You are on page 1of 8

QUALITY METALS © ALL RIGHTS RESERVED 2020

BRAZOS VALLEY SCHOOL CREDIT UNION


CROSS CREEK RANCH

ML-150
roof and wall systems
www.saqualitymetals.com

AIA 1.5” MECHANICAL LOCK


DRAWING INDEX DRAWING RELEASE HISTORY
Cover Sheet 1 TYPE DATE DESCRIPTION
FOR APPROVAL CODES AND LOADS
Notes 2 ERECTION DRAWING 12/08/2020 NOT FOR CONSTRUCTION
When multiple buildings are involved, specific load factors for differing occupancies, building dimensions,
Anchor Rod Plan heights, framing systems, roof, slopes, etc., may result in different load application factors than indicated
below. See calculations for further details. Wind loads are applied to overall building envelope. Common
Primary Structural walls between connected shapes are not subject to external wind loads.
Secondary Structural Building Code: 2009 International Building Code
Building Use:Essential Facility, Collateral Gravity: 0.00 psf (Not including bldg wt)
Covering 3 - 05
LIVE LOADS AND RAINFALL
Special Drawings Roof Live Load 20.00 psf (Not Reducible)
Rainfall: 9.00 Inches per hour
Standard Erection Details
Planograph Details SNOW LOAD
Ground Snow: 0.00 psf, Flat Roof Snow: 0.00 pdf, Design Snow (Sloped): 0.00 pdf
Snow Exposure Category (Factor): 2 Partially Exposed (1.00)
Snow Importance: 1.200 Thermal Category (Factor): Heated (1.00)

WIND LOAD
The “Low Rise” Method is used
Wind Speed: 120.00 mph, Wind Exposure: B
Basic Wind Pressure: 14.35 psf
52’-07” 14’-03” 56’-03” Wind Importance Factor: 1.150 FT=Topographic Factor: 1.0000
Wind Enclosure: Enclosed, 0.180
Note: All windows, doors, skylights and other covered openings must be designed for the specified wind
loads.
The maximum sustained test pressure was -281.0 psf.
Per ASTM E 1592-05 (2012)
STANDARD TEST METHOD FOR THE STRUCTURAL PERFORMANCE OF SHEET METAL
16’-11¼”

ROOF AND SIDING SYSTEM BY UNIFORM STATIC AIR PRESSURE DIFFERENCE.

TEST LOCATION: Force Engineering & Testing, Inc.

Slope 6:12
Underwriter’s Laboratory Approvals

METAL ROOF DECK PANELS TJPV.R27067


12’-04”

COATED STEEL PANELS, FIELD FORMED, IDENTIFIED AS

Slope 5:12
"ML-150 MECHANICAL LOCK 1.5" FOR USE IN CONSTRUCTION

Slope 9:12 UL 790 - External Fire


UL 263 - Internal Fire: Roof Assemblies UL 2218 - Impact Resistance

77’-00”
Slope 5:12
19’-04”

Slope 6:12 Slope 6:12


Slope 5:12

Slope 6:12
26’-04½”

Slope 6:12 Slope 6:12

2’-04¾”

67’-00” 14’-08¼” 16’-01” 25’-05¾”

Roof Plan
NORTH
FOR APPROVAL NOT FOR CONSTRUCTION

Quality Metals
THE QUALITY METALS ENGINEERS SEAL APPLIES
ONLY TO THE WORK PRODUCT OF QUALITY METALS
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF QUALITY METALS.
IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE APPLICABLE PURCHASE.
roof and wall systems
2701 Castroville,Rd San Antonio, Tx 78237
COVER SHEET
AND DESIGN AND PERFORMANCE REQUIREMENTS ORDER AND SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT PRIOR
REV. DATE BY DESCRIPTION BUILDER JOB- NO.
WRITTEN APPROVAL OF QUALITY METALS. GULLO COMMERCIAL CONSTRUCTION
22-044589-98
SPECIFIED BY QUALITY METALS. THE QUALITY
CUSTOMER
METALS ENGINEERS SEAL DOES NOT APPLY TO THE GULLO COMMERCIAL CONSTRUCTION DATE
PERFORMANCE OF DESIGN OF ANY OTHER LOCATION
FULSHEAR, TEXAS 77441
12-08-2020
THE GENERAL CONTRACTOR AD/ OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE GOOD QUALITY
PRODUCT OR COMPONENT FURNISHED BY QUALITY PROJECT DRAWN/CHECK
WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS DRAWING, DETAILS REFERENCED BRAZOS VALLEY SCHOOL CREDIT U
METALS EXCEPT TO ANY DESIGN OR PERFORMANCE
IN THIS DRAWING, ALL APPLICABLE QUALITY METALS BUILDING ERECTION GUIDES AND INDUSTRY BUILDERS PO#
REQUIREMENTS SPECIFIED BY QUALITY METALS. STANDARDS PERTAINING TO PROPER ERECTION, INCLUDING THE CORRECT USE OF TEMPORARY BRACING. PAGE

NTS 1
BUILDER/CONTRACTOR RESPONSIBILITIES DELIVIERIES PANELS

QUALITY METALS follows the guidelines as outlined in the AISC and MBMA Codes of Standard It is the responsibility of the builder to have adequate equipment available at the job site to Oil canning is an inherent characteristic of cold formed steel panels. It is the result of several
unload trucks in a safe and timely manner. The Builder will be responsible for all retention factors that include induced stresses in the raw material delivered to QM, fabrication methods,
govern all work unless stipulated otherwise in the contract documents. In case of discrepancies charges from carriers as a result of job site unloading delays. installation procedures, and post installation thermal forces. Thru fastened panels will exhibit
between Quality Metals structural plans and plans for other trades, Quality Metals structural some dimpling when installed, specially when insulation is installed between panels and
plans shall govern. secondary supports. Dimpling can be minimized by careful installation, taking care not to over
against the carrier by the consignee as per Quality Metals Terms of Sales (F.O.B. Plant) under the drive fasteners.
Is the responsibility of the Builder to obtain approvals and permits from all governing agencies Uniform Commercial Code. It is critical that damages or shorts be noted on the Bill-of-Landing or
and jurisdictions as required. Approval of Quality Metals drawings constitutes the builders you have little recourse with the carrier. Immediately upon delivery of material, material quanti- Roof rumble is a phenomenon that is caused by wind gusts lifting up on the roof panels and
then springing back into place. All panels experience this action to some degree, specially with
design criteria concerning interface design and details are furnished as part of the contract, Manufacturer nor the carrier is responsible for material shortages against quantities billed on the concealed clip Standing Seam Panels. Roof rumble noise may be minimized by providing a layer
Quality Metals design assumptions shall govern. shipping document if such shortages against quantities billed on the shipping document if such of blanket insulation between the panels and any hard support surface such as as steel second-
shortages are not noted on the shipping documents upon delivery material and acknowledged ary members, substrates such as plywood, steel decking, or rigid insulation. A minimum of 3 inch
Quality Metals engineers are not project engineers or engineer of record for the overall project. by carriers agent. For materials concealed in bundles, boxes, or crates, shortages must be report- blanket is recommended over steel secondary members, or 2 inch over substrates.
Quality Metals engineering supply sealed engineering design data and drawings for Quality ed immediately upon unpacking. Should products get wet, bundled and crated materials must
Metals supplied material as part of the overall project for use by others to obtain permits, be unpacked and unbundled Immediately to provide drainage of trapped moisture. See erection
Guide for proper job site storage procedure. of the panels and is not grounds for rejection of panels.
overall project coordination, including coordination with appropriate inspection or testing
agencies. All interface and/or compatibility of any materials not furnished by Quality Metals are SEALANTS The Standing Seam joint details is designed with an interlocking feature for ease installation
however, it is imperative that installed in Standing Seam panels be secured to the secondary
Sealants shall be applied in strict accordance with Quality Metals details or weather tightness structural members and properly seamed prior to departure from the job site each day.
CONSTRUCTION AND ERECTION RESPONSIBILITY will be compromised.
Sealant must be applied in temperatures and wether conditions consistent with labeling. Underwriter’s Laboratory Approvals
The Builder is responsible for construction in strict accordance with Quality Metals “FOR CON-
STRUCTION” drawings and all applicable product installation guides. Quality Metals is not INDEPENDENT MEZZANINES METAL ROOF DECK PANELS TJPV.R27067
responsible for work done from any other Quality Metals drawings that are not marked “FOR
CONSTRUCTION”, not any drawings prepared by others. Independent mezzanines must be designed by a professional engineer. The engineer must COATED STEEL PANELS, FIELD FORMED, IDENTIFIED AS
ensure that proper isolation from Quality Metals has been provided to avoid structural damage "ML-150 MECHANICAL LOCK 1.5" FOR USE IN CONSTRUCTION
The building erector shall be properly licensed and experienced in erecting material metal
building systems. The builder is responsible for having knowledge of, and shall comply with, all Quality Metals accepts no responsibility for the design of the independent mezzanine. UL 790 - External Fire
OSHA requirements and all other governing site safety criteria. The builder is responsible for UL 263 - Internal Fire: Roof Assemblies
designing, supplying, locating and installing temporary supports and bracing during erection of FIRE CODE COMPLIANCE UL 2218 - Impact Resistance
the building. Quality Metals bracing is designed for code required loads after building competi-
tion and shall not be considered as adequate erection bracing. See erection guide.
code regulations including consideration of, but not limited to, building use and occupancy, all
EXISTING STRUCTURES
systems, etc.
Quality Metals must be advised of any existing structure that is within 20 ft. of Quality Metals Builder shall advise Quality Metals of any special requirements to be furnished by Quality Metals.

distance, Quality Metals cannot be responsible for the design or loading of existing buildings. FIELD MODIFICATIONS

BRACING
be approved in writing by Quality Metals engineers, or other licensed structural engineer. This
Tension brace rods work in pairs to balance forces caused by initial tensioning. Care must be
taken while lightening brace rods so as not to cause accidental or misalignment of components. braces or rod braces, cutting of openings for doors, windows or RTU’s, correction of fabrication
All rods must be installed loose and then tightened. Rods should not exhibit excessive sag. For
long or heavy rods, or angles it may be necessary to support the rod at mid-bay by suspending it building in the contract documents. Quality Metals accepts not responsibility for the conse-
from a secondary member. quences of any unauthorized additions, alterations, or added loads to this structure.

Bracing for seismic or wing loading of objects or equipment that are not a part of the Quality
must notify Quality Metals Immediately, and obtain a Work Authorization from Quality Metals
frames and rod bracing struts. Equipment bracing and suspension connections must not impose
torsion or minor axis loads, or cause local distortion in any Quality Metals components. Quality documentation within 30 days of the building completion. Claims submitted without work
Metals accepts not responsibility for design or installation of bracing systems not furnished by
Quality Metals. plumbing, moderate amount of reaming, drilling, chipping/cutting and minor welding are
considered by Code of Standard Practice to be part of erection are not subject to claim reim-
FIELD WELDING bursement.

CONCRETE/MASONY/CONVENTIONAL STUD WALLS

The engineer responsible for the design of the wall system is responsible for coordinating with,

responsible for any special welding inspection as required by local jurisdiction. Filler metal shall compatibility, special base details, and wall to Quality Metals steel connections. All fasteners,
be 70 ksi (490 MPa) tensile strength. For welds in high seismic force resisting system (Sismic Cat
D, E or F) minimum Charpy V-Notch toughness shall meet AISC-341 criteria (20ft-lbs min @ 0Deg responsible for the wall shall design the anchorage to Quality Metals supporting elements
F). Interpass temperatures shall not exceed 550Deg F (300Deg C). consistent with Code required forces.

Quality Metals
THE QUALITY METALS ENGINEERS SEAL APPLIES
ONLY TO THE WORK PRODUCT OF QUALITY METALS
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF QUALITY METALS.
IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE APPLICABLE PURCHASE.
roof and wall systems
2701 Castroville,Rd San Antonio, Tx 78237
ERECTION NOTES
AND DESIGN AND PERFORMANCE REQUIREMENTS ORDER AND SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT PRIOR
REV. DATE BY DESCRIPTION BUILDER JOB- NO.
WRITTEN APPROVAL OF QUALITY METALS. GULLO COMMERCIAL CONSTRUCTION
22-044589-98
SPECIFIED BY QUALITY METALS. THE QUALITY
CUSTOMER
METALS ENGINEERS SEAL DOES NOT APPLY TO THE GULLO COMMERCIAL CONSTRUCTION DATE
PERFORMANCE OF DESIGN OF ANY OTHER LOCATION
FULSHEAR, TEXAS 77441
12-08-2020
THE GENERAL CONTRACTOR AD/ OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE GOOD QUALITY
PRODUCT OR COMPONENT FURNISHED BY QUALITY PROJECT DRAWN/CHECK
WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS DRAWING, DETAILS REFERENCED BRAZOS VALLEY SCHOOL CREDIT U
METALS EXCEPT TO ANY DESIGN OR PERFORMANCE
IN THIS DRAWING, ALL APPLICABLE QUALITY METALS BUILDING ERECTION GUIDES AND INDUSTRY BUILDERS PO#
REQUIREMENTS SPECIFIED BY QUALITY METALS. STANDARDS PERTAINING TO PROPER ERECTION, INCLUDING THE CORRECT USE OF TEMPORARY BRACING. PAGE

NTS 2
52’-07” 14’-03” 56’-03”

2’-11”
2’-11”
1’-6” 1’-6”

4’-10”
4’-10”
2’-10” 2’-10”

6’-8”
6’-8”
4’-1” 4’-1”
5’-4” 5’-4”

8’-6”
8’-6”
6’-7” 6’-7”

10’-5”
16’-11¼”

10’-5”
7’-10” 7’-10”

12’-3”
12’-3”
9’-1” 9’-1”

14’-1”
14’-1”
10’-4” 10’-4”

16’-0”
11’-7” 11’-7”

16’-0”

Slope 6:12

17’-10”
12’-10” 12’-10”

17’-10”
14’-1” 14’-1”

19’-9”
19’-9”
15’-4” 15’-4”

21’-7”
21’-7”
16’-8” 16’-8”

23’-5”
1'-0"

3’-10”
6’-6”
9’-1”

17’-10”
17’-11”

11’-8”
14’-3”

23’-5”
17’-11”

16’-10”
17’-4”

17’-4”

17’-4”
17’-4”
1'-11"

25’-4”
19’-2” 19’-2”

25’-4”
2'-10" 20’-5” 20’-5”

27’-2”
27’-2”
12’-04”

3'-10" 21’-8” 21’-8”

29’-0”
29’-0”
4'-9"

Slope 5:12
22’-11” 22’-11”

30’-11”

30’-11”
5'-8" 24’-2” 24’-2”
6'-7" Slope 9:12 25’-5”

32’-9”

32’-9”
24’-5”
7'-6" 24’-7” 26’-8”

34’-7”

34’-7”
8’-5” 24’-9” 27’-11”
9’-4”

36’-6”

36’-6”
24’-11” 29’-2”
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
9’-7”

38’-4”

38’-4”
30’-6”

1’-11” 1’-11”
25’-1”

8’-12” 8’-12”
6’-1” 6’-1”
4’-0” 4’-0”
9’-7” 31’-10”
25’-3”

9’-6”

39’-3”
8’-8”

Slope 5:12
27’-1” 33’-0”
6’-10”

6’-11”
28’-7” 33’-5”

77’-00”
5’-0” 33’-5”
19’-04”

29’-8”

4’-4”
3’-2”
30’-8” Slope 6:12 Slope 6:12 33’-5”

31’-9” 33’-5”

32’-10” 33’-5”
Slope 5:12

33’-5” 33’-5”

33’-0” 33’-0”

19’-5”
31’-10” 31’-10”

17’-0”

38’-4”
30’-6” 30’-6”

16'-10"

13’-8”
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
10'-8"
11'-8"
14'-3"

17'-4"
17'-4"
17'-4"
17'-4"
17'-4"
17'-4"
17'-4"
17'-4"
7'-10"

36’-6”
29’-2” 29’-2”

10’-3”
27’-11” 27’-11”

34’-7”
26’-8” 26’-8”

6’-11”

32’-9”
25’-5” 25’-5”

Slope 6:12
6’-4”
24’-2” 24’-2”

32’-9”
5’-11”
1’-4” 1’-4”

30’-11”
22’-11” 22’-11”

5’-7”
21’-8” 2’-10” 2’-10” 21’-8”

29’-0”
20’-5” 4’-4” 4’-4” 20’-5”

5’-2”

27’-2”
19’-2” 5’-10” 5’-10” 19’-2”

23’-5”

25’-4”
17’-11” 7’-4” 7’-4” 17’-11”
26’-04½”

21’-7”
8’-10” 8’-10” 16’-8”

23’-5”
16’-8”
9’-2” 9’-2” 15’-4”

19’-9”
15’-4”

21’-7”
14’-1” 9’-2” 9’-2” 14’-1”

17’-10”

19’-9”
12’-10” 9’-2” 9’-2” 12’-10”

16’-0”

17’-10”
11’-7” 9’-2” 9’-2” 11’-7”

16’-0”
14’-1”
10’-4” 9’-2” 9’-2” 10’-4”
9’-2” 9’-2” 9’-1”

12’-3”
9’-1”

14’-1”
7’-10” Slope 6:129’-2” 9’-2”
Slope 6:12 7’-10”

10’-5”

12’-3”
6’-7” 9’-2” 9’-2” 6’-7”

8’-6”

10’-5”
5’-4” 9’-2” 9’-2” 5’-4”

6’-8”

8’-6”
4’-1” 9’-2” 9’-2” 4’-11”
9’-2” 9’-2”

4’-10”
4’-10”
2’-10” 2’-10”
9’-2” 9’-2” 1’-6”

2’-11”
1’-6”

2’-11”
9’-2” 9’-2”
2’-04¾” 9’-2” 9’-2”

67’-00” 14’-08¼” 16’-01” 25’-05¾”

Roof Plan
NORTH

Quality Metals
THE QUALITY METALS ENGINEERS SEAL APPLIES
ONLY TO THE WORK PRODUCT OF QUALITY METALS
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF QUALITY METALS.
IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE APPLICABLE PURCHASE.
roof and wall systems
2701 Castroville,Rd San Antonio, Tx 78237
COVERING SCHEDULE
AND DESIGN AND PERFORMANCE REQUIREMENTS ORDER AND SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT PRIOR
REV. DATE BY DESCRIPTION BUILDER JOB- NO.
WRITTEN APPROVAL OF QUALITY METALS. GULLO COMMERCIAL CONSTRUCTION
22-044589-98
SPECIFIED BY QUALITY METALS. THE QUALITY
CUSTOMER
METALS ENGINEERS SEAL DOES NOT APPLY TO THE GULLO COMMERCIAL CONSTRUCTION DATE
PERFORMANCE OF DESIGN OF ANY OTHER LOCATION
FULSHEAR, TEXAS 77441
12-08-2020
THE GENERAL CONTRACTOR AD/ OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE GOOD QUALITY
PRODUCT OR COMPONENT FURNISHED BY QUALITY PROJECT DRAWN/CHECK
WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS DRAWING, DETAILS REFERENCED BRAZOS VALLEY SCHOOL CREDIT U
METALS EXCEPT TO ANY DESIGN OR PERFORMANCE
IN THIS DRAWING, ALL APPLICABLE QUALITY METALS BUILDING ERECTION GUIDES AND INDUSTRY BUILDERS PO#
REQUIREMENTS SPECIFIED BY QUALITY METALS. STANDARDS PERTAINING TO PROPER ERECTION, INCLUDING THE CORRECT USE OF TEMPORARY BRACING. PAGE

NTS 3
PANEL LIST

QTY PANEL WIDTH LENGTH FINISH QTY PANEL WIDTH LENGTH FINISH
83 QM ML-150 16” 10’-08” MEDIUM BRONZE 3 QM ML-150 16” 38’-04” MEDIUM BRONZE
04 QM ML-150 16” 2’- 11” MEDIUM BRONZE 1 QM ML-150 16” 39’-03” MEDIUM BRONZE
04 QM ML-150 16” 04’-10” MEDIUM BRONZE 1 QM ML-150 16” 19’-05” MEDIUM BRONZE
04 QM ML-150 16” 06’-08” MEDIUM BRONZE 1 QM ML-150 16” 17’-00” MEDIUM BRONZE
04 QM ML-150 16” 08’-06” MEDIUM BRONZE 1 QM ML-150 16” 13’-08” MEDIUM BRONZE
04 QM ML-150 16” 10’-05” MEDIUM BRONZE 1 QM ML-150 16” 10’-03” MEDIUM BRONZE
04 QM ML-150 16” 12’-03” MEDIUM BRONZE 2 QM ML-150 16” 6’-11” MEDIUM BRONZE
04 QM ML-150 16” 14’-01” MEDIUM BRONZE 1 QM ML-150 16” 6’-04” MEDIUM BRONZE
04 QM ML-150 16” 16’-00” MEDIUM BRONZE 1 QM ML-150 16” 5’-11” MEDIUM BRONZE
04 QM ML-150 16” 17’-10” MEDIUM BRONZE 1 QM ML-150 16” 5’-07” MEDIUM BRONZE
04 QM ML-150 16” 19’-09” MEDIUM BRONZE 1 QM ML-150 16” 5’-02” MEDIUM BRONZE
04 QM ML-150 16” 21’-07” MEDIUM BRONZE 2 QM ML-150 16” 9’-07” MEDIUM BRONZE
04 QM ML-150 16” 23’-05” MEDIUM BRONZE 1 QM ML-150 16” 9’-04” MEDIUM BRONZE
07 QM ML-150 16” 33’-05” MEDIUM BRONZE 1 QM ML-150 16” 8’-05” MEDIUM BRONZE
04 QM ML-150 16” 01’-06” MEDIUM BRONZE 1 QM ML-150 16” 8’-08” MEDIUM BRONZE
04 QM ML-150 16” 02’-10” MEDIUM BRONZE 1 QM ML-150 16” 6’-10” MEDIUM BRONZE
04 QM ML-150 16” 04’-01” MEDIUM BRONZE 1 QM ML-150 16” 5’-00” MEDIUM BRONZE
04 QM ML-150 16” 05’-04” MEDIUM BRONZE 1 QM ML-150 16” 3’-02” MEDIUM BRONZE
04 QM ML-150 16” 06’-07” MEDIUM BRONZE 1 QM ML-150 16” 9’-06” MEDIUM BRONZE
04 QM ML-150 16” 07’-10” MEDIUM BRONZE 1 QM ML-150 16” 6’-06” MEDIUM BRONZE
05 QM ML-150 16” 09’-01” MEDIUM BRONZE 1 QM ML-150 16” 3’-10” MEDIUM BRONZE
04 QM ML-150 16” 10’-04” MEDIUM BRONZE 1 QM ML-150 16” 1’-00” MEDIUM BRONZE
04 QM ML-150 16” 11’-07” MEDIUM BRONZE 1 QM ML-150 16” 1’-11” MEDIUM BRONZE
04 QM ML-150 16” 12’-10” MEDIUM BRONZE 1 QM ML-150 16” 2’-10” MEDIUM BRONZE
04 QM ML-150 16” 14’-01” MEDIUM BRONZE 1 QM ML-150 16” 3’-10” MEDIUM BRONZE
04 QM ML-150 16” 15’-04” MEDIUM BRONZE 1 QM ML-150 16” 4’-09” MEDIUM BRONZE
04 QM ML-150 16” 16’-08” MEDIUM BRONZE 1 QM ML-150 16” 5’-08” MEDIUM BRONZE
04 QM ML-150 16” 17’-11” MEDIUM BRONZE 1 QM ML-150 16” 6’-07” MEDIUM BRONZE
04 QM ML-150 16” 19’-02” MEDIUM BRONZE 1 QM ML-150 16” 7’-06” MEDIUM BRONZE
04 QM ML-150 16” 20’-05” MEDIUM BRONZE 1 QM ML-150 16” 24’-05” MEDIUM BRONZE
04 QM ML-150 16” 21’-08” MEDIUM BRONZE 1 QM ML-150 16” 24’-07” MEDIUM BRONZE
04 QM ML-150 16” 22’-11” MEDIUM BRONZE 1 QM ML-150 16” 24’-09” MEDIUM BRONZE
04 QM ML-150 16” 24’-02” MEDIUM BRONZE 1 QM ML-150 16” 24’-11” MEDIUM BRONZE
03 QM ML-150 16” 25’-05” MEDIUM BRONZE 1 QM ML-150 16” 25’-01” MEDIUM BRONZE
03 QM ML-150 16” 26’-08” MEDIUM BRONZE 1 QM ML-150 16” 25’-03” MEDIUM BRONZE
03 QM ML-150 16” 27’-11” MEDIUM BRONZE 1 QM ML-150 16” 27’-01” MEDIUM BRONZE
03 QM ML-150 16” 29’-02” MEDIUM BRONZE 1 QM ML-150 16” 28’-07” MEDIUM BRONZE
03 QM ML-150 16” 30’-06” MEDIUM BRONZE 1 QM ML-150 16” 29’-08” MEDIUM BRONZE
03 QM ML-150 16” 31’-10” MEDIUM BRONZE 1 QM ML-150 16” 30’-08” MEDIUM BRONZE
03 QM ML-150 16” 33’-00” MEDIUM BRONZE 1 QM ML-150 16” 31’-09” MEDIUM BRONZE
02 QM ML-150 16” 01’-04” MEDIUM BRONZE 1 QM ML-150 16” 32’-10” MEDIUM BRONZE
02 QM ML-150 16” 02’-10” MEDIUM BRONZE
03 QM ML-150 16” 04’-04” MEDIUM BRONZE
02 QM ML-150 16” 05’-10” MEDIUM BRONZE
02 QM ML-150 16” 07’-04” MEDIUM BRONZE
02 QM ML-150 16” 08’-10” MEDIUM BRONZE
28 QM ML-150 16” 09’-02” MEDIUM BRONZE
10 QM ML-150 16” 17’-04” MEDIUM BRONZE
02 QM ML-150 16” 07’-10” MEDIUM BRONZE
02 QM ML-150 16” 16’-10” MEDIUM BRONZE
02 QM ML-150 16” 14’-03” MEDIUM BRONZE
02 QM ML-150 16” 11’-08” MEDIUM BRONZE
02 QM ML-150 16” 08’-02” MEDIUM BRONZE
02 QM ML-150 16” 06’-01” MEDIUM BRONZE
02 QM ML-150 16” 04’-00” MEDIUM BRONZE
02 QM ML-150 16” 01’-11” MEDIUM BRONZE
03 QM ML-150 16” 25’-04” MEDIUM BRONZE
03 QM ML-150 16” 27’-02” MEDIUM BRONZE
03 QM ML-150 16” 29’-00” MEDIUM BRONZE
03 QM ML-150 16” 30’-11” MEDIUM BRONZE
03 QM ML-150 16” 32’-09” MEDIUM BRONZE
03 QM ML-150 16” 34’-07” MEDIUM BRONZE
03 QM ML-150 16” 36’-06” MEDIUM BRONZE

Quality Metals
THE QUALITY METALS ENGINEERS SEAL APPLIES
ONLY TO THE WORK PRODUCT OF QUALITY METALS
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF QUALITY METALS.
IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE APPLICABLE PURCHASE.
roof and wall systems
2701 Castroville,Rd San Antonio, Tx 78237
PANEL LIST
AND DESIGN AND PERFORMANCE REQUIREMENTS ORDER AND SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT PRIOR
REV. DATE BY DESCRIPTION BUILDER JOB- NO.
WRITTEN APPROVAL OF QUALITY METALS. GULLO COMMERCIAL CONSTRUCTION
22-044589-98
SPECIFIED BY QUALITY METALS. THE QUALITY
CUSTOMER
METALS ENGINEERS SEAL DOES NOT APPLY TO THE GULLO COMMERCIAL CONSTRUCTION DATE
PERFORMANCE OF DESIGN OF ANY OTHER LOCATION
FULSHEAR, TEXAS 77441
12-08-2020
THE GENERAL CONTRACTOR AD/ OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE GOOD QUALITY
PRODUCT OR COMPONENT FURNISHED BY QUALITY PROJECT DRAWN/CHECK
WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS DRAWING, DETAILS REFERENCED BRAZOS VALLEY SCHOOL CREDIT U
METALS EXCEPT TO ANY DESIGN OR PERFORMANCE
IN THIS DRAWING, ALL APPLICABLE QUALITY METALS BUILDING ERECTION GUIDES AND INDUSTRY BUILDERS PO#
REQUIREMENTS SPECIFIED BY QUALITY METALS. STANDARDS PERTAINING TO PROPER ERECTION, INCLUDING THE CORRECT USE OF TEMPORARY BRACING. PAGE

NTS 4
ROOF PANEL INSTALLATION GUIDE REQUIRED FOR THIS PROJECT: (2) TWO PER CLIP QM ML-150 FLOATING
IT IS THE RESPONSIBILITYH OF THE ERECTOR TO INSURE PROPER SEAM 14-10x X 7” DECK CLIP OVER STANDARD
TIGHTNESS. FAILURE TO PRPERLYH SEAM THE JOINT MAY RESULT IN SCREW BEARING PLATE
PREMATURE FAILURE OF PANELS AND/OR SECONDARY MEMBERS UNDER (MIN 3/4 PENETRATION @ 3’-0” O.C.
UPLIFT OR DOWNWARD LOADING CONDITIONS. INTO METAL DECK)
REFER TO: STANDARD
QM ML-150 PANEL BEARING PLATE
QM ML-150 PANEL 4” X 5”
ICE & WATER SHIELD
MECHANICAL LOCK
180º DOUBLE LOCK
SEAMED
1. STANDARD DETAILS (SED) SUPERSED SIMILAR DETAILS
0.56” FOUND IN THE ERECTION GUIDES. REFER TO THE ERECTION
(2) SCREWS PER CLIP
0.45” GUIDES FOR OTHER DETAILS, INSTALLATION, PROCEDURES AND
150 ACCESSORIES NOT DESCRIBED IN THE SED’S.
1.50”

1.48”
1.00” 1.00”
2. ALL PANEL AND TRIM SURFACES MUST BE FREE OF DIRT AND

1.25” 1.25”
INSTALLATION GUIDE OIL AT MASTIC AND SEALANT LOCATIONS.

16.00”

QM ML-150
FLOATING 5/8” COVER BOARD
CLIP 5” (R-30)
POLY-ISO
1.5” METAL DECK INSULATION
NOT BY QM (NOT BY QM)

ML-150 MECHANICAL LOCK ML-150 SEAMING GUIDELINES ML-150 TRAPEZOIDAL NOTES ML-150 PANEL CLIP ATTACHMENT
ML23D1 STANDING SEAM ROOF PANELS ML01B2 RIB AND SEAM PROFILE RRPLD01 ROOF INSTALLATION GUIDE RRPLD02 MLPLD01 UNDERLAYMENT LAYER OVER RIGID INSULATION


ICE AND WATER SHIELD

5/8” COVER BOARD

5” X 4” STANDARD
BEARING ⅝”
PLATE
22 GA ”

½”

14”
1”
specify
” roof angle
.00
18 ML-150 FLOATING
14-10x X 7” DECK CLIP TWO PIECES
SCREW @ 12” O.C. UL APPROVED

5½”
(MIN 3/4 PENETRATION
INTO METAL DECK) (2) TWO PER CLIP

4½”
14-10x X 7” DECK
SCREW
(MIN 3/4 PENETRATION
0”
2.0 INTO METAL DECK)

GUTTER SUPORT
⅝”
ANGLE 18 GA
GALVANIZED

10 X 1½ PANCAKE HEAD
METAL TO METAL
@ 12” O.C. 5¼” 1½”
URETHANE TUBE
SEALANT BETWEEN
PANEL RIBS

POP RIVET
GUTTER WITH DRIP EDGE (24 GA MEDIUM BRONZE) FASCIA FLASHING (24 GA MEDIUM BRONZE)

GUTTER STRAP
@ EVERY OTHER
RIB

GUTTER WITH
DRIP EDGE

12-11 X 1 PANCAKE 7”
HEAD SELF TAPPER
@ 12” O.C.

FASCIA FLASHING

WOOD BLOCKING
NOT BY QM

POP RIVET @ 24” O.C. SOFFIT PANEL specify

1”
roof angle

DG-SR2402 GUTTER WITH DRIP EDGE GUTTER SUPPORT ANGLE (18 GA GALVANIZED)
ML-150 OVER RIGID INSULATION

Quality Metals
THE QUALITY METALS ENGINEERS SEAL APPLIES
ONLY TO THE WORK PRODUCT OF QUALITY METALS
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF QUALITY METALS.
IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE APPLICABLE PURCHASE.
roof and wall systems
2701 Castroville,Rd San Antonio, Tx 78237
COVERING AND TRIM SED’S
AND DESIGN AND PERFORMANCE REQUIREMENTS ORDER AND SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT PRIOR
REV. DATE BY DESCRIPTION BUILDER JOB- NO.
WRITTEN APPROVAL OF QUALITY METALS. GULLO COMMERCIAL CONSTRUCTION
22-044589-98
SPECIFIED BY QUALITY METALS. THE QUALITY
CUSTOMER
METALS ENGINEERS SEAL DOES NOT APPLY TO THE GULLO COMMERCIAL CONSTRUCTION DATE
PERFORMANCE OF DESIGN OF ANY OTHER LOCATION
FULSHEAR, TEXAS 77441
12-08-2020
THE GENERAL CONTRACTOR AD/ OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE GOOD QUALITY
PRODUCT OR COMPONENT FURNISHED BY QUALITY PROJECT DRAWN/CHECK
WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS DRAWING, DETAILS REFERENCED BRAZOS VALLEY SCHOOL CREDIT U
METALS EXCEPT TO ANY DESIGN OR PERFORMANCE
IN THIS DRAWING, ALL APPLICABLE QUALITY METALS BUILDING ERECTION GUIDES AND INDUSTRY BUILDERS PO#
REQUIREMENTS SPECIFIED BY QUALITY METALS. STANDARDS PERTAINING TO PROPER ERECTION, INCLUDING THE CORRECT USE OF TEMPORARY BRACING. PAGE

NTS 5
1”


SPECIFY
ROOF ANGLE
VALLEY WITH CLEAT 1”
INTEGRATED


QM ML-150 PANEL
10 X 1½ PANCAKE HEAD
METAL TO METAL
@ 12” O.C.
ICE AND WATER SHIELD
UNIVERSAL CLEAT

VALLE SUPPORT 5/8” COVER BOARD


ANGLE 18 GA
GALVANIZED

VALLEY WITH CLEAT INTEGRATED (24 GA MEDIUM BRONZE)

URETHANE TUBE
SEALANT
BETWEEN PANEL
RIBS 1½”
1½”

½”

5” RIGID INSULATION

UNIVERSAL CLEAT (24 GA MEDIUM BRONZE)

14-10x X 7” DECK 14-10x X 7” DECK


SCREW SCREW
(MIN 3/4 PENETRATION (MIN 3/4 PENETRATION
INTO METAL DECK) INTO METAL DECK)
@ 12 O.C. @ 12” O.C.

METAL DECK METAL DECK

SPECIFY
ROOF ANGLE

12

DG-VA2402 VALLEY WITH CLEAT INTEGRATED VALLEY SUPPORT ANGLE (18 GA GALVANIZED)
ML-150 OVER RIGID INSULATION

Quality Metals
THE QUALITY METALS ENGINEERS SEAL APPLIES
ONLY TO THE WORK PRODUCT OF QUALITY METALS
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF QUALITY METALS.
IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE APPLICABLE PURCHASE.
roof and wall systems
2701 Castroville,Rd San Antonio, Tx 78237
COVERING AND TRIM SED’S
AND DESIGN AND PERFORMANCE REQUIREMENTS ORDER AND SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT PRIOR
REV. DATE BY DESCRIPTION BUILDER JOB- NO.
WRITTEN APPROVAL OF QUALITY METALS. GULLO COMMERCIAL CONSTRUCTION
22-044589-98
SPECIFIED BY QUALITY METALS. THE QUALITY
CUSTOMER
METALS ENGINEERS SEAL DOES NOT APPLY TO THE GULLO COMMERCIAL CONSTRUCTION DATE
PERFORMANCE OF DESIGN OF ANY OTHER LOCATION
FULSHEAR, TEXAS 77441
12-08-2020
THE GENERAL CONTRACTOR AD/ OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE GOOD QUALITY
PRODUCT OR COMPONENT FURNISHED BY QUALITY PROJECT DRAWN/CHECK
WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS DRAWING, DETAILS REFERENCED BRAZOS VALLEY SCHOOL CREDIT U
METALS EXCEPT TO ANY DESIGN OR PERFORMANCE
IN THIS DRAWING, ALL APPLICABLE QUALITY METALS BUILDING ERECTION GUIDES AND INDUSTRY BUILDERS PO#
REQUIREMENTS SPECIFIED BY QUALITY METALS. STANDARDS PERTAINING TO PROPER ERECTION, INCLUDING THE CORRECT USE OF TEMPORARY BRACING. PAGE

NTS 6
7”

RIDGE CAP

1 1/8” x 1/4” POP RIVET 2½


@ 18” O.C. ”
1”
DOUBLE BEAD URETHANE
TAPE SEALANT

0” 1”
2.0

RIDGE CAP (24 GA MEDIUM BRONZE)


URETHANE TUBE
SEALANT
Z-BAR CLOSURE
DOUBLE BEAD URETHANE
1/4 -14 x 1 1/4 LONG LIFE TAPE SEALANT 1”
SELF DRILL WITH
WASHER @ 12” O.C.
RIDGE CAP
SUPPORT ANGLE
18 GA GALVANIZED
5/8 COVER BOARD

QM ML-150

1⅝”
PANEL

5” RIGID INSULATION ICE AND WATER


SHIELD

1”

Z-BAR (24 GA MEDIUM BRONZE)


14-10x X 7” DECK
SCREW
(MIN 3/4 PENETRATION
INTO METAL DECK)
@ 12” O.C.

METAL DECK METAL DECK

12

SPECIFY
ROOF ANGLE

DG-RC2402 RIDGE CAP RIDGE SUPPORT ANGLE (18 GA GALVANIZED)


ML-150 OVER RIGID INSULATION

Quality Metals
THE QUALITY METALS ENGINEERS SEAL APPLIES
ONLY TO THE WORK PRODUCT OF QUALITY METALS
THIS DRAWING, INCLUDING THE INFORMATION HEREON, REMAINS THE PROPERTY OF QUALITY METALS.
IT IS PROVIDED SOLELY FOR ERECTING THE BUILDING DESCRIBED IN THE APPLICABLE PURCHASE.
roof and wall systems
2701 Castroville,Rd San Antonio, Tx 78237
COVERING AND TRIM SED’S
AND DESIGN AND PERFORMANCE REQUIREMENTS ORDER AND SHALL NOT BE MODIFIED, REPRODUCED OR USED FOR ANY OTHER PURPOSE WITHOUT PRIOR
REV. DATE BY DESCRIPTION BUILDER JOB- NO.
WRITTEN APPROVAL OF QUALITY METALS. GULLO COMMERCIAL CONSTRUCTION
22-044589-98
SPECIFIED BY QUALITY METALS. THE QUALITY
CUSTOMER
METALS ENGINEERS SEAL DOES NOT APPLY TO THE GULLO COMMERCIAL CONSTRUCTION DATE
PERFORMANCE OF DESIGN OF ANY OTHER LOCATION
FULSHEAR, TEXAS 77441
12-08-2020
THE GENERAL CONTRACTOR AD/ OR ERECTOR IS SOLELY RESPONSIBLE FOR ACCURATE GOOD QUALITY
PRODUCT OR COMPONENT FURNISHED BY QUALITY PROJECT DRAWN/CHECK
WORKMANSHIP IN ERECTING THIS BUILDING IN ACCORDANCE WITH THIS DRAWING, DETAILS REFERENCED BRAZOS VALLEY SCHOOL CREDIT U
METALS EXCEPT TO ANY DESIGN OR PERFORMANCE
IN THIS DRAWING, ALL APPLICABLE QUALITY METALS BUILDING ERECTION GUIDES AND INDUSTRY BUILDERS PO#
REQUIREMENTS SPECIFIED BY QUALITY METALS. STANDARDS PERTAINING TO PROPER ERECTION, INCLUDING THE CORRECT USE OF TEMPORARY BRACING. PAGE

NTS 7