Professional Documents
Culture Documents
#0ttOc2TcEnEhFNf6bcBqfD
Vérifié:
Vérification par rapport aux concepts émis
Reviewed:
Review is for general compliance with
et spécifiés d'après les devis du projet et la the design criteria for the project and
documentation contractuelle. Aucune contract documents. No responsibility
responsabilité ne sera assumée vis‐à‐vis is assumed for correctness of dimension
l'exactitude des dimensions et détails ci‐ or details.
joints.
10-1004D 47510-0104
RECEIVED
DOCUMENT CONTROL
17-Jan-2021
Standard Datasheet Update performance characteristic as
per latest datasheet sent for impeller CENTRIFUGAL PUMP SPECIFICATION
trim 22th january 2021 TM-938
CLIENT IRVING CONTRACT NO:
PUMPING CONDITIONS
FLUID PUMPED: Stock - 4% - pH=4.5-5.0 PUMP MATERIAL CLASS CD4MCuN
PUMPING TEMP. (PT) 60-65 deg C 140-150 deg F VISCOSITY @ PT 0.42-0.470 CST PH 4.5-5
SPECIFIC GRAVITY @ PT 0.98-1 DENSITY @ PT 61.19-62.4 Lb/ft³
VAPOR PRESS. @ PT mmHg 2.89-3.72 PSI ABS SOLIDS CONTENT 3.5-4 %WT
IMPELLER TYPE Open DIA. in (RATED) 19.1250 (MAX) 22.187517.6900 (MIN BY MFR)
DISCHARGE FLGD SCRD SIZE 12'' ANSI 150# LB.ASA FACING RF POSITION TOP CTR TANGENT SIDE
BEARINGS (MFR AND TYPE): RADIAL NUP 317ECP THRUST 7318 BECBY (VERT.) THRUST UP DOWN
SPECIAL MATERIAL
CASING: VENT NPT DRAIN 3/4 NPT GAGE CONN. SUCTION DISCHARGE 1/2 / 1/2 NPT
STUFF.BOX: TAP FOR FLUSH NPT TAP FOR DRAIN NPT JACKETED 1/2 NPT CONN:COOL WATER RQD GPM
Example
COUPLING TYPE: Non spacer #2 MAKE: Falk / 1100T10 GUARD: Steel
LUBRICATION: Flood oil HYDROSTATIC TEST PRESSURE: 348.0 PSI G
ACCOUNT DIST.NO.
DELIVERY 02/01/2021 10-1004D 47510-0104
NOT BEFORE DATE