QES PEV:C-ENG229
Rev. : 00 Date : 27-04-2021
Checks for Control Room Pipe/Box Culvert Design & Drawing
Reference 01 : Bureau of Indian Standards ( IS : 456_2000), & Other relavent IS Standards
Reference 02 : Suzlon Technical Specification No.: ENG:PEV:T-012 , CEA Technical
Standards for Construction of Electrical Plants and Electric Lines Regulations, 2010.
Sl.No Parameters to be Checked OK NOT OK Remarks, if any
A DESIGN UNITS
1 All Design units are as per Standard International (SI) Metric System
B DESIGN ASSUMPTIONS
C DESIGN PARAMETERS
D DESIGN LOADS
2 Dynamic loads are as Per Vendor Data for Heavy Rotating Equipment
Corrugated metal pipe is used in rural areas if approved by the County. All
2 corrugated metal pipe shall be galvanized or aluminized steel or aluminum
pipe.
7 Velocity in culvert for the 100-year event will not exceed 4.5m/s.
8 At a minimum, culvert is designed to withstand heavy vehicular load loading.
9 Culvert is aligned with the natural channel.
Culverts are sized to pass the 5-year flow in a ditch without overtopping the
10 driveway.
Cover over culvert must meet minimum cover recommended by the pipe
11 structural design requirements or 1-foot, which ever is greater
G CALCULATION PRESENTATION
Calculations Cover Sheet with Document Number, Project title, Caculation
1 Subject, Date, etc. is provided
The Index Sheet has been coordinated with the current list of
3 architectural drawings with respect to drawing number and title.
A drawing has been included to identify abbreviations and symbols utilized on
the project drawings and have been coordinated with the other architectural
4 drawings for compliance.
Verification team
Reviewed & Verfied by Approved & Accepted by
Remarks
Name
Date
Sign.