You are on page 1of 1

KEY PLAN:

1 6 14 25 34

LEGEND & NOTES U


MECCA

1. ASC: APPLICATION SPECIFIC CONTROLLER, CONFIGURABLE, USED FOR FCUs, VAVs, etc... 43

2. DDC: DIRECT DIGITAL CONTROLLER, FREE PROGRAMMABLE, NATIVE BACnet. L

3. NAC: NETWORK AUTOMATION CONTROLLER, BTL CERTIFIED AS B-BC (BACnet BUILDING CONTROLLER).
4. DCP: METAL ENCLOSURE, HOUSING DDCs WITH ALL REQUIRED ACCESSORIES FOR PROPER OPERATION.
5. BBMD: A BACnet/IP BROADCAST MANAGEMENT DEVICE SHALL BE INSTALLED ON EACH IP SUBNET.
6. FIELD BUS: NETWORK USED AT THE AUTOMATION LEVEL.
7. INTERFACE TO/FROM BMS: THE INTERFACE AT THE AUTOMATION LEVEL SHALL BE BACnet. Modbus AND M-bus A

INTERFACES ARE SUBJECT TO APPROVAL.


LEGENDS & PARTICULAR NOTES:
8. ALL INTERFACES AT THE MANAGEMENT LEVEL SHALL BE BACnet/IP, OTHER PROTOCOLS ARE NOT ACCEPTED.
9. FOR ACTUAL NUMBER OF PUMPS PER PUMP SET OR ACTUAL QUANTITIES OF MECHANICAL EQUIPMENT REFER TO
MECHANICAL SCHEDULES OF EQUIPMENT AND TO MECHANICAL RISERS.
10. DUCT SMOKE DETECTORS SHALL BE INSTALLED ON SUPPLY AND RETURN AIR DUCTS. IF THE RETURN DUCT HAS MORE
THAN ONE BRANCH, A DUCT SMOKE DETECTOR SHALL BE INSTALLED ON EACH BRANCH.
11. FOR BLOW THROUGH OR DRAW THROUGH CONFIGURATIONS REFER TO THE MECHANICAL SCHEDULE OF EQUIPMENT.

BMS CONTROL ROOM IN BASEMENT 1 - 6* HOTEL NORTH BMS CONTROL ROOM IN PROMENADE SOUTH BMS CONTROL ROOM IN PROMENADE

REPORT PRINTER REPORT PRINTER REPORT PRINTER


BMS OPERATOR DUAL REDUNDANT HOT BMS OPERATOR BMS OPERATOR
WORKSTATION SWAPPABLE BMS WORKSTATION WORKSTATION
DEDICATED FOR 6* HOTEL SERVERS RACK DEDICATED FOR COMMON DEDICATED FOR COMMON
& SHARED FACILITIES AREAS AREAS

BMS OPERATOR
WORKSTATION
DEDICATED FOR 6* HOTEL ALARM PRINTER ALARM PRINTER ALARM PRINTER
& SHARED FACILITIES LEVEL +9.40 M (QNHD) = +0.00 M (ARCHITECTURAL)

GENERAL NOTES:

BMS METERING
WORKSTATION THROUGH
BMS SERVER UTP CABLES UTP CABLES UTP CABLES

INTERFACE TO GUESTROOM
MANAGEMENT SYSTEM
(GRMS) DATA NETWORK DATA NETWORK DATA NETWORK
SWITCH SWITCH SWITCH

6* HOTEL & COMMON AREAS BACnet/IP NETWORK

NAC

MAIN FIRE ALARM


CONTROL PANEL
NAC NAC

PORTABLE
OPERATOR
TERMINAL

THIRD PARTY
BOILER PLANT PROTOCOL
MANAGER GATEWAY (BACnet
TO THIRD PARTY
PROTOCOL)

PROJECT

THIRD PARTY
PROTOCOL
GATEWAY (BACnet KATARA TOWERS AT LUSAIL
TO THIRD PARTY Lusail District, Doha
VARIABLE SPEED PROTOCOL)
DRIVE WITH CLIENT
COMMUNICATION
INTERFACE Katara Hospitality
BACnet MS/TP
Katara Hospitality Building, Marina District,
Lusail City, PO Box 2977 Doha, Qatar
LEAD
CONSULTANT
BACnet ASC BACnet ASC BACnet ASC
THIRD PARTY
PROTOCOL
GATEWAY (BACnet
TO THIRD PARTY
PROTOCOL)
SUB -
OTHER EQUIPMENT CONSULTANTS
PANEL WITH
BACnet MS/TP
COMMUNICATION
INTERFACE

CACU OTHER EQUIPMENT


TYPICAL TYPICAL TYPICAL
PANEL WITH
BACnet DDC BACnet DDC BACnet DDC
COMMUNICATION
CONTROL CONTROL CONTROL
INTERFACE
PANELS (DCP) PANELS (DCP) PANELS (DCP)

KATARA HOTEL
[ PK4b(i)-a & PK4b(ii)-a ]
SUBMISSION
STAMP TENDER
OCTOBER 2019 PACKAGE PK4b(ii)-a-
PACKAGE TITLE
BMS
ARCHITECTURE FOR 6* HOTEL &
F V A KW SD CO
-a- COMMON AREAS
TEMPERATURE HUMIDITY PRESSURE FLOW VOLTAGE CURRENT POWER LEVEL SMOKE TIMER END AIR DIGITAL ANALOG SMART FORMAT FIRST ISSUE DATE DESIGNED BY CHECKED BY SCALE PLOT NO. / AREA
DETECTOR SWITCH QUALITY INPUT INPUT SENSOR (ISSUE OF REV00)

Marina-hotel 001 /
LUSAIL
PROJECT NO. PHASE BLDG. NO. DISCIPLINE SERIAL NO. PART REV. NO.

FIELD INSTRUMENTATION
Q17017-0100D TD GN MI 852 1 OF 1 00