title:
2*d

CENTERLINE OF PANEL AND ACCORDANCE TO THE

RELEASED FOR CONSTRUCTION AND PERMIT


HEADED STUDS x 5" LONG.
45.

CONCRETE MOUNTING
Typical Details
GRADE BEAM. GEOTECHNICAL REPORT
45.
1' - 4"

(2) AT EACH LEG, 2" FROM


1' - 4"

2' - 0"
00°

TEMPLATE FOR ANCHORS


00°

WITH IMPROVEMENTS.
00°

(1) #5 CONT. EACH END OF ANGLE.


(1) #5 CONT. (BY OTHERS)
45.

1' - 0" MIN.


SCHEDULED WIDTH 3"

6"
6" CONT. VOID SPACE AS NOTED IN 2 #4 x2'-0" + STD HK
MINIMUM 28-DAY CONCRETE CLEAR
(Foundation)
2"
COMPRESSIVE
3"

THE GEOTECHNICAL REPORT AT ALL


3"

@ EACH JAMB
GRADE BEAMS. (2) #5 CONT. (2) #5 CONT. STRENGTH = 2,500 PSI
1' - 0" INSURE THAT #4 HOOK BAR
1' - 0" 1' - 0"

TOP & BOTTOM


FALLS WITHIN ANGLE (8) #4 EACH WAY TOP AND
FOR GRADE BEAM SIZE AND DRILLED SHAFT BEYOND. SEE PLAN (1) #4 CONT. HORIZ. 3' - 0" SQUARE
LOCATION TYPICAL. BOTTOM, A615 GRADE 60

3" CLEAR
REINFORCEMENT, SEE PLAN FOR SIZE AND SCHEDULE FOR NOTE: WHEN WALL EXCEEDS 14'-0", DISCONTINUE SLAB ON GRADE, AND EXTEND PROVIDE 1 #4 CONT. AS
AND SCHEDULES REINFORCEMENT. MASONRY DOWN TO ELEVATION [-2'-0"]. BEAR ON A 24" WIDE x18" GRADE BEAM. SHOWN ABOVE. MINIMUM SOIL BEARING CAPACITY = 1,500 PSF
REINFORCE WITH 4 #5 TOP CONT. PLUS HOOKS AT ENDS AND 4#6 BOTTOM. PROVIDE #3
HOOPS @ 16" MAX. GRADE BEAMS SHALL SPAN BETWEEN 18" Φ DRILLED PIERS AT 12' o.c. (TO BE VERIFIED BY A GEOTECHNICAL ENGINEER) Sheet Number:
Typical Detail at Base of Jamb Tube
13
S680
Typical Foundation Detail at CMU and Grade Beam
3/4" = 1'-0"
14
S680
Typical Turndown at High-Speed Door
3/4" = 1'-0"
15
S680
Typical Turndown at Coiling Door
3/4" = 1'-0"
17
S680
Typical Section at 8" or 12" Partition
3/4" = 1'-0"
18
S680
Column at O.H. Door
1" = 1'-0"
19
S680
Typical EV Charger Foundation
3/4" = 1'-0"
S680
FOR LH02 TO

PRAXIS3
1/8" 2" 3/16" 2" LH06. LH07 TO
FOR KCS
LH17 SHALL
JOISTS 1/8" 2" 3/16" 2" BE 1/4" THICK
WELD.
SEE PLAN FOR ROOF

ANGLE (D+1") x (B+2") x 1/2"


THICK x12" LONG 0 0 * INDICATED ON PLAN BY S.P. * 100 Peachtree St NW 404-875-4500 tel
B-L2 Suite 1450 404-876-8884 fax
C5x6.7 UP TO 3/16" BOLTS TO DEVELOP Atlanta, GA 30303 www.praxis3.com
1/4
10'-0" MAXIMUM THE REQUIRED SHEAR

"D"
"B"
SEE PLAN

"D"

"D"

"d" - 3"
C5x6.7 U.N.O. AROUND

"d"
SEE PLAN PERIPHERY OF UNIT AND "B""B"
.1/2" MAX @ 10'-0" MAXIMUM
5/8" DIAM. ROD OR ANGLE .1/2" MAX C5x6.7 U.N.O.
BOTTOM CHORD EXTENSIONS. C5x6.7 U.N.O.
WIND UPLIFT BRIDGING, (WELD AFTER ROOF DEAD LOAD IS ANGLE (D + 1") x (B + 1") 1/2" MAX
SEE SPECIFICATIONS IN PLACE) x1/2" x 12" LONG 1/4"
JOIST, SEE PLAN MAX.
BEAM DETAIL AT JOIST CLOSEST TO BEAM MIDSPAN
3/16" 3x3x5/16" ANGLE BOTH
JOIST, SEE PLAN SIDES OF WEB
2-1/2" DIAM. BOLTS @ EACH JOIST
WELD AFTER 1/8" 2" (@ COLUMN LINE ONLY, SEE SPEC.)
ERECTION IS SECTION "M1"
4
Typical Splice Point Detail
COMPLETED 1/8" 2" (ONE SIDE)
SECTION "M2"
PLATE TO S681 1" = 1'-0"
SEE PLAN FOR ROOF (BOTH SIDES)
BEAM
3/16" BEAR JOIST A MINIMUM OF 2-1/2" AT K NOTE : DUCT OPENINGS, SEE MECHANICAL. FOR SUPPORT OF DECK.
SERIES JOIST AND 4" AT LH JOIST ON BEAM. SEE "TYPICAL FRAMING AROUND OPENING" DETAIL SIGNED & SEALED 10.03.2022
OFFSET DECK ANGLE SUPPORT WHERE "A" "A" "A"
REQUIRED. Copyright (c) 2022 Praxis3, LLC

2 1/2x 2 1/2x 1/4" CONT. ANGLE "A" "A" "A" "A" "A" 2x2x1/4" ANGLE All reports, plans, specifications, computer files, field data, notes and other documents
WELDED TO TOP & and instruments prepared by Praxis3 shall retain all common law, statutory and other
3/16 3 @ 12

1" MIN
WELDED TO BEAM. WHERE LH JOIST OCCUR

"A"

"A"
reserved rights, including copyright thereto.
PROVIDE A 5x3x1/4" CONT. ANGLE. BOTTOM CHORD.
M2 This drawing may not be reproduced in whole or in part without written permission of
LOAD

"A"

"A"
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
MECHANICAL "A" "A" drawings.
SEE PLAN UNIT
1" 1" MECHANICAL Rev Date Comments

.10'-0"
MAX
SEE PLAN UNIT

"A"

"A"
"A" "A" "A" "A" "A"
10.03.22 Permit / Bid Set
5" MIN.
TYP.
M1

JOIST BOTTOM CHORD AFTER ROOF DEAD "A" "A" "A"


EXTENSIONS. WELD LOAD IS IN PLACE JOIST SPACING
AFTER ROOF DEAD LOAD 3/16"
6" .
IS IN PLACE.
3/16 PL THICKNESS COORDINATE "A" : INDICATES C5x6.7
WITH JOIST MANUF. x6 STEEL SEE PLAN. APPLICABLE TO BAR JOISTS THAT SUPPORT A
PLATE BETWEEN JOIST
SEE COLUMN SCHED. NOTE: FOR MECHANICAL UNIT CURB ATTACHMENT TO CONCENTRATED LOAD GREATER THAN 100 LBS.
BOTTOM CHORD ANGLES.
THAT IS NOT AT OR WITHIN 4” OF PANEL POINT ,
PROVIDE HOLE IN PLATE NOTE: WHERE DECK JOIST CHANGE DIRECTION OR, WHERE STRUCTURE AND TIE DOWN CONNECTION OF UNIT SEE PROVIDE FIELD INSTALLED WEB REINFORCEMENT. LOAD
(OSHA) JOIST FRAME TO BEAM AT OTHER THAN 90 DEGREES. MECHANICAL
COLUMN DETAIL

1
Typical Detail of Bar Joist Roof Construction 2
Typical Detail Where Joist Changes Direction 3
Typical Framing for Mechanical Units Detail 5 Typical Detail of Bar Joist Field Reinforcement at concentrated loads
S681 1" = 1'-0" S681 3/4" = 1'-0" S681 1" = 1'-0" S681 1" = 1'-0"

PLATE TO
FLANGE OF PLAN VIEW
COLUMN 3/16"

SEE
SCHED. SEE
AT BEAM SUSPENDED AT DIAGONAL 3/8" BUTT. L1 L1 SCHED.
FROM HANGER AT HANGER BRACE PLATE

(2) - 1/4" STIFFENER


PLATES (ONE ON EACH (2) - 3/8" STIFFENER PLATES
SIDE) (ONE ON EACH SIDE) TUBE SEE PLAN
COLUMN SIZE CAP PLATE
BEAM SUSPENDED BY W SECTION, PIPE, OR 3/16" TYP. AT WEB AND 3/16" W8 3/4"x14"x8-1/2"
A HANGER TUBE HANGER FLANGE OF TEE TO
FLANGE OF BEAM. W10 3/4"x16"x10-1/2"
3/16"
HSS 4x4 3/4"x10"x4-1/2"

W.P. 6" AT HSS 5x5 3/4"x11"x5-1/2"


3/16" OMIT WT WHERE BEAM
1/4" EA. END HSS 6.00 ROUND 3/4"x13"x7-1/2"
FRAMES IN AT COLUMN
HSS 6x6 3/4"x12"x6-1/2" DOUBLE CLIP ANGLE
W SECTION, PIPE, OR CONNECTION TO DEVELOP BEAM, SEE PLAN AND
HSS 8x8 3/4"x14"x8-1/2"
TUBE HANGER THE REQUIRED SHEAR. SCHEDULE BELOW
PLATE TO HSS 12"x3" 3/4"x12-1/2"x9"
TYPICAL AT
(2) - 3/8" STIFFENER PLATES HANGER
WTEE 3/16" 3/16" 3" at 12 HSS 12.75 ROUND 3/4"x14"x19"
SECTION Mark W. Nannis, P.E.
(ONE ON EACH SIDE) CONDITION 1/4" Texas Design Firm #21364
5/16" STIFFENER (ONE EACH SIDE) 1591 Riverside Drive
WT CUT FROM WF SHAPE CENTER STIFF. ON COLUMNS 6" TYP. MOMENT PLATE SCHEDULE Gainesville, GA 30501
TYPICAL AT BELOW EACH SIDE. CUT TO FIT AND SMALLER 3/16"
3/8" BUTT. BEAM SIZE TOP PLATE WIDTH AND THICKNESS L1 WELD 770-614-6114 tel
POST
CONDITION 1/4" PLATE
W6 x20 5.00" WIDE x 3/8" THICK 8" 5/16" All drawings, specifications, and other work product
(2) - 1/4" STIFFENER PLATES of Mark W. Nannis, P.E. (henceforth referred to as "The
(ONE ON EACH SIDE) W SECTION, PIPE, OR W SECTION, PIPE, OR 5" Engineer") for this project are instruments of service for
TUBE SEE PLAN W8 x10 3.50" WIDE x 5/16" THICK 3/16" this project only and shall remain the property of The
TUBE HANGER TUBE HANGER Engineer whether the project is complete or not. Reuse
3/16" W8 x18 5.00" WIDE x 1/2" THICK 7" 1/4" of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written
W8 x24 6.00" WIDE x 1/2" THICK 8" 5/16" permission of The Engineer shall be at the owner's risk
3/16" and the owner agrees to defend, indemnify, and hold
W TEE CUT TO FIT IN (4)-3/4" DIAM. A325 (4)-3/4" DIAM. 6.00" WIDE x 5/8" THICK harmless The Engineer from all claims, damages, and
W8 x28 9" 5/16"
WEB OF COLUMN x BOLTS A325 BOLTS expenses including attorney's fees arising out of such
SEE SCHEDULE SEE SCHEDULE unauthorized reuse of The Engineer's instruments of
DEPTH OF TUBE PLUS W8 x31 THRU W8 x48 7.50" WIDE x 3/4" THICK 13" 3/8" service by the owner or others acting through the owner.
4". © 2022
CHANNEL OR ANGLE, WT CUT TO FIT SAME SIZE AS 3/8" BUTT. PLATE. OMIT WHERE W10 x12 THRU W10 x19 3.50" WIDE x 5/8" THICK 7" 1/4"
SEE PLAN (4) - 3/8" STIFFENER PLATES W-SHAPE COLUMN ABOVE TUBE IS SAME DIMENSION AS 1/4" 1/4" Client:
(TWO ON EACH SIDE) EACH SIDE OF WEB. COLUMN. W10 x22 THRU W10 x30 5.00" WIDE x 3/4" THICK 10" 5/16"

W10 x33 THRU W10 x45 7.50" WIDE x 3/4" THICK 13" 3/8" Automotive
3.50" WIDE x 3/4" THICK 8"
1/4" W12 x14 THRU W12 x22
W12 x26 THRU W12 x35 9"
1/4"

3/8"
Managment
6.00" WIDE x 3/4" THICK

W14 x22 THRU W14 x26 4.50" WIDE x 3/4" THICK 8" 5/16" Services, Inc.
505 S. Flagler Dr., Suite 1400
W14 x30 THRU W14 x38 6.00" WIDE x 3/4" THICK 10" 3/8" West Palm Beach, FL 33401
TUBE SEE PLAN 9"
W16 x26 THRU W16 x31 5.00" WIDE x 5/8" THICK 5/16"
Project Number: 22008
W16 x36 THRU W16 x45 6.50" WIDE x 3/4" THICK 12" 3/8" Project Name:
W18 x35 THRU W18 x40 5.50" WIDE x 3/4" THICK 10" 3/8"
AT HANGER AT POST COLUMN AT POST COLUMN
1/4
NOTE: IF BOTTOM FLANGES ALIGN, PROVIDE FULL PENETRATION WELD OF BOTTOM FLANGES TOGETHER.
Alliance Hyundai
6 Typical Beam Stiffener at Steel Hangers or Steel Posts (U.N.O.) 7
Typical Connection of Tube Steel to Steel Columns 8
Typical Cap Plate Detail 9
Typical Beam-through-Beam Moment Connection
S681 3/4" = 1'-0"
S681 1" = 1'-0"
S681 1" = 1'-0"
S681 3/4" = 1'-0"

11001 North Fwy


STEEL JOIST OR BEAM SEE PLAN. Fort Worth, TX 76177
JOIST OR BEAM SEE PLAN
"A" "A"

FOR ANGLE SIZES,


SEE TYP. FRAMING 3"
AROUND ROOF Typical
TOP UNIT
3/16"

"A"
MEMBER SPACING
UP TO 6'-0" MAX

Typical 3 Sides
1/8" 1-1/2"
2 1/2" MIN.

"A"

"A"

SHEAR CONNECTION TO SHEAR CONNECTION TO


DEVELOP REQUIRED DEVELOP REQUIRED
1.5 X "t"

PLATE
SHEAR SHEAR HANGER, SEE C5x6.7 @
W SECTION W SECTION "MEP" DRAWINGS. 5'-0" o.c. "A"
MAX.
1/2"

1/2"
4 SIDES NOTE : DO NOT SUSPEND PIPING FROM ONE JOIST. (2 JOIST MINIMUM) 1/2" 7" 1/2" 5/16" END PLATE 8" WIDE AND 12" LONG.
ANCHOR PLATE TO CONCRETE OR Sheet Title:
NOTE : WHEN PIPES ARE RUNNING PERPENDICULAR TO JOIST MASONRY WALL WITH (2) - 3/4" Ø EPOXY

RELEASED FOR CONSTRUCTION AND PERMIT


SUSPEND PIPE FROM EACH JOIST. MINIMUM PIPE SIZE 6" DIAM. "A" "A"
ANCHORS WITH 4" MIN. EMBEDMENT.
Typical Details
"t"

2" 2"
NOTE : WHEN PIPES RUN PARALLEL TO JOIST AND IS WITHIN 2 FEET OF STEEL JOIST OR BEAM SEE PLAN. PROVIDE A 1-1/2" WIDE BLOCKOUT IN TOP

4"
A JOIST PROVIDE ADDITIONAL AX BRIDGING BETWEEN THE OF TUBE TO ALLOW TO SLIP TUBE OVER
ADJACENT JOIST ON EITHER SIDE OF PIPE AT A SPACING TO ANCHORS FROM BELOW DURING

NOTE :
MATCH THE HANGERS BUT NOT TO EXCEED 8'-0" o.c. MAX.

WHEN PIPES RUN PARALLEL TO JOIST, DO NOT PLACE


NOTE "A" : INDICATES ANGLE 4" x 3" x 1/4", LONG LEG DOWN.
WHERE BEAM SPACING IS 6'-1" AND GREATER,
CONCRETE OR
MASONRY WALL
ERECTION. WHEN FIELD WELDING TUBE
TO END PLATE, PROVIDE A COVER PLATE
TO CONCEAL ERECTION HOLE. WHERE
(Steel)

7"
PROVIDE A W6 x 9 FOR THE "A" MEMBERS
MULTIPLE PIPES BETWEEN (2) JOIST. ANCHORING INTO MASONRY, GROUT
SPANNING BETWEEN THE JOIST OR BEAMS.
WHERE CHANNEL SUPPORTS OR OTHER MISC. HANGERS CELL(S) SOLID WHERE ANCHOR IS
NOTE : NOTE : GENERAL CONTRACTOR COORDINATE ROOF INSTALLED.
SQUARE HSS COLUMN SQUARE HSS COLUMN OCCUR, AND THEY DO NOT OCCUR AT A JOIST TOP CHORD OPENING REQUIREMENTS WITH MECHANICAL,
PANEL POINT, PROVIDE JOIST STIFFENING ANGLE PER TYPICAL

1/2"
ELECTRICAL AND PLUMBING PLANS.
DETAIL. (2X2X1/4" ANGLE) Sheet Number:
NOTE : PROVIDE AT ALL ROOF DRAIN LOCATIONS
3/16"
10
S681
Typical Moment Connection of Steel Beam to Column
1" = 1'-0"
11
S681
Typical Support of Suspended Roof Pipes Parallel to Joist
3/4" = 1'-0"
12
S681
Typical Framing Around Roof Opening Detail
1" = 1'-0"
13
S681
Typical HSS Connection to Wall
1 1/2" = 1'-0"
S681
3/16" 3"
FOR JOIST SIZE, REFER
PRAXIS3
CLOSURE ANGLE. TO ROOF FRAMING PLAN. 100 Peachtree St NW 404-875-4500 tel
6" CLOSURE ANGLE IN
ANCHORED TO ELEVATION AT SPLICE Suite 1450 404-876-8884 fax
MASONRY WALL AND LAST ANCHOR INTO LOCATION.
WELDED TO EACH A Atlanta, GA 30303 www.praxis3.com
MASONRY WALL BEYOND
ROOF SUPPORT. AT LOAD BEARING
MASONRY CONDITION.

1/2"
BEVEL VERTICAL AND
SLOPING DECK SUPPORT HORIZONTAL LEG OF ANGLE HSS 4" x 4" x 1/4" TO SPAN OVER EACH
ANGLE VERTICAL LEG FOR FULL PENETRATION VERTICAL POST. SEE ARCHITECT FOR TOP
DOWN AND ANCHORED WELD. OF TUBE ELEVATION.
TO MASONRY.
HSS 4" x 4" x 3/8" SCREEN POST AT 6'-0" o.c.
MAX. PROVIDE A 1/4" CAP PLATE AT TOP
TYPICAL CLOSURE ANGLE SPLICE AND BOTTOM OF POST.
CLOSURE ANGLE CONNECTION AT (FULL-PENETRATION WELD OPTION) HSS 4" x 4" x 1/4" TO SPAN BETWEEN EACH
MASONRY WALL AND CORNER VERTICAL POST. SEE ARCHITECT FOR TOP
OF TUBE ELEVATION.

1/4 3-1/2 CONT. BOND BEAM REINFORCED WITH (2)


STEEL PLATE 8" LONG x #4 CONT. HORIZONTAL. SLOPE BOND
ROOF CLOSURE ANGLE LEG 1/4 3-1/2 BEAM WITH SLOPE OF ROOF DECK. CUT
3/16 2" MINUS 1" x ROOF CLOSURE BLOCK BELOW AS REQUIRED. SIGNED & SEALED 10.03.2022
ANGLE THICKNESS + 1/8" . BACK-TO-BACK ANGLE FASTENED TO A 12" x 9" x 5/16"" PLATE WITH (4) - 5/8" Ø
THE BOTTOM CHORD OF JOIST W/ EXPANSION ANCHORS WITH 4" MINIMUM Copyright (c) 2022 Praxis3, LLC

4" 4" (2)-1/2" Ø BOLT. SEE MANUF. NOTES EMBEDMENT INTO A VERTICALLY All reports, plans, specifications, computer files, field data, notes and other documents
CLOSURE ANGLE. RAISE CLOSURE ANGLE IN
FOR ANGLE SIZE. REINFORCED CMU CELL. GROUT CELL and instruments prepared by Praxis3 shall retain all common law, statutory and other
ELEVATION AT CORNER TO ELEVATION AT SPLICE reserved rights, including copyright thereto.
LOCATION. SOLID.
BEAR ON PERPENDICULAR This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
ANGLE WELD.

2 1/4"
VERTICAL WALL REINFORCEMENT drawings.

6"
(2) 1/2" Ø BOLT FASTENED TO CENTERED IN MASONRY WALL. FILL ALL
THE BOTTOM CHORD OF JOIST. CELLS WITH GROUT WHERE Rev Date Comments
REFER TO MANUFACTURER'S REINFORCING OCCURS. SEE WALL
ELEVATIONS, TYPICAL DETAILS AND WALL 10.03.22 Permit / Bid Set
NOTE FOR ANGLE SIZE.
SCHEDULE FOR SIZE AND LOCATION OF
1/4 3-1/2 REINFORCING.
STEEL PLATE 8" LONG x
EXTEND ANGLE TO END OF ROOF CLOSURE ANGLE LEG 12" x 9" x 5/16"" PLATE WITH (4) - 5/8"
1/4 3-1/2
ROOF CLOSURE ANGLE.

2"
MINUS 1" x ROOF CLOSURE

6"
9"
EXPANSION ANCHORS WITH 4" MINIMUM
ANGLE THICKNESS + 1/8" . EMBEDMENT INTO A VERTICALLY
REFER TO PLAN
REINFORCED CMU CELL. GROUT CELL

5"
FOR JOIST SIZE AND SPACING SOLID.
CLOSURE ANGLE CONNECTION AT TYPICAL CLOSURE ANGLE SPLICE

2"
(SPLICE PLATE OPTION) SECTION A-A 2" 8" 2"
STEEL FRAME AND CORNER

1
Typical Detail of Deck Closure Angle at Corner 2
Typical Angle Splice Detail 3
Typical Fan Support Detail 4
Typical Section at Mechanical Screen Post at CMU
S682 1 1/2" = 1'-0" S682 1 1/2" = 1'-0" S682 3/4" = 1'-0" S682 3/4" = 1'-0"

HSS 4" x 4" x 1/4" TO SPAN OVER EACH


VERTICAL POST. SEE ARCHITECT FOR HSS 4" x 4" x 1/4" TO SPAN OVER EACH
TOP OF TUBE ELEVATION. VERTICAL POST. SEE ARCHITECT FOR
TOP OF TUBE ELEVATION.

HSS 4" x 4" x 1/4" TO SPAN OVER EACH HSS 4" x 4" x 1/4" TO SPAN OVER EACH
TYPICAL AT TO VERTICAL POST. SEE ARCHITECT FOR VERTICAL POST. SEE ARCHITECT FOR
AND BOTT. TOP OF TUBE ELEVATION. TOP OF TUBE ELEVATION.
3/16" TUBE TYPICAL AT TO
AND BOTT.
3/16" TUBE
HSS 4" x 4" x 3/8" SCREEN POST AT HSS 4" x 4" x 3/8" SCREEN POST AT EACH
EACH ROOF JOIST. PROVIDE A 1/4" ROOF JOIST. PROVIDE A 1/4" CAP PLATE
CAP PLATE AT TOP AND BOTTOM OF AT TOP AND BOTTOM OF POST. HSS 4" x 4" x 3/8" SCREEN POST AT HSS 4" x 4" x 3/8" SCREEN POST AT
6'-0" o.c. MAX. PROVIDE A 1/4" CAP TYPICAL AT TO EACH ROOF JOIST. PROVIDE A 1/4" TYPICAL AT TO
POST. AND BOTT.
PLATE AT TOP AND BOTTOM OF POST. CAP PLATE AT TOP AND BOTTOM OF AND BOTT.
3/16" TUBE POST. 3/16" TUBE
HSS 4" x 4" x 1/4" TO SPAN BETWEEN
EACH VERTICAL POST. SEE HSS 4" x 4" x 1/4" TO SPAN BETWEEN
ARCHITECT FOR TOP OF TUBE EACH VERTICAL POST. SEE
ELEVATION. ARCHITECT FOR TOP OF TUBE
ELEVATION. HSS 4" x 4" x 1/4" TO SPAN BETWEEN HSS 4" x 4" x 1/4" TO SPAN BETWEEN
EACH VERTICAL POST. SEE EACH VERTICAL POST. SEE
ARCHITECT FOR TOP OF TUBE ARCHITECT FOR TOP OF TUBE
ELEVATION. ANGLE 4" x 4" x 3/8" CLIP. WELD TO ELEVATION.
ANGLE 4" x 4" x 3/8"x 6"LONG CLIP. 1/4 ANGLE 4" x 4" x 3/8"x 6"LONG CLIP. TOP OF JOIST ON BOTH SIDES ALL
1/4
WELD TO TOP OF BEAM ON BOTH WELD TO TOP OF BEAM ON BOTH AROUND WITH AN 3/16" FILLET WELD.
ANGLE 4" x 4" x 3/8" CLIP. WELD TO
1/4 SIDES ALL AROUND WITH AN 3/16" 1/4 SIDES ALL AROUND WITH AN 3/16" TYPICAL AT TOP AND BOTTOM OF
TOP OF JOIST ON BOTH SIDES ALL
FILLET WELD. TYPICAL AT TOP AND FILLET WELD. TYPICAL AT TOP AND JOIST.
AROUND WITH AN 3/16" FILLET WELD.
BOTTOM OF JOIST. BOTTOM OF JOIST. TYPICAL AT TOP AND BOTTOM OF
JOIST.

Mark W. Nannis, P.E.


Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel

ANGLE 2" x 2" x 3/16" TO TIE JOIST All drawings, specifications, and other work product
1/4 TOGETHER AT POST LOCATION. of Mark W. Nannis, P.E. (henceforth referred to as "The
Engineer") for this project are instruments of service for
1/4 this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
ANGLE 2-1/2" x 2-1/2" x 3/16" AT JOIST 2" x 2" x 3/16" "X" TYPE BRIDGING ANGLE 2" x 2" WHERE LOAD DOES NOT 2" x 2" x 3/16" "X" TYPE BRIDGING ANGLE 2" x 2" WHERE LOAD DOES NOT of any of the instruments of service of The Engineer by
6" WIDE x 1/2" BOTTOM PLATE. FIELD ANGLE 2-1/2" x 2-1/2" x 3/16" AT JOIST 6" WIDE x 1/2" BOTTOM PLATE. FIELD LOCATED AT EACH SCREEN POST. BETWEEN EACH JOIST AT ROOF OCCUR AT A JOIST PANEL POINT. BETWEEN EACH JOIST AT ROOF OCCUR AT A JOIST PANEL POINT. the owner or extensions of this project without the written
WELD TO BOTTOM FLANGE OF BEAM LOCATED AT EACH SCREEN POST. permission of The Engineer shall be at the owner's risk
WELD TO BOTTOM FLANGE OF BEAM SCREEN. SCREEN. and the owner agrees to defend, indemnify, and hold
WITH A 3/16" FILLET WELD ALL AROUND. WITH A 3/16" FILLET WELD ALL AROUND. harmless The Engineer from all claims, damages, and
expenses including attorney's fees arising out of such

5 Typical Section at Mechanical Screen (Parallel Condition) 6 Typical Section at Mechanical Screen (Perpendicular Condition) 7 Typical Section at Mechanical Screen (Parallel Condition) 8 Typical Section at Mechanical Screen (Perpendicular Condition) unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
© 2022
S682 3/4" = 1'-0"
S682 3/4" = 1'-0"
S682 3/4" = 1'-0"
S682 3/4" = 1'-0" Client:

Automotive
USE C5 x 6.7 FOR 6" STUD OR
C3 x 4.1 FOR 3-5/8" STUD 1/4" CAP PLATE
Managment
C8x11.5 AT EACH FACE OF TUBE.
(DO NOT WELD TO COLUMN)
C8x11.5 AT EACH FACE OF TUBE.
(DO NOT WELD TO COLUMN) 3/8" EMBED PLATE HSS 3" x 3" x 1/4" POST AT 5'-0" o.c.
Services, Inc.
WITH (2)- 1/2" Ø STUD CENTER IN METAL STUD 505 S. Flagler Dr., Suite 1400
WITH MIN. EMBED PARTITION. West Palm Beach, FL 33401
3-1/2"

SEE ARCH FOR Project Number: 22008


ELEVATION 3ft Project Name:
(2) - 3/4" THRU BOLTS (2) - 3/4" THRU BOLTS MAX.

SEE PLAN
IN A 1-1/2" VERT. SLOTTED
HOLES
IN A 1-1/2" VERT. SLOTTED
HOLES
1 1/2"
3"
Alliance Hyundai
1 1/2"
3/16 2@6" 3/16 2@6"

2-1/2"x2-1/2"x3/16" ANGLE SKEW BACK TO


TYP @ TOP & BOTT. TYP @ TOP & BOTT. CLOSEST FLOOR BEAM. OMIT ANGLE
FLANGE L3X3X1/4 AT COLUMN LOCATION FLANGE WHEN BEAM DEPTH IS LESS THAN OR
3/16 0 3/16 0
EQUAL TO GIRDER DEPTH
11001 North Fwy
THICKEN SLAB AT

4"
Fort Worth, TX 76177
EACH POST. 1'-0"
x 1'-0". 1' - 0"

9
Typical Roof Bracing of Wind Column (Beam) 10
Typical Section At Kneewall Partition
S682 1" = 1'-0" S682 3/4" = 1'-0"

C8x11.5 AT EACH FACE OF TUBE.


(DO NOT WELD TO COLUMN)
C8x11.5 AT EACH FACE OF TUBE.
(DO NOT WELD TO COLUMN)

(2) - 3/4" THROUGH BOLTS


IN A 1-1/2" VERT. SLOTTED (2) - 3/4" THRU BOLTS
HOLES IN A 1-1/2" VERT. SLOTTED Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


HOLES

3/16 2@6" ADDITIONAL Typical Details


"AX" BRIDGING

TYP @ TOP & BOTT.


AT COLUMN. 3/16 2@6"
(Steel)
FLANGE 3/16
TYP @ TOP & BOTT.
FLANGE 2-1/2"x2-1/2"x3/16"
3/16 ANGLE SKEW BACK
TO CLOSEST ROOF JOIST.
Sheet Number:
12
Typical Roof Bracing of Wind Column (Column)
S682 1" = 1'-0"
S682
PRAXIS3
TYP. AT EACH
OUTRIGGER TO
3/16" TUBE BEAM
PIPE COLUMN
TUBE OUTRIGGER CUT TO FIT
RADIUS OF COLUMN. FIELD WELD 1"
TO COLUMN ALL AROUND WITH A 1"
PROVIDE A 1/4" END PLATE TYPICAL AT RADIUS TO FORM 100 Peachtree St NW 404-875-4500 tel
1/4" FILLET WELD. OUTRIGGER
FRAMES OVER TOP OF TUBE END OF TUBE BEAM AT OUTRIGGER. CONTINUOUS WELD Suite 1450 404-876-8884 fax
BEAM. TYPICAL. Atlanta, GA 30303 www.praxis3.com

TUBE BEAM SEE PLAN FOR SIZE AND


ELEVATION. TUBE FRAMES TO UNDER
SIDE OF OUTRIGGER ABOVE FRAMING TO
PLAN
COLUMN. WHERE TUBE BEAMS 2" 3"
INTERSECT AT THE CORNER, FIELD WELD 3" 2"
ALL AROUND WITH A 3/16" FILLET WELD.

TYP.
1/4"

NOTE:
1"

PROVIDE A 1/4" END PLATE TYPICAL AT IF TUBE CONNECTION IS


TYP. AT SEATED
END OF TUBE BEAM AT CORNER. EXPOSED TREAT AS AESS
ANGLE 3/16"
AND GROUND SMOOTH.

CENTERLINE OF COLUMN

SIGNED & SEALED 10.03.2022

PLAN AT OUTRIGGER AT CORNER. ALTERNATIVE Copyright (c) 2022 Praxis3, LLC


CENTERLINE OF BEAM.
ELEVATION All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.

SECTION AT OUTRIGGER. This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.
TYP. AT EACH ERECTOR NOTE: TYP. TOP &
0 0
OUTRIGGER TO BOTTOM
3/16"
ONLY (1) END OF EACH WELD OF Rev Date Comments
TUBE BEAM
TUBE OUTRIGGER CUT TO FIT TUBE IS SPLICED FLANG 10.03.22 Permit / Bid Set
PIPE COLUMN
RADIUS OF COLUMN. FIELD WELD
TO COLUMN ALL AROUND WITH A
1/4" FILLET WELD. OUTRIGGER RAD. OUTLOOKER, SHOP WELD
FRAMES OVER TOP OF TUBE TYP.
TUBE BEAM SEE PLAN FOR SIZE AND TO COLUMN 1/4"
BEAM.
ELEVATION. TUBE FRAMES TO UNDER
SIDE OF OUTRIGGER ABOVE FRAMING TO
COLUMN. WHERE OUTRIGGER IS TOO 3/4" CAP PLATE
3/8" END PLATE TS BEAM SEE PLAN
NARROW, PROVIDE A SPLICE WITHIN 1'-0"
TO CENTERLINE OF COLUMN. FIELD WELD
ALL AROUND WITH A BUTT WELD.
GROUND SMOOTH IF EXPOSED.
1"

P.J.P. Typ. 3/4" BOTTOM PLATES CUT


PROVIDE A 1/4" END PLATE TYPICAL AT TO RADIUS. PLATES TO BE
END OF TUBE BEAM AT OUTRIGGER. NOTE: WIDTH OF BEAM WITH FULL
TYPICAL. PENETRATION WELDS TO
IF TUBE CONNECTION IS COLUMNS
EXPOSED TREAT AS AESS
AND GROUND SMOOTH.
PLAN AT OUTRIGGER AT INTERIOR COLUMN
1 Plan at Tube Beam Connection to Column where Beam Extends Past Column 2
Typical Connection of Tube Strut to Pipe Column 3 Typical Moment Connection of Steel Beam to Pipe Column
S683 1 1/2" = 1'-0" S683 1" = 1'-0" S683 1 1/2" = 1'-0"

#4 SUPPORT BARS SHEAR CONNECTORS, #4 SUPPORT BARS


#4 @ 12"o.c. WHERE NO TOP #4 @ 12"o.c. WHERE NO TOP #4 @ 12"o.c. COMPOSITE FLOOR BEAM
SEE PLAN FOR NUMBER
STEEL OCCURS IN STEEL OCCURS IN
SEE PLAN OTHER DIRECTION OTHER DIRECTION
(TYPICAL) #4 @ 12"o.c. TEMP.
3/4" CLEAR 3/4" CLEAR 3/4" CLEAR TYPICAL TOP BAR REINF. AT COMP.
5-1/2" MIN. FLOOR.
1' - 0"
COMPOSITE FLOOR BEAM
MAX.
#4 CONT. 1' - 0" 1' - 0"

10'-6" MAX. AT 3" COMPOSITE FLOOR DECK AND 6-1/2" SLAB


(TYPICAL)

DIRECTION OF FLOOR DECK SPAN


2" MIN. BEARING

AT 2" COMPOSITE FLOOR DECK AND 5-1/2" SLAB


WHERE SHEET IS #4 CONT.
NOT CONTINUOUS (TYPICAL) 5-1/2" x "W"-1/2" x 3/16" CONT. BENT 5-1/2" x"W"-1/2" x 3/16" CONT. BENT
W8 x10

1' - 0"
1/4" BENT PLATE 1/4" BENT PLATE PROVIDE 3/16" BENT
PLATE PLATE
Mark W. Nannis, P.E.
(TYPICAL) (TYPICAL) PLATE AT SLAB EDGE, Texas Design Firm #21364
I.H.C. AT 2'-0"o.c. WITH I.H.C. AT 2'-0"o.c. WITH THUS : 1591 Riverside Drive

5 1/2"
#4 SUPPORT BAR (CHAIR #4 SUPPORT BAR (CHAIR
TO FIT CORRUGATION) TO FIT CORRUGATION) 6-1/2" SLAB AT 3" 3/16" 3@12" 3/16" 3@12" Gainesville, GA 30501
COMPOSITE FLOOR

9'-3" MAXIMUM
770-614-6114 tel

W8 x10

W8 x10
1 #4 TOP x 1'-6" AT DECK.
EACH CORNER. BEAM OR
All drawings, specifications, and other work product
GIRDER, of Mark W. Nannis, P.E. (henceforth referred to as "The
TYPICAL EXTERIOR SPAN TYPICAL EXTERIOR SPAN SEE PLAN Engineer") for this project are instruments of service for
this project only and shall remain the property of The
1/2" 1/2"
Engineer whether the project is complete or not. Reuse
EXTERIOR CONTINUOUS INTERIOR DISCONTINUOUS INTERIOR 1 #4 BOTTOM ON W8 x10 3/16" 3@12" of any of the instruments of service of The Engineer by
#4 @ 12"o.c. TOP EACH SIDE OF CUT 1/2" U.N.O. the owner or extensions of this project without the written
DECK AT OPENING. permission of The Engineer shall be at the owner's risk
#4 @ 12"o.c. TEMP. and the owner agrees to defend, indemnify, and hold
3/4" CLEAR "W" SEE PLAN harmless The Engineer from all claims, damages, and
NOTE : CONTRACTOR MUST MAKE ALLOWANCE FOR ADDITIONAL CONCRETE. "W" SEE PLAN expenses including attorney's fees arising out of such
THICKNESS REQUIRED ABOVE THE 5 1/2" MINIMUM THICKNESS SHOWN unauthorized reuse of The Engineer's instruments of
DUE TO DEFLECTION OF DECK, BEAMS, GIRDERS, AND SLOPE OF DECK. service by the owner or others acting through the owner.
COMPOSITE FLOOR BEAM © 2022
2" 2"

NOTE : W
WHEN PLACING CONCRETE, DO NOT PUMP CONCRETE ONTO DECK
MIDSPAN. DO NOT LET CONCRETE STAND OVER 6" TO 7". PLACE CONNECTION OF METAL CONNECTION OF METAL Client:
CONCRETE OVER BEAMS AND SPREAD TO ADJACENT DECK MIDSPAN.
PLAN VIEW AT OPENING IN COMPOSITE FLOOR STUD TO ALLOW FOR 3/4" STUD TO ALLOW FOR 3/4"

SHEAR CONNECTORS,
SEE PLAN FOR NUMBER
COMPOSITE FLOOR BEAM VERT. MOVEMENT VERT. MOVEMENT
Automotive
Typical Detail at Opening in Composite Floor Typical Detail at Opening in Composite Floor Managment
Typical Composite Floor & Slab Detail (Less than 1'-0" Square) (1'-0" Square or Larger) Typical Detail at Stair and Elevator Opening
5 6 7 8 Services, Inc.
S683 1/8" = 1'-0"
S683 1/2" = 1'-0"
S683 1/2" = 1'-0"
S683 1" = 1'-0" 505 S. Flagler Dr., Suite 1400
West Palm Beach, FL 33401

Project Number: 22008


Project Name:

Alliance Hyundai

11001 North Fwy


Fort Worth, TX 76177

Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


Typical Details
(Steel)

Sheet Number:

S683
VERTICAL STUD AT
SPACING.
(2) #10-16 SCREW AT STUD VERTICAL STUD AT
STEEL BEAM SEE PLAN
PRAXIS3
ALLOWABLE DEFLECTION
(2) #10-16 SCREW AT STUD
SPACING. SPACING. SPACING. (2) - 0.157 DIAM. P.D.F.'S AT

ALLOWABLE DEFLECTION
100 Peachtree St NW 404-875-4500 tel
EACH STUD SPACING.
ALL TRACKS TO BE 1-1/4" PROVIDE 3/4" FROM Suite 1450 404-876-8884 fax
1-1/2" METAL VERTICAL FACE OF CLIP. Atlanta, GA 30303 www.praxis3.com
ALL TRACKS TO BE 1-1/4" FLANGE AND 43 MILS MIN.
3/4"
ROOF DECK. (1) #10-16 SCREW
FLANGE AND 43 MILS MIN. BETWEEN TRACKS AT 16"

3/4"
DO NOT FASTEN STEEL BEAM SEE PLAN
o.c. MAX. STUD OR DRYWALL
TOP CHORD OF JOIST OR TO TOP TRACK. CLIP BY METAL STUD
BEAM. SEE PLAN AND DESIGNER. MINIMUM SIZE
CAP CHANNEL WITH CONT. (2) - 0.157 DIAM. P.D.F.'S AT IS 2" x 2" x 14 GAUGE.
SECTION. TRACK. ATTACH TRACKS EACH STUD SPACING.
TOGETHER AT 16" o.c. MAX.
(4) #10-16 SCREW AT STUD

ALLOWABLE DEFLECTION
SPACING THROUGH CLIP
AND STUD.

2 1/2"
C7 x 9.8 CONT. TO SPAN SLOTTED TRACK WITH

2 1/2"
ACROSS TO JOIST AND (2) - 0.157 DIAM P.D.F'S 1-1/2" VERTICAL SLOTTED

2"
3/4"
BEAM. FIELD WELD TO THROUGH TRACK AND HOLES AT 1" o.c. IN EACH
TOP FLANGE OF JOIST AND STEEL CHANNEL (2) - 0.157 DIAM P.D.F'S FLANGE. MINIMUM STUD
BEAM AT BOTH FLANGES. STEEL CHANNEL AT 4'-0" THROUGH TRACK AND GAUGE IS 60 MILS.
o.c. MAX. SEE SECTION. STEEL CHANNEL
(2) #10-16 SCREW AT STUD HORIZONTAL STUD AT
(2) #10-16 SCREW AT STUD SPACING THROUGH (2) #10-16 SCREW AT STUD SPACING.
SPACING THROUGH VERTICAL SLOT. SPACING THROUGH
SLOTTED TRACK WITH

2 1/2"
VERTICAL SLOT. VERTICAL SLOT.
1-1/2" VERTICAL SLOTTED
(2) #10-16 SCREW AT STUD HOLES AT 1" o.c. IN EACH (2) #10-16 SCREW AT STUD SLOTTED TRACK WITH
1-1/2" VERTICAL SLOTTED SIGNED & SEALED 10.03.2022
SPACING THROUGH FLANGE. MINIMUM STUD SPACING THROUGH
METAL ROOF DECK GAUGE IS 60 MILS. METAL ROOF DECK HOLES AT 1" o.c. IN EACH
Copyright (c) 2022 Praxis3, LLC
DISCONTINUE AT EACH FLANGE. MINIMUM STUD
VERTICAL STUD AT INTERSECTING JOIST OR VERTICAL STUD AT GAUGE IS 60 MILS. VERTICAL STUD AT All reports, plans, specifications, computer files, field data, notes and other documents

SPACING. BEAM. SPACING. SPACING. and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.

This drawing may not be reproduced in whole or in part without written permission of

1 Typical Metal Stud Attachment to Steel Deck (deck parallel) 2 Typical Metal Stud Attachment to Steel Deck (deck perpendicular) 3 Typical Metal Stud Slip Attachment to Bottom of Beam 4 Typical Metal Stud Attachment to Bottom of Beam Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.

S684 3" = 1'-0"


S684 3" = 1'-0"
S684 3" = 1'-0"
S684 3" = 1'-0" Rev Date Comments
10.03.22 Permit / Bid Set

EXTERIOR FACE OF METAL


STUD
VERTICAL STUD AT EXTERIOR FACE OF METAL
SPACING. STUD
INSIDE FACE OF METAL STUD INSIDE FACE OF METAL STUD
(2) #10-16 SCREW AT STUD
SPACING. VERTICAL STUD AT SEE SECTION
(1) #10-16 SCREW SEE SECTION
SPACING. EDGE OF STEEL JOIST EDGE OF STEEL JOIST
BETWEEN TRACKS AT 16"
o.c. MAX. (2) #10-16 SCREW AT STUD EDGE OF STEEL ANGLE OR
EDGE OF STEEL ANGLE OR 1/2" 1/2"
SPACING. BENT PLATE. BENT PLATE.
(1) #10-16 SCREW ROOF CLOSURE ANGLE. 4" x 3" x ROOF CLOSURE ANGLE. 4" x 3" x 1/4"
1/2" 1/2"
BETWEEN TRACKS AT 16" 1/4" CONT. LONG LEG VERTICAL. CONT. LONG LEG VERTICAL.
CAP CHANNEL WITH CONT. o.c. MAX.
TRACK. ATTACH TRACKS
1/2" TOGETHER AT 16" o.c. MAX.
METAL STUD FASTENER BY CONNECTION SHALL ALLOW
METAL STUD DESIGNER. FOR 1" VERTICAL LIVE LOAD
CAP CHANNEL WITH CONT. 3/16" 3/16"
MINIMUM (2) 0.157 DIAM. MOVEMENT.
TRACK. ATTACH TRACKS P.D.F'S AT EACH CLIP ANGLE.
1/2" TOGETHER AT 16" o.c. MAX. CENTER IN WIDTH OF CLIP. ROOF DECK 1-1/2" WIDE RIB. SEE PLAN
ROOF DECK 1-1/2" WIDE RIB. SEE
MAINTAIN MINIMUM OF 1/2" PLAN AND SCHEDULE. HOLD EDGE AND SCHEDULE. HOLD EDGE OF DECK
(2) #10-16 SCREW AT STUD EDGE DISTANCE. OF DECK 1/2" FROM INTERIOR 1/2" FROM INTERIOR FACE OF CLOSURE
CONT. STEEL ANGLE 3" x 3" SPACING THROUGH METAL ANGLE.
x 3/16" FIELD WELD TO FACE OF CLOSURE ANGLE.
DECK METAL STUD CLIP
TOP OF EACH JOIST WITH METAL STUD CLIP
A 3/16" FILLET WELD. CONNECTION BY METAL STUD CONNECTION BY METAL STUD
3/4" (2) #10-16 SCREW AT STUD DESIGNER. MINIMUM SIZE DESIGNER. CONNECTION
ALL TRACKS TO BE 1-1/4" CONT. STEEL ANGLE 3" x 3" SPACING THROUGH METAL SHALL DEVELOP THE HORIZ.
x 3/16" SHOP WELD TO 1-1/2" x 1-1/2" x 4" LONG (50KSI
FLANGE AND 43 MILS MIN. DECK STEEL 14 GAUGE MIN.) REACTION FOR THE OUT OF
BEAM FLANGE WITH A 3/16" PLANE BENDING FOR STUD
FILLET WELD ON BOTH WALL BASED UPON THE
SIDES, 2" at 12" o.c. MAX. JOIST OR TUBE OUTRIGGER JOIST OR TUBE OUTRIGGER
ALL TRACKS TO BE 1-1/4" METAL STUD FASTENER BY COMPONENTS IN CLADDING
BEARING ON STEEL BEAM. BEARING ON STEEL BEAM.
FLANGE AND 43 MILS MIN. METAL STUD DESIGNER. TABLE.
SEE PLAN. SEE PLAN.
MINIMUM (4) - #10-16 SCREWS.
EDGE OF STEEL DECK EXTERIOR METAL STUDS AT
EXTERIOR METAL STUDS AT
16" o.c. MAX. SEE COLD 16" o.c. MAX. SEE COLD
FORMED STEEL NOTES. FORMED STEEL NOTES.

5 Typical Metal Stud Attachment to Steel Deck Edge (parallel) 6 Typical Metal Stud Attachment to Steel Deck Edge (perpendicular) 7 Typical Roof Closure Angle Connection to Joist Seat (Fix Clip) 8 Typical Roof Closure Angle Connection to Joist Seat (Slip Clip)
S684 3" = 1'-0" S684 3" = 1'-0" S684 1 1/2" = 1'-0" S684 1 1/2" = 1'-0"

Mark W. Nannis, P.E.


Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel

ROOF CLOSURE ANGLE. 4" x 3" x 1/4" All drawings, specifications, and other work product
ROOF CLOSURE ANGLE. 4" x 3" x 1/4" SEE SECTION CONT. LONG LEG VERTICAL. UNLESS of Mark W. Nannis, P.E. (henceforth referred to as "The
SEE SECTION SEE SECTION SEE SECTION CONT. LONG LEG VERTICAL. UNLESS NOTED OTHERWISE Engineer") for this project are instruments of service for
NOTED OTHERWISE this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
ROOF CLOSURE ANGLE. 4" x 3" x 1/4" ROOF CLOSURE ANGLE. 4" x 3" x 1/4" 1/2" of any of the instruments of service of The Engineer by
1/2" CONT. LONG LEG VERTICAL. 1/2" CONT. LONG LEG VERTICAL. UNLESS 1/2" 3/16 the owner or extensions of this project without the written
UNLESS NOTED OTHERWISE NOTED OTHERWISE 3/16 permission of The Engineer shall be at the owner's risk
and the owner agrees to defend, indemnify, and hold
3/16" harmless The Engineer from all claims, damages, and
3/16" expenses including attorney's fees arising out of such
3/16 2" at 12 3/16 2" at 12
unauthorized reuse of The Engineer's instruments of
METAL STUD CLIP CONNECTION SHALL ALLOW CONNECTION SHALL ALLOW CONNECT DECK TO ANGLE AT BEAM service by the owner or others acting through the owner.
3/16" 2" at 12 3/16" 2" at 12 METAL STUD FASTENER BY CONNECT DECK TO ANGLE AT BEAM
CONNECTION BY METAL STUD FOR 1" VERTICAL LIVE LOAD FOR 1" VERTICAL LIVE LOAD IN ADDITION ROOF CLOSURE ANGLE. © 2022
METAL STUD DESIGNER. IN ADDITION ROOF CLOSURE ANGLE.
DESIGNER. MINIMUM SIZE MOVEMENT. MOVEMENT.
MINIMUM (2) 0.157 DIAM. Client:
1-1/2" x 1-1/2" x 4" LONG (50KSI P.D.F'S AT EACH CLIP ANGLE.
STEEL 14 GAUGE MIN.) CENTER IN WIDTH OF CLIP.
MAINTAIN MINIMUM OF 1/2"
EDGE DISTANCE. 3/16 2 at 12
3/16 2 at 12 Automotive
METAL STUD CLIP CONNECTION
BY METAL STUD DESIGNER.
METAL STUD CLIP METAL STUD CLIP
3/16" 2 at 12 METAL STUD CLIP
CONNECTION BY METAL STUD
3/16" 2 at 12
Managment
CONNECTION BY METAL STUD
CONNECTION SHALL DEVELOP
THE HORIZ. REACTION FOR THE
DESIGNER. CONNECTION
SHALL DEVELOP THE HORIZ.
CONNECTION BY METAL STUD
DESIGNER. MINIMUM SIZE
DESIGNER. CONNECTION
SHALL DEVELOP THE HORIZ. Services, Inc.
OUT OF PLANE BENDING FOR REACTION FOR THE OUT OF
1-1/2" x 1-1/2" x 4" LONG (50KSI REACTION FOR THE OUT OF 505 S. Flagler Dr., Suite 1400
STUD WALL BASED UPON THE STEEL) PLANE BENDING FOR STUD
PLANE BENDING FOR STUD 1/2" West Palm Beach, FL 33401
COMPONENTS IN CLADDING WALL BASED UPON THE WALL BASED UPON THE
TABLE. COMPONENTS IN CLADDING COMPONENTS IN CLADDING
METAL STUD FASTENER BY 1/2" ANGLE 2-1/2" x 2-1/2" x 1/4" CUT Project Number: 22008
TABLE. ANGLE 2-1/2" x 2-1/2" x 1/4" CUT TABLE.
METAL STUD DESIGNER. TO FIT BETWEEN TUBE
MINIMUM (4) - #10-16 SCREWS. TO FIT BETWEEN TUBE OUTRIGGERS. WHERE A 5" DEEP Project Name:
METAL STUD FASTENER BY OUTRIGGERS. WHERE A 5" DEEP EXTERIOR METAL STUDS AT OUTRIGGER OCCURS, PROVIDE
EXTERIOR METAL STUDS AT
METAL STUD DESIGNER.
MINIMUM (4) - #10-16 SCREWS. 16" o.c. MAX. SEE COLD
FORMED STEEL NOTES.
OUTRIGGER OCCURS, PROVIDE
A 5" x 3" x 1/4" ANGLE INSTEAD.
16" o.c. MAX. SEE COLD
FORMED STEEL NOTES.
A 5" x 3" x 1/4" ANGLE INSTEAD.
Alliance Hyundai
EXTERIOR METAL STUDS AT EXTERIOR METAL STUDS AT
16" o.c. MAX. SEE COLD 16" o.c. MAX. SEE COLD
FORMED STEEL NOTES. FORMED STEEL NOTES.

9 Typical Roof Closure Angle Connection to Steel Beam (Fix Clip) 10 Typical Roof Closure Angle Connection to Steel Beam (Slip Clip) 11 Typical Roof Closure Angle Connection to Steel Outrigger (Fix Clip) 12 Typical Roof Closure Angle Connection to Steel Outrigger (Slip Clip) 11001 North Fwy
Fort Worth, TX 76177
S684 1 1/2" = 1'-0"
S684 1 1/2" = 1'-0"
S684 1 1/2" = 1'-0"
S684 1 1/2" = 1'-0"

SEE SECTION
METAL STUD FASTENER BY
METAL STUD DESIGNER.
STEEL CHANNEL, SEE CLOSURE ANGLE. 4" x 3" x 1/4"
MINIMUM (2) 0.157 DIAM.
SECTION AND OR PLAN. 1/2" CONT. LONG LEG VERTICAL.
P.D.F'S AT EACH CLIP ANGLE.
SEE SECTION UNLESS NOTED OTHERWISE
VERTICAL STUD AT CENTER IN WIDTH OF CLIP.
SPACING. METAL STUD FASTENER BY MAINTAIN MINIMUM OF 1/2"
CAP CHANNEL WITH CONT. 1/2"
METAL STUD DESIGNER. CLOSURE ANGLE. 4" x 3" x 1/4" EDGE DISTANCE.
TRACK. ATTACH TRACK TO MINIMUM (2) 0.157 DIAM.
CONT. TRACK. ATTACH CONT. LONG LEG VERTICAL. 3/16 2" at 12
CHANNEL WITH (1) - 0.157 P.D.F'S AT EACH CLIP ANGLE.
TRACK TO TUBE WITH (2) - UNLESS NOTED OTHERWISE CONNECTION SHALL ALLOW
DIAM. P.D.F.'S at 16" o.c. AT CENTER IN WIDTH OF CLIP.
0.157 DIAM. P.D.F.'S at 16" EACH FLANGE. MAINTAIN MINIMUM OF 1/2" FOR 1" VERTICAL LIVE LOAD 3/16" 2" at 12
2 1/2" o.c. AT EACH FLANGE. EDGE DISTANCE. MOVEMENT.
MIN. 3/16 2" at 12
(1) #10-16 SCREW AT EACH 2 1/2" METAL STUD CLIP
VERTICAL STUD THROUGH MIN.
CONNECTION BY METAL STUD 3/16" 2" at 12 METAL STUD CLIP Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


FLANGE. (1) #10-16 SCREW AT EACH DESIGNER. MINIMUM SIZE CONNECTION BY METAL STUD
VERTICAL STUD THROUGH
FLANGE.
1-1/2" x 1-1/2" x 4" LONG (50KSI
STEEL)
DESIGNER. CONNECTION
SHALL DEVELOP THE HORIZ.
REACTION FOR THE OUT OF
Typical Details
(Steel)
(2) #10-16 SCREW AT STUD METAL STUD FASTENER BY PLANE BENDING FOR STUD
STEEL TUBE, SEE SECTION SPACING. METAL STUD DESIGNER. WALL BASED UPON THE
AND OR PLAN. MINIMUM (4) - #10-16 SCREWS. COMPONENTS IN CLADDING
ALL TRACHS TO BE 1-1/4" TABLE.
FLANGE AND 43 MILS MIN. EXTERIOR METAL STUDS AT
TRACKS ARE A MINIMUM 16" o.c. MAX. SEE COLD EXTERIOR METAL STUDS AT
1-1/4" FLANGE AND FORMED STEEL NOTES. 16" o.c. MAX. SEE COLD
MINIMUM 43 MILS. VERTICAL STUD AT
SPACING. FORMED STEEL NOTES.
Sheet Number:

13
S684
Typical Metal Stud Attachment to Steel Tube
3" = 1'-0"
14
S684
Typical Metal Stud Attachment to Steel Channel
3" = 1'-0"
15
S684
Typical Metal Stud Attachment to Steel Tube (Fix Clip)
1 1/2" = 1'-0"
16
S684
Typical Metal Stud Attachment to Steel Tube (Slip Clip)
1 1/2" = 1'-0"
S684
WIDE FLANGE BEAM OR TUBE
AT FLOOR FRAMING.
12" CMU WALL. FILL CELL WITH
GROUT WHERE ANCHOR IS TO
OCCUR.
WIDE FLANGE BEAM OR TUBE
AT FLOOR FRAMING.
12" CMU WALL. FILL CELL WITH
GROUT WHERE ANCHOR IS TO
OCCUR.
PRAXIS3
100 Peachtree St NW 404-875-4500 tel
Suite 1450 404-876-8884 fax
8" CMU WALL. FILL CELL WITH
GROUT WHERE ANCHOR IS TO Atlanta, GA 30303 www.praxis3.com
OCCUR.

8" CMU WALL. FILL CELL WITH


GROUT WHERE ANCHOR IS TO
OCCUR.
12" x 16" CONT. BOND BEAM
REINFORCED WITH (2) #4 CONT.
BOTTOM AND 2 #4 CONT. TOP
8" x 16" CONT. BOND BEAM DISCONTINUE AT EACH BEAM 12" x 16" CONT. BOND BEAM
8" x 16" CONT. BOND BEAM REINFORCED WITH (2) #4 BEARING. THIS BOND BEAM IS IN REINFORCED WITH (2) #4 CONT.
REINFORCED WITH (2) #4 CONT. BOTTOM CONT. AND 2 #4 TOP ADDITION TO THE ONE BELOW BOTTOM AND 2 #4 CONT. TOP
BOTTOM AND 2 #4 CONT. TOP CONT. THE FLOOR BEAM BEARING. DISCONTINUE AT EACH BEAM
DISCONTINUE AT EACH BEAM BEARING. THIS BOND BEAM IS IN
BEARING. THIS BOND BEAM IS IN ADDITION TO THE ONE BELOW THE
ADDITION TO THE ONE BELOW FLOOR BEAM BEARING.
THE FLOOR BEAM BEARING. VERTICAL WALL REINFORCEMENT
VERTICAL WALL REINFORCEMENT ANGLE 6" x 4" x 3/8" CONTINUOUS.
CENTERED IN MASONRY WALL. FILL
VERTICAL WALL REINFORCEMENT CENTERED IN MASONRY WALL. FILL ALL ANCHOR TO BOND BEAM WITH A 3/4"
ALL CELLS WITH GROUT WHERE
CENTERED IN MASONRY WALL. FILL ALL CELLS WITH GROUT WHERE DIAM. EXPANSION ANCHOR 1'-0" FROM ANGLE 6" x 4" x 3/8" CONTININUOUS.
REINFORCING OCCURS. SEE WALL
CELLS WITH GROUT WHERE REINFORCING OCCURS. SEE WALL EACH END AND AT 2'-0" o.c. MAX. VERTICAL WALL REINFORCEMENT DISCONTINUE AT EACH INTERSECTING
ELEVATIONS, TYPICAL DETAILS AND
REINFORCING OCCURS. SEE WALL ELEVATIONS, TYPICAL DETAILS AND WALL PROVIDE 4" MIN. EMBEDMENT ANGLE 6" x 4" x 3/8" CONTINUOUS. CENTERED IN MASONRY WALL. FILL FLOOR BEAM. ANCHOR TO BOND
WALL SCHEDULE FOR SIZE AND
ELEVATIONS, TYPICAL DETAILS AND WALL SCHEDULE FOR SIZE AND LOCATION OF DISCONTINUE AT EACH INTERSECTING ALL CELLS WITH GROUT WHERE BEAM WITH A 3/4" DIAM. EXPANSION SIGNED & SEALED 10.03.2022
LOCATION OF REINFORCING.
SCHEDULE FOR SIZE AND LOCATION OF REINFORCING. FLOOR BEAM. ANCHOR TO BOND REINFORCING OCCURS. SEE WALL ANCHOR 1'-0" FROM EACH END AND AT
REINFORCING. BEAM WITH A 3/4" DIAM. EXPANSION ELEVATIONS, TYPICAL DETAILS AND 2'-0" o.c. MAX. Copyright (c) 2022 Praxis3, LLC

ANCHOR 1'-0" FROM EACH END AND AT WALL SCHEDULE FOR SIZE AND All reports, plans, specifications, computer files, field data, notes and other documents
ANGLE 6" x 4" x 3/8" CONT. 2'-0" o.c. MAX. LOCATION OF REINFORCING. and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.
DISCONTINUE AT EACH INTERSECTING
FLOOR BEAM. ANCHOR TO BOND This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
BEAM WITH A 3/4" DIAM. EXPANSION drawings.
ANCHOR 1'-0" FROM EACH END AND AT
2'-0" o.c. MAX.
Rev Date Comments
10.03.22 Permit / Bid Set

1 Typical Framed Floor Closure Angle at 8" CMU (deck parallel) 2 Typical Framed Floor Closure Angle at 8" CMU (deck perpendicular) 3 Typical Framed Floor Closure Angle at 12" CMU (deck parallel) 4 Typical Framed Floor Closure Angle at 12" CMU (deck parallel)
S685 3" = 1'-0" S685 3" = 1'-0" S685 3" = 1'-0" S685 3" = 1'-0"

INSIDE FACE OF METAL STUD


INSIDE FACE OF METAL STUD EDGE OF STEEL ANGLE
SEE SECTION
EDGE OF STEEL ANGLE SEE SECTION OR BENT PLATE
OR BENT PLATE EXTERIOR FACE OF METAL EDGE OF STEEL ANGLE
SEE SECTION
STUD OR BENT PLATE
EDGE OF STEEL ANGLE OR 1/2"
FLOOR CLOSURE ANGLE. 5-1/2" "d" FLOOR CLOSURE ANGLE. 5-1/2"
EDGE OF STEEL ANGLE OR FLOOR CLOSURE ANGLE. 5-1/2" BENT PLATE. VERTICAL LEG x "d-1/2" HORIZ. LEG x 1/4" VERTICAL LEG x "d-1/2" HORIZ. LEG x 1/4"
BENT PLATE. VERTICAL LEG x "d-1/2" HORIZ. LEG x 1/4" CONT. BENT PLATE. CONT. BENT PLATE.
EDGE OF STEEL ANGLE OR
CONT. BENT PLATE. BENT PLATE.
METAL STUD FASTENER BY
METAL STUD FASTENER BY 3/16 3" at 12 3/16 3" at 12 SEE PLAN SEE PLAN FOR # OF 3/4"
METAL STUD DESIGNER. 1/2" BENT PLATE BENT PLATE
MINIMUM (2) 0.157 DIAM. 3/16 3" at 12 METAL STUD DESIGNER. DIAM.HEADED STUDS. IF NO
1/2" BENT PLATE 3/16" 3" at 12 TO BEAM TO BEAM 1" MIN.
P.D.F'S AT EACH CLIP ANGLE. MINIMUM (2) 0.157 DIAM. 3/16" 3" at 12 NUMBER IS INDICATED,
3/16" 3" at 12 TO BEAM
CENTER IN WIDTH OF CLIP. P.D.F'S AT EACH CLIP ANGLE. PROVIDE AT 12" o.c. MAX.
MAINTAIN MINIMUM OF 1/2" CENTER IN WIDTH OF CLIP. 5/8"

SCHEDULE
EDGE DISTANCE. DO NOT MAINTAIN MINIMUM OF 1/2"
EDGE DISTANCE.

SEE
INSTALL UNTIL FLOOR IS
POURED.
CONNECTION SHALL ALLOW
METAL STUD CLIP FOR 1" VERTICAL LIVE LOAD
CONNECTION BY METAL STUD MOVEMENT. DO NOT INSTALL 1/4" BENT PLATE, STEEL COMPOSITTE
UNTIL FLOOR SLAB HAS BEEN COMPOSITE FLOOR REINFORCEMENT.
DESIGNER. MINIMUM SIZE UNLESS NOTED DECK, SEE SCHEDULE
POURED. SEE TYPICAL DETAIL. SEE TYPICAL
1-1/2" x 1-1/2" x 4" LONG (50KSI OTHERWISE
COMPOSITE FLOOR REINFORCEMENT. DETAIL FOR ORIENTATION AND
STEEL 14 GAUGE MIN.) COMPOSITE FLOOR REINFORCEMENT. METAL STUD CLIP SEE TYPICAL DETAIL. SEE TYPICAL CLEARANCES.
SEE TYPICAL DETAIL. SEE TYPICAL CONNECTION BY METAL STUD DETAIL FOR ORIENTATION AND
METAL STUD FASTENER BY DETAIL FOR ORIENTATION AND DESIGNER. CONNECTION CLEARANCES. DO NOT FASTEN STUD OR FLOOR DECK 2" GALVANIZED 3/16" 2"at12
METAL STUD DESIGNER. CLEARANCES. SHALL DEVELOP THE HORIZ. DRYWALL TO TOP TRACK. COMPOSITE FLOOR DECK SEE
MINIMUM (4) - #10-16 SCREWS. REACTION FOR THE OUT OF PLAN AND SCHEDULE. FOR
FLOOR DECK 2" GALVANIZED FLOOR DECK 2" GALVANIZED ORIENTATION, SEE PLAN.
PLANE BENDING FOR STUD EXTERIOR METAL STUDS AT
COMPOSITE FLOOR DECK SEE PLAN COMPOSITE FLOOR DECK SEE PLAN
EXTERIOR METAL STUDS AT WALL BASED UPON THE 16" o.c. MAX. SEE COLD
AND SCHEDULE. FOR ORIENTATION, SEE AND SCHEDULE. FOR ORIENTATION, SEE STEEL BEAM, SEE PLAN
16" o.c. MAX. SEE COLD COMPONENTS IN CLADDING FORMED STEEL NOTES. FLOOR BEAM AT SPANDREL
PLAN. PLAN.
FORMED STEEL NOTES. TABLE.
SLOTTED TRACK WITH 1-1/2"
(2) #10-16 SCREW AT STUD VERTICAL SLOTTED HOLES AT 1" o.c.
FLOOR BEAM AT SPANDREL FLOOR BEAM AT SPACING THROUGH
SPANDREL IN EACH FLANGE. MINIMUM STUD
EXTERIOR METAL STUDS AT VERTICAL SLOT. GAUGE IS 60 MILS.
16" o.c. MAX. SEE COLD (2) - 0.157 DIAM. P.D.F.'S AT
FORMED STEEL NOTES. EACH STUD SPACING.

5 Typical Metal Stud Attachment to Framed Floor Closure Angle (Fix Clip) 6 Typical Metal Stud Attachment to Framed Floor Closure Angle (Slip Clip) 7 Typical Metal Stud Attachment to Framed Floor Closure Angle (Slip Clip) 8
Typical Composite Floor Edge Detail Mark W. Nannis, P.E.
Texas Design Firm #21364
S685 1 1/2" = 1'-0"
S685 1 1/2" = 1'-0"
S685 1 1/2" = 1'-0"
S685 1 1/2" = 1'-0" 1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel

All drawings, specifications, and other work product


of Mark W. Nannis, P.E. (henceforth referred to as "The
Engineer") for this project are instruments of service for
this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk
and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
expenses including attorney's fees arising out of such
unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
© 2022

Client:

Automotive
Managment
Services, Inc.
505 S. Flagler Dr., Suite 1400
West Palm Beach, FL 33401

Project Number: 22008


Project Name:

Alliance Hyundai

8"

3/8" Ø HOOKED ANCHOR BOLT


COUNTERSUNK AT 2'-8" o.c. MAX. 11001 North Fwy
WITH 3" MIN. EMBEDMENT. Fort Worth, TX 76177
CLEAR
1 1/2"

ARCHITECT
SEE

CURB CONCRETE SAME MIX AS


COMPOSITE SLAB

#3 AT 12" o.c. MAX. WITH


STANDARD HOOK
2 1/2"

PVC DRAIN THROUGH CURB


(SEE ARCHITECTURAL
DRAWINGS FOR LOCATIONS)

ROUGHEN CONCRETE SURFACE


AT CURB AND PROVIDE
WATERSTOP
Sheet Title:
WIDE FLANGE BEAM

RELEASED FOR CONSTRUCTION AND PERMIT


(SEE PLAN)
Typical Details
(Steel)

Sheet Number:

9
S685
Typical Concrete Curb at Composite Slab
1 1/2" = 1'-0"
S685
G.C.: VERIFY ANCHOR BOLT

PRAXIS3
PATTERN WILL BE IN #3 HOOPS STRUCTURAL
STEEL CAGE
MAX. AREA OF FIXTURE COLUMN
3" CLR. TYP. AT
4 SQUARE FEET
HSS10 3/16"
6 #5 VERT HSS 10X4X1/4 HSS 10X4X1/4
+ HK'S

COORDINATE WITH MANUF. 100 Peachtree St NW 404-875-4500 tel

4"
8" CONT BOND BEAM SEE ELECTRICAL DWGS FOR
ALL OTHER NOTES AND Suite 1450 404-876-8884 fax
REINF. W/ (2)-#4 CONT. FRAME ANCHOR TO BE
COORD.WITH MANUF. REQUIREMENTS ARCH. ARCH. Atlanta, GA 30303 www.praxis3.com
BENT 45 DEGREES DOWNWARD
COLUMN COLUMN
REFER TO FOUNDATION (3) #6 BARS TOP. EXTEND
EIFS - SEE PROVIDE VERTICAL MASONRY PLAN FOR SLAB REINF. 2'-0" PAST LIFT INSERT. POLE, BASE PLATE & ANCHORS ANCHORS FOR BASE PLATE
ARCHITECTURAL CONTROL JOINTS IN WALL. PROVIDE ON ALL SIDES. LIGHT POLE MANUF. MUST ALWAYS FALL WITHIN
DRAWINGS PROVIDE AT CORNERS AND CEILING,
CAGED REINF.
MIDLENGTH OF WALLS NOT TO SEE ARCH.
EXCEED 25 FT ON CENTER.
PLAN AT BASE

H = 27' - 6" MAX HEIGHT


FILL ALL CELLS WITH
GROUT FULL HEIGHT

1' - 6"
OF WALL. JOINT REINFORCEMENT AT 16" o.c. 2'-0" DIAM.
MAX.
4
Hyundai Slanted Column Connection at Top
S686
8' - 0"

1" = 1'-0"
MAX

1 1/2"
(3) #6 BARS BOTTOM.

2"
5"
8" CMU WALL REINFORCED WITH (1) EXTEND 2'-0" PAST LIFT
#5 VERTICAL AT 32" o.c. MAX. INSERT. PROVIDE ON ALL 3 #3 HOOPS IN TOP 5"
CENTER BAR IN WALL. SIDES. 3" CLEAR BOTTOM 5 STRUCTURAL
COLUMN

OR 6" WHERE NOTED,


BARS ARE IN THE SAME PLANE. 6 #5 VERTICAL PLUS HOOKS GRAVEL BED
ARCH. COLUMN ARCH. (SEE ARCHITECTURAL DRAWINGS)
8" CONT BOND BEAM

SEE ELEC. DWGS


2'-6" MAX
COLUMN

VARIES
LIFT UNIT & SIGNED & SEALED 02.16.2024
REINF. W/ (2)-#4 ARCH. ISOLATION JOINT
CONTAINER
CONT. COLUMNS 1/4" Copyright (c) 2023 Praxis3, LLC

All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
FILL ALL CELLS WITH
SEE CIVIL DRAWINGS FOR SLAB AT 14"X14"X3/4" BASE PLATE reserved rights, including copyright thereto.
GROUT FULL HEIGHT GRADE
OF WALL. ENCLOSURE. 6" MINIMUM REINF. CLEAN PEA This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
WITH FLAT SHEETS OF W.W.F.
VARIES

GRAVEL FILL (4) 3/4" Ø EXPANSION ANCHORS


drawings.
MAX.
6"

WITH 6" EMBEDMENT


W.W.F. (TYPICAL AT ARCHICTECTURAL Rev Date Comments
COLUMNS) 10.03.2022 Permit / Bid Set
54 02.16.2024 Foundation Coor.
1-1/2" GROUT BED
2' - 0"

.6'-0" DEPTH
DOWEL SAME SIZE AND
SPACING AS VERT. WALL
REINF. #4 TOP BAR PLUS HOOKS AT

DEPTH
EACH END AT 8" o.c. MAX.
3000 psi
CONCRETE

3"
1' - 6"

PREPARE SUBGRADE AT LIGHT


3" 3" POLE FOUNDATION AS NOTED IN 3" 3"
THE GEOTECHNICAL REPORT
(4) #5 CONT. TOP FOR THE BUILDING STRUCTURE.
3"

AND BOTTOM. SEE SCHEDULE FOR FOOTING


3' - 9" #4 AT 8" o.c. MAX.
SIZE AND REINFORCING

1
Typical Detail of Dumpster Enclosure 2
Typical Detail of In-Ground Lift 3
Typical Detail of Light Pole Base 5
Hyundai Slanted Column Connection at Footing
S686 3/4" = 1'-0"
S686 3/4" = 1'-0"
S686 3/4" = 1'-0"
S686 1" = 1'-0"

5
5
STRUCTURAL
COLUMN

ARCH. COLUMN ARCH.


COLUMN 14"X14"X3/4" BASE PLATE
ATTACH SLIP TRACK TO STRUCTURE
WITH (2) 0.145" DIAM. PDF's AT EACH ARCH. (4) 3/4" Ø EXPANSION ANCHORS
STUD AND (4) 0.145"DIAM. @ EACH JAMB COLUMNS WITH 3" EMBEDMENT
1/4"
(TYPICAL AT ARCHICTECTURAL
DEEP LEG RUNNER TRACK MEMBER COLUMNS)
SIZE AS REQUIRED PER DESIGN
1-1/2" GROUT BED
FO DEF
GA 1/2" ECT
R
P T VE ION

3"
O

TYP. WALL
L

AL TIC
LO AL
R

STUD
W

JAMB AND HEADER 1 1/2" (TYPICAL)


SCHEDULED (EXTERIOR)
150U50-54
SPAN HEADER JAMB COLD ROLLED CHANNEL
6 Hyundai Slanted Column Connection at Composite Slab Mark W. Nannis, P.E.
(FT) STUDS (1-1/2"x16 GA. CRC) Texas Design Firm #21364
TO BE PLACED WITHIN 12" S686 1591 Riverside Drive
<4 (2) 60S200-43 1 1" = 1'-0" Gainesville, GA 30501
OF SLIP TRACK
6 (2) 60S200-43 2 TYP. WALL BACK TO BACK JAMB STUDS 770-614-6114 tel
8 (2) 725S200-54 2 STUD MEMBER SIZES & QUANTITY. B-1 / B-2 B-1 All drawings, specifications, and other work product
SEE SCHEDULE of Mark W. Nannis, P.E. (henceforth referred to as "The
10 (2) 800s200-68 3
SLIP TRACK DETAIL CAP OPENING SIDE OF JAMB
Engineer") for this project are instruments of service for
this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
WITH A SECTION OF TRACK of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written
A EXTEND TRACK 12" PAST TOP permission of The Engineer shall be at the owner's risk
OF OPENING. ATTACHED TO JAMB and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
w/(1)#10-16 SCREW @ 16"o.c. IN expenses including attorney's fees arising out of such
FULL HEIGHT JAMB STUD, EACH LG unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
SEE SCHEDULE © 2023
CRIPPLE STUD 3/16" 3"
LINTEL Client:
6" LONG SECTION OF STUD SILL/HEAD TRACK.

1"
ATTACHED TO JAMB CAP OPENING SIDE OF JAMB
w/ (4)#10-16 SCREWS
(1) #10-16 SCREW
TYP. EACH FLANGE
MEMBER SIZES AS
REQ'S PER DESIGN WITH A SECTION OF TRACK
6 X 6 X 5/16 X 6" LONG ANGLE
ON NEAR SIDE & FAR SIDE OF Automotive
FLOOR OR ROOF TUBE
EXTEND TRACK 12" PAST TOP
18ga. MIN TRACK WINDOW
HEAD TRACK
OF OPENING. ATTACHED TO
BEAM/JOIST 3/4" BOLT IN A 2" VERT.
SLOTTED HOLE
Managment
HEADER CONNECTION ROUGH JAMB w/(1)#10-16 SCREW @
(2)#10-16
SCREWS @ 16"
OPENING
6" LONG SECTION OF STUD 16"o.c. IN EACH LEG Services, Inc.
GAP OPENING SIDE OF JAMB 505 S. Flagler Dr., Suite 1400
o.c. ATTACHED West Palm Beach, FL 33401

L
w/ TRACK ATTACHED TO JAMB w/(4)#10-16 BACK TO BACK JAMB STUDS
w/ (1)#10-16 SCREW @ 16" SCREWS MEMBER SIZES & QUANTITY.
Project Number: 22008
o.c. IN EACH LEG SEE SCHEDULE
Project Name:
(2)UNPUNCHED STUDS. A-1/A-2
MEMBER SIZED AS REQ'D 1/2" B B-2 Alliance Hyundai
PER DESIGN ADDITIONAL "X" BRIDGING
EQUAL HEAD TRACK
1/2"

HEADER DETAIL TYP LIGHT GAUGE SILL HEAD TRACK CONNECTION


(A) STEEL WALL FRAMING 11001 North Fwy
WHERE BRACING TERMINATES Fort Worth, TX 76177
(2) JAMB STUDS (2) JAMB STUDS
BACK TO BACK TYP. JAMB AT BUILD-UP JAMB OR POST,
STUD OR POST EXTEND CHANNEL INTO PUNCH OUT
EDGE OF SLAB

NOTE:
2" MIN FROM

FULL HEIGHT JAMB USE 2"x2"x16 GA. CLIP ANGLE


L = 0'-0" - 14'-0" HSS 3 X 3 X 5/16" (A-1)
STUDS. 1-1/4" LESS THAN STUD WIDTH
ATTACH TRACK TO SLAB L = 14'-0" - 18'-0" HSS 4 X 4 X 5/16" (A-1)
SPACING

CAP JAMB WITH 20GA. ATTACH JAMB MEMBERS MEMBER SIZES AS ATTACH USING (4) #10-16 SCREWS.
3" MIN

MIN TRACK FOR WINDOW USING (2) #10-16 SCREWS w/(4) 0.145"DIA. HILTI X-DNI L = 18'-0" - 22'-0" HSS 6 X 4 X 1/4" (A-2)
REQ'D
ATTACHMENT. EXTEND 6" @ 16"o.c. PDF's w/1-1/2"MIN 150U50-54 COLD ROLLED CHANNEL L = 22'-0" - 25'-0" HSS 6 X 4 X 5/16" (A-2)
PER DESIGN.
ABOVE HEADER & 6" EMBEDDMENT (1-1/2"x16 GA. CRC)
SEE ELEVATION FOR SPACING
A-1
BELOW SILL
GE

CONNECTIONS. (4) 3/8" DIAM. WEDGE, ALL


OM IN

TYP. WALL STUD


ED
F R 2" M

ANCHORS BY SIMPSON (3" C5 X 6.7


MIN. EMBED)
3" MIN
`
o .c

RUNNER TRACK 3/4" BOLT IN A 1-1/2" VERT.


OR 8-1/4 X 6 X 1/4" PLATE
X.
"

(1) #10-16 SCREW SPACING


24

MA

3/16" SLOTTED HOLE


@ EACH FLANGE
TOP VIEW TYP. LATERAL BRACING SPLICE FINISH LINE (TYP. 5/8") A-2
G

1 1/2"
AC N
IN
SP " MI

USE: (1)12" LONG CRC INVERTED


Sheet Title:
3

OVER CENTER OF SPLICE w/(3) # (4) 3/8" DIAM. WEDGE, ALL

RELEASED FOR CONSTRUCTION AND PERMIT


2"x2"x16" GA. CLIP ANGLE 10-16 SCREWS ON EACH SIDE OF ANCHORS BY SIMPSON (3"
Typical Details
STUD

3 1/2"
MIN. EMBED)
1/4" LESS THAN STUDS WIDTH.

6"
SPLICE
CONCRETE SLAB ATTACH USING (4)#10-16 SCREWS 8-1/4 X 6-1/2 X 1/4" PLATE
ATTACH JAMB MEMBER USING
6" SECTION OF RUNNER TRACK
20GA. MIN. USE 8 #10-16 SCREWS
SEE PLAN PLACE CLIP ANGLE AT EACH STUD
6" 2"
FINISH LINE (TYP. 5/8")
1 1/2"
3/16"
(Misc)

1/4"
AS SHOWN
STUD TO TRACK DETAIL (B) 1/4"

STUD

3 1/2"
6"
TIED JAMB STUDS BRIDGING DETAIL Sheet Number:

S686
6" 2"
Typical Metal Stud Detail Typical Detail of Post at Coiling Door Support

1/4"
7 8 1/4"
S686 12" = 1'-0"
S686 1 1/2" = 1'-0"
PRAXIS3
2' - 0"

CORNER BARS. LOCATE AT MIN. LAP SPLICE LENGTH


EACH HORIZONTAL BAR. FOR REINF. MASONRY
CONT. BOND BM. REINF. W/ 2 # 4 TOP OF PARAPET, OR TOP OF WHERE BOND BEAMS
2'-0" 3/8" MASONRY CONTROL JOINT.
CONT. AT TOP OF PARAPET/WALL, WALL AT UNDERSIDE OF SLOPE WITH ROOF SLOPE, BAR LENGTH (IN.)
SEE DETAIL 7 / S687 STRUCTURE. 100 Peachtree St NW 404-875-4500 tel
AND AT ROOF LINE. STEP BOND BEAMS AS #3

2'-0"
18"
Suite 1450 404-876-8884 fax

2' - 0"
SHOWN IN DETAIL PROVIDE 4" HOOK IN CORNER CELL
3 / S687 #4 24" WHERE BAR IS NOT LAPPED BY A
METAL LATH UNDER BOND BEAM
#5
Atlanta, GA 30303 www.praxis3.com
30" CORNER BAR - TYP.
TO CONFINE GROUT
AT ALL LINTELS OVER OPENINGS, #5 AT SCHEDULED WALL #6 46"
SEE TYPICAL MASONRY LINTEL SPACING AS NOTED ON 2' - 0" BOND
SCHEDULE. MINIMUM OF (2) BARS ELEVATIONS, BUT NOT REINF. IN BOND BEAMS SHALL BE SET
IN BOTTOM TYPICAL. GREATER THAN 48" o.c. IN PLACE AS WALL IS LAID UP. LAP BEAM LAP
MAX. TYPICAL ABOVE ALL SPLICE AT LEAST 48 BAR DIAMETERS.
OPENINGS IN WALL. PROVIDE HOOKS AT ENDS. CELLS CONTAINING REINF. SHALL BE
FILLED SOLIDLY W/ GROUT.
SEE PLANS AND SECTIONS VERTICAL CELLS SHALL PROVIDE A
CONT. BOND BM. REINF. W/
FOR FLOOR SLAB CONTINUOUS CAVITY, FREE OF
2 # 4 AT 12'-0" o.c. MAX
MORTAR DROPPINGS STEPPED
VERTICALLY
FLOOR LINE OR ROOF LINE.
UNLESS WALL IS FULLY GROUTED,
PLACE MORTAR ON CROSS WEBS 2' - 0" min.
ADJACENT TO GROUTED CELLS TO
CONT. BOND BM. REINF. W/ 2 # 4 FOOTING 45 diam. BENT REBARS TO MATCH
CONFINE GROUT TO THE GROUT
CONT. AT FLOOR LINE, AND AT ROOF BOND BEAM REINFORCING
SPACE.
LINE.

#5 VERTICAL AT CORNERS,
VARIES
2
Typical Detail of Masonry Wall Reinforcement 3 Typical Detail of Step in Bond Beam at Sloped Roof Bearing
AND ENDS OF WALLS
TYPICAL. S687 3/4" = 1'-0" S687 3/4" = 1'-0"
SIGNED & SEALED 10.03.2022
TYPICAL AT ALL OPENINGS, SEE
DETAIL X-X BELOW. UNLESS NOTED Copyright (c) 2022 Praxis3, LLC
OTHERWISE ON MASONRY COLUMN 2' - 0" All reports, plans, specifications, computer files, field data, notes and other documents
SCHEDULE. TYPICAL and instruments prepared by Praxis3 shall retain all common law, statutory and other
CONT. BOND BM. REINF. W/ 2 reserved rights, including copyright thereto.
# 4 CONT. AT FLOOR LINE, CENTER LINE
BEND VERT. BAR DOWN This drawing may not be reproduced in whole or in part without written permission of
1 #5 VERTICAL AT EACH SIDE OF OF MEMBER Praxis3. It is to be returned upon request. Scales as stated are valid on the original
MASONRY CONTROL JOINT. INTO U-BLOCK. drawings.

TYPICAL. 1 1/2" EXPANSION JOINT

.2'-0"
FLOOR LINE, MATERIAL SAME WIDTH Rev Date Comments
AS PARTITION DECK UNDERSIDE OF
2 #4 IN CONC. FILLED DECKING
10.03.22 Permit / Bid Set
U-BLOCK DISCONT. AT
CONTRACTION JOINT.
EXT. FINISH,
EXT. FINISH, SEE ARCH. BEAM OR
SEE ARCH. #5 VERT. REINF. AT CORNERS,
OPENINGS, CONTRACTIONJOINTS. JOIST SEE PLAN
PROVIDE DOWEL AT FOOTING.BEND 2'-0" CONT. BOND BEAM
INTO U-BLOCK AT TOP.SEE SPECS. FOR AT 12'-0"o.c. MAX RINF.
CONT. BOND BM. REINF. W/
DOWEL TO FTG. SAME SIZE & NUMBER AS PLACING INSTRUCTIONS. WITH 2#4 CONT.
2 # 4 BELOW OPENINGS IN
VERT. REINF., TYP. (@ EA. VERT. BAR) SEE SEE WALL ELEVATIONS FOR BAR SIZE AND SPACING. WALL.
LAP SCHEDULE FOR REINFORCMENT LAP. PROVIDE #5 AT 48" o.c. MAX, AT JAMBS OF 8" OR 12" CMU SEE WALL SCHEDULE
WALL 1 1/2" EXPANSION

FOR LAP SPLICE


SEE SCHEDULE
OPEININGS, ENDS OF WALLS, AND EACH SIDE OF SEE PLAN JOINT MATERIAL
MASONRY CONTROL JOINTS. UNLESS NOTED PARTITION
OTHERWISE.
JAMB REINFORCEMENT - LADDER TYPE HORIZ.
REINFORCE WITH 1 #5 AT EDGE REINF. EVERY OTHER
CELL AS NOTED. COURSE.
NOTES: 8" @ OPNG ≤ 4'-0" DOWELS SAME SIZE
1'-4" @ 4'-0" ≤ OPNG < 9'-11" CONTRACTION & NUMBER AS
FILL CELLS OF CMU CONTAINING REINF. ONLY WITH CONCRETE GROUT, NOT MORTAR. 2'-0" @ 9'-11" ≤ OPNG < 14'-0" JOINTS @ 30'-0"± WALL REINF.
FIRE PROOF
VERTICAL CONTRACTION JOINT.
MIN. REINFORCING LAP 48 DIA., 2'-0"MIN. INSULATION
SEE PLAN FOR LOCATION.
MATERIAL
PROVIDE LADDER TYPE REINF. @ EVERY OTHER COURSE. PAINT JOINT WITH MASTIC
BEFORE PLACING CONCRETE. FOR FTG./REINF.,
PROVIDE MASONRY CONTROL JOINTS AS NOTED ON THE PLAN NOTES. SEE PLAN
SEE MASONRY WALL ELEVATIONS. LIMIT SPACING TO 16'-0" FROM CORNERS,
AND 32'-0" o.c. MAX. TYPICAL. PAINT JOINT W/ MASTIC.
VERTICAL REINFORCING HORIZONTAL REINFORCING

DETAIL - XX Typical Masonry Walls that Extend up to Underside


1
Typical Masonry Wall Elevation 4
Typical Detail of Masonry Wall Reinforcement 5
of Structure
S687 1/4" = 1'-0"
S687 3/4" = 1'-0"
S687 1" = 1'-0"

Mark W. Nannis, P.E.


Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
770-614-6114 tel

All drawings, specifications, and other work product


of Mark W. Nannis, P.E. (henceforth referred to as "The
Engineer") for this project are instruments of service for
this project only and shall remain the property of The
Engineer whether the project is complete or not. Reuse
of any of the instruments of service of The Engineer by
the owner or extensions of this project without the written
permission of The Engineer shall be at the owner's risk
and the owner agrees to defend, indemnify, and hold
harmless The Engineer from all claims, damages, and
GENERAL NOTES: MAXIMUM UNBRACED LENGTH expenses including attorney's fees arising out of such
OF INTERIOR PARTITION unauthorized reuse of The Engineer's instruments of
service by the owner or others acting through the owner.
IF THE UNBRACED LENGTH OF A PARTITION IS GREATER THAN MAXIMUM UNBRACED LENGTH © 2022
NOMINAL UNBRACED HORIZ. GENERAL NOTES: OF INTERIOR PARTITION
SPECIFIED ON THE ADJACENT TABLE OR INTERRUPTED BY AN OPENING,
THEN IT IS CONSIDERED DISCONTINUOUS AND CANNOT SPAN BEYOND SIZE SPAN OF PARTITION Client:
IF THE UNBRACED LENGTH OF A PARTITION IS GREATER THAN NOMINAL UNBRACED HORIZ.
THAT POINT. PROVIDE BRACING AS OUTLINED IN DETAILS BELOW. 4" 13'-0"
LINE ONE SIDE OF CORE
W/ #15 BUILDING PAPER
6" 19'-6"
SPECIFIED ON THE ADJACENT TABLE OR INTERRUPTED BY AN OPENING,
THEN IT IS CONSIDERED DISCONTINUOUS AND CANNOT SPAN BEYOND
SIZE SPAN OF PARTITION Automotive
BEFORE FILLING CORE. NOTE "A": INDICATES TO USE A 2-1/2"x2-1/2"x5/16" ANGLE WHEN LENGTH 4" 13'-0"
OF ANGLE IS 6'-6" OR LESS. WHEN ANGLE IS GREATER THAN 6'-6" AND 8" 26'-0"
THAT POINT. PROVIDE BRACING AS OUTLINED IN DETAILS BELOW.
6" 19'-6" Managment
LESS THAN 9'-0", PROVIDE A 3"x3"x1/4" ANGLE. FOR LENGTHS GREATER
THAN 9'-0" CONSULT THE STRUCTURAL ENGINEER.
10"
12"
32'-6"
39'-0"
DO NOT WELD ANGLE UNTIL ALL ROOF OR FLOOR DEAD LOAD IS IN
PLACE.
8" 26'-0" Services, Inc.
10" 32'-6" 505 S. Flagler Dr., Suite 1400
DO NOT WELD ANGLE UNTIL ALL ROOF OR FLOOR DEAD LOAD IS IN West Palm Beach, FL 33401
PLACE. 12" 39'-0"
FLOOR OR ROOF JOIST FLOOR OR ROOF JOIST
OR BEAM. OR BEAM. 3/16" Project Number: 22008
.1/2"
FLOOR OR ROOF JOIST FLOOR OR ROOF JOIST Project Name:
3/16"
OR BEAM. OR BEAM.

ALTERNATE COURSES NOTE "A" NOTE "A" Alliance Hyundai

Typ. At Each Typ. At Each


3/16" End 3/16" End
MA .
MA .

60° ° MIN
X.
60° ° MIN
X.

6" x 12" x 1/4" PLATE AT EACH ADDITIONAL X TYPE (2) - 5/8" EXPANSION ADDITIONAL X TYPE
SET OF ANCHORS. BRIDGING ANCHORS LOCATED 2-1/2" BRIDGING 11001 North Fwy
30
30

3/16" "U" SHAPED BENT 5" x 8" x 1/4" PLATE WITH HSS 2-1/2" x 2-1/2"x 1/4" AT EVERY BELOW TOP OF ANGLE.
PLATE WITH A 6" VERT. LEG (2) - 1/2" DIAM. HEADED OTHER JOIST BOTTOM CHORD PANEL PLACE IN A 1-1/2" VERTICAL HSS 2-1/2" x 2-1/2"x 1/4" AT EVERY Fort Worth, TX 76177
CEILING SEE ARCH. x 1'-0" LONG AT 8'-0" o.c. CEILING SEE ARCH. STUDS WITH 4" EMBED. POINT NOT TO EXCEED 10'-0" o.c. MAX. SLOTTED HOLE. OTHER JOIST BOTTOM CHORD PANEL
.1/2" DWGS. MAX. DWGS. SPACE AT A JOIST OR BEAM (2) - 5/8" THRU-BOLTS POINT NOT TO EXCEED 10'-0" o.c. MAX.
WELD TO BOTTOM CHORD OF JOIST
NOT TO EXCEED 12'-0" LOCATED 2-1/2" BELOW TOP CONT. BOND BEAM WELD TO BOTTOM CHORD OF JOIST
CONT. BOND BEAM WITH A 1/8" FILLET WELD.
CAULKING (2) - 5/8" THRU-BOLTS 4", OR 6" CMU. MAX. OF ANGLE. PLACE IN A 1-1/2" REINFORCED WITH 2 #4 WITH A 1/8" FILLET WELD.
LOCATED 4" BELOW REINFORCED WITH 2 #4 VERTICAL SLOTTED HOLE. CONT. HORIZ.
CONT. HORIZ. 8",10", OR 12" CMU. 4" x 3" x 1/4" x 1'-0" LONG ANGLE 4" x 3" x 1/4" x 1'-0" LONG ANGLE
TOP OF PARTITION.
AT EVERY OTHER JOIST PANEL 8",10", OR 12" CMU. AT EVERY OTHER JOIST PANEL
4" OR 6" PARTITION PARALLEL TO FRAMING ABOVE 8",10", OR 12" PARTITION PARALLEL TO FRAMING ABOVE 4", OR 6" CMU. POINT NOT TO EXCEED 10'-0" POINT NOT TO EXCEED 10'-0"
o.c MAX. o.c MAX.
BUILDING PAPER
FLOOR OR ROOF JOIST FLOOR OR ROOF JOIST 4" OR 6" PARTITION PARALLEL TO FRAMING ABOVE 8",10", OR 12" PARTITION PARALLEL TO FRAMING ABOVE
OR BEAM. OR BEAM.
FLOOR OR ROOF JOIST FLOOR OR ROOF JOIST
CONCRETE FILL OR BEAM. 1/8" OR BEAM. 1/8"
NOTE "A" NOTE "A" 1/8" 1/8"
#5 EA. SIDE OF JOINT
00°

Typ. At Each Typ. At Each


00°
45.

End End
45.

3/16" 3/16"
PROVIDE 1" COMPRESSIBLE (2)- 5/8" DIAM. EXPANSION PROVIDE 1" COMPRESSIBLE Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


MATERIAL AROUND JOIST THAT ANCHORS LOCATED 2-1/2" MATERIAL AROUND JOIST THAT

CEILING SEE ARCH.


3/16" "U" SHAPED BENT
PLATE WITH A 6" VERT. LEG
x 1'-0" LONG AT 8'-0" o.c. CEILING SEE ARCH.
5" x 8" x 1/4" PLATE WITH
(2) - 1/2" DIAM. HEADED
STUDS WITH 4" EMBED.
PENETRATES A NON LOAD
BEARING PARTITION.
BELOW TOP OF ANGLE.
CENTER IN A 1-1/2" VERTICAL
SLOTTED HOLE.
PENETRATES A NON LOAD
BEARING PARTITION. Typical Details
5" x 3" x 1/4" x 1'-0" LONG ANGLE 5" x 3" x 1/4" x 1'-0" LONG ANGLE
DWGS.
(2) - 5/8" THRU-BOLTS
MAX. DWGS.
CONT. BOND BEAM
SPACE AT A JOIST OR BEAM
NOT TO EXCEED 12'-0"
MAX.
(2) - 5/8" THRU-BOLTS
LOCATED 2-1/2" BELOW TOP
OF ANGLE. CENTER IN A
AT EVERY OTHER JOIST AND
SPACING NOT TO EXCEED
10'-0" o.c MAX. CONT. BOND BEAM
AT EVERY OTHER JOIST AND
SPACING NOT TO EXCEED
10'-0" o.c MAX.
(CMU)
LOCATED 4" BELOW REINFORCED WITH 2 #4 1-1/2" VERTICAL SLOTTED REINFORCED WITH 2 #4
NOTE: TOP OF PARTITION. 4", OR 6" CMU. CONT. HORIZ. 8",10", OR 12" CMU. HOLE. 4", OR 6" CMU. 8",10", OR 12" CMU.
CONT. HORIZ.
CUT ALTERNATING (INSIDE &
OUTSIDE FACE) SIDE RODS OF 4" OR 6" PARTITION PERPENDICULAR TO FRAMING ABOVE
HORIZ. JOINT REINFORCEMENT
4" OR 6" PARTITION PERPENDICULAR TO FRAMING ABOVE 8",10", OR 12" PARTITION PERPENDICULAR TO FRAMING ABOVE 8",10", OR 12" PARTITION PERPENDICULAR TO FRAMING ABOVE
AT CONTROL JOINT. SEE ARCH. FOR SEALANT
Sheet Number:
Typical Bracing of Non-Full-Height or Typical Bracing of Full-Height/Non-Load-Bearing
7
S687
Typical Masonry Contol Joint
1 1/2" = 1'-0"
8
S687
Non-Load-Bearing Masonry Partitions
1/2" = 1'-0"
9
S687
Masonry Partitions
1/2" = 1'-0"
S687
TYPICAL AT
1/8" 2"
WHER JOIST BEAR FROM OPPOSITE EACH JOIST

PRAXIS3
SIDE OF WALL, MIRROR BEARING 1/8" 2" FROM EACH
PLATE LOCATION ON CENTERLINE OF SIDE OF WALL.
WALL. JOIST SPACING SHOULD NOT
FOR TOP ELEVATION OF PARAPET SEE EFFECT THE BEARING PLATE
FOR TOP ELEVATION OF PARAPET SEE
ARCHITECTURAL DRAWINGS. LOCATION OF THE MIRRORED JOIST
ARCHITECTURAL DRAWINGS.
CONDITION.
SEE TYPICAL DETAIL OF MASONRY 1/8" 2"
REINFORCING. HOOK VERTICAL BAR 100 Peachtree St NW 404-875-4500 tel
FOR BEARING PLATE SIZE AND
12" CONT. BOND BEAM REINFORCED WITH
2'-0" INTO BOND BEAM.
HEADED STUDS, SEE BEARING PLATE
Suite 1450 404-876-8884 fax
SEE TYPICAL DETAIL OF MASONRY REINFORCING. (2) #4 CONT HORIZONTAL. SCHEDULE. Atlanta, GA 30303 www.praxis3.com
HOOK VERTICAL BAR 2'-0" INTO BOND BEAM.

4" x 3" x 1/4" CONT. ANGLE. LONG LEG


1/2" VERTICAL.
8" CONT. BOND BEAM REINFORCED
8" CONT. BOND BEAM REINFORCED WITH (2) VERTICAL WALL REINFORCEMENT CENTERED IN
WITH (1) #4 TOP CONT. AND (1) #4
#4 CONT HORIZONTAL. MASONRY WALL. FILL ALL CELLS WITH GROUT
CONT. BOTTOM.
WHERE REINFORCING OCCURS. SEE WALL
ELEVATIONS, TYPICAL DETAILS AND WALL
SCHEDULE FOR SIZE AND LOCATION OF
VERTICAL WALL REINFORCEMENT CENTERED IN
REINFORCING. HOOK VERTICAL WALL REINFORCEMENT 2'-0"
MASONRY WALL. FILL ALL CELLS WITH GROUT
WHERE REINFORCING OCCURS. SEE WALL HORIZONTALLY INTO BOND BEAM.
ELEVATIONS, TYPICAL DETAILS AND WALL
SCHEDULE FOR SIZE AND LOCATION OF VERTICAL WALL REINFORCEMENT
REINFORCING. CENTERED IN MASONRY WALL. FILL ALL
CELLS WITH GROUT WHERE
REINFORCING OCCURS. SEE WALL
ELEVATIONS, TYPICAL DETAILS AND WALL
SCHEDULE FOR SIZE AND LOCATION OF
REINFORCING.

1
Typical 8" CMU Parapet Bond Beam 2
Typical 8" CMU Parapet Bond Beam 3 Typical 8" CMU/Joist Connection (where joists occur on each side) SIGNED & SEALED 10.03.2022

S688 3" = 1'-0" S688 3" = 1'-0" S688 1 1/2" = 1'-0"


Copyright (c) 2022 Praxis3, LLC

All reports, plans, specifications, computer files, field data, notes and other documents
WHER JOIST BEAR FROM OPPOSITE and instruments prepared by Praxis3 shall retain all common law, statutory and other
reserved rights, including copyright thereto.
SIDE OF WALL, MIRROR BEARING
PLATE LOCATION ON CENTERLINE OF 1/8" 2"
This drawing may not be reproduced in whole or in part without written permission of
Praxis3. It is to be returned upon request. Scales as stated are valid on the original
WALL. JOIST SPACING SHOULD NOT TYPICAL AT EACH JOIST drawings.
EFFECT THE BEARING PLATE 1/8" 2" FROM EACH SIDE OF
LOCATION OF THE MIRRORED JOIST WALL.
Rev Date Comments
CONDITION.
WHERE A K SERIES JOIST BEARS ON THE 10.03.22 Permit / Bid Set
FOR BEARING PLATE SIZE AND SAME WALL OR BEAM AS A "LH" JOIST,
HEADED STUDS, SEE BEARING PLATE PROVIDE A SPECIAL 5" JOIST BEARING SEAT
SCHEDULE. INSTEAD OF 2-1/2".

11 5/8"
1/8" 2" TYPICAL AT EACH
5 1/2" JOIST FROM EACH
5/8" DIAM. EXPANSION ANCHOR AT 2'-8"
1/8" 2" SIDE OF WALL. 1/8" 2" TYPICAL AT EACH
o.c. MAX. FILL CELLS SOLID WITH
6" JOIST FROM EACH SIDE 1/2" 1/2"
GROUT WHERE ANCHORS OCCUR. 1/8" 2" OF WALL.
EMBED A MINIMUM OF 5" INTO CMU. 4" x 3" x 1/4" CONT. ANGLE. WELD TO
EACH ROOF JOIST WITH A 3/16" FILLET
WELD IN THE FIELD. PROVIDE A 3/4"
DIAM. EXPANSION ANCHOR INTO A
CLOSURE ANGLE TO GROUTED CELL AT 2'-0" o.c. MAX WITH 5"
4" x 3" x 1/4" CONT. ANGLE. LONG LEG JOIST TOP CHORD MINIMUM EMBEDMENT.
1/8" 2" 3/16
VERTICAL.
12" CONT. BOND BEAM REINFORCED
WITH (1) #4 TOP CONT. AND (1) #4
FOR BEARING PLATE SIZE AND
CONT. BOTTOM.
FOR BEARING PLATE SIZE AND HEADED STUDS, SEE BEARING PLATE
HEADED STUDS, SEE BEARING PLATE SCHEDULE.
SCHEDULE.

HOOK VERTICAL WALL REINFORCEMENT 2'-0"


1/2" HORIZONTALLY INTO BOND BEAM.
1/2" 12" CONT. BOND BEAM REINFORCED
8" CONT. BOND BEAM REINFORCED
WITH (1) #4 TOP CONT. AND (1) #4 WITH (1) #4 TOP CONT. AND (1) #4
CONT. BOTTOM. CONT. BOTTOM. VERTICAL WALL REINFORCEMENT
CENTERED IN MASONRY WALL. FILL ALL
NOTE: WHERE JOISTS BEAR ON MASONRY CELLS WITH GROUT WHERE
WALLS, GROUT POCKET SOLID WITH HOOK VERTICAL WALL REINFORCEMENT 2'-0" REINFORCING OCCURS. SEE WALL
GROUT TO THE SAME FINISH FACE AS HORIZONTALLY INTO BOND BEAM. ELEVATIONS, TYPICAL DETAILS AND WALL
MASONRY ABOVE AND BELOW. DO THIS SCHEDULE FOR SIZE AND LOCATION OF
ONLY AFTER JOIST SEAT CONNECTION HAS VERTICAL WALL REINFORCEMENT REINFORCING.
BEEN INSPECTED. CENTERED IN MASONRY WALL. FILL ALL NOTE: WHERE JOISTS BEAR ON MASONRY
CELLS WITH GROUT WHERE WALLS, GROUT POCKET SOLID WITH
VERTICAL WALL REINFORCEMENT
REINFORCING OCCURS. SEE WALL GROUT TO THE SAME FINISH FACE AS
CENTERED IN MASONRY WALL. FILL ALL
ELEVATIONS, TYPICAL DETAILS AND WALL MASONRY ABOVE AND BELOW. DO THIS
CELLS WITH GROUT WHERE
SCHEDULE FOR SIZE AND LOCATION OF ONLY AFTER JOIST SEAT CONNECTION HAS
REINFORCING OCCURS. SEE WALL
REINFORCING. BEEN INSPECTED.
ELEVATIONS, TYPICAL DETAILS AND WALL
SCHEDULE FOR SIZE AND LOCATION OF
REINFORCING.

4 Typical 8" CMU/Joist Connection (where parapet occurs) 5 Typical 12" CMU/Joist Connection (where parapet occurs) 6 Typical 12" CMU/Joist Connection (where joists occur on each side)
S688 1 1/2" = 1'-0" S688 1 1/2" = 1'-0" S688 1 1/2" = 1'-0"

1 1/2" EDGE
Mark W. Nannis, P.E.
1 1/2" Texas Design Firm #21364
OF DECK
1591 Riverside Drive
Gainesville, GA 30501
2" 2" END
OF JOIST 770-614-6114 tel
4" x 3" x 1/4" CONT. ANGLE. WELD TO 3/16 4" x 3" x 1/4" CONT. ANGLE. WELD TO 3/16
EACH ROOF JOIST WITH A 3/16" FILLET EACH ROOF JOIST WITH A 3/16" FILLET All drawings, specifications, and other work product
WELD IN THE FIELD. ANCHOR WOOD WELD IN THE FIELD. ANCHOR WOOD of Mark W. Nannis, P.E. (henceforth referred to as "The
BLOCKING TO VERTICAL LEG WITH A BLOCKING TO VERTICAL LEG WITH A 1/8" 2" Engineer") for this project are instruments of service for
1/8" 2" TYPICAL AT EACH TYPICAL AT EACH
"TB1460S" SCREW BY "SIMPSON" AT 12" "TB1460S" SCREW BY "SIMPSON" AT 12" this project only and shall remain the property of The
JOIST FROM EACH SIDE JOIST FROM EACH SIDE Engineer whether the project is complete or not. Reuse
o.c. MAX o.c. MAX 1/8" 2"
1/8" 2" OF WALL. OF WALL. of any of the instruments of service of The Engineer by
CMU WALL. FILL CELL WITH the owner or extensions of this project without the written
GROUT WHERE ANCHOR IS TO permission of The Engineer shall be at the owner's risk
FOR BEARING PLATE SIZE AND FOR BEARING PLATE SIZE AND and the owner agrees to defend, indemnify, and hold
HEADED STUDS, SEE BEARING PLATE OCCUR. harmless The Engineer from all claims, damages, and
HEADED STUDS, SEE BEARING PLATE 5/8" DIAMETER EXPANSION
SCHEDULE. SCHEDULE. expenses including attorney's fees arising out of such
ANCHOR WITH 4" MINIMUM unauthorized reuse of The Engineer's instruments of
EMBEDMENT INTO MASONRY service by the owner or others acting through the owner.
WALL © 2022

1/2" 1/2" Client:


8" CONT. BOND BEAM REINFORCED 12" CONT. BOND BEAM REINFORCED
WITH (1) #4 TOP CONT. AND (1) #4
CONT. BOTTOM.
WITH (1) #4 TOP CONT. AND (1) #4
CONT. BOTTOM. VERTICAL WALL REINFORCEMENT
Automotive
CENTERED IN MASONRY WALL. FILL ALL
CELLS WITH GROUT WHERE
REINFORCING OCCURS. SEE WALL
Managment
HOOK VERTICAL WALL REINFORCEMENT 2'-0"
HOOK VERTICAL WALL REINFORCEMENT 2'-0"
HORIZONTALLY INTO BOND BEAM. HORIZONTALLY INTO BOND BEAM.
ELEVATIONS, TYPICAL DETAILS AND WALL
SCHEDULE FOR SIZE AND LOCATION OF Services, Inc.
REINFORCING. 505 S. Flagler Dr., Suite 1400
VERTICAL WALL REINFORCEMENT VERTICAL WALL REINFORCEMENT West Palm Beach, FL 33401
CENTERED IN MASONRY WALL. FILL ALL CENTERED IN MASONRY WALL. FILL ALL ANGLE 3" x 3" x 1/4" x 6" LONG AT EACH
CELLS WITH GROUT WHERE CELLS WITH GROUT WHERE BRIDGIN LOCATION WHERE WALL IS
REINFORCING OCCURS. SEE WALL REINFORCING OCCURS. SEE WALL PARALLEL TO ROOF JOIST.
Project Number: 22008
ELEVATIONS, TYPICAL DETAILS AND WALL ELEVATIONS, TYPICAL DETAILS AND WALL Project Name:
SCHEDULE FOR SIZE AND LOCATION OF SCHEDULE FOR SIZE AND LOCATION OF
REINFORCING. REINFORCING.
Alliance Hyundai
7 Typical 8" CMU/Joist Connection (where no parapet occurs) 8 Typical 12" CMU/Joist Connection (where no parapet occurs) 9
Typical CMU/Joist Bridging Connection
S688 1 1/2" = 1'-0"
S688 1 1/2" = 1'-0"
S688 3" = 1'-0"

11001 North Fwy


Fort Worth, TX 76177

8" CONT. BOND BEAM REINFORCED WITH WELD DECK TO CLOSURE 12" CONT. BOND BEAM REINFORCED WITH (2) #4 WELD DECK TO CLOSURE
(2) #4 CONT. HORIZONTAL. STEP BOND ANGLE AS PER DECKS 8" CONT. BOND BEAM REINFORCED WITH (2) # WELD DECK TO CLOSURE CONT. HORIZONTAL. STEP BOND BEAM AS ANGLE AS PER DECKS
BEAM AS REQUIRED AT INCREMENTS OF SPECIFICATION. AT ZONE 2 4 CONT. HORIZONTAL. STEP BOND BEAM AS ANGLE AS PER DECKS REQUIRED AT INCREMENTS OF BLOCK COURSING SPECIFICATION. AT ZONE 2
BLOCK COURSING TO MATCH SLOPE OF AND 3 OF ROOF, WELD AT 6" REQUIRED AT INCREMENTS OF BLOCK SPECIFICATION. AT ZONE 2 TO MATCH SLOPE OF ROOF DECK. AND 3 OF ROOF, WELD AT 6"
ROOF DECK. o.c. MAX. COURSING TO MATCH SLOPE OF ROOF DECK. AND 3 OF ROOF, WELD AT 6" o.c. MAX.
o.c. MAX.

1 1/2"
1 1/2"

1 3/8"

VERTICAL WALL REINFORCEMENT VERTICAL WALL REINFORCEMENT CENTERED IN


CENTERED IN MASONRY WALL. FILL ALL VERTICAL WALL REINFORCEMENT CENTERED IN MASONRY WALL. FILL ALL CELLS WITH GROUT
CELLS WITH GROUT WHERE REINFORCING MASONRY WALL. FILL ALL CELLS WITH GROUT WHERE REINFORCING OCCURS. SEE WALL
OCCURS. SEE WALL ELEVATIONS, TYPICAL WHERE REINFORCING OCCURS. SEE WALL ELEVATIONS, TYPICAL DETAILS AND WALL
DETAILS AND WALL SCHEDULE FOR SIZE ELEVATIONS, TYPICAL DETAILS AND WALL SCHEDULE FOR SIZE AND LOCATION OF
AND LOCATION OF REINFORCING. SCHEDULE FOR SIZE AND LOCATION OF REINFORCING.
REINFORCING.
Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


4" x 4" x 5/16" CONT. ANGLE. LONG LEG
VERTICAL. ANCHOR TO BOND BEAM AT
ROOF WITH A 3/4" DIAM. EXPANSION
ANCHOR AT 2'-6" o.c. MAX. PROVIDE 5"
Typical Details
4" x 4" x 1/4" CONT. ANGLE. LONG LEG
MINIMUM EMBEDMENT.
VERTICAL. ANCHOR TO BOND BEAM AT
ROOF WITH A 3/4" DIAM. EXPANSION
4" x 4" x 5/16" CONT. ANGLE. LONG LEG
VERTICAL. ANCHOR TO BOND BEAM AT
ROOF WITH A 3/4" DIAM. EXPANSION
(CMU)
ANCHOR AT 2'-6" o.c. MAX. PROVIDE 4"
MINIMUM EMBEDMENT. ANCHOR AT 2'-6" o.c. MAX. PROVIDE 5"
MINIMUM EMBEDMENT.

Sheet Number:

10
S688
Typical 8" CMU/Roof Deck Connection (K-Series Joists)
3" = 1'-0"
11
S688
Typical 8" CMU/Roof Deck Connection (LH Joists)
3" = 1'-0"
12
S688
Typical 12" CMU/Roof Deck Connection (LH Joists)
3" = 1'-0"
S688
PRAXIS3
WELD DECK TO CLOSURE ANGLE AS PER 8" CONT. BOND BEAM REINFORCED WITH (2) #
3/16" STIFFENER PLATE ON EACH SIDE 3/16" STIFFENER PLATE ON EACH SIDE
5 1/2" DECKS SPECIFICATION. AT ZONE 2 AND 3 4 CONT. HORIZONTAL. SLOPE BOND BEAM
OF FLOOR BEAM OF FLOOR BEAM
OF ROOF, WELD AT 6" o.c. MAX. WITH SLOPE OF ROOF DECK. CUT BLOCK
BELOW AS REQUIRED.
TYPICAL AT EACH TYPICAL AT EACH
BEAM BEARING AND 7 5/8" BEAM BEARING AND
3/16 PLATE 3/16 PLATE
BUILD MASONRY AROUND EACH BEAM BUILD MASONRY AROUND EACH BEAM
POCKET AND GROUT FULLY UPON POCKET AND GROUT FULLY UPON
100 Peachtree St NW 404-875-4500 tel
Suite 1450 404-876-8884 fax

2"
INSPECTION OF BEAM BEARING PLATE INSPECTION OF BEAM BEARING PLATE
AND WELD AND WELD Atlanta, GA 30303 www.praxis3.com

FOR BEARING PLATE SIZE AND FOR BEARING PLATE SIZE AND
HEADED STUDS, SEE BEARING PLATE WIDE FLANGE FLOOR HEADED STUDS, SEE BEARING PLATE WIDE FLANGE BEAM
SCHEDULE. BEAM SCHEDULE.

5" x 3" x 1/4" CONT. ANGLE. LONG LEG VERTICAL


DOWN. ANCHOR TO BOND BEAM WITH A 5/8" DIAM. HORIZONTAL BRIDGING AT TOP AND
8" CONT. BOND BEAM REINFORCED 12" CONT. BOND BEAM REINFORCED
EXPANSION ANCHOR 1'-0" FROM EACH END OF BOTTOM CHORD OF JOIST TO BE FIELD
WITH (2) #5 CONT. BOTTOM. WITH (2) #5 CONT. BOTTOM.
WALL AND AT 2'-0" o.c. MAX. PROVIDE 4" MINIMUM WELDED TO OUTSTANDING LEG OF
EMBEDMENT. ANGLE.
1/2" 1/2"

VERTICAL WALL REINFORCEMENT CENTERED IN


MASONRY WALL. FILL ALL CELLS WITH GROUT
WHERE REINFORCING OCCURS. SEE WALL 3" x 3" x 3/16" ANGLE x DEPTH OF
ELEVATIONS, TYPICAL DETAILS AND WALL ADJACENT JOIST WITH (2) - 5/8" DIAM.
SCHEDULE FOR SIZE AND LOCATION OF EXPANSION ANCHORS WITH 3-1/2"
REINFORCING. MINIMUM EMBEDMENT. FILL CELLS
WITH GROUT WHERE ANCHORS
OCCUR. SIGNED & SEALED 10.03.2022
VERTICAL WALL REINFORCEMENT VERTICAL WALL REINFORCEMENT
CENTERED IN MASONRY WALL. FILL ALL CENTERED IN MASONRY WALL. FILL ALL
Copyright (c) 2022 Praxis3, LLC
CELLS WITH GROUT WHERE CELLS WITH GROUT WHERE HORIZONTAL BRIDGING AT TOP AND HORIZONTAL BRIDGING AT TOP AND
REINFORCING OCCURS. SEE WALL REINFORCING OCCURS. SEE WALL BOTTOM CHORD OF JOIST TO BE FIELD BOTTOM CHORD OF JOIST TO BE FIELD All reports, plans, specifications, computer files, field data, notes and other documents
and instruments prepared by Praxis3 shall retain all common law, statutory and other
ELEVATIONS, TYPICAL DETAILS AND WALL ELEVATIONS, TYPICAL DETAILS AND WALL WELDED TO OUTSTANDING LEG OF WELDED TO OUTSTANDING LEG OF reserved rights, including copyright thereto.
SCHEDULE FOR SIZE AND LOCATION OF SCHEDULE FOR SIZE AND LOCATION OF ANGLE. ANGLE. This drawing may not be reproduced in whole or in part without written permission of
REINFORCING. REINFORCING. Praxis3. It is to be returned upon request. Scales as stated are valid on the original
drawings.

1
Typical Wide Flange Beam Bearing on 8" CMU 2
Typical Wide Flange Beam Bearing on 12" CMU Rev Date Comments
10.03.22 Permit / Bid Set
S689 1 1/2" = 1'-0"
S689 1 1/2" = 1'-0"

3" x 3" x 3/16" ANGLE x 9" LONG WITH (2) - 5/8"


CENTERLINE OF SPLICE SEE PLAN DIAM. EXPANSION ANCHORS WITH 3-1/2"
CENTERLINE OF SPLICE SEE PLAN MINIMUM EMBEDMENT. FILL CELLS WITH
POINT. 3/16" STIFFENER PLATE ON EACH SIDE POINT. 3/16" STIFFENER PLATE ON EACH SIDE GROUT WHERE ANCHORS OCCUR.
OF FLOOR BEAM OF FLOOR BEAM

TYPICAL AT EACH
BUILD MASONRY AROUND EACH BEAM BEAM BEARING AND BUILD MASONRY AROUND EACH BEAM TYPICAL AT EACH
POCKET AND GROUT FULLY UPON PLATE POCKET AND GROUT FULLY UPON BEAM BEARING AND
INSPECTION OF BEAM BEARING PLATE 3/16 3/16
INSPECTION OF BEAM BEARING PLATE PLATE
AND WELD 1/2" AND WELD
1/2"

WIDE FLANGE FLOOR WIDE FLANGE FLOOR 3 Typical 8" CMU/Deck Connection (where joists occur on each side)
BEAM BEAM
S689 3" = 1'-0"

1/2" 1/2"
10" x 6-1/2" x 5/8" BEAM BEARING PLATE 12" x 10-1/2" x 5/8" BEAM BEARING
WHERE BEAM IS 12" IN DEPTH OR PLATE WHERE BEAM IS 12" IN DEPTH
SHALLOWER. WHERE BEAM IS OR SHALLOWER. WHERE BEAM IS
GREATER THAN 12" IN DEPTH , GREATER THAN 12" IN DEPTH , WELD DECK TO CLOSURE ANGLE AS PER 12" CONT. BOND BEAM REINFORCED WITH (2)
PROVIDE A 12" x 6-1/2" x 3/4" BEARING PROVIDE A 12" x 10-1/2" x 3/4" BEARING DECKS SPECIFICATION. AT ZONE 2 AND 3 #4 CONT. HORIZONTAL. SLOPE BOND BEAM
PLATE. IN BOTH CONDITIONS, PROVIDE PROVIDE HOOK BARS AT EACH OF ROOF, WELD AT 6" o.c. MAX. WITH SLOPE OF ROOF DECK. CUT BLOCK
PLATE. IN BOTH CONDITIONS, PROVIDE
(2) - 3/4" DIAM. HEADED STUDS x 5" VERTICALLY REINFORCED CELL OF BELOW AS REQUIRED.
(4) - 5/8" DIAM. HEADED STUDS x 5"
EMBEDMENT MASONRY. SEE TYPICAL DETAIL.
PROVIDE HOOK BARS AT EACH EMBEDMENT
VERTICALLY REINFORCED CELL OF
8" CONT. BOND BEAM REINFORCED MASONRY. SEE TYPICAL DETAIL. 12" CONT. BOND BEAM REINFORCED
WITH (2) #5 CONT. BOTTOM.

2"
WITH (2) #5 CONT. BOTTOM.

VERTICAL WALL REINFORCEMENT VERTICAL WALL REINFORCEMENT


CENTERED IN MASONRY WALL. FILL ALL CENTERED IN MASONRY WALL. FILL ALL
CELLS WITH GROUT WHERE CELLS WITH GROUT WHERE
REINFORCING OCCURS. SEE WALL REINFORCING OCCURS. SEE WALL
ELEVATIONS, TYPICAL DETAILS AND WALL ELEVATIONS, TYPICAL DETAILS AND WALL
SCHEDULE FOR SIZE AND LOCATION OF SCHEDULE FOR SIZE AND LOCATION OF
REINFORCING. REINFORCING.

4
Typical Wide Flange Beam Spliced Over 8" CMU 5
Typical Wide Flange Beam Spliced Over 12" CMU 5" x 3" x 1/4" CONT. ANGLE. LONG LEG VERTICAL
DOWN. ANCHOR TO BOND BEAM WITH A 5/8" DIAM. HORIZONTAL BRIDGING AT TOP AND
EXPANSION ANCHOR 1'-0" FROM EACH END OF WALL BOTTOM CHORD OF JOIST TO BE FIELD
S689 1 1/2" = 1'-0"
S689 1 1/2" = 1'-0" AND AT 2'-0" o.c. MAX. PROVIDE 4" MINIMUM WELDED TO OUTSTANDING LEG OF Mark W. Nannis, P.E.
EMBEDMENT. ANGLE. Texas Design Firm #21364
1591 Riverside Drive
Gainesville, GA 30501
BUILD MASONRY AROUND EACH BEAM POCKET 3/16" STIFFENER PLATE ON EACH SIDE BUILD MASONRY AROUND EACH BEAM 3/16" STIFFENER PLATE ON EACH SIDE
POCKET AND GROUT FULLY UPON OF BEAM 770-614-6114 tel
AND GROUT FULLY UPON INSPECTION OF BEAM OF BEAM
BEARING PLATE AND WELD INSPECTION OF BEAM BEARING PLATE AND VERTICAL WALL REINFORCEMENT CENTERED IN
WELD MASONRY WALL. FILL ALL CELLS WITH GROUT All drawings, specifications, and other work product
WHERE REINFORCING OCCURS. SEE WALL 3" x 3" x 3/16" ANGLE x DEPTH OF ADJACENT of Mark W. Nannis, P.E. (henceforth referred to as "The
1' - 3 3/8" TYPICAL AT EACH JOIST WITH (2) - 5/8" DIAM. EXPANSION Engineer") for this project are instruments of service for
TYPICAL AT EACH ELEVATIONS, TYPICAL DETAILS AND WALL SCHEDULE
BEAM BEARING ANCHORS WITH 3-1/2" MINIMUM this project only and shall remain the property of The
1' - 3 3/8" BEAM BEARING 3/16 FOR SIZE AND LOCATION OF REINFORCING. Engineer whether the project is complete or not. Reuse
3/16 AND PLATE EMBEDMENT. FILL CELLS WITH GROUT
AND PLATE of any of the instruments of service of The Engineer by
15" x 6-5/8" x 5/8" BEAM BEARING PLATE WHERE 15" x 10-1/2" x 5/8" BEAM BEARING PLATE WHERE ANCHORS OCCUR. the owner or extensions of this project without the written
BEAM IS 12" IN DEPTH OR SHALLOWER. WHERE WHERE BEAM IS 12" IN DEPTH OR permission of The Engineer shall be at the owner's risk
BEAM IS GREATER THAN 12" IN DEPTH , PROVIDE SHALLOWER. WHERE BEAM IS GREATER and the owner agrees to defend, indemnify, and hold
A 15" x 6-5/8" x 3/4" BEARING PLATE. IN BOTH THAN 12" IN DEPTH , PROVIDE A 15" x 10-1/2" x harmless The Engineer from all claims, damages, and
3/4" BEARING PLATE. IN BOTH CONDITIONS, HORIZONTAL BRIDGING AT TOP AND HORIZONTAL BRIDGING AT TOP AND expenses including attorney's fees arising out of such
CONDITIONS, PROVIDE (4) - 3/4" DIAM. ANCHOR unauthorized reuse of The Engineer's instruments of
PROVIDE (4) - 3/4" DIAM. ANCHOR BOLTS x BOTTOM CHORD OF JOIST TO BE FIELD BOTTOM CHORD OF JOIST TO BE FIELD
BOLTS x 1'-2" LONG. WIDE FLANGE BEAM WIDE FLANGE BEAM service by the owner or others acting through the owner.
1'-2" LONG. WELDED TO OUTSTANDING LEG OF ANGLE. WELDED TO OUTSTANDING LEG OF
© 2022
ANGLE.
Client:

1/2"
VERTICAL WALL REINFORCEMENT
1/2"
Automotive
CENTERED IN MASONRY WALL. FILL ALL
VERTICAL WALL REINFORCEMENT CENTERED IN
MASONRY WALL. FILL ALL CELLS WITH GROUT
CELLS WITH GROUT WHERE REINFORCING
OCCURS. SEE WALL ELEVATIONS, TYPICAL
Managment
WHERE REINFORCING OCCURS. SEE WALL
ELEVATIONS, TYPICAL DETAILS AND WALL
SCHEDULE FOR SIZE AND LOCATION OF
DETAILS AND WALL SCHEDULE FOR SIZE
AND LOCATION OF REINFORCING. MINIMUM
3" x 3" x 3/16" ANGLE x 9" LONG WITH (2) - 5/8"
DIAM. EXPANSION ANCHORS WITH 3-1/2" MINIMUM Services, Inc.
OF (2) REINFORCED CELLS AT BEAM
PROVIDE HOOK BARS AT EACH EMBEDMENT. FILL CELLS WITH GROUT WHERE 505 S. Flagler Dr., Suite 1400
REINFORCING. MINIMUM OF (2) REINFORCED PROVIDE HOOK BARS AT EACH BEARING.
CELLS AT BEAM BEARING. VERTICALLY REINFORCED CELL OF VERTICALLY REINFORCED CELL OF ANCHORS OCCUR. West Palm Beach, FL 33401
MASONRY. SEE TYPICAL DETAIL. MASONRY. SEE TYPICAL DETAIL.
Project Number: 22008
Project Name:

Alliance Hyundai

6
Typical Detail at Beam Bearing at end of 8" CMU 7
Typical Detail at Beam Bearing at end of 12" CMU 8 Typical 12" CMU/Deck Connection (where joists occur on each side) 11001 North Fwy
Fort Worth, TX 76177
S689 1 1/2" = 1'-0" S689 1 1/2" = 1'-0" S689 3" = 1'-0"

Sheet Title:

RELEASED FOR CONSTRUCTION AND PERMIT


Typical Details
(CMU)

Sheet Number:

S689