You are on page 1of 36

1.

3 MOUNTING REQUIREMENTS

TC10 This instrument is intended for permanent installation, for


indoor use only, in an electrical panel which encloses the
rear housing, exposed terminals and wiring on the back.
Select a mounting location having the following characteristics:
1. It should be easily accessible;
TEMPERATURE 2. There is minimum vibrations and no impact;
CONTROLLER 3. There are no corrosive gases;
4. There are no water or other fluids (i.e. condensation);
5. The ambient temperature is in accordance with the
operative temperature (0 to 50°C);
6. The relative humidity is in accordance with the instrument
specifications (20 to 90%);
The instrument can be mounted on panel with a maximum
thickness of 8 mm.
When the maximum front protection (IP65) is desired, the
optional gasket must be mounted.

Engineering Manual 2. CONNECTION DIAGRAM


Code: IM 05C01E81-02EN
8
NO + + 16 DI1
Third edition: Feb. 2018
Out1
C
Yokogawa Electric Corporation DI2 7 - - 15
2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750 Japan + NO
www.yokogawa.com/ns 6 D-
- 14 Out2
RS485
5 D+ C 13
+
1. OUTLINE DIMENSIONS (mm) 12 VDC/20 mA max. Out4 +- NO
+ 4 12 Out3
1.1 INSTRUMENT DIMENSIONS 3 C
11
-
48 11 48 14
2 10 Power
supply
+ + + 1 9
0/12 to 60 mV, 0/1 to 5V, 0/2 to 10V
Passive TX, 2 wires, 4 to 20 mA

4 to 20 mA (active)

Pt1000

Pt100
TC

PV
48

AT

Relay Out 1: 4 (4) A/250 VAC


Relay Out 2, 3: 2 (1) A/250 VAC
SSR Out 1, 2 , 3: 10 VDC/15 mA
Optional SSR Out4: 12 VDC/20 mA
8 mm max. Current Out1: 0/4 to 20 mA, 0/2 to 10V
gasket

1.2 PANEL CUT-OUT


65 mm min.
2.56 in min. 2.1 GENERAL NOTES ABOUT WIRING
1. Do not run input wires together with power cables.
2. External components (like zener barriers, etc.) connected
between sensor and input terminals may cause errors in
measurement due to excessive and/or not balanced line
resistance or possible leakage currents.
2.56 in min.

3. When a shielded cable is used, it should be connected at


65 mm min.

one point only.


4. Pay attention to the line resistance; a high line resistance
1.78+0.023 in

may cause measurement errors.


45+0.6 mm

45+0.6 mm
1.78+0.023 in

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 1


2.2 INPUTS 2.2.5 mA Input
2.2.1 Termocouple Input 0/4 to 20 mA input wiring for passive transmitter
using the auxiliary pws
2 _
+ 4
1 + 4 to 20 mA
Passive
transmitter
External resistance: 100Ω max., maximum error 25 mV. _ 1
Cold junction: automatic compensation between 0 to 50°C.
Cold junction accuracy: 0.05°C/°C after a warm-up of Input impedance: < 53Ω.
20 minutes. Internal auxiliary PWS: 12 VDC (±10%), 20 mA max..
Input impedance: > 1 MΩ.
0/4 to 20 mA input wiring for passive transmitter
Calibration: According to EN 60584-1. using an external pws
Note: For TC wiring use proper compensating cable
+ External
preferable shielded. 0/4 to 20 mA + PWS
_ 2 _
Passive
2.2.2 RTD Pt 100 Input transmitter _ 1 +
3
RTD 0/4 to 20 mA input wiring for active transmitter
2
0/4 to 20 mA _ 2 _
1 Active
transmitter + 1 +
Input circuit: Current injection (150 µA).
Line resistance: Automatic compensation up to 20Ω/wire 2.2.6 Logic Inputs
with maximum error ±0.1% of the input span.
Calibration: According to EN 60751/A2. Safety notes:
Note: The resistance of the 3 wires must be the same. ––Do not run logic input wiring together with power cables;
––The instrument needs 150 ms to recognize a contact
2.2.3 RTD Pt 1000 Input status variation;
––Logic inputs are NOT isolated by the measuring input.
3 A double or reinforced isolation between logic inputs and
Pt1000 power line must be assured by the external elements.
2
Logic input driven by dry contact
Line resistance: Not compensated.
Pt 1000 input circuit: Current injection (15 µA). 16
Pt 1000 calibration: According to EN 60751/A2.
15 Digital
2.2.4 V and mV Input Digital 4 Input 1
Input 2
mV
_ 2 _ Maximum contact resistance: 100Ω.
V + Contact rating: DI1 = 10 V, 6 mA;
1 + DI2 = 12 V, 30 mA.

Input impedance: > 1 MΩ for mV Input Logic inputs driven by 24 VDC


500 kΩ for Volt Input.
- 16 -
Digital
+ 15 + Input 1
Digital 4
Input 2
Logic status 1: 6 to 24 VDC;
Logic status 0: 0 to 3 VDC.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 2


2.3 OUTPUTS SSR Output
Safety notes: +
SSR 14
––To avoid electrical shocks, connect power line at last.
––For supply connections use No. 16 AWG or larger wires 13
rated for at last 75°C. -
––Use copper conductors only. Logic level 0: Vout < 0.5 VDC;
––SSR outputs are not isolated. A reinforced isolation must Logic level 1: 12 V ±20%, 15 mA max..
be assured by the external solid state relays.
––For SSR, mA and V outputs if the line length is longer than 2.3.3 Output 3 (OP3)
30 m use a shielded wire. Relay Output
––Do not short-circuit the terminals of the SSR output.
NO
WARNING! Before connecting the output actuators, 12
we recommend to configure the parameters to C
suit your application (e.g.: input type, Control 11
strategy, alarms, etc.).
Contact rating: • 2 A /250 V cosj = 1;
2.3.1 Output 1 (OP1) • 1 A /250 V cosj = 0.4.
Relay Output Operation: 1 x 105.
NO SSR Output
8
+
C SSR 12
7
- 11
Contact rating: • 4 A /250 V cosj =1;
• 2 A /250 V cosj =0.4.
Logic level 0: Vout < 0.5 VDC;
Operation: 1 x 105.
Logic level 1: 12 V ±20%, 15 mA max..
SSR Output
2.3.4 Output 4 (OP4)
+
8 SSR SSR Output

7 16
- -
Logic level 0: Vout < 0.5 VDC; + SSR
Logic level 1: 12 V ±20%, 15 mA max.. Out4 4
Current Analog Output
Logic level 0: Vout < 0.5 VDC;
+
8 mA Logic level 1: 12 V ±20%, 20 mA max..
Note: Overload protected.
7
-
mA output: 0/4... 20 mA, galvanically isolated, RL max. 600Ω.
Voltage Analog Output
+
8 V
7
-
V output: 0/2... 10 V, galvanically isolated, RL min.: 500Ω.

2.3.2 Output 2 (OP2)


Relay Output
NO
14
C 13

Contact rating: • 2 A /250 V cosj = 1;


• 1 A /250 V cosj = 0.4.
Operation: 1 x 105.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 3


2.4 SERIAL INTERFACE 3. TECHNICAL CHARACTERISTICS
RS-485 D - 3.1 TECHNICAL SPECIFICATION
D- 6 Case: Plastic, self-extinguishing degree: V-0 according to UL 94;
5 Front protection: IP 65 (when the optional panel gasket is
D+ mounted) for indoor locations according to EN 60070-1;
D+
Terminals protection: IP 20 according to EN 60070-1;
D-
Installation: Panel mounting;
D+ Terminal block: 16 screw terminals for cables of
0.25 to 2.5 mm2 (AWG22 to AWG14) with connection diagram,
tightening torque 0.5 Nm;
D- Dimensions: 48 x 48, depth 73 mm, (1.89 x 1.89 x 2.87 in.)
Panel cutout: 45[-0, +0.6] x 45[-0, +0.6] mm
D+ (1.78[- 0.000, +0.023] x 1.78[- 0.000, +0.023] in.)
Weight: 180 g max..
Interface type: Isolated (50 V) RS-485;
Voltage levels: According to EIA standard; Power supply: • 24 VAC/DC (±10% of the nominal value);
Protocol type: Modbus RTU; • 100 to 240 VAC (-15 to +10% of the
Byte format: 8 bit with no parity; nominal value);
Stop bit: 1 (one); Power consumption: 4.5 VA max. (24 VAC/DC)
Baud rate: Programmable between 1200 to 38400 baud; 6.0 VA max. (100 to 240 VAC);
Address: Programmable between 1 to 254. Insulation voltage: 2300 V rms according to EN 61010-1;
Notes: 1. RS-485 interface allows to connect up to 30 Display updating time: 500 ms;
devices with one remote master unit. Sampling time: 130 ms;
2. The cable length must not exceed 1.5 km at Resolution: 30000 counts;
9600 baud.
Total Accuracy: ±0.5% F.S.V. ±1 digit @ 25°C of room
2.5 POWER SUPPLY temperature;
Electromagnetic compatibility and safety requirements
10 Line Compliance: directive EMC 2004/108/CE (EN 61326-1),
Power Supply directive LV 2006/95/CE (EN 61010-1),
9 Neutral UL 61010-1 CSA 61010-1;
Note: During the test, the instrument continues to operate at
the measurement accuracy within specification.
Supply Voltage: • 24 VAC/DC (±10%);
• 100 to 240 VAC (-15 to +10%). Installation category: II;
Notes: 1. Before connecting the instrument to the power Pollution category: 2;
line, make sure that line voltage is equal to the Temperature drift: It is part of the global accuracy;
voltage shown on the identification label; Operating temperature: 0 to 50°C (32 to 122°F);
2. The polarity of the power supply has no importance; Storage temperature: -30 to +70°C (-22 to +158°F);
3. The power supply input is NOT fuse protected. Humidity: 20 to 90% RH, not condensing.
Please, provide a T type 1A, 250 V fuse externally.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 4


4. MODEL AND SUFFIX CODES
Model Code Suffix codes Description
TC10 -N o C o o o D o F Temperature Controller
Fixed code -N Always "-N"
L 24 VAC/DC (Custom order)
Power supply
H 100 to 240 VAC
Fixed code C Always "C"
R N N Relay output for on/off control
Relay output with 2 alarm relays,
R R R for ON/OFF or Heat/Cool control
with 1 alarm
V N N DC Output for SSR
DC Output for SSR with 2 alarm
OUT1 - 3 relays or DCV and relay output
V R R
for Heat/Cool control with 1
alarm
2 DCV outputs for SSR with 1
V V R
relay (Custom order)
Analog output with 2 alarm relays,
A R R or analog output and relay output
for Heat/Cool control with 1 alarm
Always "D" - Selectable I/O (logic
IN/OUT4 (Fixed code) D input/12 V SSR drive output/12VDC
20 mA transmitter power supply
S RS485 Modbus
Serial communication
N None
Fixed code F Always “F”
Option Code /GK Panel gasket for IP65

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 5


5. CONFIGURATION PROCEDURE 5.3 HOW TO ENTER THE
“CONFIGURATION MODES”
5.1 INTRODUCTION
Note: The TC10 is equipped with two different “configuration”
When the instrument is powered, it starts immediately to work methods:
according to the parameters values loaded in its memory. A) The “code” configuration method;
The instrument behaviour and its performance are governed B) The “complete” configuration method.
by the value of the stored parameters. The “code” configuration method is really fast but modifies
At the first start up the instrument will use a “default” only the most common configuration parameters.
parameter set (factory parameter set); this set is a generic The “complete” configuration method allows to take
one (e.g. a TC J input is programmed). advantage of all instrument features, giving more capabilities
WARNING! Before connecting the output actuators, it requires more actions and time.
we recommend to configure the parameters to Note that you can take advantage by both methods because if
suit your application (e.g.: input type, Control
you use the code configuration and then you enter in the
strategy, alarms, etc.).
complete configuration, all selections made by code are still valid.
To change these parameters you need to enter the
In both cases the instrument have one complete parameter set.
“Configuration mode”.
We call this set “configuration parameter set” (or
5.2 INSTRUMENT BEHAVIOUR AT “configuration parameters”).
POWER ON When code configuration method is used all the parameters
not modified by the code will maintain their default values.
At power ON the instrument can start in one of the following
mode depending on its configuration: In both cases the access to the configuration parameters is
protected by a password (a specific password for each method).
Auto mode
Note: The instrument will show only the parameters consis-
––The upper display shows the measured value; tent with the specific hardware and in accordance with
––The lower display shows the Set point value; the value assigned to the previous parameters
––The decimal figure of the less significant digit of the lower (e.g.: if you set an output as “not used” the instrument
display is OFF; will mask all other parameters related to this output).
–– The instrument is performing the standard closed loop control. 5.3.1 “Code” configuration procedure
Manual mode (OPLO) The controller configuration (Input type, Control mode, etc.)
––The upper display shows the measured value; can be made entering two 4-digit codes.
Before to enter into code configuration we suggest you to
––The lower display shows the power output [preceded by H
prepare the two codes according to the tables that follow.
(for heating) or C (for cooling)]. The MAN LED is lit;
Notes: 1. During the Code configuration procedure there is
––The instrument does not perform Automatic control;
no timeout.
––The control output is equal to 0% and can be manually
2. To leave, at any time, the Configuration session
modified by and buttons.
without saving the settings made, press the
Stand by mode (St.bY) button.
––The upper display shows the measured value; To enter into code configuration proceed as follows:
––The lower display shows alternately the set point value and 1. Push the button for more than 3 seconds.
the message St.bY or od; The upper display will show PASS (flashing) while the
––The instrument performs no control (the control outputs lower display will show 0;
are OFF); 2. Using and buttons set the password programmed
––The instrument is working as an indicator. in parameter [120] PAS4. The factory default password
We define all the above described conditions as for Code configuration is 300;
“Standard Display”. 3. Push the button;
If the password is correct the instrument will show one of
the following conditions:
• If no code is present, the display shows codE on the
upper display and oFF on the lower display.
Push the button to continue.
The upper display will flash cod1 while the lower display
shows 0000.
• If a previous code was stored, the upper display will
flash cod1 while the lower display shows the value of
cod1 stored in memory.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 6


4. Using and buttons set the code 1 value 5. Push the button.
according to the following tables. The upper display shows cod2 flashing while the lower
L M N O display shows 0000 or the cod2 value stored in memory.
Prepare your code 1 6. Using and buttons set the code 2 value
Input Type and Range L M according to the following tables.
TC J -50 to +1000°C 0 0 P Q R S
TC K -50 to +1370°C 0 1 Prepare your code 2
TC S -50 to 1760°C 0 2
Alarm 3 R
TC R -50 to +1760°C 0 3
Alarm 2 Q
TC T -70 to +400°C 0 4
Alarm 1 P
PT 100 -200 to +850°C 0 7
Not used 0 0 0
PT 1000 -200 to +850°C 0 8
Sensor break 1 1 1
Linear 0 to 60 mV 0 9
High 2 2 2
Linear 12 to 60 mV 1 0 Absolute
Low 3 3 3
Linear 0 to 20 mA (this selection forces Out 4 = TX) 1 1
External High/Low 4 4 4
Linear 4 to 20 mA (this selection forces Out 4 = TX) 1 2 Absolute High/Low
Internal High/Low 5 5 5
Linear 0 to 5 V 1 3
Deviation high 6 6 6
Linear 1 to 5 V 1 4 Deviation
Deviation low 7 7 7
Linear 0 to 10 V 1 5
External band 8 8 8
Linear 2 to 10 V 1 6 Band
Internal band 9 9 9
TC J -58 to +1832°F 1 7
TC K -58 to +2498°F 1 8
TC S -58 to 3200°F 1 9 c%d2: P Q R S
TC R -58 to +3200°F 2 0
TC T -94 to +752°F 2 1 Auxiliary functions activation S
PT 100 -328 to +1562°F 2 4 None 0
PT 1000 -328 to +1562°F 2 5 Wattmeter (instantaneous power expressed in W) 1
Wattmeter (energy expressed in Wh) 2
c%d1: L MN O Absolute worked time (expressed in days) 3
Absolute worked time (expressed in hours) 4
Control mode OP1 OP2 OP3 OP4 N O
H AL1 AL2 AL3 0 0 7. Push the button.
ON/OFF heating = H If the just entered codes are accepted, the upper display
NU AL1 AL2 H 0 1
C AL1 AL2 AL3 0 2 shows code while the lower display shows good.
ON/OFF cooling = C
NU AL1 AL2 C 0 3 8. Push the button to save the configuration code and
H C AL2 AL3 0 4 exit the Code configuration procedure.
H AL1 AL2 C 0 5
C H AL2 AL3 0 6
Note: After using the “Code configuration” method, it will
ON/OFF with neutral
zone (H/C) NU H AL2 C 0 7 always be possible to modify the parameters using the
C AL1 AL2 H 0 8 “Complete configuration” method. If the value of a
NU C AL2 H 0 9 parameter among those included in the configuration
H AL1 AL2 AL3 1 0 codes (cod1 - cod2) gets modified, the instrument
PID heating = H will acquire the change while maintaining all the other
NU AL1 AL2 H 1 1
C AL1 AL2 AL3 1 2 parameters.
PID cooling = C
NU AL1 AL2 C 1 3 WARNING! After a parameter change made as described
H C AL2 AL3 1 4 in the previous “Note”, when retrieving the
H AL1 AL2 C 1 5 configuration codes (cod1 - cod2), the lower
C H AL2 AL3 1 6
PID double action (H/C) display will show “oFF” to alert the operator that
NU H AL2 C 1 7
one of the parameters has been changed.
C AL1 AL2 H 1 8
NU C AL2 H 1 9

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 7


5.3.2 Complete configuration procedure 5.6 FACTORY RESET - DEFAULT
The configuration parameters are collected in various PARAMETERS LOADING PROCEDURE
groups. Every group defines all parameters related with a Sometime, e.g. when you re-configure an instrument
specific function (e.g.: control, alarms, output functions). previously used for other works or from other people or when
1. Push the button for more than 3 seconds. The upper you have made too many errors during configuration and
display will show PASS while the lower display will show 0. you decided to re-configure the instrument, it is possible to
2. Using and buttons set the programmed password. restore the factory configuration.
Notes: 1. The factory default password for configuration This action allows to put the instrument in a defined
parameters is equal to 30. condition (the same it was at the first power ON).
2. During parameter modification the instrument The default data are those typical values loaded in the
continue to perform the control. instrument prior to ship it from factory.
In certain conditions, when a configuration chan- To load the factory default parameter set, proceed as follows:
ge can produce a heavy bump to the process, it is 1. Press the button for more than 5 seconds. The upper
advisable to temporarily stop the controller from display will show PASS while the lower display shows 0;
controlling during the programming procedure
(control output will be OFF). 2. Using and buttons set the value -481;
A password equal to 2000 + the programmed 3. Push button;
value (e.g. 2000 + 30 = 2030). 4. The instrument will turn OFF all LEDs for a few seconds,
The control will restart automatically when the then the upper display will show dFLt (default) and then
configuration procedure will be manually closed. all LEDs are turned ON for 2 seconds. At this point the
Push the button instrument restarts as for a new power ON.
If the password is correct the display will show the acronym The procedure is complete.
].
of the first parameter group preceded by the symbol: Note: The complete list of the default parameters is available
In other words the upper display will show: ]inp
in Appendix A.
(group of the Input parameters). 5.7 CONFIGURING ALL THE PARAMETERS
The instrument is in configuration mode. In the following pages we will describe all the parameters of
the instrument. However, the instrument will only show the
5.4 HOW TO EXIT THE “CONFIGURATION parameters applicable to its hardware options in accordance
MODE” with the specific instrument configuration (i.e. setting AL1t
Push button for more than 3 seconds, the instrument will [Alarm 1 type] to nonE [not used], all parameters related to
come back to the “standard display”. alarm 1 will be skipped).

5.5 KEYBOARD FUNCTIONS DURING ]inP Group - Main and auxiliary input configuration
PARAMETER CHANGING [1] SEnS - Input type
A short press allows to exit from the current parameter Available: Always
group and select a new parameter group. Range: J = TC J
A long press allows you to close the configuration crAL = TC K
parameter procedure (the instrument will come back S = TC S
to the “standard display”). r = TC R
When the upper display is showing a group and the t = TC T
lower display is blank, this key allows to enter in the Pt1 = RTD Pt 100
selected group. Pt10 = RTD Pt 1000
When the upper display is showing a parameter and 0.60 = 0 to 60 mV linear
the lower display is showing its value, this key allows 12.60 = 12 to 60 mV linear
to store the selected value for the current parameter 0.20 = 0 to 20 mA linear
and access the next parameter within the same group. 4.20 = 4 to 20 mA linear
Allows to increase the value of the selected parameter. 0.5 = 0 to 5 V linear
Allows to decrease the value of the selected parameter. 1.5 = 1 to 5 V linear
+ These two keys allow to return to the previous 0.10 = 0 to 10 V linear
group. Proceed as follows: 2.10 = 2 to 10 V linear
Push the button and maintaining the pressure, Notes: 1. When a TC input is selected and a decimal figure
is programmed (see the next parameter) the max.
then push the button; release both the buttons.
displayed value becomes 999.9°C or 999.9°F.
Note: The group selection is cyclic as well as the selection
2. Every change of the SEnS parameter setting
of the parameters in a group.
will force the [2] dP = 0 and it will change all
parameters related with dP (e.g. set points,
proportional band, etc.).

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 8


[2] dP - Decimal point position [8] oPE - Safety output value
Available: Always. Available: Always.
Range: 0 to 3 when [1] SenS = Linear input; Range: -100 to 100 % (of the output).
0 or 1 when [1] SenS different from linear input. Notes: 1. When the instrument is programmed with one
Note: Every change of the dP parameter setting will produce control action only (heat or cool), setting a value
a change of the parameters related with it (e.g.: set outside of the available output range, the instrument
points, proportional band, etc.). will use Zero.
E.g.: When heat action only has been programmed,
[3] SSc - Initial scale read-out for linear inputs
and oPE is equal to -50% (cooling) the instrument
Available: When a linear input is selected by [1] SenS. will use Zero.
Range: -1999 to 9999.
2. When ON/OFF control is programmed and an out
Notes: 1. SSc allows the scaling of the analog input to set
of range is detected, the instrument will perform
the minimum displayed/measured value.
the safety output value using a fixed cycle time
The instrument will show a measured value up to
equal to 20 seconds.
5% less then SSc value and than it will show an
underrange error. [9] io4.F - I/O4 function selection
2. It is possible to set a initial scale read-out higher Available: Always.
then the full scale read-out in order to obtain a Range: on = Out4 will be ever ON (used as a transmitter
reverse read-out scaling. power supply);
E.g.: out4 = Used as digital output 4;
0 mA = 0 mBar and 20 mA = -1000 mBar (vacuum). dG2.c = Digital input 2 for contact closure;
dG2.U = Digital input 2 driven by 12 to 24 VDC.
[4] FSc - Full scale read-out for linear input
Notes: 1. Setting [9] io4.F = dG2.C or dG2U, the [25] O4F
Available: When a linear input is selected by [1] SenS. parameter becomes not visible while [11] diF2
Range: -1999 to 9999. parameter will become visible.
Notes: 1. Fsc allows the scaling of the analog input to set
2. Setting [9] io4F = on the [25] O4F parameter and
the maximum displayed/measured value.
the [11]diF2 parameter will NOT be visible.
The instrument will show a measured value up to
5% higher than [4] FSc value and then it will show 3. Setting [9] io4F different from dG2.c or dG2.U,
an overrange error. the instrument will force [13] diF2 parameter
equal to nonE. If [11] diF1 was equal to (SP4 or
2. It is possible to set a full scale read-out lower
UPDN) it will be forced to nonE.
than the initial scale read-out in order to obtain a
reverse read-out scaling. 4. The transfer from [9] io4F = ON to [9] io4F = Out4
E.g.: will make the [25] O4F parameter visible equal to
0 mA = 0 mBar and 20 mA = -1000 mBar (vacuum). nonE.

[5] unit - Engineering unit [10] diF1 - Digital input 1 function


Available: When a temperature sensor is selected by [1] Available: Always.
SenS parameter. Range: oFF = No function;
Range: °C = Celsius; 1 Alarm Reset [status];
°F = Fahrenheit. 2 Alarm acknowledge (ACK) [status];
3 Hold of the measured value [status]
[6] FiL - Digital filter on the measured value When the contact is closed the instrument ope-
Available: Always. rates in hold of the measured value;
Range: oFF (No filter); 4 Stand by mode of the instrument [status]
0.1 to 20.0 s. When the contact is closed the instrument oper-
Note: This is a first order digital filter applied on the ates in stand by mode;
measured value. For this reason it will affect the 5 Manual mode
measured value but also the control action and the When the contact is closed the instrument ope-
alarms behaviour. rates in manual mode;
6 HEAt with SP1 and CooL with “SP2” [status]
[7] inE - Selection of the Sensor Out of Range type
(see “Note about digital inputs”);
that will enable the safety output value 7 to 17 Reserved;
Available: Always. 18 Sequential set point selection [transition]
Range: our = When an overrange or an underrange is (see “Note about digital inputs”);
detected, the power output will be forced to 19 SP1/SP2 selection [status];
the value of [8] oPE parameter; 20 Binary selection of the set point made by digital
or = When an overrange is detected, the power input 1 (less significant bit) and digital input 2
output will be forced to the value of [8] oPE (most significant bit) [status];
parameter; 21 Digital input 1 will work in parallel with but-
ur = When an underrange is detected, the po- ton while digital input 2 will work in parallel with
wer output will be forced to the value of the button.
[8] oPE parameter. Note: When [11] diF2 is not available, items 20 and 21 are
not visible.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 9


[11] diF2 - Digital input 2 function 2 = DI1 Direct action,
Available: When [9] Io4.F = diG2. DI2 (if configured) Reverse action;
Range: oFF = No function; 3 = DI1 Reverse action,
1 Alarm Reset [status]; DI2 (if configured) Reverse action.
2 Alarm acknowledge (ACK) [status];
3 Hold of the measured value [status] ]out Group - Output parameters
When the contact is closed the instrument ope- 13] o1.t - Out 1 type
rates in hold of the measured value; Available: When the out 1 is a linear output.
4 Stand by mode of the instrument [status] Range: 0-20 0 to 20 mA;
When the contact is closed the instrument ope- 4-20 4 to 20 mA;
rates in stand by mode; 0-10 0 to 10 V;
5 Manual mode 2-10 2 to 10 V.
When the contact is closed the instrument ope-
[14] o1.F - Out 1 function
rates in manual mode;
Available: Always.
6 HEAt with SP1 and CooL with “SP2” [status]
Range:  • When the out 1 is a linear output:
(see “Note about digital inputs”);
nonE = Output not used. With this setting the status
7 Timer Run/Hold/Reset [transition]
of this output can be driven directly from
Short closure allows to start timer execution
serial link;
and to suspend it while a long closure (longer
H.rEG = Heating output;
than 10 seconds) allows to reset the timer;
c.rEG = Cooling output;
7 to 17 Reserved;
r.inP = Measured value Analog retransmission.
18 Sequential set point selection [transition]
r.Err = Analog retransmission of the measured
(see “Note about digital inputs”);
error (PV-SP);
19 SP1/SP2 selection [status];
r.SP = Analog retransmission of the operative set
20 Binary selection of the set point made by digital
point;
input 1 (less significant bit) and digital input 2
r.SEr = Analog retransmission of a value coming
(most significant bit) [status];
from serial link;
21 Digital input 1 will work in parallel with the
• When the out 1 is a digital output (relay or SSR):
button while digital input 2 will work in parallel
nonE = Output not used. With this setting the status
with the button.
of this output can be driven directly from
Notes: 1. When [10] diF1 or [11] diF2 (e.g. diF1) are equal serial link;
to 6 the instrument operates as follows: H.rEG = Heating output;
• When the contact is open, the control action is an c.rEG = Cooling output;
heating action and the active set point is SP. AL = Alarm output;
• When the contact is closed, the control action is t.out = Reserved;
a cooling action and the active set point is SP2. t.HoF = Reserved;
2. When [10] diF1 = 20, [11] diF2 setting is forced to P.End = Reserved;
20 and diF2 cannot perform another function. P.HLd = Reserved;
3. When [10] diF1 = 20 and [11] diF2 = 20, the set P. uit = Reserved;
point selection will be in accordance with the P.run = Reserved;
following table: P.Et1 = Reserved;
Dig In1 Dig. In2 Operative set point P.Et2 = Reserved;
or.bo = Out-of-range or burn out indicator;
Off Off Set point 1
P.FAL = Power failure indicator;
On Off Set point 2 bo.PF = Out-of-range, Burnout and Power failure
Off On Set point 3 indicator;
On On Set point 4 St.By = Stand By status indicator;
diF1 = Repeats the digital input 1 status;
4. When [10] diF1 is equal to 21, [11] diF2 setting diF2 = Repeats the digital input 2 status;
is forced to up.du (21 value) and cannot perform on = Out1 always ON;
another function. riSP = Inspection request.
5. When a “Sequential set point selection” is used Notes: 1. When two or more outputs are programmed in the
(diF1 or diF2 = 18), every closure of of the logic same way, these outputs will be driven in parallel.
input increase the value of SPAT (active set point) 2. The power failure indicator will be reset when the
of one step. The selection is cyclic: instrument detect an alarm reset command by
SP -> SP2 -> SP3 -> SP4. key, digital input or serial link.
3. When no control output is programmed, all the
[12] di.A - Digital Inputs Action relative alarm (when present) will be forced to
Available: Always. nonE (not used).
Range: 0 = DI1 Direct action,
DI2 (if configured) Direct action;
1 = DI1 Reverse action,
DI2 (if configured) Direct action;

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 10


[15] A.o1L - Initial scale value of the analog bo.PF = Out-of-range, Burnout and Power failure
retransmission indicator;
Available: When Out 1 is a linear output and [14] O1F is St.By = Stand By status indicator;
equal to r.inp, r.Err, r.SP or r.SEr diF1 = Out2 repeates the digital input 1 status;
Range: -1999 to [16] Ao1H. diF2 = Out2 repeates the digital input 2 status;
on = Out 2 always ON;
[16] A.o1H - Full scale value of the analog riSP = Inspection request.For other details see
retransmission [14] O1F parameter.
Available: When Out 1 is a linear output and [14] O1F is [20] o2.AL - Alarms linked up with Out 2
equal to r.inp, r.Err, r.SP or r.SEr.
Available: When [18] o2F = AL.
Range: [15] Ao1L to 9999.
Range: 0 to 63 with the following rule:
[17] o1.AL - Alarms linked up with the out 1 +1 = Alarm 1;
Available: When [14] o1F = AL. +2 = Alarm 2;
Range: 0 to 63 with the following rules: +4 = Alarm 3;
+1 = Alarm 1; +8 = Loop break alarm;
+2 = Alarm 2; +16 = Sensor break (burn out);
+4 = Alarm 3; +32 = Overload on Out 4 (short circuit on OP4).
+8 = Loop break alarm; For more details see [17] o1.AL parameter.
+16 = Sensor break (burn out);
+32 = Overload on Out4 (short circuit on the Out4). [21] o2Ac - Out 2 action
Example 1: Setting 3 (2+1) the output will be driven by the Available: When [19] o2F is different from “nonE”.
alarm 1 and 2 (OR condition). Range: dir = Direct action;
rEU = Reverse action;
Example 2: Setting 13 (8+4+1) the output will be driven by
dir.r = Direct action with revers LED indication;
alarm 1 + alarm 3 + loop break alarm.
rEU.r = Reverse action with reverse LED indication.
[18] o1.Ac - Out 1 action For more details see [18] o1.Ac parameter.
Available: When [14] o1F is different from “nonE”. [22] o3F - Out 3 function
Range: dir = Direct action;
Available: When the instrument has out 3 option.
rEU = Reverse action;
Range: nonE = Output not used. With this setting the status
dir.r = Direct action with revers LED indication;
of the this output can be driven directly from
rEU.r = Reverse action with reverse LED indication.
serial link;
Notes: 1. Direct action: the output repeats the status of the
H.rEG = Heating output;
driven element.
c.rEG = Cooling output;
E.g.: The output is an alarm output with direct
AL = Alarm output;
action. When the alarm is ON, the relay will be
t.out = Reserved;
energized (logic output 1).
t.HoF = Reserved;
2. Reverse action: the output status is the opposite P.End = Reserved;
of the status of the driven element. P.HLd = Reserved;
E.g.: The output is an alarm output with reverse P. uit = Reserved;
action. When the alarm is OFF, the relay will be P.run = Reserved;
energized (logic output 1). This setting is usually P.Et1 = Reserved;
named “fail-safe” and it is generally used in P.Et2 = Reserved;
dangerous process in order to generate an alarm or.bo = Out-of-range or burn out indicator;
when the instrument power supply goes OFF or P.FAL = Power failure indicator;
the internal watchdog starts. bo.PF = Out-of-range, burn out and Power failure
[19] o2F - Out 2 function indicator;
Available: When the instrument has out 2 option. St.By = Stand By status indicator
Range: nonE = Output not used. With this setting the sta- diF1 = The output repeats the digital input 1 status;
tus of the this output can be driven directly diF2 = The output repeats the digital input 2 status;
from serial link; on = Out 3 always ON;
H.rEG = Heating output (see warning); riSP = Inspection request.
c.rEG = Cooling output; For other details see [14] O1F parameter.
AL = Alarm output; [23] o3.AL - Alarms linked up with Out 3
t.out = Reserved;
Available: When [21] o3F = AL.
t.HoF = Reserved;
Range: 0 to 63 with the following rule:
P.End = Reserved;
+1 = Alarm 1;
P.HLd = Reserved;
+2 = Alarm 2;
P. uit = Reserved;
+4 = Alarm 3;
P.run = Reserved;
+8 = Loop break alarm;
P.Et1 = Reserved;
+16 = Sensor break (burn out);
P.Et2 = Reserved;
+32 = Overload on Out 4 (short circuit on OP 4).
or.bo = Out-of-range or burn out indicator;
For more details see [17] o1.AL parameter.
P.FAL = Power failure indicator;

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 11


[24] o3Ac - Out 3 action LodE = Deviation low alarm (relative);
Available: when [21] o3F is different from “nonE”. HidE = Deviation high alarm (relative);
Range: dir = Direct action; LHdo = Relative band alarm with alarm indication
rEU = Reverse action; out of the band;
dir.r = Direct action with revers LED indication; LHdi = Relative band alarm with alarm indication
rEU.r = Reverse action with reverse LED indication. inside the band.
For more details see [18] o1.Ac parameter. • When no output is programmed as control output:
nonE = Alarm not used;
[25] o4F - Out 4 function LoAb = Absolute low alarm;
Available: When the [9] io4.F = Out4. HiAb = Absolute high alarm;
Range: nonE = Output not used. With this setting the status LHAo = Absolute band alarm with alarm indication
of the this output can be driven directly out of the band;
from serial link. LHAi = Absolute band alarm with alarm indication
H.rEG = Heating output; inside the band;
c.rEG = Cooling output; SE.br = Sensor break.
AL = Alarm output; Notes: 1. The relative and deviation alarms are “relative” to
t.out = Reserved; the operative set point value.
t.HoF = Reserved; PV PV
P.End = Reserved; AL1
HAL1
P.HLd = Reserved; HAL1
P. uit = Reserved; AL1

P.run = Reserved; OUT time OUT time


off ON off ON off off ON off ON off
P.Et1 = Reserved; AL1 AL1
P.Et2 = Reserved; LoAb HiAb
or.bo = Out-of-range or burn out indicator; PV PV
P.FAL = Power failure indicator; AL1H HAL1 AL1H HAL1
bo.PF = Out-of-range, burn out and Power failure SP
indicator; AL1L HAL1 -AL1L HAL1
St.By = Stand By status indicator.
OUT time time
For other details see [14] O1F parameter. AL1 off ON off ON off OUT off ON off ON off
AL1
[26] o4.AL - Alarms linked up with Out 4 LHAo LHdo
Available: When [25] o4F = AL. 2. The (SE.br) sensor break alarm will be ON when
Range: 0 to 63 with the following rule. the display shows ---- indication.
+1 = Alarm 1; [29] Ab1 - Alarm 1 function
+2 = Alarm 2;
Available: When [28] AL1t is different from “nonE”.
+4 = Alarm 3;
Range: 0 to 15 with the following rule:
+8 = loop break alarm;
+1 = Not active at power up;
+16 = Sensor break (burn out);
+2 = Latched alarm (manual reset);
+32 = overload on Out 4 (short circuit on OP4).
+4 = Acknowledgeable alarm;
For more details see [17] o1.AL parameter.
+8 = Relative alarm not active at set point change.
[27] o4Ac - Out 4 action Example: Setting Ab1 equal to 5 (1+4) the alarm 1 will be
Available: When [25] o4F is different from “nonE”. “not active at power up” and “Acknowledgeable”.
Range: dir = Direct action; Notes: 1. The “not active at power up” selection allows to
rEU = Reverse action; inhibit the alarm function at instrument power up
dir.r = Direct action with revers LED indication; or when the instrument detects a transfer from:
rEU.r = Reverse action with reverse LED indication. • Manual mode (oplo) to auto mode;
For more details see [18] o1.Ac parameter. • Stand-by mode to auto mode.
The alarm will be automatically enabled when
]AL1 Group - Alarm 1 parameters the measured value reaches, for the first time,
[28] AL1t - Alarm 1 type the alarm threshold ±hysteresis (in other words,
when the initial alarm condition disappears).
Available: Always.
Range:  • When one or more outputs are programmed as PV
AL1
control output:
nonE = Alarm not used; time
LoAb = Absolute low alarm; Ab1 = +0 ON off ON off
HiAb = Absolute high alarm;
Ab1 = +1 off ON off
LHAo = Absolute band alarm with alarm indication
out of the band; PWR ON
LHAi = Absolute band alarm with alarm indication 2. A “Latched alarm” (manual reset) is an alarm
inside the band; that will remain active even if the conditions that
SE.br = Sensor break; generated the alarm no longer persist. Alarm

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 12


reset can be done only by an external command the Alarm threshold value and the point the Alarm
( button, digital inputs or serial link). automatically resets.
PV 2. When the alarm threshold plus or minus the
AL1
hysteresis is out of input range, the instrument
will not be able to reset the alarm.
time
Ab1 = +0 off ON off Example: Input range 0 to 1000 (mBar).
off ON off
––Set point equal to 900 (mBar);
Ab1 = +2
Alarm reset Alarm reset ––Deviation low alarm equal to 50 (mBar);
––Hysteresis equal to 160 (mBar) the theoretical reset point is
3. An “Acknowledgeable” alarm is an alarm that can
900 - 50 + 160 = 1010 (mBar) but this value is out of range.
be reset even if the conditions that generated the
The reset can be made only by turning the instrument
alarm are still present. Alarm acknowledge can
OFF, removing the condition that generate the alarm and
be done only by an external command ( button,
then turn the instrument ON again;
digital inputs or serial link).
––All band alarms use the same hysteresis value for both
PV
AL1
thresholds;
––When the hysteresis of a band alarm is bigger than the
time programmed band, the instrument will not be able to reset
Ab1 = +0 off ON off the alarm.
Ab1 = +4 off ON off ON off Example: Input range 0 to 500 (°C).
Alarm ACK Alarm ACK ––Set point equal to 250 (°C);
A “relative alarm not active at set point change” ––Relative band alarm;
is an alarm that masks the alarm condition after ––Low threshold equal to 10 (°C);
a set point change until process variable reaches ––High threshold equal to 10 (°C);
the alarm threshold ±hysteresis.
––Hysteresis equal to 25 (°C).
Sp2 PV
AL1 [34] AL1d - Alarm 1 delay
Sp1 Available: When [28] AL1t is different from “nonE”.
AL1
Range: From oFF (0) to 9999 seconds.
time
Ab1 = +0 ON off ON off ON off Note: The alarm goes ON only when the alarm condition
ON off ON off
persists for a time longer than [34] AL1d time but the
Ab1 = +8
reset is immediate.
4. The instrument does not store in EEPROM the [35] AL1o - Alarm 1 enabling during Stand-by mode
alarm status. For this reason, the alarm status and out of range indications
will be lost if a power down occurs.
Available: When [28] AL1t is different from “nonE”.
[30] AL1L - For High and low alarms it is the low Range: 0 = Never;
limit of the AL1 threshold 1 = During stand by;
- For band alarm it is low alarm threshold 2 = During overrange and underrange;
Available: When [28] AL1t is different from “nonE” or [28] 3 = During overrange, underrange and stand-by;
AL1t is different from “SE.br”.
Range: From -1999 to [31] AL1H engineering units. ]AL2 Group - Alarm 2 parameters
[31] AL1H - For High and low alarms, it is the high [36] AL2t - Alarm 2 type
limit of the AL1 threshold Available: Aways.
- For band alarm, it is the high alarm Range:  • When one or more outputs are programmed as
threshold control output:
Available: When [28] AL1t is different from “nonE” or [28] nonE = Alarm not used;
AL1t is different from “SE.br”. LoAb = Absolute low alarm;
Range: From [30] AL1L to 9999 engineering units. HiAb = Absolute high alarm;
LHAo = Absolute band alarm with alarm indication
[32] AL1- Alarm 1 threshold
out of the band;
Available: When: LHAi = Absolute band alarm with alarm indication
[28] AL1t = LoAb - Absolute low alarm; inside the band;
[28] AL1t = HiAb - Absolute high alarm; SE.br = Sensor break;
[28] AL1t = LodE - Deviation low alarm (relative); LodE = Deviation low alarm (relative);
[28] AL1t = LidE - Deviation high alarm (relative). HidE = Deviation high alarm (relative);
Range: From [30] AL1L to [31] AL1H engineering units. LHdo = Relative band alarm with alarm indication
[33] HAL1 - Alarm 1 hysteresis out of the band;
Available: When [28] AL1t is different from “nonE” or LHdi = Relative band alarm with alarm indication
[28] AL1t is different from “SE.br”. inside the band;
Range: 1 to 9999 engineering units. • When no output is programmed as control output:
Notes: 1. The hysteresis value is the difference between nonE = Alarm not used;

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 13


LoAb = Absolute low alarm; ]AL3 Group - Alarm 3 parameters
HiAb = Absolute high alarm;
LHAo = Absolute band alarm with alarm indication
[44] AL3t - Alarm 3 type
out of the band; Available: Always.
LHAi = Absolute band alarm with alarm indication Range:  • When one or more outputs are programmed as
inside the band; control output:
SE.br = Sensor break. nonE = Alarm not used;
Note: The relative alarm are “relative” to the current set point LoAb = Absolute low alarm;
(this may be different from the Target setpoint if you HiAb = Absolute high alarm;
are using the ramp to set point function). LHAo = Absolute band alarm with alarm indication
out of the band;
[37] Ab2 - Alarm 2 function LHAi = Absolute band alarm with alarm indication
Available: When [36] AL2t is different from “nonE”. inside the band;
Range: 0 to 15 with the following rule: SE.br = Sensor break;
+1 = Not active at power up; LodE = Deviation low alarm (relative);
+2 = Latched alarm (manual reset); HidE = Deviation high alarm (relative);
+4 = Acknowledgeable alarm; LHdo = Relative band alarm with alarm indication
+8 = Relative alarm not active at set point change. out of the band;
Example: Setting Ad2 equal to 5 (1+4) the alarm 2 will be LHdi = Relative band alarm with alarm indication
“not active at power up” and “Acknowledgeable”. inside the band.
Note: For other details see [28] Ab1 parameter. • When no output is programmed as control output:
nonE = Alarm not used;
[38] AL2L - For High and low alarms it is the low LoAb = Absolute low alarm;
limit of the AL2 threshold HiAb = Absolute high alarm;
- For band alarm it is low alarm threshold LHAo = Absolute band alarm with alarm indication
Available: When [36] AL2t is different from “nonE” or [36] out of the band;
AL2t is different from “SE.br”. LHAi = Absolute band alarm with alarm indication
Range: -1999 to [39] AL2H engineering units. inside the band;
[39] AL2H - For High and low alarms it is the high SE.br = Sensor break.
limit of the AL2 threshold Note: The relative alarm are “relative” to the current set point
(this may be different to the Target set point if you are
- For band alarm it is high alarm threshold
using the ramp to set point function).
Available: When [36] AL2t is different from “nonE” or
[36] AL2t is different from “SE.br”. [45] Ab3 - Alarm 3 function
Range: From [38] AL2L to 9999 engineering units. Available: When [43] AL3t is different from “nonE”.
[40] AL2 - Alarm 2 threshold Range: 0 to 15 with the following rule:
Available: When: +1 = Not active at power up;
[36] AL2t = LoAb Absolute low alarm; +2 = Latched alarm (manual reset);
[36] AL2t = HiAb Absolute high alarm; +4 = Acknowledgeable alarm;
[36] AL2t = LodE Deviation low alarm (relative); +8 = Relative alarm not active at set point change.
[36] AL2t = LidE Deviation high alarm (relative). Example: Setting Ad3 equal to 5 (1+4) the alarm 3 will be
Range: From [38] AL2L to [39] AL2H engineering units. “not active at power up” and “Acknowledgeable”.
[41] HAL2 - Alarm 2 hysteresis Note: For other details see [29] Ab1 parameter.
Available: When [36] AL2t is different to “nonE” or [36] AL2t [46] AL3L - For High and low alarms it is the low
is different from “SE.br”. limit of the AL3 threshold
Range: 1 to 9999 engineering units. - For band alarm, it is low alarm threshold
Note: For other details see [33] HAL1 parameter. Available: When [44] AL3t is different from “nonE” or [44]
[42] AL2d - Alarm 2 delay AL3t is different from “SE.br”.
Available: When [36] AL2t different form “nonE”. Range: -1999 to [47] AL3H engineering units.
Range: From oFF (0) to 9999 seconds. [47] AL3H - For High and low alarms it is the high
Note: The alarm goes ON only when the alarm condition limit of the AL3 threshold
persist for a time longer than [42] AL2d time but the - For band alarm it is high alarm threshold
reset is immediate. Available: When [44] AL3t is different from “nonE” or [44]
[43] AL2o - Alarm 2 enabling during Stand-by mode AL3t is different from “SE.br”.
Range: From [46] AL3L to 9999 engineering units.
and out of range indications
Available: When [36] AL2t different from “nonE”. [48] AL3 - Alarm 3 threshold
Range: 0 = Never; Available: When:
1 = During stand by; • [44] AL3t = LoAb Absolute low alarm;
2 = During overrange and underrange; • [44] AL3t = HiAb Absolute high alarm;
3 = During overrange, underrange and stand-by. • [44] AL3t = LodE Deviation low alarm (relative);
• [44] AL3t = LidE Deviation high alarm (relative).
Range: From [46] AL3L to [47] AL3H engineering units.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 14


[49] HAL3 - Alarm 3 hysteresis [55] LbcA - Condition for LBA enabling
Available: When [44] AL3t is different to “nonE” or [44] AL3t Available: when [52] LbAt is different from oFF.
is different from “SE.br”. Range: uP = Enabled when the PID requires the maxi-
Range: 1 to 9999 engineering units. mum power only;
Note: For other details see [33] HAL1 parameter. dn = Enabled when the PID requires the mini-
mum power only;
[50] AL3d - Alarm 3 delay both = Enabled in both condition (when the PID re-
Available: When [44] AL3t different form “nonE”. quires the maximum or the minimum power).
Range: From oFF (0) to 9999 seconds. LBA application example:
Note: The alarm goes ON only when the alarm condition LbAt (LBA time) = 120 seconds (2 minutes);
persist for a time longer than [50] AL3d time but the LbAS (delta LBA) = 5°C.
reset is immediate.
The machine has been designed in order to reach 200°C in
[51] AL3o - Alarm 3 enabling during Stand-by mode 20 minutes (20°C/min);
and out of range indications When the PID demands 100% power, the instrument starts
Available: When [44] AL3t is different from “nonE” or the time count.
[44] AL3t is different from “SE.br”. During time count if the measured value increases more
Range: 0 = Never; than 5°C, the instrument restarts the time count. Otherwise
1 = During stand by; if the measured value does not reach the programmed delta
2 = During overrange and underrange; (5°C in 2 minutes) the instrument will generate the alarm.
3 = During overrange, underrange and stand-by.
]rEG group - Control parameters
] LbA group - Loop break alarm
The rEG group will be available only when at least one
General note about LBA alarm output is programmed as control output (H.rEG or C.rEG).
The LBA operate as follows: applying the 100% of the power
[56] cont - Control type:
output to a process, the process variable, after a time due to the
process inertia, begins to change in a known direction (increases Available: When at least one output is programmed as con-
for an heating action or decreases for a cooling action). trol output (H.rEG or C.rEG).
Range:  • When two control action (heat & cool) are pro-
Example: If I apply 100% of the power output to a furnace, grammed:
the temperature must go up unless one of the component in Pid = PID (heat and cool);
the loop is faulty (heater, sensor, power supply, fuse, etc.) nr = Heat/Cool ON/OFF control with neutral zone.
The same philosophy can be applied to the minimum power.
PV
In our example, when I turn OFF the power to a furnace, the HSEt
SP
temperature must go down, if not the SSR is in short circuit, HSEt
the valve is jammed, etc..
LBA function is automatically enabled when the PID requires OUTH.rEG time
the maximum or the minimum power. (heating) ON off ON
OUTc.rEG
When the process response is slower than the programmed (cooling)
off ON off

limit the instrument generates an alarm.


• When one control action (heat or cool) is programmed:
Notes: 1. When the instrument is in manual mode, the LBA Pid = PID (heat or cool);
function is disabled. On.FA = ON/OFF asymmetric hysteresis;
2. When LBA alarm is ON the instrument continues On.FS = ON/OFF symmetric hysteresis;
to perform the standard control. If the process
PV PV
response comes back into the programmed limit, SP
the instrument automatically resets the LBA alarm. HSEt
SP
HSEt

3. This function is available only when the programmed time time


control algorithm is equal to PID (Cont = PID). OUT OUT
ON off ON off ON ON off ON off ON
H.rEG C.rEG
[52] LbAt - LBA time HEAt - On.FA C oo L - O n .FA
Available: When [56] Cont = PID.
Range: oFF = LBA not used; PV
HSEt PV
SP
1 to 9999 seconds. HSEt SP HSEt
HSEt
[53] LbSt - Delta measure used by LBA during time time
Soft start OUT
off
OUT
ON ON off ON ON off ON off ON
Available: When [52] LbAt is different from oFF. H.rEG H.rEG
HEAt - On.FS C oo L - O n .FS
Range: oFF = loop break alarm is inhibit during soft start;
1 to 9999 engineering units. Notes: 1. ON/OFF control with asymmetric hysteresis:
• OFF when PV > SP;
[54] LbAS - Delta measure used by loop break • ON when PV < (SP - hysteresis).
alarm (loop break alarm step)
2. ON/OFF control with symmetric hysteresis:
Available: When [52] LbAt is different from oFF. • OFF when PV > (SP + hysteresis);
Range: 1 to 9999 engineering units. • ON when PV < (SP - hysteresis).

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 15


[57] Auto - Auto tune selection [60] HSEt - Hysteresis of the ON/OFF control
There are three auto-tune algorithms: Available: When [56] cont is different from PID.
• Oscillating auto-tune; Range: 0 to 9999 engineering units.
• Fast auto-tune; [61] cPdt - Time for compressor protection
• EvoTune. Available: When [56] cont = nr.
Range: OFF = Protection disabled
1. The oscillating auto-tune is the usual auto-tune and:
1 to 9999 seconds.
• It is more accurate;
• Can start even if PV is close to the set point; [62] Pb - Proportional band
• Can be used even if the set point is close to the Available: When [56] cont = PID and [59] SELF = no.
ambient temperature. Range: 1 to 9999 engineering units.
2. The fast type is suitable when: Note: Auto-tune functions calculate this value.
• The process is very slow and you want to be opera- [63] ti - Integral time
tive in a short time; Available: When [56] cont = PID and [59] SELF = no.
• When an overshoot is not acceptable; Range:  • OFF = Integral action excluded;
• In multi loop machinery where the fast method reduces • 1 to 9999 seconds;
the calculation error due to the effect of the other loops. • inF= Integral action excluded.
3. The EvoTune type is suitable when: Note: Auto-tune functions calculate this value.
• You have no information about your process;
• You can not be sure about the end user skills; [64] td - Derivative time
• You desire an auto tune calculation independently Available: When [56] cont = PID and [59] SELF = no.
from the starting conditions (e.g. set point change Range:  • oFF - derivative action excluded;
during tune execution, etc). • 1 to 9999 seconds.
Note: Fast auto-tune can start only when the measured Note: Auto-tune functions calculate this value.
value (PV) is lower than (SP + 1/2 SP). [65] Fuoc - Fuzzy overshoot control
Available: When [56] cont = PID
This parameter reduces the overshoot usually present at
Range: -4 to 8 where:
instrument start up or after a set point change and it will be
-4 = Oscillating auto-tune with automatic restart
active only in this two cases.
at all set point change;
-3 = Oscillating auto-tune with manual start; Setting a value between 0.00 and 1.00 it is possible to slow
-2 = Oscillating auto-tune with automatic start at down the instrument action during set point approach.
the first power up only; Setting Fuoc = 1 this function is disabled.
-1 = Oscillating auto-tune with automatic restart PV 2
at every power up; SP
1
0 = Not used;
1 = Fast auto tuning with automatic restart at 3
every power up;
2 = Fast auto-tune with automatic start at the time
first power up only;
3 = FAST auto-tune with manual start; Available: When [56] cont = PID and [59] SELF = no.
4 = FAST auto-tune with automatic restart at all Range: 0 to 2.00.
set point change. Note: Fast auto-tune calculates the Fuoc parameter while
5 = EvoTune with automatic restart at every the oscillating one sets it equal to 0.5.
power up; [66] tcH - Cycle time of the heating output
6 = EvoTune with automatic start at the first
Available: When at least one output is programmed in order
power up only;
to be the heating output (H.rEG),
7 = EvoTune with manual start;
[56] cont = PID and [59] SELF = no.
8 = EvoTune with automatic restart at all set
Range: 1.0 to 130.0 seconds.
point change.
[58] Aut.r - Manual start of the auto-tune [67] rcG - Power ratio between heating and
cooling action (relative cooling gain)
Available: When [56] cont = PID.
Range: oFF = The instrument is not performing the auto-tune; The instrument uses the same PID parameter set for heat
on = The instrument is performing the auto-tune. and for cool action but the efficiency of the two actions are
usually different.
[59] SELF - Self-tune enable
This parameter allows to define the ratio between the efficiency
The self-tuning is an adaptive algorithm able to optimize of the heating system and the efficiency of the cooling one.
continuously the PID parameter value.
An example will help us to explain you the philosophy.
This algorithm is specifically designed for all process subjected to
big load variation able to change heavily the process response. Consider one loop of a plastic extruder. The working
temperature is equal to 250°C.
Available: When [56] cont = PID .
Range: YES = self-tune active; When you want to increase the temperature from 250 to 270°C
no = self-tune not active. (DT = 20°C) using 100% of the heating power (resistor), you
will need 60 seconds.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 16


On the contrary, when you want to decrease the temperature [74] SSt - Soft start time
from 250 to 230°C (DT = 20°C) using 100% of the cooling Available: When at least one output is programmed as
power (fan), you will need 20 seconds only. control output.
In our example the ratio is equal to 60/20 = 3 ([67] rcG = 3) Range: oFF = Function not used;
and it say that the efficiency of the cooling system is 3 time 0.01 to 7.59 hh.mm;
more efficient of the heating one. inF = Soft start always active.
Available: When two control action are programmed
[75] SS.tH - Threshold for soft start disabling
(H.rEG and c.rEG) and [56] cont = PID and
[59] SELF = no. Available: When at least one output is programmed as
Range: 0.01 to 99.99. control output.
Range: -1999 to 9999 engineering units.
Note: auto-tune functions calculate this value.
Notes: 1. When the power limiter have a positive value (the
[68] tcc - Cycle time of the cooling output limit is applied to the heating action) the soft start
Available: When at least one output is programmed in order function will be aborted when the measured value
to be the cooling output (c.rEG), [56] cont = PID is greater or equal to SS.tH parameter.
and [59] SELF = no. 2. When the power limiter have a negative value
Range: 1.0 to 130.0 seconds. (the limit is applied to the cooling action) the soft
[69] rS - Manual reset (integral pre-load) start function will be aborted when the measured
It allows to drastically reduce the undershoot due to a value is lower or equal to SS.tH parameter.
hot restart. When your process is steady, the instrument
operates with a steady power output (e.g.: 30%).
]SP Group - Set point parameters
If a short power down occurs, the process restarts with a The SP group will be available only when at least one output
process variable close to the set point while the instrument is programmed as control output (H.rEG or C.rEG).
starts with an integral action equal to zero. [76] nSP - Number of used set points
Setting a manual reset equal to the average power output (in our Available: When at least one output is programmed as
example 30%) the instrument will start with a power output equal control output.
to the value it will use at steady state (instead of zero) and the Range: 1 to 4.
undershoot will become very little (in theory equal to zero).
Note: When you change the value of this parameter, the
Available: When [56] cont = PID.
instrument operates as follows:
Range: -100.0 to +100.0%.
• [83] A.SP parameter will be forced to SP.
[72] od - Delay at power up • The instrument verifies that all used set point are
Available: When at least one output is programmed as within the limits programmed by [77] SPLL and [78]
control output. SPHL. If an SP is out of this range, the instrument
Range: oFF: Function not used; forces it to the maximum acceptable value
0.01 to 99.59 hh.mm.
[77] SPLL - Minimum set point value
Notes: 1. This parameter defines the time during which
(after a power up) the instrument remains in stand Available: When at least one output is programmed as
by mode before to start all other function (control, control output.
alarms, program, etc.). Range: From -1999 to [78] SPHL engineering units.
2. When a program with automatic start at power up Notes: 1. When you change the [77] SPLL value, the
and od function are programmed, the instrument instrument checks all local set points (SP, SP2,
performs od function before to start the program. SP3 and SP4 parameters) and all set points of the
program ([97] Pr.S1, [102] Pr.S2, [107] Pr.S3, [112]
3. When an auto-tune with automatic start at power
Pr.S4 parameters). If an SP is out of this range, the
up and od function are programmed, the autotune
instrument forces it to the maximum acceptable value
will start at the end of od delay.
2. A [77] SPLL change produces the following actions:
[73] St.P - Maximum power output used during • When [84] SP.rt = SP the remote set point will
soft start be forced to be equal to the active set point
Available: When at least one output is programmed as • When [84] SP.rt = trim the remote set point will
control output. be forced to zero
Range: -100 to +100%. • When [84] SP.rt = PErc the remote set point
Notes: 1. When St.P parameter have a positive value, the will be forced to zero
limit will be applied to the heating output(s) only.
[78] SPHL - Maximum set point value
2. When St.P parameter have a negative value, the
Available: When at least one output is programmed as
limit will be applied to the cooling output(s) only.
control output.
3. When a program with automatic start at power
Range: From [78] SPLL to 9999 engineering units.
up and soft start function are programmed, the
instrument performs the soft start and than the Note: For other details see [78] SPLL parameter.
program function. [79] SP - Set Point 1
4. The auto-tune function will be performed after Available: When at least one output is programmed as
soft start function. control output.
5. The Soft start function is available also when ON/ Range: From [77] SPLL to [78] SPHL engineering units.
OFF contro l is used.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 17


[80] SP 2 - Set Point 2 The first zone is the master zone and it uses a set point
Available: When at least one output is programmed as con- equal to 210°C.
trol output and [76] nSP > 2. The second zone has a local set point equal to -45°C.
Range: From [77] SPLL to [78] SPHL engineering units. The third zone has a local set point equal to -45 (°C).
[81] SP 3 - Set Point 3 The fourth zone has a local set point equal to -30.
Available: When at least one output is programmed as con- The fifth zone has a local set point equal to +40.
trol output and [76] nSP > 3.
The sixth zone has a local set point equal to +50.
Range: From [77] SPLL to [78] SPHL engineering units.
In this way, the thermal profile will be the following:
[82] SP 4 - Set Point 4
––Master SP = 210°C;
Available: When at least one output is programmed as con-
trol output and [76] nSP =4. ––Second zone SP = 210 -45 = 165°C;
Range: From [77] SPLL to [78] SPHL engineering units. ––Third zone SP = 210 -45 = 165°C;
[83] A.SP - Selection of the active Set point ––Fourth zone SP = 210 - 30 = 180°C;
Available: When at least one output is programmed as ––Fifth zone SP = 210 + 40 = 250°C;
control output. ––Sixth zone SP = 210 + 50 = 260°C.
Range: From “SP” to [76] nSP. Changing the SP of the master unit, all the other slave units
Notes: 1. A [83] A.SP change produces the following actions: will immediately change their operative set point.
• When [84] SP.rt = SP - the remote set point will
be forced to be equal to the active set point;
[85] SPLr - Local/remote set point selection
• When [84] SP.rt = trin - the remote set point will Available: When at least one output is programmed as
be forced to zero; control output.
• When [84] SP.rt = PErc - the remote set point Range: Loc = Local set point selected by [83] A.SP;
will be forced to zero. rEn = Remote set point (coming from serial link).
2. SP2, SP3 and SP4 selection will be shown [86] SP.u - Rate of rise for positive set point
only when the relative set point is enabled (see change (ramp up)
[76] nSP parameter). Available: When at least one output is e programmed as
[84] SP.rt - Remote set point type control output.
These instruments will communicate with each other, using Range:  • 0.01 to 99.99 units per minute;
RS 485 serial interface without a PC. An instrument can be • inF = ramp disabled (step transfer).
set as a Master while the other are (as usual) Slave units. The [87] SP.d - Rate of rise for negative set point
Master unit can send his operative set point to the slave units. change (ramp down)
In this way, for example, is possible to change simultaneously Available: When at least one output is e programmed as
the set point of 20 instruments by changing the set point of the control output.
master unit (e.g. hot runner application). Range: 0.01 to 99.99 units per minute;
SP.rt parameter defines how the slaves units will use the value inF = ramp disabled (step transfer).
coming from serial link. General note about remote set point: when the remote set
[133] tr.SP parameter [selection of the value to be retransmitted point (RSP) with trim action is programmed, the local set
(Master)] allows to define the value sent by master unit. point range becomes the following:
Available: When at least one output is e programmed as from [77] SPLL+ RSP to [78] SPHL - RSP
control output and the serial interface is present.
Range: rSP = The value coming from serial link is used ]PAn group - Operator HMI
as remote set point (RSP); [118] PAS2 - Level 2 password: Limited access level
trin = The value coming from serial link will be
Available: Always.
algebraically added to the local set point
Range: oFF = Level 2 not protected by password
selected by A.SP and the sum becomes
(as level 1 = Operator level);
the operative set point;
1 to 200.
PErc = The value coming from serial will be scaled
on the input range and this value will be [119] PAS3 - Level 3 password:
used as remote set point. Complete configuration level
Note: A [84] SPrt change produces the following actions: Available: Always.
• When [84] SP.rt = rSP - the remote set point will be Range: 3 to 200.
forced to be equal to the active set point; Note: Setting [118] PAS2 equal to [119] PAS3, the level 2
• When [84] SP.rt = trin - the remote set point will will be masked.
be forced to zero;
[120] PAS4 - Level 4 password:
• When [84] SP.rt = PErc - the remote set point will
be forced to zero.
CODE configuration level
Example: A 6 zone reflow-oven for PCB. Available: Always.
The master unit sends its set point value to 5 other zones Range: 201 to 400.
(slave controllers).
The Slave zones use it as a set point trim.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 18


[121] uSrb - button function during RUN TIME [125] diS.t - Display time out
Available: Always. Available: Always.
Range: nonE = No function; Range: oFF = The display is ever ON;
tunE = Auto-tune/self-tune enabling. A single 0.1 to 99.59 minutes and seconds.
press (longer than 1) starts the auto-tune; Note: This function allows to turn OFF the display when no
oPLo = Manual mode. The first pressure puts the alarm is present and no action is made on the instrument.
instrument in manual mode (OPLO) while a When diS.t is different from OFF and no button is
second one puts the instrument in Auto mode; pressed for more than the programmed time out, the
AAc = Alarm reset; display goes OFF and only 4 segments of the less
ASi = Alarm acknowledge; significant digit are turned ON in sequence in order to
chSP = Sequential set point selection (note); show that the instrument is working correctly.
St.by = Stand by mode. The first press puts the in- If an alarm occures or a buton is pressed, the display
strument in stand by mode while a second will come back to the normal operation.
one puts the instrument in Auto mode;
[126] FiLd - Filter on the displayed value
Str.t = Reserved;
P.run = Reserved; Available: Always.
P.rES = Reserved; Range: oFF = Filter disabled;
P.r.H.r = Reserved. From 0.0 (oFF) to 20.0 engineering units.
Notes: 1. When “Sequential set point selection” is used, Note: This is a “window filter” related to the set point; it is
every press of the button (longer than 1 applied to the displayed value only and it have no
second) increase the value of A.SP (active set effect on the other functions of the instrument (control,
point) of one step. alarms, etc.).
The selection is cyclic: SP -> SP2 -> SP3 -> SP4 [128] dSPu - Status of the instrument at power up
When a new set point is selected using the Available: Always.
key, the display will show for 2 seconds the Range: AS.Pr = Starts in the same way it was prior to the
acronym of the new set point (e.g. SP2). power down;
2. When “Sequential set point selection” is used, the Auto = Starts in Auto mode;
number of set points selectable is limited by [74] nSP. oP.0 = Starts in manual mode with a power output
equal to zero.
[122] diSP - Display management St.bY = Starts in stand-by mode
Available: Always. Notes: 1. When you change the value of [129] oPr.E, the
Range: nonE = Standard display; instrument forces [130] oPEr parameter to Auto.
Pou = Power output;
2. If the “[128] dSPu” parameter is different from
SPF = Final set point;
“AS.Pr” the memorization function is inhibited.
SPo = Operative set point;
AL1 = Alarm 1 threshold; [129] oPr.E - Operative modes enabling
AL2 = Alarm 2 threshold; Available: Always.
AL3 = Alarm 3 threshold;; Range: ALL = All modes will be selectable by the next
Pr.tu = Reserved; parameter;
Pr.td = Reserved; Au.oP = Auto and manual (OPLO) mode only will be
P.t.tu = Reserved; selectable by the next parameter;
P.t.td = Reserved; Au.Sb = Auto and Stand-by modes only will be se-
ti.uP = Reserved; lectable by the next parameter.
ti.du = Reserved; Note: When you change the value of [129] oPr.E, the
PErc = Percent of the power output used during soft instrument forces [130] oPEr parameter equal to Auto.
start (when the soft start time is equal to
infinite, the limit is ever active and it can be [130] oPEr - Operative mode selection
used also when ON/OFF control is selected); Available: Always.
PoS = Reserved. Range:  • When [129] oPr.E = ALL:
[123] di.CL - Display colour Auto = Auto mode;
oPLo = Manual mode;
Available: Always.
St.bY = Stand by mod.e
Range: 0 = The display colour is used to show the
• When [129] oPr.E = Au.oP:
actual deviation (PV - SP);
Auto = Auto mode;
1 = Display red (fix);
oPLo = Manual mode.
2 = Display green (fix);
• When [129] oPr.E = Au.Sb:
3 = Display orange (fix).
Auto = Auto mode;
[124] AdE - Deviation for display colour management St.bY = Stand by mode.
Available: When [123] di.CL = 0. ]Ser group - Serial link parameter
Range: 1 to 9999 engineering units.
[131] Add - Instrument address
Available: Always.
Range: oFF = Serial interface not used;
1 to 254.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 19


[132] bAud - Baud rate reset causes the controller to exit the stand-by
Available: When [131] Add different from oFF. status returning to the control status.
Range: 1200 = 1200 baud; [135] UoLt - Nominal Voltage of the load
2400 = 2400 baud; Available: When [134] Co.tY = ist or
9600 = 9600 baud; [134] Co.tY = h or
19.2 = 19200 baud; [134] Co.tY = S.S.
38.4 = 38400 baud. Range: 1 to 9999 (V).
[133] trSP - Selection of the value to be [136] cur - Nominal current of the load
retransmitted (Master) Available: When [134] Co.tY = ist or
Available: When [131] Add different from oFF. [134] Co.tY = h or
Range: nonE = Retransmission not used (the instrument is [134] Co.tY = S.S.
a slave); Range: 1 to 999 (A).
rSP = The instrument become a Master and it
[137] h.Job - Threshold of the working period
retransmits the operative set point;
PErc = The instrument become a Master and it Available: When [134] Co.tY = tot.d or
retransmits the power output. [134] Co.tY = tot.H.
Range: oFF = Threshold not used
Note: For more details see [84] SP.rt (Remote set point type)
1 to 9999 days when [134] Co.tY = 4;
parameter.
1 to 9999 hours when [134] Co.tY = 5.
]COn Group - Consumption parameters [138] t.Job - Worked time (not resettable)
[134] Co.tY - Count type Available: Always.
Available: Always. Range: 1 to 9999 days.
Range: oFF Not used;
1 Instantaneous power (kW);
]CAL group - User calibration group
2 Consumed energy (kWh); This function allows to calibrate the complete measuring
3 Reserved; chain and to compensate the errors due to:
4 Total worked days: number of hours the instru- ––Sensor location;
ment is turned ON divided by 24; ––Sensor class (sensor errors);
5 Total worked hours: number of hours that the ––Instrument accuracy.
instrument is turned ON; [139] A.L.P - Adjust Low Point
6 Total worked days with threshold: number of Available: Always.
hours the instrument is turned ON divided by 24, Range: -1999 to (AH.P - 10) engineering units.
the controller is forced in stand-by when Co.ty
Note: The minimum difference between AL.P and AH.P is
value reaches the threshold set in [137] h.Job;
equal to 10 Engineering Units.
7 Total worked hours with threshold: number of
hours that the instrument is turned ON, the [140] A.L.o - Adjust Low Offset
controller is forced in stand-by when Co.ty value Available: Always.
reaches the threshold set in [137] h.Job; Range: -300 to +300 engineering units.
8 Totalizer of control relay worked days: number [141] A.H.P - Adjust High Point
of hours the control relay has been in ON condi-
Available: Always.
tion, divided by 24;
Range: From (AL.P + 10) to 9999 engineering units.
9 Totalizer of control relay worked hours: number of
hours the control relay has been in ON condition; Note: The minimum difference between AL.P and AH.P is
10 Totalizer of control relay worked days with equal to 10 Engineering Units.
threshold: number of hours the control relay [142] A.H.o - Adjust High Offset
has been in ON condition divided by 24, the Available: Always.
controller is forced in stand-by when Co.ty value Range: -300 to +300 Engineering Units.
reaches the threshold set in [137] h.Job;
Example: Environmental chamber with an operative range:
11 Totalizer of control relay worked hours with
10 to 100°C.
threshold: number of hours the control relay has
been in ON condition, the controller is forced in 1. Insert in the chamber a reference sensor connected with
stand-by when Co.ty value reaches the th- a reference instrument (usually a calibrator).
reshold set in [137] h.Job. 2. Start the control of the instrument, and set a set point equal to
Notes: 1. Selections 4 to 11 represent an internal count: the minimum value of the operative range (e.g.: 10°C). When
these modes calculate the instrument work in the temperature in the chamber is steady, take note of the
hours or days. When the count reaches the temperature measured by the reference system (e.g.: 9°C).
threshold set with parameter [137] h.Job the 3. Set [139] A.L.P = 10 (low working point) and [140]
display shows “r.iSP” (Inspection Requested). A.L.o = -1 (it is the difference between the reading of the
The count reset (with r.iSP cancellation) can be instrument and the reading of the reference system). Note
done only by changing the threshold value - that after this set the measured value of the instrument is
parameter [137] h.Job. equal to the measured value of the reference system.
Using counting methods 6, 7, 10, 11, the count 4. Set a set point equal to the maximum value of the

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 20


operative range (e.g. 100°C). When the temperature 6. PARAMETER PROMOTION
in the chamber is steady, take note of the temperature
Another important step of the instrument configuration is due
measured by the reference system (e.g. 98°C).
to the possibility to create a custom HMI (interface) in order
5. Set [141] A.H.P = 100 (low working point) and [142] to make the instrument easy to use for the operator and
A.H.o = +2 (it is the difference between the reading of the comfortable for the assistance.
instrument and the reading of the reference system). Note
By a special procedure, named promotion, the OEM can
that after this set the measured value of the instrument is
create two parameter subsets.
equal to the measured value of the reference system.
The first one is the “limited access” level. This subset is protected
AH.o = 2 by the password programmed by [118] PAS2 parameter.
Modified curve The last subset is the “Operator” set (Level1). This level is
Real curve
NOT password protected.
AL.o = -1 Notes: 1. The “limited access” parameter are collected in a list.
AH.P 10°C AH.P 100°C 2. The sequence of the “limited access” parameters
The most important step of the configuration procedure is is programmable and can be made according to
completed. your needs.
3. The parameter sequence of the operator level is
In order to exit from configuration parameter procedure,
the same programmed for “limited access” level
proceed as follows:
but only specified parameters can be displayed
• Push button.
and modified. This set must be create according
• Push button for more than 3 s. The instru-
to your requirements.
ment will come back to the “standard display”.
6.1 PARAMETER PROMOTION PROCEDURE
The limited access parameter set is a list, so that, before to
start promotion procedure, we suggest to operate as follows:
1. Prepare the exact parameter list you want to make
accessible for limited access.
2. Number the desired parameters in the same sequence
you want to have in the limited access.
3. Define which of the selected parameter will be available
in Operator level also.
Example: I would like to obtain the following limited access list:
OPEr Operative mode selection;
SP First set point;
SP2 Second set point;
A.SP Set point selection;
AL1 Alarm 1 threshold;
AL2 Alarm 2 threshold;
Pb Proportional band;
ti Integral time;
td Derivative time;
Aut.r Manual start of the auto-tune.
But I want that the operator to be able to change: the
operative mode, the SP value and the AL1 value. In this
case the promotion will be the following:

Parameter Promotion Limited Access Operator


- OPEr - o1 OPEr OPEr
- SP - o2 SP SP
- SP2 - A3 SP2
- A.SP - A4 A.SP
- AL1 - o5 AL1 AL1
- AL2 - A6 AL2
- Pb - A7 Pb
- ti - A8 ti
- td - A9 td
- Aut.r - A 10 Aut.r

Now, proceed as follows:

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 21


1. Push the button for more than 3 seconds. 7. OPERATIVE MODES
2. The upper display will show PASS while the lower display As we said at paragraph 4.1, when the instrument is
will show 0. powered, it starts immediately to work according to the
3. By and buttons set a password equal to -81. memorized parameter value.
4. Push button. In other words, the instrument has one status only, the “run
The instrument will show the acronym of the first time” status.
configuration parameter group “]inp”. During “run time” we can force the instrument to operate
in three different modes: Automatic mode, Manual mode or
5. By button select the group of the first parameter of
Stand by mode:
your list.
––In Automatic mode the instrument drives automatically
6. By button select the first parameter of your list
the control output according to the parameter value set
7. The upper display will show the acronym of the parameter and the set point/measured value.
while the lower display will show his current promotion level.
–– In Manual mode the the upper display shows the measured
The promotion level is defined by a letter followed by a
value while the lower display shows the power output The
number.
lower display shows the power output [preceded by H (for
The letter can be: heating) or C (for cooling)], MAN is lit and the instrument
c: It shows that this parameter is NOT promoted allows you to set manually the control output power.
and it is present only in configuration.
In this case the number is forced to zero. No Automatic action will be made.
A: It shows that this parameter has been promoted ––In Stand by mode the instrument operates as an indicator.
to the limited access level. It will show on the upper display the measured value and
The number will show the position in the limited on the lower display the set point alternately to the “St.bY”
access list. messages and forces the control outputs to zero.
o: It shows that the parameter has been promoted As we have seen, it is always possible to modify the value
to the Operator level. assigned to a parameter independently from the operative
The number will show the position in the limited modes selected.
access list.
8. By and buttons assign to this parameter the 7.1 MODIFY A PARAMETER DURING
desired position. “OPERATOR LEVEL”
Note: Setting a value different from 0 the letter c will change The instrument is showing the “standard display”.
automatically to A and the parameter is automatically
1. Press the button.
promoted to the limited access level.
2. The upper display will show the acronym of the first
9. In order to modify the level from limited access
parameter promoted to this level while the lower display
to operator and vice versa, push button and,
will show its value.
maintaining the pressure, push button.
The letter will change from A to o and vice versa. 3. By and button assign to this parameter the
desired value.
10. Select the second parameter that you want to add to the
assistance level and repeat step 6, 7 and 8. 4. Press the button in order to memorize the new value
and go to the next parameter.
11. Repeat step 5, 6, 7, 8 until the list has been completed.
5. When you want to come back to the “standard display”
12. When you need to exit from promotion procedure, push
push the button for more than 3 seconds.
button and maintain the pressure for more than 10 s.
The instrument will show the “standard display”. Note: The parameter modification of the Operator level
is subject to a time out. If no button is pressed for
Note: When you set the some number to two parameter,
more than 10 seconds, the instrument goes back to
the instrument will use only the last programmed
the “standard display” and the new value of the last
parameter.
selected parameter will be lost.
Example: In the previous example, I have set for SP2 a
promotion value equal to A3. 7.2 ENTER THE “LIMITED ACCESS LEVEL”
If now I set for SP3 a promotion value equal to o3, the The instrument is showing the “standard display”.
Limited Access list and the operator list becomes. 1. Press the button for more than 3 seconds;
Parameter Promotion Limited Access Operator 2. The upper display will show PASS while the lower display
- OPEr - o1 OPEr OPEr will show 0;
- SP - o2 SP SP 3. By and buttons set the value assigned to
- SP3 - o3 SP3 SP3
[118] PAS2 (Level 2 password).
- A.SP - A4 A.SP
Notes: 1. The factory default password for configuration
parameters is equal to 20.
- AL1 - o5 AL1 AL1
2. All parameter modification are protected by a
time out. If no button is pressed for more than
10 second the instrument comes automatically
back to the Standard display, the new value of the
last selected parameter is lost and the parameter

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 22


modification procedure is closed. Allows to start the “Direct set point modification” fun-
When you desire to remove the time out (e.g. ction (see below).
for the first configuration of an instrument) you Allows to display the “additional informations”
can use a password equal to 1000 plus the (see below).
programmed password
(e.g. 1000 + 20 [default] = 1020). 7.4.2 Direct set point modification
It is always possible to manually End the This function allows to modify rapidly the set point value
parameter configuration procedure (see below). selected by [83] A.SP (selection of the active Set point).
3. During parameter modification the instrument The instrument is showing the “standard display”.
continues to perform the control. 1. Push button.
In certain conditions (e.g. when a parameter The upper display shows the acronym of the selected set
change can produces a heavy bump to the point (e.g. SP2) and the lower display will show its value.
process) it is advisable to temporarily stop the 2. By and buttons, assign to this parameter the
controller from controlling during the programming desired value.
procedure (its control output will be Off). A 3. Do not push any button for more than 10 second or push
password equal to 2000 + the programmed value the button.
(e.g. 2000 + 20 = 2020) will switch the control out
In both cases the instrument memorize the new value and
off during configuration. The control will restart
come back to the “standard display”.
automatically when the parameter modification
procedure will be manually ended. Note: If the selected set point has not been promoted to the
Operator level, the instrument allows you to see the
4. Push button.
value but not to modify it.
5. The instrument will show on the upper display the
acronym of the first parameter promoted to this 7.4.3 Additional information
level and on the lower display its value. This instrument is able to show you some additional
6. By and buttons assign to this parameter informations that can help you to manage your system.
the desired value. The additional informations are related to how the instrument
7. Press the button in order to memorize the is programmed, hence in many cases, only part of this
new value and go to the next parameter. information is available.
8. When you want to come back to the “standard 1. When the instrument is showing the “standard display”
display” push the button for more than 3 s. push button.
The lower display will show H or c followed by a number.
7.3 HOW TO SEE BUT NOT MODIFY THE “LIMITED This value is the current power output applied to the
ACCESS PARAMETERS” process. The H show you that the action is a Heating action
Sometime it is necessary to give to the operator the possibility while the c show you that the action is a Cooling action.
to see the value assigned to the parameter promoted in the 2. Push button again. When the wattmeter function
Limited Access level but it is important that all changes are is running the lower display will show U followed by the
made by authorized personnel only. measured energy.
In this cases, proceed as follows: Note: The energy calculation will be in accordance with
1. Press the button for more than 3 seconds; the [134] Co.tY parameter setting.
2. The upper display will show PASS while the lower display 3. Push button again. When the “Worked time count”
will show 0; is running the lower display will show d for days or h for
hours followed by the measured time.
3. By and button set the value -181;
4. Push button again. The instrument returns to the
4. Push button; “standard display”.
5. The upper display will show the acronym of the first Note: The additional information visualization is subject to
parameter promoted to the level 2 and lower display will a time out. If no button is pressed for more than 5
show its value; second the instrument comes automatically back to
6. Using button it is possible to see the value assigned the Standard display.
to all parameter present in level 2 but it will not be
possible to modify it; 7.4.4 Display management
7. It is possible to come back to the “standard display” by This instrument allows you to program (see parameter
pushing the button for more than 3 seconds or by [125] diS.t the time out of the display.
pushing no pushbutton for more than 10 seconds. This function allows to turn OFF the display when no alarm
is present and no action is made on the instrument.
7.4 AUTOMATIC MODE When [125] diS.t is different to OFF (display ever ON) and
7.4.1 Keyboard function when the instrument no button is pressed for more than the programmed time
out, the display goes OFF and only 4 segments of the less
is in Auto mode significant digit are turned ON in sequence in order to show
Performs the action programmed by [121] uSrb that the instrument is working correctly.
( button function during RUN TIME) parameter.
If an alarm occurs or a button is pressed, the display will
Allows to entrer the parameter modification procedures. come back to the normal operation.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 23


7.4.5 The display colour shows the Deviation 8. ERROR MESSAGES
This instrument allows to program the deviation (PV - SP) for
colour display change (see parameter [124] AdE). 8.1 OUT OF RANGE SIGNALS
In this way the upper display will be: The upper display shows the OVER-RANGE and UNDER-
––Amber when PV is lower than SP - AdE. RANGE conditions with the following indications:
––Green when (SP - AdE) < PV<SP + AdE) Over-range Under-range
––Red when PV is higher than SP+AdE

7.5 MANUAL MODE The sensor break will be signalled as an out of range
This operative mode allows you to deactivate automatic
control and manually program the percentage power output
to the process. Note: When an over-range or an under-range is detected,
When the instrument is in manual mode, the upper display the alarms operate as in presence of the maximum or
will show the measured value while the lower display will the minimum measurable value respectively.
show alternately the power output [preceded by H (for To check the out of span Error condition, proceed as follows:
heating action) or C (for cooling action)] and the message
oPLo (open loop). 1. Check the input signal source and the connecting line.
When manual control is selected, the instrument will start to 2. Make sure that the input signal is in accordance with the
operate with the same power output as the last one supplied instrument configuration.
by automatic mode and can be modified using the and Otherwise, modify the input configuration (see section 4).
buttons. 3. If no error is detected, send the instrument to your
In case of ON/OFF control, 0% corresponds to the supplier to be checked.
deactivated output while any value different from 0
corresponds to the activated output.
8.2 LIST OF POSSIBLE ERRORS
ErAT Fast Auto-tune cannot start. The measure value is too
As in the case of visualization, the programmable values
close to the set point.
range from H100 (100% output power with reverse action) to
C100 (100% output power with direct action). Push the button in order to delete the error message.
ouLd Overload on the out 4
Notes: 1. During manual mode, the alarms are operative.
The messages shows that a short circuit is present on
2. If you set manual modes during self-tune the Out 4 when it is used as output or as a transmitter
execution, the self- tune function will be aborted. power suply.
3. During manual mode, all functions not related When the short circuit disappears the output restart to
with the control (wattmeter, independent timer, operate.
“worked time”, etc) continue to operate normally. NoAt Auto-tune not finished within 12 hours.
ErEP Possible problem of the instrument memory.
7.6 STAND BY MODE The messages disappears automatically.
This operative mode also deactivates the automatic control When the error continues, send the instrument to your
but forces the control output to zero. supplier.
In this mode the instrument operates as an indicator. RonE Possible problem of the firmware memory.
When the instrument is in stand by mode the upper display When this error is detected, send the instrument to
will show the measured value while the lower display will your supplier.
show alternately the set point and the message “St.bY”. Errt Possible problem of the calibration memory.
Notes: 1. During stand by mode, the relative alarms are When this error is detected, send the instrument to
disabled while the absolute alarms are operative your supplier.
or not according to the ALxo (Alarm x enabling
during Stand-by mode) parameter setting.
2. If you set stand by mode during program
execution, the program will be aborted.
3. If you set stand by mode during self-tune
execution, the self- tune function will be aborted.
4. During stand by mode, all functions not related
with the control (wattmeter, independent timer,
“worked time”, etc) continue to operate normally.
5. When the instrument is swapped from stand
by to auto modes, the instrument will start
automatically the alarm masking, the soft start
functions and the auto-tune (if programmed).

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 24


9. GENERAL NOTES

9.1 PROPER USE


Every possible use not described in this manual must be
consider as a improper use.
This instrument is in compliance with EN 61010-1 “Safety
requirements for electrical equipment for measurement,
control and laboratory use”; for this reason it coud not be
used as a safety equipment.
Whenever a failure or a malfunction of the control device
may cause dangerous situations for persons, thing or
animals, please remember that the plant has to be equipped
with additional safety devices.
Yokogawa Electric Corporation and its legal representatives do
not assume any responsibility for any damage to people, things
or animals deriving from violation, wrong or improper use or in
any case not in compliance with the instrument’s features.

9.2 WARRANTY
This product is under warranty against manufacturing
defects or faulty materials that are found within 18 months
from manufacturing date. The warranty is limited to the
replacement of the instrument.
The tampering of the instrument or an improper use of the
product will bring about the immediate withdrawal of the
warranty’s effects.
In the event of a faulty instrument, either within the period
of warranty, or further to its expiry, please contact our
sales department to obtain authorisation for sending the
instrument to our company.

9.3 DISPOSAL
The appliance (or the product) must be disposed
of separately in compliance with the local
standards in force on waste disposal.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 25


Appendix A

]]
inP GROUP - Main and auxiliary input configuration
Dec.
no. Param. Description Values Default
Point
J = TC J,
crAL = TC K,
S = TC S,
r = TC R,
t = TC T,
Pt1 = RTD Pt100,
Pt10 = RTD Pt1000,
1 SEnS Sensor selection 0 0.60 = 0 to 60 mV, J
12.60 = 12 to 60 mV,
0.20 = 0 to 20 mA,
4.20 = 4 to 20 mA,
0.5 = 0 to 5 V,
1.5 = 1 to 5 V,
0.10 = 0 to 10 V,
2.10 = 2 to 10 V
Decimal Point Position (linear inputs) 0 to 3
2 dp 0 0
Decimal Point Position (different than linear inputs) 0/1
3 SSC Initial scale read-out for linear inputs dp -1999 to 9999 0
4 FSc Full Scale Readout for linear inputs dp -1999 to 9999 1000
5 unit Engineer unit °C/°F °C
6 Fil Digital filter on the measured value 1 0 (= OFF) to 20.0 s 1.0
Sensor error used to enable the safety output or = Over range
7 inE ou = Under range our
value our = Over and under range
8 oPE Safety output value (% of the output) -100 to 100 0
on = Output used as PWS for TX,
out4 = Output 4 (digital output 4),
9 IO4.F I/O 4 function out4
dG2c = Digital input 2 driven by contact,
dG2U = Digital input 2 driven by voltage
oFF = Not used,
1 = Alarm reset,
10 diF1 Digital Input 1 function 2 = Alarm acknowledge (ACK), oFF
3 = Hold of the measured value,
4 = Stand by mode,
5 = Manual mode,
6 = HEAt with SP1 and CooL with SP2,
7 to 17 = No action
11 diF2 Digital Input 2 function 18 = Sequential SP selection, oFF
19 = SP1 - SP2 selection,
20 = SP1 to SP4 binary selection,
21 = Digital inputs in parallel to and keys
0 = DI1 direct action, DI2 direct action
Digital Inputs Action 1 = DI1 reverse action, DI2 direct action
12 di.A 0
(DI2 only if configured) 2 = DI1 direct action, DI2 reverse action
3 = DI1 reverse action, DI2 reverse action

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 26


]]
Out group
Dec.
no. Param. Description Values Default
Point
0-20 = 0 to 20 mA;
Output 1 type 4-20 = 4 to 20 mA;
13 o1t 0-20
(when Out 1 is an analog output) 0-10 = 0 to 10 V;
2-10 = 2 to 10 V.
NonE = Output not used;
H.rEG = Heating output;
Out 1 function c.rEG = Cooling output;
0 r.inP = Measure retransmission;
(when Out 1 is an analog output) r.Err = Error (SP - PV) retransmission;
r.SP = Set point retransmission ;
r.SEr = Serial value retransmission.
NonE = Output not used
H.rEG = Heating output
c.rEG = Cooling output
AL = Alarm output
t.out = Reserved
t.HoF = Reserved
14 o1F P.End = Reserved H.rEG
P.HLd = Reserved
P.uit = Reserved
P.run = Reserved
Out 1 function 0 P.Et1 = Reserved
P.Et2 = Reserved
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
St.bY = Stand by status indicator
diF.1 = The output repeats the digital input 1 status
diF.2 = The output repeats the digital input 2 status
on = Out 1 always ON
riSP = Inspection requested (the worked hours/days
counter has reached the programmed threshold)
Initial scale value of the analog retransmission
15 Ao1L dP -1999 ... Ao1H -1999
(when Out 1 is an analog output)
Full scale value of the analog retransmission
16 Ao1H dP Ao1L ... 9999. 9999
(when Out 1 is an analog output)
0 to 63
+1 = Alarm 1
+2 = Alarm 2
17 o1AL Alarms linked up with the out 1 0 +4 = Alarm 3 AL1
+8 = Loop break alarm
+16 = Sensor Break
+32 = Overload on output 4
dir = Direct action
rEU = Reverse action
18 o1Ac Out 1 action 0 dir
dir.r = Direct with reversed LED
ReU.r = Reverse with reversed LED
NonE = Output not used
H.rEG = Heating output
c.rEG = Cooling output
AL = Alarm output
t.out = Reserved
t.HoF = Reserved
P.End = Reserved
P.HLd = Reserved
P.uit = Reserved
P.run = Reserved
19 o2F Out 2 function 0 P.Et1 = Reserved AL
P.Et2 = Reserved
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
St.bY = Stand by status indicator
diF.1 = The output repeats the digital input 1 status
diF.2 = The output repeats the digital input 2 status
on = Out 2 always ON
riSP = Inspection requested (the worked hours/days
counter has reached the programmed threshold)
0 to 63
+1 = Alarm 1
+2 = Alarm 2
20 o2AL Alarms linked up with the out 2 0 +4 = Alarm 3 AL1
+8 = Loop break alarm
+16 = Sensor Break
+32 = Overload on output 4

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 27


Dec.
no. Param. Description Values Default
Point
dir = Direct action
rEU = Reverse action
21 o2Ac Out 2 action 0 dir
dir.r = Direct with reversed LED
ReU.r = Reverse with reversed LED
NonE = Output not used
H.rEG = Heating output
c.rEG = Cooling output
AL = Alarm output
t.out = Reserved
t.HoF = Reserved
P.End = Reserved
P.HLd = Reserved
P.uit = Reserved
P.run = Reserved
22 o3F Out 3 function 0 P.Et1 = Reserved AL
P.Et2 = Reserved
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
St.bY = Stand by status indicator
diF.1 = The output repeats the digital input 1 status
diF.2 = The output repeats the digital input 2 status
on = Out 3 always ON
riSP = Inspection requested (the worked hours/days
counter has reached the programmed threshold)
0 to 63
+1 = Alarm 1
+2 = Alarm 2
23 o3AL Alarms linked up with the out 3 0 +4 = Alarm 3 AL2
+8 = Loop break alarm
+16 = Sensor Break
+32 = Overload on output 4
dir = Direct action
rEU = Reverse action
24 o3Ac Out 3 action 0 dir
dir.r = Direct with reversed LED
ReU.r = Reverse with reversed LED
NonE = Output not used
H.rEG = Heating output
c.rEG = Cooling output
AL = Alarm output
t.out = Reserved
t.HoF = Reserved
P.End = Reserved
P.HLd = Reserved
25 o4F Out 4 function 0 AL
P.uit = Reserved
P.run = Reserved
P.Et1 = Reserved
P.Et2 = Reserved
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
St.bY = Stand by status indicator
0 to 63
+1 = Alarm 1
+2 = Alarm 2
AL1 +
26 o4AL Alarms linked up with the out 4 0 +4 = Alarm 3
AL2
+8 = Loop break alarm
+16 = Sensor Break
+32 = Overload on output 4
dir = Direct action
rEU = Reverse action
27 o4Ac Out 4 action 0 dir
dir.r = Direct with reversed LED
ReU.r = Reverse with reversed LED

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 28


]]
AL1 group
Dec.
no. Param. Description Values Default
Point
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Windows alarm in alarm outside the windows
LHAI = Windows alarm in alarm inside the windows
28 AL1t Alarm 1 type 0 HiAb
SE.br = Sensor Break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdo = Relative band alarm in alarm out of the band
LHdi = Relative band alarm in alarm inside the band
0 to 15
+1 = Not active at power up
29 Ab1 Alarm 1 function 0 +2 = Latched alarm (manual reset) 0
+4 = Acknowledgeable alarm
+8 = Relative alarm not active at set point change
-- For High and low alarms, it is the low limit
30 AL1L of the AL1 threshold; dp From -1999 to AL1H (E.U.) -1999
-- For band alarm, it is low alarm threshold
-- For High and low alarms, it is the high
31 AL1H limit of the AL1 threshold; dp From AL1L to 9999 (E.U.) 9999
-- For band alarm, it is high alarm threshold
32 AL1 AL1 threshold dp From AL1L to AL1H (E.U.) 0
33 HAL1 AL1 hysteresis dp 1 to 9999 (E.U.) 1
34 AL1d AL1 delay 0 From 0 (oFF) to 9999 (s) oFF
0 = Alarm 1 disabled during Stand by and out of range
Alarm 1 enabling during Stand-by mode and 1 = Alarm 1 enabled in stand by mode
35 AL1o 0 2 = Alarm 1 enabled in out of range condition 0
out of range conditions 3 = Alarm 1 enabled in stand by mode and in overrange
condition

]]
AL2 group
Dec.
no. Param. Description Values Default
Point
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Windows alarm in alarm outside the windows
LHAI = Windows alarm in alarm inside the windows
36 AL2t Alarm 2 type 0 Loab
SE.br = Sensor Break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdo = Relative band alarm in alarm out of the band
LHdi = Relative band alarm in alarm inside the band
0 to 15
+1 = Not active at power up
37 Ab2 Alarm 2 function 0 +2 = Latched alarm (manual reset) 0
+4 = Acknowledgeable alarm
+8 = Relative alarm not active at set point change
-- For High and low alarms, it is the low limit
38 AL2L of the AL2 threshold; dp From -1999 to AL2H (E.U.) -1999
-- For band alarm, it is low alarm threshold
-- For High and low alarms, it is the high
39 AL2H limit of the AL2 threshold; dp From AL2L to 9999 (E.U.) 9999
-- For band alarm, it is high alarm threshold
40 AL2 AL2 threshold dp From AL2L to AL2H (E.U.) 0
41 HAL2 AL2 hysteresis dp 1 to 9999 (E.U.) 1
42 AL2d AL2 delay 0 From 0 (oFF) to 9999 (s) oFF
0 = Alarm 2 disabled during Stand by and out of range
Alarm 2 enabling during Stand-by mode and 1 = Alarm 2 enabled in stand by mode
43 AL2o 0 2 = Alarm 2 enabled in out of range condition 0
out of range conditions 3 = Alarm 2 enabled in stand by mode and in overrange
condition

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 29


]]
AL3 group
Dec.
no. Param. Description Values Default
Point
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Windows alarm in alarm outside the windows
LHAI = Windows alarm in alarm inside the windows
44 AL3t Alarm 3 type 0 nonE
SE.br = Sensor Break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdo = Relative band alarm in alarm out of the band
LHdi = Relative band alarm in alarm inside the band
0 to 15
+1 = Not active at power up
45 Ab3 Alarm 3 function 0 +2 = Latched alarm (manual reset) 0
+4 = Acknowledgeable alarm
+8 = Relative alarm not active at set point change
-- For High and low alarms, it is the low limit
46 AL3L of the AL3 threshold; dp From -1999 to AL3H (E.U.) -1999
-- For band alarm, it is low alarm threshold
-- For High and low alarms, it is the high
47 AL3H limit of the AL3 threshold; dp From AL3L to 9999 (E.U.) 9999
-- For band alarm, it is high alarm threshold
48 AL3 AL3 threshold dp From AL3L to AL3H (E.U.) 0
49 HAL3 AL3 hysteresis dp 1 to 9999 (E.U.) 1
50 AL3d AL3 delay 0 From 0 (oFF) to 9999 (s) oFF
0 = Alarm 3 disabled during Stand by and out of range
Alarm 3 enabling during Stand-by mode and 1 = Alarm 3 enabled in stand by mode
51 AL3o 0 2 = Alarm 3 enabled in out of range condition 0
out of range conditions 3 = Alarm 3 enabled in stand by mode and in overrange
condition

]]
LBA group - Loop Break Alarm Parameters
Dec.
no. Param. Description Values Default
Point
52 LbAt LBA time 0 From 0 (oFF) to 9999 (s) oFF
53 LbSt Delta measure used by LBA during Soft start dP From 0 (oFF) to 9999 (E.U.) 10
54 LbAS Delta measure used by LBA dP 1 to 9999 (E.U.) 20
uP = Active when Pout = 100%
55 LbcA Condition for LBA enabling 0 dn = Active when Pout = -100% both
both = Active in both cases

]]
rEG group - Control Parameters
Dec.
no. Param. Description Values Default
Point
Pid = PID (heat and/or)
On.FA = ON/OFF asymmetric hysteresis
56 cont Control type 0 Pid
On.FS = ON/OFF symmetric hysteresis
nr = Heat/Cool ON/OFF control with neutral zone
-4 = Oscillating auto-tune with automaticrestart at power up
and after all point change
-3 = Oscillating auto-tune with manual start
-2 = Oscillating -tune with auto-matic start at the first power up only
-1 = Oscillating auto-tune with auto-matic restart at every power up
0 = Not used
1 = Fast auto tuning with automatic restart at every power up
2 = Fast auto-tune with automatic start the first power up only
57 Auto Autotuning selection 0 7
3 = FAST auto-tune with manual start
4 = FAST auto-tune with automatic restart at power up and after
a set point change
5 = Evo-tune with automatic restart at every power up
6 = Evo-tune with automatic start the first power up only
7 = Evo-tune with manual start
8 = Evo-tune with automatic restart at power up and after a set
point change
oFF = Not active
58 Aut.r Manual start of the Autotuning 0 oFF
on = Active

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 30


Dec.
no. Param. Description Values Default
Point
no = The instrument does not perform the self-tuning
59 SELF Self tuning enabling 0 no
YES = The instrument is performing the self-tuning
60 HSEt Hysteresis of the ON/OFF control dP 0 to 9999 (E.U.) 1
61 cPdt Time for compressor protection 0 From 0 (oFF) to 9999 (s) oFF
62 Pb Proportional band dP 1 to 9999 (E.U.) 50
63 ti Integral time 0 From 0 (oFF) to 9999 (s) 200
64 td Derivative time 0 From 0 (oFF) to 9999 (s) 50
65 Fuoc Fuzzy overshoot control 2 0.00 to 2.00 0.50
66 tcH Heating output cycle time 1 0.1 to 130.0 (s) 20.0
Power ratio between heating and
67 rcG 2 0.01 to 99.99 1.00
cooling action
68 tcc Cooling output cycle time 1 0.1 to 130.0 (s) 20.0
69 rS Manual reset (Integral pre-load) 1 -100.0 to +100.0 (%) 0.0
70 Str.t Servomotor stroke time 0 5 to 1000 seconds 60
71 db.S Servomotor dead band 0 0 to 100% 50
72 od Delay at power up 2 From 0.00 (oFF) to 99.59 (hh.mm) oFF
Maximum power output used during
73 St.P 0 -100 to 100 (%) 0
soft start
-- 0.00 (oFF);
74 SSt Soft start time 2 -- 0.01 to 7.59 (hh.mm); oFF
-- inF (always ON).
75 SS.tH Threshold for soft start disabling dP -1999 to +9999 (E.U.) 9999

]]
SP group - Set point parameters
Dec.
no. Param. Description Values Default
Point
76 nSP Number of used set points 0 1 to 4 1
77 SPLL Minimum set point value dP From -1999 to SPHL -1999
78 SPHL Maximum set point value dP From SPLL to 9999 9999
79 SP Set point 1 dP From SPLL to SPLH 0
80 SP 2 Set point 2 dP From SPLL to SPLH 0
81 SP 3 Set point 3 dP From SPLL to SPLH 0
82 SP 4 Set point 4 dP From SPLL to SPLH 0
83 A.SP Selection of the active set point 0 From 1 (SP 1) to nSP 1
RSP = The value coming from serial link is used as remote set point;
trin = The value will be added to the local set point selected by
84 SP.rt Remote set point type 0 A.SP and the sum becomes the operative set point; trin
PErc = The value will be scaled on the input range and this value
will be used as remote SP.
Loc = local;
85 SPLr Local/remote set point selection 0 Loc
rEn = remote.
Rate of rise for POSITIVE set point
86 SP.u 2 0.01 to 99.99 (inF) Eng. units per minute inF
change (ramp UP)
Rate of rise for NEGATIVE set point
87 SP.d 2 0.01 to 99.99 (inF) Eng. units per minute inF
change (ramp DOWN)

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 31


]]
PAn group - Operator HMI parameters
Dec.
no. Param. Description Values Default
Point
Level 2 password (limited -- oFF (Level 2 not protected by password);
118 PAS2 0 20
access level) -- 1 to 200.
Level 3 password (com-
119 PAS3 0 3 to 200 30
plete configuration level)
Level 4 password (CODE
120 PAS4 0 201 to 400 300
configuration level)
nonE = No function;
tunE = Auto-tune/self-tune enabling. A single press (longer than 1 se-
cond) starts the auto-tune;
oPLo = Manual mode. The first pressure puts the instrument in manual mode
(OPLO) while a second one puts the instrument in Auto mode;
AAc = Alarm reset;
button function during ASi = Alarm acknowledge;
121 uSrb tunE
RUN TIME chSP = Sequential set point selection;
St.by = Stand by mode. The first press puts the instrument in stand by
mode while a second one puts the instrument in Auto mode;
Str.t = Reserved;
P.run = Reserved;
P.rES = Reserved;
P.r.H.r = Reserved.
nonE = Standard display;
Pou = Power output;
SPF = Final set point;
SPo = Operative set point;
AL1 = Alarm 1 threshold;
AL2 = Alarm 2 threshold;
AL3 = Alarm 3 threshold;
Pr.tu = Reserved;
122 diSP Display management Pr.td = Reserved; 0
P.t.tu = Reserved;
P.t.td = Reserved;
ti.uP = Reserved;
ti.du = Reserved;
PErc = Percent of the power output used during soft start (when the soft
start time is equal to infinite, the limit is ever active and it can be
used also when ON/OFF control is selected);
PoS = Reserved.
0 = The display colour is used to show the actual deviation (PV - SP);
1 = Display red (fix);
123 di.cL Display colour 0
2 = Display green (fix);
3 = Display orange (fix).
Deviation for display col-
124 AdE 1 to 999 (E.U.) 5
our management
-- oFF (display always ON);
125 di.St Display Timeout 2 oFF
-- 0.1 to 99.59 (mm.ss).
Filter on the displayed -- oFF (filter disabled)
126 fiLd 1 oFF
value -- From 0.0 (oFF) to 20.0 (E.U.)
AS.Pr = Starts in the same way it was prior to the power down;
Instrument status at Auto = Starts in Auto mode;
128 dSPu AS.Pr
power ON oP.0 = Starts in manual mode with a power output equal to zero;
St.bY = Starts in stand-by mode.
ALL = All modes will be selectable by the next parameter;
Au.oP = Auto and manual (OPLO) mode only will be selectable by the next
129 oPr.E Operative modes enabling ALL
parameter;
Au.Sb = Auto and Stand-by modes only will be selectable by the next parameter.
If oPr.E = ALL: - Auto = Auto mode;
- oPLo = Manual mode;
- St.bY = Stand by mode.
130 oPEr Operative mode selection If oPr.E = Au.oP: - Auto = Auto mode; Auto
- oPLo = Manual mode.
If oPr.E = Au.Sb: - Auto = Auto mode;
- St.bY = Stand by mode.

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 32


]]
Ser group - Serial link parameters
Dec.
no. Param. Description Values Default
Point
-- oFF
131 Add Instrument address 1
-- 1 to 254
1200 = 1200 baud
2400 = 2400 baud
132 bAud baud rate 9600 = 9600 baud 9600
19.2 = 19200 baud
38.4 = 38400 baud
nonE = Retransmission not used (the instrument is a slave);
Selection of the value to be rSP = The instrument becomes a Master and retransmits the operati-
133 trSP ve set point; nonE
retransmitted (Master) PErc = The instrument become a Master and it retransmits the power
output.

]]
COn group - Consumption parameters
Dec.
no. Param. Description Values Default
Point
oFF = Not used;
1 = Instantaneous power (kW);
2 = Power consumption (kW/h);
3 = Reserved;
4 = Total worked days: number of hours the instrument is turned ON
divided by 24;
5 = Total worked hours: number of hours the instrument is turned ON;
6 = Total worked days with threshold: number of hours the instru-
ment is turned ON divided by 24, the controller is forced in stand-
by when Co.ty value reaches the threshold set in [137] h.Job;
7 = Total worked hours with threshold: number of hours the instru-
ment is turned ON, the controller is forced in stand-by when
134 Co.tY Count type Co.ty value reaches the threshold set in [137] h.Job; oFF
8 = Totalizer of control relay worked days: number of hours the con-
trol relay has been in ON condition, divided by 24;
9 = Totalizer of control relay worked hours: number of hours the
control relay has been in ON condition;
10 = Totalizer of control relay worked days with threshold: number of
hours the control relay has been in ON condition divided by 24,
the controller is forced in stand-by when Co.ty value reaches the
threshold set in [137] h.Job;
11 = Totalizer of control relay worked hours with threshold: number of
hours the control relay has been in ON condition, the controller is
forced in stand-by when Co.ty value reaches the threshold set in
[137] h.Job.
135 UoLt Nominal Voltage of the load 1 to 9999 (V) 230
136 cur Nominal current of the load 1 to 999 (A) 10
Threshold of the working oFF = threshold not used
137 h.Job 0 to 9999 days (when [133] cotY = 4) 0
period 0 to 9999 hours (when [133] cotY = 5)
138 t.Job Worked time (not resettable) 0 to 9999 days

]]
CAl group - User calibration parameters
Dec.
no. Param. Description Values Default
Point
139 AL.P Adjust Low Point From -1999 to (AH.P - 10) in engineering units 0
140 AL.o Adjust Low Offset -300 to +300 (E.U.) 0
141 AH.P Adjust High Point From (AL.P + 10) to 9999 engineering units 9999
142 AH.o Adjust High Offset -300 to +300 0

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 33


Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 34
Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 35
Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 36

You might also like