Control Room Pipe/Box Culvert Design & Drawing Doc. No.

QES PEV:C-ENG229
Rev. : 00 Date : 27-04-2021
Checks for Control Room Pipe/Box Culvert Design & Drawing
Reference 01 : Bureau of Indian Standards ( IS : 456_2000), & Other relavent IS Standards
Reference 02 : Suzlon Technical Specification No.: ENG:PEV:T-012 , CEA Technical
Standards for Construction of Electrical Plants and Electric Lines Regulations, 2010.
Sl.No Parameters to be Checked OK NOT OK Remarks, if any

A DESIGN UNITS

1 All Design units are as per Standard International (SI) Metric System

B DESIGN ASSUMPTIONS

1 General design Methodology is provided

2 All Design assumptions are clearly described

C DESIGN PARAMETERS

1 Concrete & Reinforcement grades

2 Soil Unit weight is provided

3 Young's modulus is provided

D DESIGN LOADS

1 Design Loads are as per Project Design Basis /IS Codes

2 Dynamic loads are as Per Vendor Data for Heavy Rotating Equipment

3 Thermal loads are as per Project Design Basis


Load combinations for Allowable Stress Design are as per Project Design Basis ,
4 IS Codes
Load combinations for Ultimate Strength Design are as per Project Design
5 Basis , IS Codes

F BOX/PIPE CULVERT DESIGN


All culverts shall be constructed of reinforced concrete in round, elliptical, or
box shapes. (Concrete box culverts may be cast-in-place or supplied in precast
1 sections.)

Corrugated metal pipe is used in rural areas if approved by the County. All
2 corrugated metal pipe shall be galvanized or aluminized steel or aluminum
pipe.

Culverts within public right-of-way have a minimum of 24-inches in diameter,


3 or a minimum cross sectional area of 3.3 ft2.

4 Box culverts have a minimum inside height dimension of 3-feet.


The culvert capacity charts and nomographs provided in the Culverts IS
5 standards were used to determine culvert capacity.

Minimum flow velocity in culvert for frequently occurring storms is 1.25m/s.


Velocities have been checked for a flow depth in the culvert equal to 25% of
6 the culvert diameter

7 Velocity in culvert for the 100-year event will not exceed 4.5m/s.
8 At a minimum, culvert is designed to withstand heavy vehicular load loading.
9 Culvert is aligned with the natural channel.
Culverts are sized to pass the 5-year flow in a ditch without overtopping the
10 driveway.
Cover over culvert must meet minimum cover recommended by the pipe
11 structural design requirements or 1-foot, which ever is greater

Proposed culverts are designed to be constructed with flared end sections or


12 headwall/wingwalls as appropriate.

Culvert slopes are a minimum of 2% or are the result of a minimum flow


velocity in culvert for frequently occurring storms of 1.25 m/s. Velocity shall be
13 checked for a flow depth in the culvert equal to 25% of the culvert diameter.

G CALCULATION PRESENTATION
Calculations Cover Sheet with Document Number, Project title, Caculation
1 Subject, Date, etc. is provided

2 Name of calculation originator/Checker on Claculation Sheets


3 Subject of Structural Calculations
Reference drawing number,Table of contents , List of appilcable coded,&
4 Standards .
General description of Structure design Methodology/Design Criteria /Primary
5 Loads Definition
H Drawings
1 Check North Direction, Check Scale, Check units, Check Grid Dimensions
The information within the Title Block of each drawing has been reviewed for
accuracy including the “Designed By”, “Drawn By”, “Checked By” and “File No.”
2 fields.

The Index Sheet has been coordinated with the current list of
3 architectural drawings with respect to drawing number and title.
A drawing has been included to identify abbreviations and symbols utilized on
the project drawings and have been coordinated with the other architectural
4 drawings for compliance.

Proposed culvert entrance and exit end treatmen


Labels for culvert length, slope, diameter, material and upstream and
downstream pipe inverts
Boundaries of project and plan sheet layout (key map
5 Loading plans, vertical loads layout
Deviations, if any

Verification team
Reviewed & Verfied by Approved & Accepted by
Remarks
Name
Date
Sign.

Prepared by Reviewed by Accepted by


Rupesh Khandekar Jagadish Ghogare Pravinkumar Patil