Tan Delta Test | Loss Angle Test | Dissipation Factor Test


Last updated October 27, 2020 by Electrical4U

Principle of Tan Delta Test


A pure insulator when is connected across line and earth, it behaves as a capacitor. In an ideal insulator, as the insulating
material which acts as dielectric too, is 100 % pure, the electric current passing through the insulator, only have
capacitive component. There is no resistive component of the current, flowing from line to earth through insulator as in
ideal insulating material, there is zero percent impurity.

In a pure capacitor, the capacitive electric current leads the applied voltage by 90o.
In practice, the insulator cannot be made 100% pure. Also due to the aging of insulators, the impurities like dirt and
moisture enter into it. These impurities provide the conductive path to the current. Consequently, an electric leakage
current flowing from line to earth through the insulator has a resistive component.

https://www.electrical4u.com/tan-delta-test-loss-angle-test-dissipation-factor-test/?__cf_chl_managed_tk__=186fbfec2d709487ed968c380f73faa5b99… 1/10
5/5/2021 Tan Delta Test | Loss Angle Test | Dissipation Factor Test | Electrical4U

Hence, it is needless to say that, for good insulator, this resistive component of electric leakage current is quite low. In
another way, the healthiness of an electrical insulator can be determined by the ratio of the resistive component to the
capacitive component. For good insulator, this ratio would be quite low. This ratio is commonly known as tanδ or tan
delta. Sometimes it is also referred to as dissipation factor.

In the vector diagram above, the system voltage is drawn along the x-axis. Conductive electric current i.e. resistive
component of leakage current, IR will also be along x-axis.
As the capacitive component of leakage electric current IC leads system voltage by 90o, it will be drawn along y-axis.
Now, total leakage electric current IL(Ic + IR) makes an angle δ (say) with y-axis.
Now, from the diagram above, it is cleared, the ratio, IR to IC is nothing but tanδ or tan delta.

NB: This δ angle is known as loss angle.

Method of Tan Delta Testing


The cable, winding, current transformer, potential transformer, transformer bushing, on which tan delta test or
dissipation factor test to be conducted, is first isolated from the system. A very low-frequency test voltage is applied
across the equipment whose insulation to be tested.

https://www.electrical4u.com/tan-delta-test-loss-angle-test-dissipation-factor-test/?__cf_chl_managed_tk__=186fbfec2d709487ed968c380f73faa5b99… 2/10
5/5/2021 Tan Delta Test | Loss Angle Test | Dissipation Factor Test | Electrical4U

First, the normal voltage is applied. If the value of tan delta appears good enough, the applied voltage is raised to 1.5 to 2
times of normal voltage, of the equipment. The tan delta controller unit takes measurement of tan delta values. A loss
angle analyzer is connected with tan delta measuring unit to compare the tan delta values at normal voltage and higher
voltages and analyze the results.

During the test, it is essential to apply test voltage at a very low frequency.

Reason of applying Very Low Frequency


If the frequency of the applied voltage is high, then capacitive reactance of the insulator becomes low, hence the
capacitive component of electric current is high. The resistive component is nearly fixed; it depends upon applied
voltage and conductivity of the insulator. At high frequency as capacitive current, is large, the amplitude of the vector
sum of capacitive and resistive components of electric current becomes large too.

Therefore, required apparent power for tan delta test would become high enough which is not practical. So to keep the
power requirement for this dissipation factor test, very low-frequency test voltage is required. The frequency range for
tan delta test is generally from 0.1 to 0.01 Hz depending upon size and nature of insulation.

There is another reason for which it is essential to keep the input frequency of the test as low as possible.

As we know,

https://www.electrical4u.com/tan-delta-test-loss-angle-test-dissipation-factor-test/?__cf_chl_managed_tk__=186fbfec2d709487ed968c380f73faa5b99… 3/10
5/5/2021 Tan Delta Test | Loss Angle Test | Dissipation Factor Test | Electrical4U

That means, dissipation factor tanδ ∝ 1/f.


Hence, at low frequency, the tan delta number is higher, and the measurement becomes easier.

How to Predict the Result of Tan Delta Testing


There are two ways to predict the condition of an insulation system during tan delta or dissipation factor test.

First, one is, comparing the results of previous tests to determine, the deterioration of the condition of insulation due to
aging effect.

The second one is, determining the condition of insulation from the value of tanδ, directly. No requirement of comparing
previous results of tan delta test.

If the insulation is perfect, the loss factor will be approximately the same for all range of test voltages. But if the
insulation is not sufficient, the value of tan delta increases in the higher range of test voltage.

https://www.electrical4u.com/tan-delta-test-loss-angle-test-dissipation-factor-test/?__cf_chl_managed_tk__=186fbfec2d709487ed968c380f73faa5b99… 4/10
5/5/2021 Tan Delta Test | Loss Angle Test | Dissipation Factor Test | Electrical4U

From the graph, it is clear that the tan and delta number nonlinearly increases with increasing test very low-frequency
voltage. The increasing tan&delta, means, high resistive electric current component, in the insulation. These results can
be compared with the results of previously tested insulators, to take the proper decision whether the equipment would
be replaced or not.

Want To Learn Faster? 🎓


Get electrical articles delivered to your inbox every week.
No credit card required—it’s 100% free.

Your name

Your email address

Join (it’s free)

About Electrical4U

Electrical4U is dedicated to the teaching and sharing of all things related to electrical and electronics engineering.

...

Related Articles

Polarization Index Test or PI Test Dielectric Material as an…


https://www.electrical4u.com/tan-delta-test-loss-angle-test-dissipation-factor-test/?__cf_chl_managed_tk__=186fbfec2d709487ed968c380f73faa5b99… 5/10
5/5/2021 Tan Delta Test | Loss Angle Test | Dissipation Factor Test | Electrical4U

Dielectric Properties of… High Voltage Testing | Low…

6 thoughts on “Tan Delta Test | Loss Angle Test | Dissipation Factor Test”

VENKAT B
February 11, 2019 at 2:52 am

Very good &easily understandable article. Thanks for sharing

Reply

Electrical4U
February 15, 2019 at 11:51 pm

No worries Venkat – thank you for your kind words.

Reply

Amit Moitra
February 20, 2019 at 12:53 pm

Very useful and easily understandable article.

Reply

Electrical4U
February 23, 2019 at 1:08 am

https://www.electrical4u.com/tan-delta-test-loss-angle-test-dissipation-factor-test/?__cf_chl_managed_tk__=186fbfec2d709487ed968c380f73faa5b99… 6/10
5/5/2021 Tan Delta Test | Loss Angle Test | Dissipation Factor Test | Electrical4U

Thank you Amit – very happy to hear!

Reply

Kaishnair
February 22, 2019 at 4:29 am

Very good and very clearly explained article.Thanks for sharing.

Reply

Electrical4U
February 23, 2019 at 4:47 am

No worries at all Kaishnair. Happy to hear you found the information helpful!

Reply

Leave a Comment

Name *

Email *

Post Comment

https://www.electrical4u.com/tan-delta-test-loss-angle-test-dissipation-factor-test/?__cf_chl_managed_tk__=186fbfec2d709487ed968c380f73faa5b99… 7/10
5/5/2021 Tan Delta Test | Loss Angle Test | Dissipation Factor Test | Electrical4U

Recent Posts
» SCADA System: What is it? (Supervisory Control and Data Acquisition)

» Programmable Logic Controllers (PLCs): Basics, Types & Applications

» Diode: Definition, Symbol, and Types of Diodes

» Thermistor: Definition, Uses & How They Work

» Half Wave Rectifier Circuit Diagram & Working Principle

» Lenz’s Law of Electromagnetic Induction: Definition & Formula

https://www.electrical4u.com/tan-delta-test-loss-angle-test-dissipation-factor-test/?__cf_chl_managed_tk__=186fbfec2d709487ed968c380f73faa5b99… 8/10
5/5/2021 Tan Delta Test | Loss Angle Test | Dissipation Factor Test | Electrical4U

report this ad

Please feel free to contact us if you’d like to request a specific topic. Click here to see our privacy policy.
https://www.electrical4u.com/tan-delta-test-loss-angle-test-dissipation-factor-test/?__cf_chl_managed_tk__=186fbfec2d709487ed968c380f73faa5b99… 9/10
5/5/2021 Tan Delta Test | Loss Angle Test | Dissipation Factor Test | Electrical4U

We are a participant in the Amazon Services LLC Associates Program, an affiliate advertising program designed to
provide a means for us to earn fees by linking to Amazon.com and affiliated sites. Full disclaimer here.

© 2021 Electrical4U

https://www.electrical4u.com/tan-delta-test-loss-angle-test-dissipation-factor-test/?__cf_chl_managed_tk__=186fbfec2d709487ed968c380f73faa5b9… 10/10

You might also like