Part 5 - Central Area - DRAINED SAND

ASV Pad 8330x12175 [IT4 new]

Spread footing verification


Input data
Project
Task : Part 5 - Central Area - DRAINED SAND
Part : Pad 8330x12175 [IT4 new]
Author : ASV
Date : 06-Apr-21

Settings
(input for current task)
Materials and standards
Concrete structures : EN 1992-1-1 (EC2)
Coefficients EN 1992-1-1 : user-defined
Article 2.4.2.4 : γc = 1.74
Article 2.4.2.4 : γs = 1.44

Settlement
Analysis method : Analysis using oedometric modulus
Restriction of influence zone : by percentage of Sigma,Or
Coeff. of restriction of influence zone : 20.0 [%]

Spread Footing
Analysis for drained conditions : DS/EN 1997-1 DK NA:2013
Analysis of uplift : Standard
Allowable eccentricity : 0.333
Verification methodology : according to EN 1997
Design approach : 3 - reduction of actions (GEO, STR) and soil parameters
Partial factors on actions (A)
Permanent design situation
State STR State GEO
Unfavourable Favourable Unfavourable Favourable
Permanent actions : γG = 1.10 [–] 0.90 [–] 1.10 [–] 0.90 [–]

Partial factors for soil parameters (M)


Permanent design situation
Partial factor on internal friction : γφ = 1.44 [–]
Partial factor on effective cohesion : γc = 1.44 [–]
Partial factor on undrained shear strength : γcu = 2.16 [–]
Partial factor on unconfined strength : γv = 2.16 [–]
Basic soil parameters
ϕef cef γ γsu δ
No. Name Pattern
[°] [kPa] [kN/m3] [kN/m3] [°]

1 Meltwater Sand 38.00 0.00 20.00 11.00

All soils are considered as cohesionless for at rest pressure analysis.

1
[GEO5 - Spread Footing (demoversion) | version 5.2020.42.0 | Copyright © 2020 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]
Part 5 - Central Area - DRAINED SAND
ASV Pad 8330x12175 [IT4 new]

Soil parameters
Meltwater Sand
Unit weight : γ = 20.00 kN/m3
Angle of internal friction : ϕef = 38.00 °
Cohesion of soil : cef = 0.00 kPa
Oedometric modulus : Eoed = 85.00 MPa
Saturated unit weight : γsat = 21.00 kN/m3

Foundation
Foundation type: centric spread footing
Depth from original ground surface hz = 1.50 m
Depth of footing bottom d = 1.50 m
Foundation thickness t = 1.50 m
Incl. of finished grade s1 = 0.00 °
Incl. of footing bottom s2 = 0.00 °
Overburden
Type: input unit weight
Unit weight of soil above foundation = 22.00 kN/m3

Geometry of structure
Foundation type: centric spread footing
Spread footing length x = 8.34 m
Spread footing width y = 12.18 m
Column width in the direction of x cx = 4.00 m
Column width in the direction of y cy = 4.00 m
Spread footing volume = 152.37 m3
Volume of excavation = 152.37 m3
Volume of fill = 0.00 m3
Material of structure
Unit weight γ = 25.00 kN/m3
Analysis of concrete structures carried out according to the standard EN 1992-1-1 (EC2).

Concrete : C 35/45
Cylinder compressive strength fck = 35.00 MPa
Tensile strength fctm = 3.20 MPa
Elasticity modulus Ecm = 34000.00 MPa
Longitudinal steel : B500
Yield strength fyk = 500.00 MPa
Transverse steel: B500
Yield strength fyk = 500.00 MPa
Geological profile and assigned soils
Thickness of layer Depth
No. Assigned soil Pattern
t [m] z [m]

1 - 0.00 .. ∞ Meltwater Sand

2
[GEO5 - Spread Footing (demoversion) | version 5.2020.42.0 | Copyright © 2020 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]
Part 5 - Central Area - DRAINED SAND
ASV Pad 8330x12175 [IT4 new]

Load
Load N Mx My Hx Hy
No. Name Type
new change [kN] [kNm] [kNm] [kN] [kN]
1 Yes DESIGN Design 20935.00 0.00 0.00 0.00 0.00
2 Yes SERVICE Service 19171.00 0.00 0.00 0.00 0.00
Surface surcharges in the vicinity of footing
Surcharge xs ys x y q α h
No. Name
new change [m] [m] [m] [m] [kPa] [°] [m]
1 Yes Surcharge No. 1 -11.64 -3.13 2.50 2.50 291.00 0.00 0.00
2 Yes Surcharge No. 2 -11.64 4.84 2.50 2.50 358.40 0.00 0.00
3 Yes Surcharge No. 3 -5.25 11.31 3.75 3.75 292.60 0.00 0.00
4 Yes Surcharge No. 4 0.43 9.64 2.50 7.05 331.00 0.00 0.00
5 Yes Surcharge No. 5 6.62 4.84 3.75 3.75 227.00 0.00 0.00

Name : Surcharge Stage - analysis : 1 - 0

12.18
+x
+y

8.34

Ground water table


The ground water table is at a depth of 5.08 m from the original terrain.

Global settings
Type of analysis : analysis for drained conditions

Settings of the stage of construction


Design situation : permanent

3
[GEO5 - Spread Footing (demoversion) | version 5.2020.42.0 | Copyright © 2020 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]
Part 5 - Central Area - DRAINED SAND
ASV Pad 8330x12175 [IT4 new]

Verification No. 1
Load case verification
Self w. ex ey σ Rd Utilization
Name Is satisfactory
in favor [m] [m] [kPa] [kPa] [%]
DESIGN Yes 0.00 0.00 239.84 1020.05 23.51 Yes
DESIGN No 0.00 0.00 247.34 1020.05 24.25 Yes
Analysis of bearing capacity - partial results
ϕd = 28.482 °
cd = 0.000 kPa
γ1prum = 20.000 kN/m3
γ2prum = 14.207 kN/m3
bef = 8.340 m
Nq = 15.524
Nc = 26.770
Nγ = 11.403
sq = 1.137
sc = 1.137
sγ = 0.726
dq = 1.000
dc = 1.000
dγ = 1.000
iq = 1.000
ic = 1.000
iγ = 1.000
bq = 1.000
bc = 1.000
bγ = 1.000
gq = 1.000
gc = 1.000
gγ = 1.000
Rd = 1020.048 kPa
Analysis carried out with automatic selection of the most unfavourable load cases.

Computed weight of spread footing G = 4190.22 kN


Computed weight of overburden Z = 0.00 kN
Vertical bearing capacity check
Shape of contact stress : rectangle
Most unfavorable load case No. 1. (DESIGN)

Parameters of slip surface below foundation:


Depth of slip surface zsp = 15.86 m
Length of slip surface lsp = 52.19 m

Design bearing capacity of found.soil Rd = 1020.05 kPa


Extreme contact stress σ = 247.34 kPa
Bearing capacity in the vertical direction is SATISFACTORY

4
[GEO5 - Spread Footing (demoversion) | version 5.2020.42.0 | Copyright © 2020 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]
Part 5 - Central Area - DRAINED SAND
ASV Pad 8330x12175 [IT4 new]

Verification of load eccentricity


Max. eccentricity in direction of base length ex = 0.000<0.333
Max. eccentricity in direction of base width ey = 0.000<0.333
Max. overall eccentricity et = 0.000<0.333
Eccentricity of load is SATISFACTORY

Horizontal bearing capacity check

Most unfavorable load case No. 1. (DESIGN)


Earth resistance: not considered
Horizontal bearing capacity Rdh = 13218.57 kN
Extreme horizontal force H = 0.00 kN
Bearing capacity in the horizontal direction is SATISFACTORY

Bearing capacity of foundation is SATISFACTORY

Verification No. 1
Settlement and rotation of foundation - input data
Analysis carried out with automatic selection of the most unfavourable load cases.
Stress at the footing bottom is not considered.

Computed weight of spread footing G = 3809.30 kN


Computed weight of overburden Z = 0.00 kN
Settlement and rotation of foundation - partial results
Layer Origin End Thickness Edef σor ∆σz Settlement
No. [m] [m] [m] [MPa] [kPa] [kPa] [mm]
1 1.50 1.55 0.05 57.37 30.50 226.22 0.13
2 1.55 1.60 0.05 57.37 31.50 226.20 0.13
3 1.60 1.65 0.05 57.37 32.50 226.12 0.13
4 1.65 1.70 0.05 57.37 33.50 225.96 0.13
5 1.70 1.75 0.05 57.37 34.50 225.69 0.13
6 1.75 1.80 0.05 57.37 35.50 225.28 0.13
7 1.80 1.90 0.10 57.37 37.00 224.31 0.26
8 1.90 2.00 0.10 57.37 39.00 222.50 0.26
9 2.00 2.10 0.10 57.37 41.00 219.99 0.26
10 2.10 2.20 0.10 57.37 43.00 216.84 0.26
11 2.20 2.30 0.10 57.37 45.00 213.13 0.25
12 2.30 2.40 0.10 57.37 47.00 208.99 0.25
13 2.40 2.65 0.25 57.37 50.50 200.94 0.59
14 2.65 2.90 0.25 57.37 55.50 189.07 0.56
15 2.90 3.15 0.25 57.37 60.50 177.42 0.52
16 3.15 3.40 0.25 57.37 65.50 166.61 0.49
17 3.40 3.65 0.25 57.37 70.50 156.88 0.46
18 3.65 3.90 0.25 57.37 75.50 148.27 0.44
19 3.90 4.40 0.50 57.37 83.00 137.61 0.81
20 4.40 4.90 0.50 57.37 93.00 125.85 0.74
21 4.90 5.08 0.18 57.37 99.80 119.26 0.25

5
[GEO5 - Spread Footing (demoversion) | version 5.2020.42.0 | Copyright © 2020 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]
Part 5 - Central Area - DRAINED SAND
ASV Pad 8330x12175 [IT4 new]

Layer Origin End Thickness Edef σor ∆σz Settlement


No. [m] [m] [m] [MPa] [kPa] [kPa] [mm]
22 5.08 5.40 0.32 57.37 103.36 115.21 0.43
23 5.40 5.90 0.50 57.37 107.87 109.34 0.64
24 5.90 6.40 0.50 57.37 113.37 103.31 0.61
25 6.40 6.90 0.50 57.37 118.87 98.20 0.58
26 6.90 7.90 1.00 57.37 127.12 91.87 1.08
27 7.90 8.90 1.00 57.37 138.12 84.54 0.99
28 8.90 9.90 1.00 57.37 149.12 78.19 0.92
29 9.90 10.90 1.00 57.37 160.12 72.47 0.85
30 10.90 11.90 1.00 57.37 171.12 67.22 0.79
31 11.90 12.90 1.00 57.37 182.12 62.37 0.73
32 12.90 14.90 2.00 57.37 198.62 55.87 1.31
33 14.90 16.61 1.71 57.37 219.00 48.70 0.82
Settlement of mid point of edge x - 1 = 13.6 mm
Settlement of mid point of edge x - 2 = 13.6 mm
Settlement of mid point of edge y - 1 = 15.3 mm
Settlement of mid point of edge y - 2 = 15.3 mm
Settlement of foundation center point = 23.9 mm
Settlement of characteristic point = 17.0 mm
(1-max.compressed edge; 2-min.compressed edge)

Settlement and rotation of foundation - results

Foundation stiffness:
Computed weighted average modulus of deformation Edef = 57.37 MPa
Foundation in the longitudinal direction is rigid (k=3.45)
Foundation in the direction of width is rigid (k=1.11)

Verification of load eccentricity


Max. eccentricity in direction of base length ex = 0.000<0.333
Max. eccentricity in direction of base width ey = 0.000<0.333
Max. overall eccentricity et = 0.000<0.333
Eccentricity of load is SATISFACTORY

Overall settlement and rotation of foundation:


Foundation settlement = 17.0 mm
Depth of influence zone = 15.11 m
Rotation in direction of x = 0.000 (tan*1000); (1.2E-17 °)
Rotation in direction of y = 0.000 (tan*1000); (0.0E+00 °)

6
[GEO5 - Spread Footing (demoversion) | version 5.2020.42.0 | Copyright © 2020 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]
Part 5 - Central Area - DRAINED SAND
ASV Pad 8330x12175 [IT4 new]

Name : Settlement Stage - analysis : 1 - 1

OG FG
1.50 1.50 1.50

15.11

Sigma,z
Sigma,or

Dimensioning No. 1
Analysis carried out with automatic selection of the most unfavourable load cases.

Verification of longitudinal reinforcement of foundation in the direction of x


60 prof. 25.0 mm, cover 75.0 mm
Cross-section width = 12.18 m
Cross-section depth = 1.50 m
Reinforcement ratio ρ = 0.17 % > 0.17 % = ρmin
Position of neutral axis x = 0.05 m < 0.94 m = xmax
Ultimate moment MRd = 14231.55 kNm > 5910.12 kNm = MEd
Cross-section is SATISFACTORY.

Verification of longitudinal reinforcement of foundation in the direction of y


40 prof. 32.0 mm, cover 75.0 mm
Cross-section width = 8.34 m
Cross-section depth = 1.50 m
Reinforcement ratio ρ = 0.27 % > 0.17 % = ρmin
Position of neutral axis x = 0.08 m < 0.94 m = xmax
Ultimate moment MRd = 15366.80 kNm > 14376.14 kNm = MEd
Cross-section is SATISFACTORY.

Spread footing for punching shear failure check


Column normal force = 20935.00 kN

7
[GEO5 - Spread Footing (demoversion) | version 5.2020.42.0 | Copyright © 2020 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]
Part 5 - Central Area - DRAINED SAND
ASV Pad 8330x12175 [IT4 new]

Maximum resistance at the column perimeter


Force transferred into found. soil = 3297.48 kN
Force transferred by shear strength of foundation = 17637.52 kN
Considered column perimeter u0 = 16.00 m
Shear resistance at the column perimeter vEd,max = 0.78 MPa
Resistance at the column perimeter vRd,max = 4.15 MPa
Critical section without shear reinforcement
Force transferred into found. soil = 15362.08 kN
Force transferred by shear strength of foundation = 5572.92 kN
Distance of section from the column = 2.47 m
Section perimeter u = 16.68 m
Shear stress at section vEd = 0.24 MPa
Shear resistance of section without shear reinforcement vRd,c = 0.39 MPa
vEd < vRd,c => Reinforcement is not required

Spread footing for punching shear is SATISFACTORY

8
[GEO5 - Spread Footing (demoversion) | version 5.2020.42.0 | Copyright © 2020 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]