You are on page 1of 2

Vérifié 

/ Reviewed No. de projet / Project No. 10-1004D


 Date reçue / Rec'd 17-Jan-2021
 No. de dossier KSH / KSH File No. 47510-0109
 No. d'équipement / Equipment No. 45-2510
 No. de réf KSH / KSH Code
This Stamp Displays the Acrobat Folder Paths
Refusé voir remarques / Rejected
Example #2
Revisez tel que noté / Revise as noted Resoumettre / Resubmit
Certifiez tel que noté / Certify as noted
This Stamp Displays the Name of the Stamp
Pour information / For information
Non retour / No return
Pas de commentaires / No comments

#0ttOc2TcEnEhFNf6bcBqfD
Vérifié: Reviewed:
Review is for general compliance with 
Vérification par rapport aux concepts émis 
et spécifiés d'après les devis du projet et la  the design criteria for the project and 
documentation contractuelle.  Aucune  contract documents.  No responsibility 
responsabilité ne sera assumée vis‐à‐vis  is assumed for correctness of dimension 
l'exactitude des dimensions et détails ci‐ or details.
joints.

Par / By: AP Date: 22-02-2021

10-1004D 47510-0109

RECEIVED
DOCUMENT CONTROL

17-Jan-2021
Update Performance
Standard Datasheet Characteristic as per latest CENTRIFUGAL PUMP SPECIFICATION
datasheet issued for impeller
CLIENT IRVING trim on 14th January 2021 CONTRACT NO:

ADDRESS: TM921 BY: Nicolas Billiau DATE: 07/17/2020


PLANT LOCATION: CANADA APPROVED: DATE:

ITEM: 45-2510 EQUIP.IDENT.NO: E217H412

60-69.4 PUMPING CONDITIONS 0.40-0.47


FLUID PUMPED: Stock - 3.5-4 % - pH=4.5-5.0 140-157 PUMP MATERIAL CLASS CD4MCuN
PUMPING TEMP. (PT) 60-65.6 deg C 140-150 deg F VISCOSITY @ PT 0.42-0.47 CST PH 4.5-5
2.89-4.42
SPECIFIC GRAVITY @ PT 0.98-1 DENSITY @ PT 61.19-61.38 Lb/ft³ 61.19-62.4
VAPOR PRESS. @ PT mmHg 2.89-3.72 PSI ABS SOLIDS CONTENT 3.5-4 %WT

PERFORMANCE CHARACTERISTICS
CAPACITY, GPM NORMAL 300
253 RATED 300.0 MIN. HYDRAULIC / THERMAL FLOW 157.4 / N/A
TDH, FT: NORMAL 63
83 RATED 112.0
115 DISCH.PRESSURE 47.6 PSI G

SUCTION PRESS., PSI G RATED 0.0 MAXIMUM 2.92


3.9
NPSH, FT ABS: AVAIL.(NORMAL) 23.8
26.0 (RATED) 6.0 REQD BY PUMP CURVE NO. 4155-1
BHP, hp (RATED) 17.3 (MAX) 27.0 EFFICIENCY (NORMAL) (RATED) 48.0
PUMP DESCRIPTION
TYPE 3180 S SIZE 3x6-12 RPM 1780 ROTATION CW CCW

IMPELLER TYPE Open DIA. in (RATED) 10.4375 (MAX) 12.0000


9.0600 (MIN BY MFR)

PACKING TYPE Add flushing plan


SIZE 0 NO. OF RINGS
SEAL CAGE YES NO
MECH.SEAL MFR and MODEL/DYN SEAL Chesterton 442C -19 SA RSC/RSC S FEPM W/ ADPT - Mechanical seal supplied and installed by end user
SUCTION FLGD SCRD SIZE 6'' ANSI 150# LB.ASA FACING RF POSITION CL SIDE FACING UP

DISCHARGE FLGD SCRD SIZE 3'' ANSI 150# LB.ASA FACING RF POSITION TOP CTR TANGENT SIDE

BEARINGS (MFR AND TYPE): RADIAL NUP 311ECP THRUST 7311 BECBY (VERT.) THRUST UP DOWN

MATERIAL: CASING CD4MCuN IMPELLER CD4MCuN SHAFT/SLEEVE Steel 4340 / 316SS

SPECIAL MATERIAL
CASING: VENT NPT DRAIN 3/4 NPT GAGE CONN. SUCTION DISCHARGE 1/2 / 1/2 NPT

STUFF.BOX: TAP FOR FLUSH NPT TAP FOR DRAIN NPT JACKETED 1/2 NPT CONN:COOL WATER RQD GPM

CASING: NO OF STAGE 1 MOUNTING: CENTERLINE FOOT BRACKET VERTICAL

CASING SPLIT: HORZ VERTICAL TYPE OF VOLUTE: SINGLE DOUBLE DIFFUSER


COVER PLATE JACKETED NPT CONN. GLAND COOLING NPT CONN. BEARING HOUSING JACKETED 1/2" drain NPT
PUMP BUILT TO: x ANSI API STD 610 SPECIAL SPECIFICATIONS
ThisCOUPLING
Stamp Displays the Acrobat Folder
TYPE: Non spacer
Paths
MAKE: Falk / 1050T10 GUARD: Steel
Example #2
LUBRICATION: Flood oil HYDROSTATIC TEST PRESSURE: 348.0 PSI G

WEIGHT (LB): PUMP 368.0 DRIVER 448 BASEPLATE 706


This
PUMP SERIALStamp
NO.: Displays
E217H412 the Name of the Stamp
PUMP CURVE NO.: 4155-1
SECTIONAL DWG.NO.: E217H412-PUMP-D-0197P
#0ttOc2TcEnEhFNf6bcBqfD
ELECTRIC MOTOR HP V
DRIVER
PH CPS RPM EQUIP # 45-2510
30.0 575 3 1800
MFR Customer's Choice Frame 286T CLASS DIVISION

STEAM TURBINE MFR STEAM PSI G EXHAUST PSI G


SPECIAL: MFR

REMARKS: Future Frame 324T Add future motor HP

REV.NO. REVISION BY DATE APPD DATE VENDOR ITT Corporation


1 comments added per KSH JD 11-4-2020 P.O.NO 910376
2 comments added per KSH JD 1-13-2021 C.O.NO
P.O.ITEM NO

ACCOUNT DIST.NO.
DELIVERY

NOT BEFORE DATE


02/01/2021 10-1004D 47510-0109
Customer: IRVING PULP & PAPER,LTD
Goulds Serial No: E217H412
RECEIVED Customer P.O. No: 910376
DOCUMENT CONTROL
Item No: 45-2510
17-Jan-2021 Project No: NEW PULP DRYER
Service: Wet-End Pulper Trim Pump Wet End Pulper Trim
Pump (no dash)

You might also like