Project Precast Boundary Wall Designed by AN

Location ABU DHABI - Zayed City Checked by AN


Client Date 3/8/2021
Contractor M/s Zonal Link General Contracting Rev.No 0

DESIGN OF TYP. PRECAST BOUNDARY WALL WITH IN BUILT FOOTING


MATERIALS:
Concrete density, δc 25 kN/m³ FOR SAFE BEARING CAPACITY -120 kPa
Steel yield stress, fy 460 N/mm²
Soil Bearing Capacity 120 kN/m² t1=120
Soil Density, δsoil 18 kN/m³
Reinf. concrete, fcu 40 N/mm²
DIMENSIONS:
Wall
Height of panel above GFL, H1 3000 mm
Panel thickness, t1 120 mm
P4 P1 H1=3000
Panel thickness, t2 150 mm 3000
panel d1 750 mm
Panel length, Lp 5000 mm
concrete cover 60 mm
FOOTING
Width of footing, Wf 1500 mm
M1 P7
P5
Length of footing, Lf 1700 mm d1=750
P2
depth of footing from inside lvl, H2 1000 mm H3=1000
P3 M2 P6
depth of footing from outside lvl, H3 1000 mm f2=50
footing depth, f1 200 mm f1=200
footing depth, f2 50 mm A

No. of footings 2 nos. t2=150 1550

concrete cover 50 mm Lf=1700
Concrete Blinding, PCC 0 mm
Wind Load, qs = 1.20 kN/m²
SOIL:
ka = (1‐sinθ)/(1+sinθ)
θ = 36.00 °
ka = 0.26
kp = 3.85

LOAD CALCULATION :
P1 = (H1*Lp)*qs 18.00 kN
P2 = 1/2 ka* δsoil* H2²* Lp 11.68 kN
P3 = 1/2 kp* δsoil* H3²* Wf 51.99 kN
P4 = t1*(H1+d2)*Lp* δc 44.10 kN
P5 = t2*(H2-d2)*Lp* δc 18.38 kN
P6 = 2*(Lf-t2)*(0.5*(f1+f1+f2))*Wf*δc 39.73 kN
P7 = 2*{[(H2-f1)+(d1+d2)]*0.5}*(Lf-t2)*Wf*δsoil 64.87 kN
Project Precast Boundary Wall Designed by AN
Location ABU DHABI - Zayed City Checked by AN
Client Date 3/8/2021
Contractor M/s Zonal Link General Contracting Rev.No 0

STABILITY CHECK

Table 1: Load and Moment Values


Load ID Load Value (KN) Load Distance Moment Moment
Value
from A (m) ID ( kN-m)
P1 18.00 2.500 M1 45.00
P2 11.68 0.333 M2 3.89
P3 51.99 0.333 M3 17.33
P4 44.10 0.060 M4 2.65
P5 18.38 0.075 M5 1.38
P6 39.73 0.925 M6 36.75
P7 64.87 0.925 M7 60.00

Total overturning Moment = M1+M2 = 48.89 kN‐m


Total resisting Moment = M4+M5+M6+M7 = 118.11 kN‐m
Factor of safety against overturning, FOS = (Total resisting moment/total overturning moment)

2.42 > 1.50 Safe Against Overturning

* A is the point of overturning P4

BEARING CAPACITY CALCULATION : P7


P5
Total vertical Load P = (P4+P5 P6+P7) 167.07 kN P2
Moment @ center of footing, Mc =M1+M2+(P4*X4)+(P5*X 72.798 kN-m P3 P6
5)-(P6*X6)-(P7*X6)-M3

Inertia, I =( Wf*Lf ³/12)*no. of foot 1.228 m4 A


x5
Area, = ( Lf*Wf )*no. of footing 5.1 m²
eL, =Mc/P 0.436 m x4 x6
 Lf/6 < el < Lf/2 
L1, =3[Lf/2)‐eL] 1.243 m
Max. Soil Pressure 89.62 kN/m² < 120 kN/m² Safe

Min. Soil Pressure = 0.00 kN/m² < 120 kN/m² Safe

SLIDING RESISTANCE

Frictional coefficient f =tanθ = 0.73


nal Force due to verical load Pr =2 *P*f = 242.75
Sliding Force = P1 + = 29.68 kN
Sliding resisting force = P3+ P = 294.74 kN

Factor of safety against sliding = Sliding resisting force/Sliding Force ≥ 1.50

9.93 > 1.50 Safe Against Sliding

Note: Frictional resistance of footing against sliding is not considered which will give more factor of safety against sliding.
Project Precast Boundary Wall Designed by AN
Location ABU DHABI - Zayed City Checked by AN
Client Date 3/8/2021
Contractor M/s Zonal Link General Contracting Rev.No 0

FOOTING DESIGN

As
1700

250
200

A
Mmax
MIN. SOIL PRESSURE = 0.00 kN/m²

MAX. SOIL PRESSURE = 89.62 kN/m²

CONSIDERING WORST CASE CONDITION WHERE MIN. SOIL PRESSURE = 0 kN/m²

W= MAX. SOIL PRESSURE * LENGTH OF FOOTING/3


W= 76.18 kN
Mmax @ POINT A = WL/3
Mmax @ POINT A = 43.17 kN-m
Mmax ultimate= 69.07 kN-m

Check if compression reinforcement required:


k = Mmax ultimate / Length of footing*depth²*fcu
k = 69.07*1000000/(1700*200²*40)
k= 0.025
k' = 0.15
k < k' No compression reinforcement required

d (effective depth) = 194 mm
0.95*d= 184 mm
z= d[ 0.5 +(0.25-k'/0.9)1/2]
z= 153 mm

As required = Mmax ultimate / 0.95*fy*z


use z = 153.0 mm
As required = 1,032.98 mm²
Assumed bar dia. = 12 mm @ 150 mm c/c
As Provided = 1,131.00 mm²

No. of Extra bars provided = 0


Bar dia. = 12 mm
As for extra bar = 0 mm²

Total As provided = 1131 mm² As Required < As provided OK


Project Precast Boundary Wall Designed by AN
Location ABU DHABI - Zayed City Checked by AN
Client Date 3/8/2021
Contractor M/s Zonal Link General Contracting Rev.No 0

PANEL DESIGN

Moment M1= 0.5*qs*Lp*H1² = 27.00 kN-m


Factored Moment Mf = 1.0*M = = 27.00 kN-m
Moment M2= (qs*H1*0.5H1+d1+d1)+(P2'*(d1+d2)/3)+(P1*t2-t2*0.5) = 42.41 kN-m
Factored Moment M2 = 1.0*M2 = 42.41 kN-m

Panel Design for 120 mm thickness


Clear Height = 3000 mm
thickness = 120 mm
Length = 3500 mm

Check if compression reinforcement required:


k = Mmax ultimate / Length of footing*depth²*fcu As 120mm WALL
k = 27.00*1000000/(3000*120²*40) 8mm @200mm c/c
k= 0.016
k' = 0.15 As 150mm WALL
k < k' No compression reinforcement required M1 12mm @200mm c/c

d (effective depth) = 56 mm
0.95*d= 53 mm
z= d[ 0.5 +(0.25-k'/0.9)1/2] M2
z= 44.2 mm

As required = Mf / 0.95*fy*z
use z = 44.2 mm As FOOTING
As required = 1,398.93 mm² 12mm @150mm c/c
Assumed bar dia. = 8 mm @ 200 mm c/c
As Provided = 849.39 mm² As required > As provided, increase bar diameter

Panel Design for 150 mm thickness (Below Ground Level)


Clear Height = 750 mm
thickness = 150 mm
Length = 1500 mm

Check if compression reinforcement required:


k = Mmax ultimate / Length of footing*depth²*fcu
k = 42.41*1000000/(750*150²*40)
k= 0.063
k' = 0.15
k < k' No compression reinforcement required

d (effective depth) = 84 mm
0.95*d= 80 mm
z= d[ 0.5 +(0.25-k'/0.9)1/2]
z= 66.2 mm

As required = M2 / 0.95*fy*z
use z = 66.2 mm
As required = 1,078.39 mm²
Assumed bar dia. = 12 mm @ 200 mm c/c
As Provided = 780.39 mm² As required > As provided, increase bar diameter