Professional Documents
Culture Documents
Introduction To Electrical Machines: Step-Up Transformer. When The Secondary Winding Has Less Turns Than The
Introduction To Electrical Machines: Step-Up Transformer. When The Secondary Winding Has Less Turns Than The
CHAPTER TWO
TRANSFORMERS
2.1. INTRODUCTION
The transformer is a static device that transfers electrical energy from one electrical
circuit to another electrical circuit through the medium of magnetic field and without
a change in the frequency. The electric circuit which receives energy from the supply
mains is called primary winding and the other circuit which delivers electrical
energy to the load is called secondary winding.
Actually the transformer is an electric energy conversion device, since the energy
received by the primary is converted to useful electrical energy in the other circuits
(secondary winding circuit).
If the secondary winding has more turns than the primary winding, then the
secondary voltage is higher than the primary voltage and the transformer is called a
step-up transformer. When the secondary winding has less turns than the
primary windings then the secondary voltage is lower than the primary voltage and
the transformer is called step down transformer.
Note that a step-up transformer can be used as a step-down transformer, in which
the secondary of step-up transformer becomes the primary of the step-down
transformer. Actually a transformer can be termed a step-up or step-down
transformer only after it has been put into service.
The most important tasks performed by transformers are:-
i) Changing voltage and current levels in electrical power systems
ii) Matching source and load impedances for maximum power
transfer in electronic and control circuit and
iii) Electrical isolation (isolating one circuit from another )
Transformers are used extensively in ac power systems. AC electrical power can be
generated at one central location, its voltage stepped up for transmission over long
distances at very low losses and its voltage stepped down again for final use.
1
Introduction to Electrical Machines
voltage (HV) winding also , half of the winding is over one leg and the other half
over the second leg, as shown in Figure 2.1.
2 2 2
2
(a) (b)
Figure 2.1 Constructional details of single-phase (a) core-type transformer (b) Shell-
type transformer
Low voltage winding is placed adjacent to the steel core and high voltage winding
outside, in order to minimize the amount of insulation required. In shell-type
transformer the low voltage and high voltage windings are wound over the central
limb and are interleaved or sandwiched as shown in Figure2.1(b). Note that the
bottom and top are low voltage coils.
In core-type transformer, the flux has a single path around the legs or yokes. Figure
2.1(a). In shell-type transformer, the flux in the central limb divides equally and
returns through the outer two legs as shown in Figure 2.1(b).
There are two types of windings employed in transformers. The concentric coils are
used for core-type transformer as shown in Figure 2.1(a) and interleaved (or
sandwiched) coils for shell- type transformers as shown in Figure 2.2(b).
One type of laminations for the core and shell type of transformers is illustrated in
Figure 2.2 (a) and (b) respectively. In both core and shell-type transformers, the
individual laminations are cut in the form of long strips of L's, E’s and I's as shown in
Figure 2.3 .
2
Introduction to Electrical Machines
(a) (b)
Figure 2.2 two adjacent layers for (a) core and (b) shell type transformers
3
Introduction to Electrical Machines
and the steel core is placed. The laminations are then tightened by means of
clamps and bolts.
Low-power transformers are air cooled whereas larger power transformers are
immersed in oil for better cooling. In oil-cooled transformer, the coil serves as a
coolant and also as an insulation medium.
4
Introduction to Electrical Machines
The emf e1 in volt, induced in the primary of N1 turns by the alternating flux is given
by
d
e 1 N1
dt
N1mCos t
N1m sin( t )
2
Its maximum value, E1max occurs when Sin t is equal to 1.
2
E1m N1 m
and e E1m sin t
1
2
The RMS value of the induced emf E1 in the primary winding is
E 2
E1 1m fN1m
2 2
2 fN1m (2.1)
4.44 fN1m
Since the primary winding resistance is negligible hence e1, at every instant, must
be equal and opposite of V1. That is,
d
v1 e1 N1
dt
or V1 E1
The emf induced in the secondary is
d
e2 N 2 N 2 m cos t
dt
N 2 s in ( t )
2
Em 2 sin ( t )
2
Rms value of emf E2 induced in secondary winding is given by
E
E2 2m 2 fN 2 m (2.2)
2
4.44 fN 2 m
5
Introduction to Electrical Machines
E1 E2
Also, the ratio of 2 f m and this shows that the emf per turn in each
N1 N 2
of the windings is the same.
Example 2.1 A single phase transformer has 350 primary and 1050 secondary
turns. The net cross-sectional area of the core is 55 cm2. If the primary winding be
connected to a 400 V, 50 Hz single phase supply, calculate (i) the maximum value of
flux density in the core and (ii) the voltage induced in the secondary winding.
Solution
i) Voltage applied to the primary = 400 V
Induced emf in the primary, E1 voltage applied to the primary, V1 = 400 V
Number of turns in the primary N1 = 350
Net cross-sectional area Ai = 55 cm2
= 55 10-4 m2
Frequency of the supply f = 50 Hz
Induced emf in the primary is given by
E1 4.44f m N1 4.44f B m A i N1 E1 =
Maximum value of flux density in the core,
400
Bm
4.44 50 55 10 4 350
0.93 T ( Wb / m 2 )
ii) Number of turns in the secondary winding, N2 = 1050
For an ideal transformer,
6
Introduction to Electrical Machines
E1 N1
E2 N 2
Voltage induced in the secondary winding,
N2
E 2 E1
N1
1050
400
350
1200 V
Example 2.2 The required no-load voltage ratio in a single phase 50 Hz, core type
transformer is 6600/500. Find the number of turns in each winding, if the flux is to
be 0.06 Wb.
Solution
6000
i) No-load voltage ratio =
500
No-load voltage of low voltage winding = 500 V
Flux = 0.06 Wb
Frequency f = 50Hz
Induced emf in the low voltage winding (secondary) of the transformer is given by,
E 2 4.44f m N 2
or 500 4.44 50 0.06 N 2
Number ut turns in the low voltage,
500
N2
4.44 50 0.06
37.5 (not possible)
The number of turns in each winding should be a whole number, moreover each
winding in the core type transformer is accommodated on both the limbs. i.e. half
number of turns of each winding on one limb. As such the number of turns in each
winding should be even.
Considering these facts , the number of turns in low voltage winding, N2 = 38
ii) Number of turns in high voltage winding
V1 6600
N1 = N 2 × = 38 ×
V2 500
= 501.6 ( not possible)
Considering all the factors mentioned above, the number of turns in the high voltage
winding N1=500. Here the number of turns finally taken is 500 and not 502, because
the high voltage winding will be split up into a number of coils. With 250 turns on
each limb, high voltage winding on one limb can be split into 5 coils of 50 turns
each.
7
Introduction to Electrical Machines
V1' E1 .
The primary current I1 consists of two components. One component I1' is the load
component and counteracts the secondary m.m.f. I2N2 completely. The other
component is exciting current Ie which is composed of Ic and Im. The current Ic is in
' ' '
phase with V1 and product V1 Ic gives core loss. The resistance Rc parallel with V1
represents the core loss Pc, such that.
Pc I 2c R c V1' I c
V1'
2
Rc
V'
And Rc 1
Ic
'
The current Im lags V1 by 90° and this can, therefore , be represented in the
equivalent circuit by a reactance Xm, such that
V'
Xm 1
Im
Rc and Xm are shown in Figure 2.6 (b), which is the exact equivalent circuit of a
transformer. The resistance Rc and reactance Xm are called core-loss resistance and
magnetizing reactance, respectively.
For minor changes in supply voltage and frequency, which is common under normal
operation, Rc and Xm are treated constant.
In Figure 2.6 (a) and (b) , the ideal transformer has been introduced to show the
transformation of voltage and current between primary and secondary windings .
Even at this stage the transformer magnetization curve is assumed linear, since the
effect of higher order harmonic can't be represented in the equivalent circuit.
R1 jX1 jX2 R2
+
+ + +
I1 I2
E1 E2
V1 V2
_ _ _ _
8
Introduction to Electrical Machines
I1'
E1
N
I1' I 2 2
N1
N
E1 N V2 1
E2 1 N2
N2
r1' jx1'
N
I e 1 I2
N N2
I1 1
N2 I'c I'm
N
V1 2 N V2
N1 E1 2 E2
N1
N N
I1 1 r2 1
N2 N2
N
putting I 2 I1 1
N2
9
Introduction to Electrical Machines
N 2
I1 1 r2 I1r2'
N 2
2
N
Where r2' r2 1
N2
'
If resistance r2 is placed in the primary circuit, then the relation between voltage V1
'
and V2 is unaffected. This resistance r2 is called the secondary resistance referred
to primary. Therefore, the total resistance in the primary circuit is
2
N
re1 r1 r2 1 r1 r2'
N2
Hence re1 is called the transformer equivalent (or total) resistance referred to
primary winding. Similarly the primary resistance referred to secondary is
2
N
r1 2 and the equivalent ( or total) resistance referred to secondary is
N1
2
N
re2 r2 r1 2 r2 r1'
N1
Fehler! Es ist nicht möglich, durch die Bearbeitung von Feldfunktionen
Objekte zu erstellen.
Figure 2.6 (e) equivalent circuit in general form.
Secondary leakage reactance drop I2 x2, when transferred to primary is
N1 N 2
I 2 x 2 I1 1 x 2 I1x '2
N2 N 2
'
The quantity x 2 is called the secondary leakage reactance referred to primary. Total
primary leakage reactance is
2
N
x e1 x1 x 2 1 x1 x '2
N2
Where xe1, is called the equivalent or total leakage reactance referred to primary.
Likewise, the equivalent or total leakage reactance referred to secondary is
2
N
xe 2 x2 x1 2 x2 x1'
N1
The equivalent (or total) leakage impedance referred to primary is
z e1 re1 jx e1
10
Introduction to Electrical Machines
11
Introduction to Electrical Machines
jI
V1 1x
1
I1r1
jI x
2
2
E2
I2r2
V2
I1
I2
1 2
Ic Ie
Im
Figure 2.7 Phasor diagram for equivalent circuit of Figure 2.6 (e)
Approximate Equivalent Circuit: Approximate equivalent circuit is obtained from
the exact equivalent circuit Figure 2.6(e), if the shunt branch (Rc and Xm in parallel)
is moved to the .primary or secondary terminals as shown in Figure 2.8(a) and (b)
respectively. It may be seen from Figure 2.8 (a) that the exciting current Ie does not
flow through rl and x1, whereas Ie does flow through r1 and x1 in the exact
equivalent circuit. Thus the primary leakage impedance drop due to the exciting
current, i.e. Ie( r1 +jx1) has been neglected in Figure 2.8 (a), though it is not so
actually.
It may also be seen from Figure 2.8 (b) that Ie flows through r2 and x2, whereas Ie
does not flow through r2 and x2 in the exact equivalent circuit. Thus the secondary
leakage impedance drop due to Ie, i.e. Ie (r2 + jx2) has been included, though Ie (r2 +
jx2) is actually zero.
(a)
(b)
12
Introduction to Electrical Machines
(c) (d)
Figure 2.8 (a) and (b) Approximate equivalent circuits of a transformer (c) and (d)
Simplified forms of the approximate equivalent circuit.
Since the exciting current is only about 2 to 6 per cent of the rated winding current
in power and distribution transformers, the error introduced by neglecting Ie( r1
+jx1) or including Ie (r2 + jx2) is insignificant. However, the computational labor
involved is reduced considerably by the use of approximate equivalent circuits of
Figure 2.8(a) and (b). As before, one must keep in mind about the side to which all
the equivalent-circuit quantities have been referred.
Still further simplification is achieved by neglecting the shunt branch Rc and Xm in
Figure 2.8 (a) and (b) and this leads to equivalent circuit of Figure 2.8(c). This
simplification is tantamount to neglecting exciting current Ie in comparison with
rated currents, which is almost justifiable in large transformers, say over 100 KVA or
so. For transformers having ratings near 500 KVA or more, the equivalent resistance
re is quite small as compared with equivalent leakage reactance xe. Consequently re
may be neglected, leading to the equivalent circuit of Figure3 (d). Thus, when a
large power system is studied, a transformer is usually replaced by its equivalent
circuit of the form shown in Figure 2.8(d).
The equivalent circuit Figure 2.6(e) should be used only when the exciting current is
a large percentage of the rated current e.g., in audio-frequency transformers used in
electronic circuits, in transformers used for relaying and measurement purposes etc.
For high voltage surge investigations, the transformer equivalent circuit must be
modified to include the effects of inter-turn and turn to earth capacitances.
13
Introduction to Electrical Machines
(a) (b)
Figure 2.9 (a) Circuit diagram for open-circuit test on a transformer and (b)
approximate equivalent circuit at no load
The-ammeter records the no-load current or exciting current Ie. Since Ie is quite
small (2 to 6%) of rated current), the primary leakage impedance drop is almost
negligible, and for all practical purposes, the applied voltage V1 is equal to the
induced emf E1. Consequently, the equivalent circuit of Figure 2.6 (e) gets modified
to that shown in Figure 2.9( b).
The input power given by the wattmeter reading consists of core loss and ohmic
loss. The exciting current being about 2 to 6 percent of the full load current, the
2 2 2
ohmic loss in the primary( I e r1 ) varies from 0.04 percent 100 to 0.36
100 100
percent of the full-load primary ohmic loss . In view of this fact, the ohmic loss
during open circuit test is negligible in comparison with the normal core loss
(approximately proportional to the square of the applied voltage). Hence the
wattmeter reading can be taken as equal to transformer core loss.
V1 = Applied rated voltage on L.V. side,
Ie = exciting current ( or no-load current) and
Pc = core loss
14
Introduction to Electrical Machines
V V1
R CL 1
I c I e cos o
Core loss resistant
V12 V121
V1I e cos o Pc o
Also I c2 R CL Pc
P Pc
R CL c
I c2 I e cos o 2
Magnetizing reactance
V1 Pc
X mL
I m I e sin o
The subscript L with Rc and Xm is used merely to emphasize that theses values are
for the L.V. side.
It must be kept is mind that the values of Rc and Xm, in general, refer to the
side, in which the instruments are placed (the L.V. side in the present case). A
voltmeter is sometimes, used at the open-circuited secondary terminals, in order to
determine the turns ratio.
Thus the open-circuit test gives the following information: (i) core loss at rated
voltage and frequency, (ii) the shunt branch parameters of the equivalent circuit,
i.e. Rc and Xm and (iii) turns ratio of the transformer.
2.6.2. Short-Circuit Test
The low voltage-side of the transformer is short-circuited and the instruments are
placed on the high voltage side, as illustrated in Figure 2.10 (a).
Figure 2.10 (a) connection diagram for short circuit test on a transformer
Figure 2.10 (b) Equivalent circuit with short-circuit on the secondary side
15
Introduction to Electrical Machines
16
Introduction to Electrical Machines
leakage impedance parameters for both primary and secondary are required
separately, then it is usual to take r1 = r2=½ re) and x1 = x2=½ xe, referred to the
same side.
Thus, the short-circuit test gives the following information: (i) ohmic loss at rated
current and frequency and (ii) the equivalent resistance and equivalent leakage
reactance.
Voltage regulation of a transformer can be determined from the data obtained from
short-circuit test. Data of both open-circuit and short-circuit tests is necessary (i)
for, obtaining all the parameters of exact equivalent circuit and (ii) for calculating
the transformer efficiency.
How can a wattmeter connected on the H.V. side, record the ohmic in the L.V.
winding also? When rated current is made to flow in the H.V. winding, the 1.v.
winding must also carry rated current, because the transformer action requires
I1N1= I2N2. The flow of rated current in the L.V. winding causes ohmic loss, which
must be supplied from somewhere. The only way to provide L.V. winding loss is
from the input to H.V. side. But the entire input power to H.V. side is recorded by
the wattmeter, therefore, the ohmic losses in both windings are given by the
wattmeter reading.
It has already been stated that open-circuit and short-circuit tests should be
performed on the L.V. side and H.V. side respectively only for the sake of
convenience. This can he illustrated by considering a 3300/220V, 33KVA, single-
phase transformer.
For open-circuit test on low voltage side, the ranges of voltmeter, ammeter and
wattmeter are 220V (rated value), 6A ( 2 to 6% of rated current of 150A) and 6A,
220V respectively. These are the standard ranges for ordinary instruments and
therefore, more accurate readings can be obtained. If the open circuit test is
performed on the H.V. side, a source of 3300V may not be readily available. At the
same time, the instrument ranges are 3300V, 0.4A and 0.4A , 3300V which are
which are not within the range of ordinary instruments and the results obtained may
not be so accurate . Also it may not be safe to work on the high voltage side.
For a short-circuit test on the H.V. side, the instrument ranges are 165V (2 to 12%
of rated voltage of 3300V), l0A (rated current) and 10A, 165V, which are well within
the range of the ordinary instruments. On the other hand, instrument ranges, for a
short-circuit test on L.V. side are 11V, 150A, and 150A. 11V. Instruments of such
ranges and auto-transformer capable of handling 150A may not be readily available
and at the same time, the results may not be so accurate. It is for these reasons
that the open-circuit and short-circuit tests are conducted on L.V. and H.V. sides
respectively.
2.6.3. Polarity Test
On the primary side of a two-winding transformer, one terminal is positive with
respect to the other terminal at any one instant. At the same instant, one terminal
of the secondary winding is positive with respect to the other terminal. These
relative polarities of the primary and secondary terminals at any instant must be
known if the transformers are to be operated in parallel or are to be used in a
polyphase circuit.
17
Introduction to Electrical Machines
(a) (b)
Figure 2.11 Polarity test on a two winding transformer (a) subtractive polarity and
(b) additive polarity
When viewed from the H.V. side, the terminals are marked A1 and A2, the former,
i.e. A1 being on the extreme right. Terminals A1 and A2 marked plus and minus
arbitrarily in Figure 6. Now terminal A 1 is connected to one end of the secondary
winding and a voltmeter is connected between A2 and the other end of the
secondary winding. A voltage of suitable value is now applied to the H.V. winding.
Let E1 and E2 be the e.m.fs induced on H.V. and L.V. sides respectively. If the
voltmeter reading is equal to E1–E2 then secondary terminal connected to A1 is
positive and is marked a1, the L.V. terminal connected to A2 through the voltmeter is
negative and is marked a2 as shown in Figure 2.11(a). If voltmeter reading is equal
to E1+E2, then the terminals connected to A1 and A2 are negative and positive and
are marked a2 and a1 respectively as shown in Figure 2.11(b). The subscript
numbers 1,2 on the H.V. and L.V. windings are so arranged that when A2 is negative
with respect to A1. a2 is also negative with respect to a1 at the same instant. In
other words, if the instantaneous emf is directed from A2 to A1 in H.V. winding, it is
at the same time directed from a2 to a1 in the L.V. winding.
When the voltmeter reads the difference E1–E2, the transformer is said to possess a
subtractive polarity and when voltmeter reads E1+E2 the transformer has additive
polarity. In subtractive polarity, the voltage between A2 and a2 (or A1 and a1) is
reduced. The leads connected to these terminals and the two windings are,
therefore, not subjected to high voltage stress. In additive polarity the windings and
the leads connected to A1, A2, a1 and a2 are subjected to high voltage stresses. On
account of these reasons, subtractive polarity is preferable to additive polarity.
Example 2.3 A 20 kVA, 2500/250 V, 50 Hz, single-phase transformer gave the
following test result
Open-circuit test (on L.V. side):250 V, 1.4 A, 105 W.
Short-circuit test (on H.V. side): 104 V, 8 A, 320 watts.
Compute the parameters of the approximate equivalent circuit referred to high-
voltage and low-voltage sides. Also draw the exact equivalent circuit referred to the
low -voltage side.
Solution
From open-circuit test:
105
No-load power factor, cos 0 0.3
250 1.4
0 = 72.55 and sin 0 =0.954
Ic = Ie cos 0 = 1.40.3 = 0.42 A
18
Introduction to Electrical Machines
V 250
hence, R cL 1 595
I c 0.42
V 250
X mL 1 187
I m 1.336
Alternatively, the value of RcL and XmL can be determined as follows:
V 2 2502
R cL 1 595
Pc 105
V1 250
Now Ic 0.42 A
R cL 595
and I m I 2e I 2c 1.4 2 0.42 2 1.336 A
V 250
X mL 1 187
I m 1.336
From short circuit test:
V 104
Z eH sc 13
I sc 8
P 320
reH sc 8
2
Isc 82
2 2
x eH Z eH reH 132 52 12
Equivalent circuit parameters referred to L.V. side are:
RcL = 595 XmL = 187
2 2 2 2
1 1 1 1
reL reH 5 0.05 ; x eL x eH 12 0.12
k 10 k 10
This equivalent circuit is shown in Figure below (a)
x eL 0.12 reL 0.05
595 187
(a) (b)
19
Introduction to Electrical Machines
Figure (a) approximate equivalent circuit referred to L.V. side and exact equivalent
circuit referred to L.V. side.
Equivalent circuit parameters referred to H.V. side are:
R cH R cL k 2 595102 59,500
X mH X mL k 2 187102 18,700
reH = 5 ; xeH = 12
An equivalent circuit showing these parameters can easily be drawn.
Exact equivalent circuit parameters referred to L.V. side are:
1 1
r1L r1' H reL 0.05 0.025
2 2
1 1
x1L x1' H x eL 0.12 0.06
2 2
RcL = 595 and XmL = 187
The exact equivalent circuit is shown in Figure (b)
20
Introduction to Electrical Machines
or ,
t
t 2
t1
(a)
(b)
21
Introduction to Electrical Machines
0
l1
(c)
Figure 2.12 (a) Hysteresis loop for transformer core (b) exciting current and core
flux waveforms and (c) no-load phasor diagram of a transformer.
The no-load primary current Ie is called the exciting current of the transformer and
can be resolved into two components. The component Im along m is called the
reactive or magnetizing current , since its function is to provide the required
magnetic flux m. The second component along V'1 is Ic and this component is called
the core- loss component. When multiplied by V'1 gives the total core loss Pc.
P
V ' 1 I c Pc or I c c Amp.
V' 1
From Figure 2.12 (c), it is seen that
I e I m2 I 2c
Note that in an ideal transformer, core-loss current I c 0 and therefore exciting
current Ie equals to magnetizing current Im i.e. I e I m .
22
Introduction to Electrical Machines
emf Ex1 in the primary winding and lagging it (i.e. l1) by 90°. Since Ie leads Ex1 by
90°, it is possible to write EX1= -jIexl. The primary applied voltage V l must have a
component jIexl, equal and opposite to Exl. Here xl has the nature of reactance and is
referred to as the primary leakage reactance in ohms. It may be noted that x1 is a
fictitious quantity merely introduced to represent the effects of primary leakage flux.
V1 V1' I e ( r1 jx1 )
The primary leakage impedance drop shown in Figure 2.12(c), is drawn to a larger
scale, in comparison with Vl' or Vl, just for the sake of clarity. At no-load and V'1 and
V1 are very nearly equal. Even at full load primary leakage impedance drop in power
transformer is about 2 to 5% of V1, so that the magnitude of V'1 or E1 does not
change appreciably from no-load to full load.
2.6.5. Transformer Phasor Diagram Under Load
The secondary circuit of transformer is considered first and then the primary circuit,
for developing the phasor diagram of a transformer under load.
Further the mutual flux is drawn leading E2 by 90° and exciting current Ie is drawn
leading by the hysteretic angle . Note that the phasor V2 has purposely been
taken to the left of vertical line, so that E2 is vertically downward and the mutual
flux is horizontal.
The component of the primary current which neutralizes the demagnetizing effect of
I2 is
I'1 (I1N1 = I2N2) and drawn opposite to I2. The phasor sun of I'1 and Ie gives the
total primary current I1 taken from the supply mains . The primary leakage
impedance drop I1(r1+jx1) is depicted as explained earlier.
The voltage equation for primary circuit under load can be written as
1
1
l 2
2
2
jI 2
x2
x2
jI 2
Figure 2.15 Transformer phasor diagram for (a) lagging p.f. load and (b) leading p.f.
load
24
Introduction to Electrical Machines
N2 N
V1 V2 V1 V2 1
N1 N2
100 in percentage 100 in percentage
N2 V1
V1
N1
Here V1 is the primary applied voltage.
The change in secondary terminal voltage with load current is due to the primary
and secondary leakage impedances of the transformer. The magnitude of this
change depends on the load power factor, load current, total resistance and leakage
reactance of a transformer.
A distribution transformer should have a small value of voltage regulation (i.e. good
voltage regulation) so that the terminal voltage at the consumers does not vary
widely as the load changes. For a transformer of large voltage regulation (i.e. poor
voltage regulation), the voltage at the consumers' terminals will fall appreciably with
increase in load. This has a detrimental effect on the operation of fluorescent tubes,
T.V. sets, refrigeration motors, etc since these are designed to operate satisfactorily
at a constant voltage. Thus distribution transformer should be designed to have a
low value of leakage impedances.
The voltage regulation of a transformer can be obtained form its approximate
equivalent circuit referred to primary or secondary. Figure 2.16 (a) illustrates the
approximate equivalent circuit of a transformer referred to the secondary side and
the phasor diagram for this circuit is drawn in Figure 2.16 (b) for a lagging power
factor load. For the calculation of voltage regulation, draw an arc of radius OD
meeting the extension of line OA in F. It may be seen from Figure 2.16 (b) that OF
(= E2) is approximately equal to OC.
25
Introduction to Electrical Machines
2
2
2
2
Note carefully that E2-V2 is not equal to AD i.e. I2ze2. The change in secondary
terminal voltage is equal to the magnitude of E2 minus the magnitude of V2.
In Eq.(2.1), per unit voltage regulation for any load current I2 is
E 2 V2 I 2 re 2 I x
cos 2 2 e 2 sin 2 2.2
E2 E2 E2
In case I2, is rated current, then
It should be noted that Eqs. (2.1) to (2.3) are valid for lagging power factors only.
For leading power factor loads, the phasor diagram of Figure reveals that
26
Introduction to Electrical Machines
E 2 Oc V2 I 2 re 2 cos 2 I 2 xe 2 sin 2
Therefore , secondary terminal voltage drop, for any load current I2, is
E 2 V2 I 2 re 2 cos 2 I 2 xe 2 sin 2
p.u. voltage regulation at any load current I2 is given by
I 2 re 2 I x
cos 2 2 e2 sin 2
E2 E2
In case I2 is the rated ( or full-load)current, then p.u. voltage regulation is given by
r cos 2 x sin 2
Condition for zero voltage regulation: It can be seen from Eq. (2.3) that voltage
regulation varies with load power factor. If load power factor is varied with constant
values of load current and secondary emf, then zero voltage regulation will occur
when
r cos 2 x sin 2 0
I 2 re 2 r
tan 2 r e2
x I x xe 2
E2 2 e2
E2
x
magnitude of the load p.f. , cos 2 e 2
re 2
The negative value of tan2 indicates a leading power factor. Therefore, zero
x
voltage regulation occurs when load power factor is e 2 leading . For leading p.f.s.
ze2
x
greater than e 2 , the voltage regulation will be negative, i.e. the voltage will rise
ze2
from its no load value, as the transformer load is increased.
Condition for maximum voltage regulation: P.u. voltage regulation
r cos 2 x sin 2 .
The condition for maximum voltage regulation is obtained by dedifferentiating the
above expression with respect to 2 and equating the results to zero. Here again the
load current and secondary emf are assumed to remain constant.
d
p .u. regulation r sin 2 x cos 2 0
d 2
x
Or tan 2 x e 2
r re2
r
Any cos 2 e 2
z e2
Here tan2 is positive, therefore, maximum voltage regulation occurs at lagging load
re 2
p.f. equal to . In other words, maximum voltage regulation occurs when load
ze 2
power-factor angle 2 is equal to the leakage impedance angle of the transformer.
the magnitude of maximum voltage regulation is:
27
Introduction to Electrical Machines
r x I r r I x x
r e2 x e2 2 e2 e2 2 e2 e2
ze2 re 2 E 2 ze 2 E2 re 2
I2
E2 z e2
I z
re22 xe22 2 e 2 ze 2 pu
E2
2 2
2
I 2 re2 cos 2
I 2 x e 2 cos 2
2 2
2 90
(a) (b)
(c)
Figure 2.17 Phasor diagram for 1-phase transformer for (a) negative voltage
regulation (V.R);(b) zero V.R and (c) maximum V.R
Thus the magnitude of maximum voltage regulation is equal to the p.u value
equivalent leakage impedance of the transformer. For example, if a transformer has
ze2 = 0.054. then magnitude of maximum possible voltage regulation is 5.4%.
Phasor diagrams for a single-phase transformer for different operating power factors
are illustrated in Figure 2. In Figure 2.17 (a), E2 < V2 voltage regulation (V.R.) is
therefore negative . In Figure 2.17 (b) E2 = V2. V.R is zero. Figure 2.17 (c) is drawn
under the condition of maximum V.R, because here load power-factor angle 2 =
leakage-impedance angle of the transformer where
x cos 1 re 2
tan 1 e 2 .
re 2
ze 2
Example 2.4 A 6600/440 V, single-phase transformer has an equivalent resistance
of 0.02 p.u. and an equivalent reactance of 0.05 p.u. Find the full-load voltage
regulation at 0.8 pf lagging, if
the primary voltage is 6600 V. Find also the secondary terminal voltage at full load.
Solution
r cos 2 x sin 2
P.u. voltage regulation
0.02 0.8 0.050.6 0.046
E 2 V2
0.046
E2
For a primary voltage of 6600 V, the secondary no load voltage E2 is 440 V.
The change in the secondary terminal voltage
E2 V2 = 440 (0.046) = 20.25 V
and secondary terminal voltage
V2 = 440 + 20.25 V
28
Introduction to Electrical Machines
Example 2.5 A short-circuit test, when performed on the H.V. side of a 10 kVA,
2000/400 V, single-phase transformer gave the following data:
60 V, 4 A, 100 W
If the L.V. side is delivering full load (or rated) current at 0.8 p.f. lag and at 400 V,
find the voltage applied to H.V. side.
Solution
From short circuit data
P 100
reH sc 6.25
2
Isc 42
V 60
ZeH sc 15
Isc 4
2 2
x eH Z eH reH 152 6.252 13.61
For the L.V. side, the parameters are
2 2
1 1
reL reH 6.25 0.25
k 5
2 2
1 1
x eL x eH 13.61 0.544
k 5
Full load secondary current
S 10,000
I 2L 25 A
V2 400
E 2 V2 I 2 L reL cos 2 I 2 L x eL sin 2
Now
25 0.25 0.8 25 0.544 0.6 13.16 V
For V2 = 400 V, E2 = 400 + 13.16 = 413.16 V
The voltage applied to the primary is
2000
413.16 2065 .8 V .
400
2.9. TRANSFORMER LOSSES AND EFFICIENCY
Equipment is desired to operate at a high efficiency. Fortunately, losses in
transformers are small. Because the transformer is a static device, there are no
rotational losses such as windage and friction losses in a rotating machine. In a well-
designed transformer the efficiency can be as high as 99%.
2.9.1. Transformer Losses
There are mainly two kinds of losses in a transformer, namely
i) Core loss and
ii) ohmic loss
Core loss The core loss P c occurring in the transformer iron, consists of two
components, hysteresis loss Ph and eddy current loss P e i.e.
P c = P h + Pe
29
Introduction to Electrical Machines
The hysteresis and eddy current losses in the core can be expressed by :-
Ph K h f Bxm
and
2 2
Pe K e f B m
Where Kh = proportionality constant which depends upon the volume and quality of
the core material and units used.
Ke = Proportionality constant whose value depends on the volume and
resistivity of the core material, thickness of laminations and the units
employed
Bm = maximum flux density in the core and
f = frequency of the alternating flux
The value of the exponent x (called Steinmetz’s constant) varies from 1.5 to 2.5
depending upon the magnetic properties of the core material. Therefore, the total
core loss is
P c = KhfB1.6m + Kef2B2m
Ohmic Loss When a transformer is loaded, ohmic loss (I2R) occurs in both the
primary and secondary winding resistances. Since the standard operating
temperature of electrical machines is 750C. The ohmic loss should be calculated at
750C.
2.9.2. Transformer Efficiency
The efficiency of a transformer ( or any other device) is defined as the ratio the
output power to input power. Thus
Output power
Efficiency =
Input power
V2 I 2 cos 2
= 2.4
V2 I 2 cos 2 + Pc + I 2 2 R
Where P c = total core loss
I22R = total ohmic losses
V2I2 = output VA
Cos 2 = load power factor
Since the efficiencies of power and distribution transformers are usually very high, it
is therefore, more accurate to determine the efficiency from measurement of losses
than from the measurement of output.
Condition for Maximum Efficiency.
In Eq. (*), P c is constant and the load voltage V2 remains practically constant. A
d
specified values of load p.f. cos2, the efficiency will be maximum when 0.
dI 2
d
Therefore, 0 for Eq.(2.4) is
dI 2
30
Introduction to Electrical Machines
d V2 I 2 cos 2 Pc I 22 re 2 V2 cos 2 V2 I 2 cos 2 V2 cos 2 2 I 2 re 2
0
dI 2
V2 I 2 cos 2 Pc I 22 re 2
2
Or V2 I 2 cos 2 Pc I 22re2 V2 cos 2 V2 I 2 cos 2 V2 cos 2 2I 2re2
Or I 22 re 2 Pc 2.5
Hence the maximum efficiency occurs when the variable ohmic loss I 22 re 2 is equal to
the fixed core loss Pc. From Eq.(2.5) the load current I2 at which maximum
efficiency occurs is given by
Pc Pc
I2 I fl 2.6
re 2 2
I fl re 2
Thus the maximum efficiency, for a constant load current, occurs at unity power
factor (i.e. at purely resistive load). It is seen from Eq. (2.6) that the load current at
which maximum efficiency occurs does not depend upon the load power factor
because Pc and re2 are almost unaffected by a variation in the load power factor.
A reduction in the load power factor reduces the transformer output and therefore
the transformer efficiency is also reduced accordingly. Figure 2.18 illustrates the
effect of p.f. on efficiency. Note that transformer efficiency is maximum at the same
load current regardless of variation in the load power factor.
31
Introduction to Electrical Machines
max
32
Introduction to Electrical Machines
Note that the rated primary and secondary currents refer to the currents for which
the windings are designed.
Rated frequency refers to the frequency for which the transformer is designed to
operate.
Example 2.6 A 100 kVA, 1000/10000 V, 50 Hz, single phase transformer has an
iron loss of 1100 W. The copper loss with 5 A in the high voltage winding is 400 W.
Calculate the efficiencies at (i) 25 %, (ii) 50 % and (iii) 100 % of normal load for
power factors of (a) 1.0 and (b) 0.8. The output terminal voltage being maintained
at 10000 V. Find also the load for maximum efficiency at both power factors.
Solution
i) Efficiency at 25% of normal load, unity pf:
Iron losses = 1100 W
Copper losses with 5 A in secondary = 400 W
Secondary full load current, I2
100 1000
I2
10000
10 A
Current in the secondary at 25 % full load = ¼ 10 = 2.5 A
2
2.5
Copper losses at 25% full load = 400
5
= 100 W
Output at 25% full load = 0.25 100 1000 1
= 25 000 W
Efficiency at 25 % load, unity pf
25000
at 25% 100
25000 1100 100
95.4%
ii) Efficiency at 25 % full load, 0.8 pf:
25000 0.8
at 25% 100
25000 0.8 1100 100
94.34%
iii) Efficiency at 50 % full load, unity pf:
Copper losses at 25% full load = 400 W
Output at 50 % full load, unity pf = 0.5 100 1000 1
= 50 000 W
Iron losses = 1100 W
50000 1.0
at 50% 100
50000 1.0 1100 100
97.65%
iv) Efficiency at 50 % full load, 0.8 pf:
33
Introduction to Electrical Machines
50000 0.8
at 50% 100
50000 0.8 1100 400
97.1%
v) Efficiency at 100 % full load, unity pf:
2
10
Copper losses at 100% full load = 400
5
= 1600 W
Output = 100 1000 1 = 100 000 W
Iron losses = 1100 W
100000 1.0
at 100% 100
100000 1.0 1100 1600
97.37%
vi) Efficiency at full load, 0.8 pf:
100000 0.8
at 100% 100
100000 0.8 1100 1600
96.73%
vii) Load for maximum efficiency at unity pf:
Maximum efficiency occurs when the iron losses equal the copper losses. Let the
maximum efficiency occur at x per cent of the full load.
Copper losses at x % of full load = x2 1600
Thus x2 1600 = 1100
x = 0.829
Load for maximum efficiency = 0.829 100 = 82.9 kVA
viii) Load for maximum efficiency at 0.8 pf:
Load for maximum efficiency will remain the same irrespective of power factor
Thus load for maximum efficiency = 82.9 kVA
Example 2.7 A single phase transformer working at unity power factor has an
efficiency of 90% at both one half load and at the full load of 500 W. Determine the
efficiency at 75 % of full load.
Solution
Efficiency of the transformer at full-load = 0.9
Output at full load = 500 W
Let the iron losses of the transformer be = x watts
and the total copper losses at full load be = y watts
Then, the total losses at full load = x + y
Hence,
500
0.9
500 x y
10 A
Or 0.9x + 0.9y = 50 (i)
34
Introduction to Electrical Machines
3. The cost of standby (or spare) unit is much less when two or more
transformers are installed.
In any case, in the long run , electric power demand may become more than rated
KVA capacity of already existing transformer or transformers. Under such
35
Introduction to Electrical Machines
circumstances, the need for extra transformer arises; the extra unit must be
connected in parallel.
Note that the parallel operation of transformers requires that their primary windings
, as well as secondary windings are connected in parallel . In this section only the
parallel operation of single-phase transformers is considered.
The various conditions which must be fulfilled for the satisfactory parallel operation
of two or more single-phase transformers are as follows:
a) The transformer must have the same voltage ratios, i.e with the primaries
connected to the same voltage sources, the secondary voltage of all
transformers should be equal in magnitude.
Out of the conditions listed above, condition(d) must be strictly fulfilled. If the
secondary terminals are connected with wrong polarities, large circulating currents
will flow and the transformers may get damaged.
36
Introduction to Electrical Machines
inducted in a 3-phase energy system for stepping-up or stepping – down the voltage
as required. For 3-phase up or down transformation, three units of 1-phase
transformers or one unit of 3-phase transformer may be used. When three identical
units of 1-phase transformers are used as shown in Figure 2.20(a), the arrangement
is usually called a bank of three transformers or a 3-phase transformer bank. A
single 3-phase transformer unit may employ 3–phase core-type construction Figure
2.20(b) or three phase shell type construction.
Input
A B C
P S P S P S
a b c
Output
(a) (b)
Figure 2.20 (a)Three-phase transformer bank, both windings in star;(b) three-phase
core-type transformer
A single-unit 3-phase core-type transformer uses a three-limbed core, one limb for
each phase winding as shown in Figure 2.20(b). Actually, each limb has the L.V.
winding placed adjacent to the laminated steel core and then H.V. winding is placed
over the 1.v. winding. Appropriate insulation is placed in between the core and 1.v.
winding and also in between the two windings.
A 3-phase core-type transformer costs about 15% less than a bank of three 1-phase
transformers. Also, a single unit occupies less floor space than a bank.
2.12.1. Three-Phase Transformer Connections
Three-phase transformers may have the following four standard connections
(a) Star-Delta ( Y-) (b) Delta-Star (-Y)
(c) Delta-Delta (-) (d) Star-Star (Y-Y)
These connections are shown in Figures 2.21 and 2.22, where V and I are taken as
input line voltage and line current respectively. Primary and secondary windings of
one phase are drawn parallel to each other. With phase turns ratio from primary to
secondary as
N1/N2= a, the voltages and current in the windings and lines are shown in Figures
2.21 and 2.22. The various connections are now described briefly.
(a) Star-delta (Y-) Connection This connection is commonly used for stepping
down the voltage from a high level to a medium or low level. The insulation
on the h.v. side of the transformer is stressed only to 57.74%
1
x 100 of line to line voltage
3
For per-phase m.m.f. balance, I2N2 =I1N1
Here primary phase current, I1 = primary line current I
37
Introduction to Electrical Machines
N1
Secondary phase current , I 2 I aI
N2 1
Secondary line current 3 I 2 3 . aI
Also, voltage per turn on primary = voltage per turn on secondary
V 1 V2
.
3 N1 N 2
N2 V V
Secondary phase voltage, V2 .
N 1 3 a. 3
V
Secondary line voltage = secondary phase voltage =
a. 3
V V
Input VA = 3 . I = output VA = 3. . aI 3 VI
3 a. 3
Phase and line values for voltages and currents on both primary and secondary sides
of star-delta transformer are shown in Figure 2.21(a)
I 3kI kI
I 3
V
V I
3 3k V
V kI kI
I 3 k 3V
V
3 k
(a)
(b)
Figure 2.21 (a) Star-delta connection and (b) delta-star connection of 3-phase
transformers
(b) Delta-Star (-Y) connection:- This type of connection is used for stepping
up the voltage to a high level. For example, these are used in the beginning
of h.v. transmission lines so that insulation is stressed to about 57.74% of
line voltage
Delta-star transformers are also generally used as distribution transformers for
providing mixed line to line voltage to high-power equipment and line to neutral
voltage to 1-phase low-power equipment. For example, 11kV/400V, delta-star
distribution transformer is used to distribute power to consumers by 3-phase four-
wire system. Three-phase high–power equipment is connected to 400V, three line
wires, whereas 1-phase low-power equipment is energized from 231 V line to
neutral circuits.
38
Introduction to Electrical Machines
39
Introduction to Electrical Machines
I kI kI
V V I V
k 3 kI V
I kI V 3k
V k
3 3
(a) (b)
Figure 2.22 (a) Delta-delta connection and (b) Star-star connection of three-phase
transformers.
(d) Star-Star (Y-Y) Connection
This connection is used for small h.v transformers . As stated before, with star
connection, turns per phase are minimum and the winding insulation is stressed to
57.74% of line voltage. Star-star connection is rarely used in practice because of
oscillatory neutral problems.
40
Introduction to Electrical Machines
V 11000
phase voltage on primary, VP1 L1 V
3 3
phase current on primary, I P1 I L1 20A
VP1 VP 2
Here, and I p1 12 I p 2 1
12 1
11000
Phase voltage on sec ondary, Vp2 529.25V
3 x 12
Line voltage on sec ondary , VL2 Vp2 529.25V
Phase current on sec ondary I p 2 12 I p1 12 20 240A
Line current on sec ondary I L2 3 I p 2 3 240 415.68A
3Vp2 .I p2 11000 1
Output KVA 3. 240 x 381.04 KVA
1000 3 x 12 1000
41
Introduction to Electrical Machines
I L1 20A I L2
I L1 20 A
VP1 I P1 VP 2 VL2
VL1 11000 V I P2
I P2 VP 2
VL1 11000 V I P1 VL 2
(a)
(b)
I L1 20A I L2 3I P 2 IL2
(c) (d)
42
Introduction to Electrical Machines
1 1
= (line current on h.v. side) = x 2.1 = 1.212A
3 3
Phase Shift
Some of the three-phase transformer connections will result in a phase shift
between the primary and secondary line-voltages. Consider the phase voltages,
shown in Figure 2.24, for the Y- connections. The phases VAN and Va are aligned,
but line voltage VAB of the primary leads the line voltage Vab of the secondary by
300. It can be shown the -Y connection also provides a 300 phase shift in there line
–to-line voltage. This property of phase shift in Y- or -Y connections can be used
advantageously in some applications.
(a)
43
Introduction to Electrical Machines
30
30
(b)
Figure 2.25 V-connection
Consider Figure 2.25(a) in which one transformer, shown dotted is removed. For
simplicity the load is considered to by Y- connected. Figure 2.25(b) shows the phase
diagram for voltages and currents. Here VAB, VBC and VCA represent the line-to line
voltage of the primary Vab, Vbc and Vcb secondary and Van, Vbn and Vcn represent the
phase voltages of the load. For an inductive load the load currents Ia, Ib and Ic will
lag the corresponding voltages Van, Vbn and Vcn by the load phase angle θ.
Transformer winding ab and bc deliver power
Pab Vab I a cos30
Pbc Vcb I c cos 30
Let Vah = Vcb = V, Voltage rating of the transformer secondary winding.
Ia = Ic = I current rating of the transformer secondary winding and = 0 for
a resistive load. Power delivered to the load by the V connection is
Pv 2 cos 300
0.58
P 3
The V connection is capable of delivering 58% power without overloading the
transformer (i.e., not exceeding the current rating of the transformer winding).
2.12.2. Three-Phase Transformer of A Common Magnetic Core (Three
Phase Unit Transformer)
A three phase transformer can be constructed by having three primary and three
secondary windings on a common magnetic core. Consider three single-phase core-
type units as shown in Figure 2.26(a). For simplicity, only the primary winding has
been shown. If balanced three-phase sinusoidal voltages are applied to the
windings, the fluxes a, b, and c will also be sinusoidal and balanced. If the three
legs carrying these fluxes are merged, the net flux in the merged leg is zero. This
leg can therefore be removed as shown in Figure 2.26(b). This structure is not
convenient to build.
44
Introduction to Electrical Machines
c a
a
b
b c
a b c 0
(a)
(b) (c)
(d)
Figure 2.26 development of a three-phase core-type transformer.
However, If section II is pushed in between sections I and III by removing its yokes,
a common magnetic structure shown in Figure 2.26(c), is obtained.
This core structure can be built using stacked laminations as shown in Figure
2.26(d). Both primary and secondary windings of a phase are placed on the same
leg. Note that the magnetic paths of legs a and c are somewhere longer than that of
leg b (Figure 2.26 (c). This will result in some imbalance in the magnetizing
currents. However, this imbalance is not significant.
Figurer 2.27 shows a picture of a three-phase transformer of this type. Such a
transformer weight less , costs less, and requires less space than a three-phase
transformer bank of the same rating. The disadvantage is that if one phase breaks
down, the whole transformer must be removed for repair.
45
Introduction to Electrical Machines
2.13. AUTOTRANSFORMERS
Introduction to Electrical Machines
In principle and in general construction, the autotransformer does not differ from
the conventional two-winding transformer so far discussed. It does differ from it.
however, in the way the primary and secondary windings are interrelated.
It will be recalled that in discussing the transformer principles of operation, it was
pointed out that a counter emf was induced in the winding, which acted as a primary
to establish the excitation ampere turns. The induced voltage per turn was the same
in each and every turn linking with the common flux of the transformer. Therefore,
fundamentally it makes no difference in the operation whether the secondary
induced voltage is obtained from a separate winding linked with the core or from a
portion of the primary turns. The same voltage transformation results in the two
situations. When the primary and secondary voltage are derived from the same
winding. the transformer is called an autotransformer.
An ordinary two-winding transformer may also be used as an autotransformer by
connecting the two windings in series and applying the impressed voltage across the
two, or merely to one of the windings. It depends on whether it is desired to step
the voltage down or up, respectively. This is shown in Figure 2.29(a) for the step-
down connection; the step-up connection is illustrated in Figure 2.29(b).
b
V2
I1
I2 - I1
(a) (b)
Figure 2.29 Autotransformers: (a) step-down; (b) step-up.
In Figure 2.29(a) the input voltage V1 is connected to the complete winding (a-c)
and the load RL is connected across a portion of the winding, that is, (b-c).The
voltage V2 is related to V1 as in the conventional two-winding transformer, that is,
N bc
V2 V1 2.10
N ac
where Nbc and Nac are the number of turns on the respective windings. The ratio of
voltage transformation in an autotransformer is the same as that for an ordinary -
transformer, namely,
N ac V1 I 2
k 2.11
N bc V2 I1
with k > 1 for step-down.
Assuming a resistive load for convenience, then,
V
I2 2
RL
Assume that the transformer is 100% efficient.The power output is
P V2 I 2 2.12
47
Introduction to Electrical Machines
Note that I1 flows in the portion of winding ab, whereas the current (I2 – I1) flows in
the remaining portion bc. The resulting current flowing in the winding bc is always
the arithmetic difference between I1 and I2 , since they are always in opposite sense.
Remember that the induced voltage in the primary opposes the primary voltage. As
a result. the current caused by the induced voltage flows opposite to the input
current.
In an autotransformer, the secondary current is this induced current, that is,
I1 I 2 I1 I 2 2.13
Hence the ampere-turns due to section bc, where the substitutions I 2 kI1 and
N
N bc ac are made according to Eq. (2.11), is
k
ampere-turns due to section bc I 2 I1 N bc
kI1 I1 N bc 1
I1N ac 1 I1N ab
k k
ampere turns due to sec tion ab
Thus the ampere-turns due to sections bc and ab balance each other, a characterstic
of all transformer actions.
Equation (2.12) gives the power determined by the load. To see how this power is
delivered, we can write the equation in a slightly modified forn. By substituting Eq.
(2.13) into Eq. (2.12), we obtain
P V2 I 2 V2 I1 I 2 I1
V2 I1 V2 I 2 I1 W 2.14
This indicates that the load power consists of two parts. The first part is
We will see in the following examples that most of the power to the load is directly
conducted by winding ab. The remaining power is transferred by the common
winding bc. To show these powers Pc and P tr in terms of the total power P. ue
proceed as follows:
Pc V2 I1 I1 1
P V2 I 2 I 2 k
and
Ptr V2 I 2 I1 I 2 I1 k 1
P V2 I 2 I2 k
P P k 1
Thus Pc and Ptr with a > 1 for a step-down autotransformer.
k k
Example 2.10 A standard 5-kVA 2300/230-V distribution transformer is
connected as an autotransformer to step down the voltage from 2530 V to 2300 V.
The transformer connection is as shown in Figure 2.29 (a). The 230-V winding is
section ab, the 2300-V winding is bc. Compare the kVA rating of the autotrans-
48
Introduction to Electrical Machines
former with that of the original two-winding transformer. Also calculate Pc, P tr, and
the currents.
Solution
The rated current in the 230-V winding (or in ab) is
5000 VA
I1 21.74 A
230
The rated current in the 2300-V winding (or in bc) is
5000
I 2 I1 2.174 A
2300
Therefore,
I 2 2.174 I1 23.914 A
The secondary current I2 can also be calculated from
2530
I 2 kI1 21.74 23.914 A
2300
2530
Since the transformation ratio k 1.1
2300
P V1I1 V2 I 2 2530 21.74 55.00 kVA
The conducted power is
P 55,000
Pc 50 kVA
k 1 .1
and that transformed is
Ptr P
k 1 55,000 1.1 1 5.0 kVA
k 1.1
Consider now the step-up transformer of Figure 2.29(b). Following reasons similar to
those above, it follows that
where we made the substitution of I1 from Eq. (2.13), which really is kirchhoff's
current law applied to point b. To show this, note at point b we have
I1 I 2 I1 I 2
so that
I1 I 2 I 2 I1 I 2 I1 I 2
Again, Eq. (2.17) shows us that the power supplied to the load consists of two parts,
and
49
Introduction to Electrical Machines
Pc V1I 2 I 2
k 2.20
P V1 I1 I1
and
Ptr V1 I1 I 2 I1 I 2
1 k 2.21
P V1I1 I1
Thus for the step-up transformer with a < 1, we obtain Pc kP and Ptr P 1 k
As before, Pc is the power directly conducted to the load and Ptr is the portion that is
transformed.
Example 2.11 Repeat the problem of Example 2.10 for a 2300 V-to-2530 V
step-up connection as shown in Figure 2.29 (b).
Solution
As calculated in Example 2.10, the current rating of the winding ab is I2 = 21.74 A,
which also is the load current. The output voltage is 2530 V; thus the volt-ampere
rating of the autotransformer is
50
Introduction to Electrical Machines
51
Introduction to Electrical Machines
PROBLEMS
2.2. A single phase, 50 Hz, 220/3000 V, transformer has a net cross-sectional area
of the core 400 cm2. If the peak value of flux density in the core is 1.239 T,
calculate the suitable values for the number of turns in primary and secondary
windings
2.3. Single-phase 50 Hz transformer has 80 turns on the primary winding and 280
in the secondary winding. The voltage applied across the primary winding is
240 V at 50 Hz. Calculate (i) the maximum flux density in the core and (ii)
induced emf in the secondary. The net cross-sectional area of the core can be
taken 200 cm2.
Ans.(i) 0.675 Wb/m2; (ii) 840 V
2.4. The values of the resistance of the primary and secondary windings of a
2200/200V, 50 Hz single phase transformer are 2.4 and 0.02 respectively.
Find (i) equivalent resistance of primary referred to secondary, (ii) equivalent
resistance of secondary referred to primary, (iii) total resistance of transformer
referred to secondary and (iv) total resistance of transformer referred to
primary.
2.5. Short circuit test performed on 20 kVA, 2000/200 V, 50 Hz, single phase
transformer gave the following readings:
With 100 V applied to the primary, full load current circulated in the short
circuited secondary with power drawn of 300 W. Calculate the secondary
terminal voltage on full- load (i) at unity power factor, (ii) at pf of 0.75
lagging and (iii) at pf of 0.8 leading. Find also the percentage regulation in
each case. Ans.:(i) 197 V, 1.5 % (ii) 191.4 V, 4.28% (iii)
203.3 V, -1.66%
2.6. The iron and full load copper losses in a 40 kVA single phase transformer are
450 and 850 W respectively. Find (i) the efficiency at full load when the power
factor of the load is 0.8 lagging, (ii) the maximum efficiency and (iii) the load
at which the maximum efficiency occurs.
2.8. Calculate the efficiency at full load, half load and one-fourth load at (i) unity pf
and (ii) 0.71 pf lagging, for a 80 kVA, 1100/250 V, 50 Hz, single phase
transformer, whose losses are as follows:
Iron losses= 800 W
Total copper losses with 160 A in the low voltage winding is 200 W.
52
Introduction to Electrical Machines
Ans.:(i) 98.04 Y., 97.57 %, 95.92 % (ii) 97.25 %, 96.61 %;, 94.36
%.
2.9. The parameters of the equivalent circuit of a 10 kVA, 2000/ 400 V, 50 Hz,
single phase transformer are as follows:
Primary winding: r1=5.5 ; x1=12
Secondary winding: r2 =0.2 ; x2 = 0.45
If the primary supply voltage is 2000 V, calculate the approximate value of
the secondary voltage at full load 0.8 power factor lagging.
Ans.:377.6 V
2.12. A 50-hp 440-V three-phase motor with an efficiency of 0.88 and a power
factor of 0.82 on full load is supplied from a 6600/440-V -Y connected
transformer. Calculate the currents in the high- and low-voltage transformer
windings when the motor is running at full load.
53