1-10Ø VERT BAR

GENERAL STRUCTURAL NOTES 300


PER INTERSECTION
THE FOLLOWING NOTES APPLY UNLESS INDICATED OTHERWISE: CONCRETE COVER:
FOOTINGS AND TIE BEAMS: 75 mm (3")
GENERAL:
1. CONSTRUCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS OTHERWISE BEAMS AND COLUMNS: 40 mm OR AT LEAST 1 21" TO STIRRUPS OR TIES
SHOWN OR NOTED. SUSPENDED SLABS: 25 mm (1")
10Ø VERT BARS @
2. CONTRACTOR SHALL VERIFY ALL DIMENSIONS BEFORE ALL WORK BEGINS. CHECK WITH SLABS ON GRADE 40 mm OR AT LEAST 1 21" 400mm OC
ARCHITECT/CIVIL ENGINEER FOR CONDUITS/PIPE SLEEVES TO BE EMBEDDED IN CONCRETE. IN NO CASE SHALL COVER TO BE LESS THAN ANY BAR DIAMETER W/IN THE MEMBER FINISHED
3. CONTRACTOR MUST PROVIDE ADEQUATE SHORING & BRACING OF THE STRUCTURE FOR ALL PROVIDE CONCRETE SPACERS BEFORE FORM PLACEMENT TO MAINTAIN CONCRETE COVER. SURFACE
LOADS THAT MAY BE IMPOSED DURING CONSTRUCTION. GROUT:
CODE: 10Ø HOR BARS @
APPLY GROUT TO ANY CONSTRUCTION JOINT BEFORE POURING OF NEW CONCRETE.
UBC, 1997 EDITION UNIFORM BUILDING CODE EVERY 3 LAYERS OF CHB
ACI 318-14M AMERICAN CONCRETE INSTITUTE "BUILDING CODE REQUIREMENTS FOR SHORING AND FORM REMOVAL:
REINFORCED CONCRETE" ANY SHORING AND FORMWORKS INSTALLED SHALL BE STRIPPED OR DISMANTLED ONLY AFTER THE
AISC-05 MANUAL OF "AMERICAN INSTITUTE OF STEEL CONSTRUCTION" PRESCRIBED PERIODS AS FOLLOWS:
ASCE/SEI 7-10 AMERICAN SOCIETY OF CIVIL ENGINEERS, "MINIMUM DESIGN LOADS FOR WALL INTERSECTION DETAIL
BUILDINGS AND OTHER STRUCTURES" FOOTING SIDINGS 24 HOURS
NSCP, 2015 EDITION ASSOCIATION OF STRUCTURAL ENGINEERS OF THE PHILIPPINES, 300
1-10Ø VERT BAR
"NATIONAL STRUCTURAL CODE OF THE PHILIPPINES", C101-01 BEAMS
PER CORNER
DESIGN LIVE LOADS: SIDINGS 24 HOURS
RESIDENTIAL 1.9 KPa (40 PSF) BEAM BOTTOMS 7 DAYS

300
PARKING, RAMP 2.4 KPa (50 PSF)
STAIRS, CORRIDORS & LOBBIES 4.8 KPa (100 PSF) 10Ø VERT BARS @
SUSPENDED SLAB/SLABS ON DECKS 7 DAYS
EXTERIOR BALCONIES/AREAS 1.4 KPa (30 PSF) 400mm OC
ROOF DECKS 2.9 KPa (100 PSF) COLUMNS 24 HOURS
10Ø HORIZ BARS @
WIND - DESIGN WIND FORCES ARE BASED ON NATIONAL STRUCTURAL CODE LOOSEN FORMS CAREFULLY. DO NOT WEDGE PRY BARS, HAMMERS, OR TOOLS AGAINST FINISH
EVERY 3 LAYERS OF CHB
OF THE PHILIPPINES, 2015 EDITION CONCRETE SURFACES SCHEDULED FOR EXPOSURE TO VIEW.
SEISMIC - DYNAMIC ANALYSIS BASED ON THE NORMALIZED RESPONSE SPECTRUM CURVE
MISCELLANEOUS: FINISHED SURFACE
GIVEN IN THE UNIFORM BUILDING CODE (UBC) 1997.
REFER TO ARCHITECTURAL DRAWINGS FOR WALL OPENINGS, ARCHITECTURAL TREATMENT AND
STRUCTURAL SYSTEM: DIMENSIONS NOT SHOWN.
SPECIAL REINFORCED CONCRETE MOMENT RESISTING FRAME
CORNER WALL DETAIL
REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR SIZE AND LOCATION OF DUCT
DESIGN SOIL PRESSURES: OPENINGS, PIPING, CONDUITS, ETC, NOT SHOWN.
(3140 psf FROM SOIL TEST) MAX ALLOWABLE SOIL BEARING PRESSURE FOR DEAD + LIVE LOADS WITH A 1.33
INCREASE (4170 psf) PERMITTED FOR WIND OR SEISMIC LOADS COMBINED WITH GRAVITY LOADS. SHOP DRAWINGS SHALL BE SUBMITTED AND REVIEWED PRIOR TO FABRICATION.
THE BOTTOM OF EXCAVATIONS IS TO BE COATED WITH A LAYER OF 50 mm THICK GRAVEL BED PRIOR TO VERIFY ALL DIMENSIONS AND CONDITIONS AT THE PROJECT SITE PRIOR TO STARTING WORK
CASTING FOUNDATIONS OR PLACING ANY OTHER IMPORTED MATERIALS. CAST SLAB ON GRADE OVER A 50 AND NOTIFY THE ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.
mm THICK SAND OR GRAVEL BASE COMPACTED TO 95% MAXIMUM DRY DENSITY AND PROVIDE A 0.15 mm
VAPOR BARRIER (6MIL PE SHEET) IMMEDIATELY BENEATH ALL SLABS THICKNESS LESS THAN 400 mm. PROVIDE TEMPORARY ERECTION BRACING AND SHORING AS REQUIRED FOR STABILITY OF THE
STRUCTURE DURING ALL PHASES OF CONSTRUCTION. DOWELS
REINFORCED CONCRETE:

400
UNLESS OTHERWISE NOTED ALL CONCRETE - f'c = 20.7 MPa (3000 PSI), RANGE FOR W/C = 0.40 TO 0.42.
EVERY CUBIC METER OF CONCRETE SHOULD HAVE A MINIMUM OF 205 KGS OF CEMENT. SUBMIT MIX ADDITIONAL DETAILS AND STRUCTURAL NOTES 200 200
DESIGN INCLUDING ADMIXTURES TO BE USED PRIOR TO ANY CONCRETE POURING. THE FOLLOWING DETAILS SHALL APPLY TO THE STRUCTURE UNLESS INDICATED OTHERWISE:

THICKNESS
SLAB
MATERIAL SPECIFICATION: CMU LINTEL BM DETAIL & REINF SCHEDULE
10Ø @ 250
CONCRETE STRENGTH
NOTES:

75
COMBINED FOOTINGS f'c = 20.70 MPa (3,000 psi) 3 - 10Ø 400
VERT REINF PER 1. LINE UP BOND BEAMS IN CMU WALL WITH

450 LAP
ISOLATED FOOTINGS f'c = 20.70 MPa (3,000 psi)
GEN NOTES LINTEL AT TOP OF OPENING. EXTEND

MIN
TIE BEAMS f'c = 20.70 MPa (4,000 psi)
LINTEL REINF MIN 600mm PAST OPENING. CHB WALL FOOTING DETAIL
COLUMNS f'c = 20.70 MPa (3,000 psi) SCHED TOP BAR
2. CONSULT STRUCTURAL ENGINEER FOR
BEAM/SLABS ON METAL DECK f'c = 20.70 MPa (3,000 psi)
SCHED STIRRUPS OPENINGS LARGER THAN 3000mm.
STAIRS f'c = 20.70 MPa (3,000 psi)

D
LEAN CONCRETE f'c = 10.35 MPa (1,500 psi) GROUT SOLID

SEE PLAN
STEP HT
SLAB ON FILL f'c = 20.70 MPa (3,000 psi) 300
SCHED BOT BARS 12Ø x @ 460
LINTEL BEAM AND STIFFENER COLUMN f'c = 20.70 MPa (3,000 psi) W
300
FIN FLR
THE CONCRETE STRENGTH FOR ALL MOMENT FRAME COLUMN & BEAM JOINTS SHALL BE AS MENTIONED
ABOVE UNLESS NOTED OTHERWISE, REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 40. LINTEL REINF SCHEDULE
SUBMIT REINFORCING STEEL SHOP DRAWINGS WITH DETAILS PER ACI 315 MANUAL OF STANDARD WIDTH OPENING DEPTH HORIZ
STRIRRUPS
PRACTICE. W CLEAR SPAN D REINF

THICKNESS
100 1200 OR LESS 200 2-10Ø BOT 10Ø @ 400 1
ASTM A615, GRADE 40, REINFORCING STEEL SHALL BE USED FOR:

THICKNESS
1

SLAB
40
MAIN REINFORCEMENTS, SPIRALS, TIES AND STIRRUPS IN THE FRAME MEMBERS (BEAMS AND 100 1200 TO 3000 400 2-12Ø BOT 10Ø @ 200 300

SLAB
COLUMNS) COMPRISING THE LATERAL FORCE RESISTING SYSTEM
150 1200 OR LESS 200 2-16Ø BOT 10Ø @400
FIELD-BENT BARS
IN CASES WHERE WELDING OF BARS ARE REQUIRED, CONSULT WITH CIVIL ENGINEER OF RECORD BEFORE 150 1200 TO 1800 410 2-16Ø BOT 10Ø @ 200
IMPLEMENTATION. 2-22Ø BOT
STANDARD SPLICES SHALL BE 40 x BAR Ø AND 90° HOOKS OR BENDS SHALL BE 12 x BAR Ø. 150 1800 TO 3000 610 10Ø @ 200
1-16Ø TOP
TYPICAL DEPRESSED SLAB ON GRADE

ARCHITECT INTELLECTUAL PROPERTY LAW CIVIL / STRUCTURAL ENGINEER PROJECT TITLE OWNER SHEET CONTENTS DRAWING /
SHEET NO.
GENERAL STRUCTURAL
A PROPOSED THREE- NOTES
SPS. Atty. Rheina Lapena-Laguing
STOREY RESIDENTIAL BLDG.
WITH ROOFDECK
&
Atty. Robert Paul Gabao-Laguing S-1
PRC NO: 43097 VALID UNTIL : 05/13/2021 TIN NO: 712-316-211 PRC NO. : 163517 VALID UNTIL : 05/18/2021 LOCATION: ADDRESS:

PTR NO: 4605031 DATE ISSUED: FEBRUARY 19, 2020 PTR NO. : 4600470 DATE ISSUED : FEBRUARY 2020
Pinesville Subdivision Baguio City Pinesville Subdivision Baguio City
CAD BY: 1 8
DKBD
IAPOA NO: 41376-0239817-092718 PLACE ISSUED: BAGUIO CITY TIN : 333-064-693-000 PLACE ISSUED : BAGUIO CITY