You are on page 1of 14

14

System Stability and Out-of-Step Relaying


W. A. ELMORE

1 INTRODUCTION given by the following equation:


VS VR
Since relaying systems must function properly during P¼ sin f ð14-1Þ
system swings, it is necessary to understand the effects X
of these disturbances on relay performance. Swings are where
the oscillations of synchronous machines with respect
to other synchronous machines. They are caused by VS and VR ¼ sending- and receiving-end voltages,
changes in load, switching, and faults. A swing does respectively
not necessarily indicate system instability. In some X ¼ reactance between VS and VR
cases, however, the swing is severe enough to cause f ¼ angle by which VS leads VR
synchronous machines to go out of step. Before
See Figure 14-1.
examining the influence of system swings on relay
If system resistance is not neglected, different
performance, three factors must be considered: steady-
equations apply for the sending- and receiving-end
state stability, transient stability, and relay quantities
power. The variables, however, are essentially the same.
encountered during swings.
If phase-to-phase voltages are used, Eq. (14-1) yields
A system is stable when it is able to develop
three-phase power. For this discussion, VS and VR are
restorative forces in excess of the disruptive forces to
taken as per unit quantities, and Eq. (14-1) gives per
which it is subjected. Disruptive forces are produced by
unit power. If VS, VR, and X are held constant in Eq.
such factors as faults, loss of excitation, or switching of
(14-1), the power flow is changed by varying the angle f.
lines, transformers, or generation. Restorative forces
As the load increases at the receiving end, synchro-
are produced by current flow, voltage increase, or
nous machines are momentarily slowed down, and the
impedance reduction produced by fault removal and/
machine-rotor inertia meets the increased load require-
or line switching.
ments. That is, an increase in load results in a small
reduction of system frequency until there is a change in
mechanical input via the governor or manual action.

2 STEADY-STATE STABILITY

The fundamentals of power transmission and stability


are more easily understood if both system resistance,
excluding the load impedances, and machine saliency
are neglected. In this case, the power P transmitted
over circuits connecting two portions of the systems is Figure 14-1 Simple equivalent system.

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


To restore system frequency, the mechanical input to
the machines must be increased. This input must be
greater than the steady-state load requirements, since
the machines must be accelerated to a new and larger
angle. When the new angle f is reached, the mechan-
ical input will exceed the load requirements by the
amount required to accelerate the machines. The
mechanical input must then be reduced to maintain
frequency and required power transfer. Any load
change therefore results in swings or oscillations as
the system adjusts to the changes. Steady-state stability
is the ability of the system to adjust to gradual load
changes.
The extreme unstable condition occurs when f is Figure 14-2 Power transfer curve.
equal to 908. At this point, increased load conditions
could only be met by increasing VS or VR. An increase
in f would cause a reduction, rather than an increase,
in power transfer.

3 TRANSIENT STABILITY

Transient stability is the ability of the system to


properly adjust (remain in synchronism) to sudden
large changes. Again, if we ignore system resistance
and machine saliency, the power transmitted during
the transient interval P is given by the following
equation:
V0S V0R
P¼ sin f ð14-2Þ
X0 Figure 14-3 Effect on X0 of fault.
In Eq. (14–2), P is three-phase MW if and VS0
are 0
VR
0
expressed in kV (phase to phase) and X in ohms per
phase, where intact without reduction, whereas X2 and X0 are the
thevenin impedances in the negative and zero sequence
V0S ¼ voltage behind transient reactance at the
networks, respectively. XF for the ff fault is simply
sending end
X2. For the fG fault, XF is X2 and X0 in series.
V0R ¼ voltage behind transient reactance at the
Based on the normal relationship found between
receiving end
X1, X2, and X0, the relative order of severity of the
X0 ¼ reactance between VS0 and VR 0
, including
various types of faults produces the relative power-
transient reactances of the machines
transfer curves shown in Figure 14-4. The reduction of
f ¼ angle by which VS0 leads VR0
the ‘‘T,’’ of which XF is one leg, to an equivalent ‘‘pi’’
Figure 14-2 shows a power-transfer curve. Note that produces X0 which is the transfer impedance that, with
the peak value is inversely proportional to the total the voltage VS and VR, defines the peak value of the
reactance X. Figure 14-3 describes how X is influenced power-transfer curve.
by the presence of a fault, as well as the type of fault. Figure 14-5 describes a representative case of two
It is recognized that the quantity to be inserted as parallel lines with generation at each end. The power
XF in the fault representation is dependent on the type transfer curves show that a fault causes an immediate
of fault, whether 3f, ffG, ff, or fG. For the 3f drop in transmitted power from bus S to bus R because
fault, XF is 0. For the ffG fault, XF is X2 and X0 in of the fact that the ‘‘torque angle’’ m cannot change
parallel. The positive sequence network is retained instantaneously, but X0 does. This change in power

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


power output at the receiving end, causing deceleration
there. Both of these effects increase m.
When the fault occurs (Fig. 14-5), the transmitted
power is reduced to point E because of the increased
effective X0 , and the swing begins along E-F. At point
F, breaker A opens, and the transmitted power
increases to G. The swing then continues along G-H.
When the fault is cleared at H by breaker B
opening, the sending-end rotor kinetic energy has
increased by an amount proportional to area I, since
the mechanical input has exceeded the transmitted
electrical power. As the fault is cleared, the transmitted
power increases to J, exceeding the mechanical input
Figure 14-4 Relative order of severity of fault types.
and causing the sending-end machines to decelerate
and the receiving-end machines to accelerate. Since the
velocity of a rotating mass cannot be changed
quantity DE. Power DE is the difference between
instantly, the swing continues to K, at which point
mechanical input and electrical output that, therefore,
the additional sending-end rotor energy, resulting from
produces acceleration of the rotating mass. With losses
the fault, is completely absorbed (area II equals area I).
ignored in this example, quantity DE is also the
The velocity of the sending-end mass, with respect
difference between electrical power input and mechanic
to the receiving-end mass, is 0 at K. At K, the electrical
output of the sending end exceeds the mechanical
input; therefore, the swing reverses, reaching a point
N. At N, the swing reverses again. Voltage regulator
and governor action, as well as system resistance, will
dampen the oscillation, until the final operating point
is reached.
If the initial swing went to point L and the sending-
end generators still had excess rotor energy (area II
smaller than area I), the swing would continue in the
same direction. After L was passed, the mechanical
input of the sending-end generators would again
exceed the electrical output, and the swing would be
accelerated, resulting in instability with the machines
operating out of synchronism with each other. After
this, only system separation and resynchronizing of the
machines could restore normal system operation.

4 RELAY QUANTITIES DURING SWINGS

With the fault cleared and the system operating out of


step, extreme variations in voltage and current will
occur throughout the system. Figure 14-6 provides
insight into this phenomenon. A simple system is
represented with the relay of interest shown at some
intermediate point between the two sources. The relay
voltage VR is established by the angle between VS and
VU (each assumed here to maintain their predisturbance
values) and the distribution of impedances (ZS, ZL, and
Figure 14-5 Power transfer curves before, during, and after ZU) between these two sources. VR will assume some
line-to-line fault. position between them. As VS, the accelerating source,

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


Figure 14-6 Relay quantities for OS condition. (Shown for 908 impedance angles.)

moves in phase position with respect to VU, the apparent fully cleared) appears to be a three-phase fault. The
impedance viewed by the relay (VR/IR) will change with location of this apparent fault is at the electrical center
time, producing a trajectory on an R-X (resistance- of the system. If this apparent impedance enters the
reactance) diagram such as that of Figure 14-6c. operating area of a distance relay, it will operate.
With the depressed voltage and large current, this If VR and VU are not supported at full value, their
swing condition (long after the fault has been success- ratio is influential in determining the locus on the R-X

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


diagram as the swing progresses. Also, if impedances such a swing is virtually nil. In general, zone 1 swing-
are not pure reactance values as is assumed in trips occur only on unrecoverable swings.
Figure 14-6, the effect can be determined using a Some form of blinding is required to screen over-
similar simple diagram. reaching distance relays against tripping on severe
Interaction between machines in complex networks swings from which recovery is possible. Operating
can only be determined by a large-scale digital study. independently, a phase-distance relay (21) will initiate
For distance relaying evaluation, actual impedance tripping when the angle between the two system
(using line current and relay voltage) values must be voltages is very large and increasing (Fig. 14-7).
determined with respect to time for each pertinent Figure 14-8a shows that zone 1 tripping is highly
relay location, and each chosen switching condition, dependent on the locus of the swing ohms and
fault location, and type. therefore the distance to the electrical center for the
case involved.

5 EFFECT OF OUT-OF-STEP CONDITIONS


5.1 Distance Relays

A distance relay (21) responsive to three-phase faults


will operate if an out-of-step (OS) condition produces
a swing locus that falls within its operating area (Fig.
14-7).
When swing ohms enter the operating area of a zone
1 relay with a circular characteristic, there is a 908
angle between the voltages at the points along the line
angle identified by the relay reach. In Figure 14-7, for
example, there must be a 908 phase displacement
between the voltage phasors at relay location A and a
point at 90% of the line length for a 90% reach zone 1
phase relay to operate on a swing. The effective
generator voltages will be displaced substantially more
than 908 (angle m in Fig. 14-7). The likelihood of a
system attaining a stable operating condition after

Figure 14-7 Source angle relationship for swing trip on the Figure 14-8 Effect of OS swings on various line relaying
system of Figure 14-6. systems.

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


5.2 Directional Comparison Systems

Swing ohms entering a protected line area will produce


simultaneous high-speed tripping at the two terminals.
Only swings entering external to the line area will block
tripping, and then only if local 21S operates and/or the
remote 21P does not. For the permissive overreaching
transfer-trip or the unblock system, tripping occurs on
OS conditions only if the 21P at both terminals
operate. If tripping is to be avoided for cases where
operation takes place, out-of-step blocking must be
used.

5.3 Phase-Comparison or Pilot-Wire Systems

Phase-comparison or pilot-wire schemes are solely


current-responsive, and since swings produce a
through-current condition, tripping does not occur.

5.4 Underreaching Transfer-Trip Schemes

Out-of-step swings entering the circle of either zone 1


relay will cause tripping at both terminals when using Figure 14-9 Maximum recovery voltage on OS trip with
breaker at electrical center.
the underreaching transfer-trip (whether direct or
permissive) scheme.
must be initiated at a favorable angle, preferably just
5.5 Circuit Breakers before the two sources are in phase.

With the two system segments 1808 apart at the instant 5.6 Overcurrent Relays
of interruption, a theoretical undamped recovery
voltage of four times normal is possible. Figure 14-9 Figure 14-6 can be used to illustrate the conditions
describes this phenomenon with the breaker at the encountered by phase-overcurrent units during swings.
electrical center of the system. At current 0, where Assume, for example, that an instantaneous over-
interruption takes place, the voltage on each side of the current unit set for 2.5 times full load were used in a
breaker must settle at a new value. In the process of line connecting Vs and Vu, and that ZS þ ZL þ ZU
getting there, overshoot takes place as a result of the equals 0.765 per unit on the full-load base. During an
presence of inductance and distributed capacitance in OS condition, the instantaneous unit would operate
the system. Recovery voltage is the voltage across the because the current reaches at least 2.61 (2/0.765) times
breaker contacts following current interruption. full load when VU lags by 1808. Swings during stable
Figure 14-10 shows that this identical phenomenon conditions will also result in higher than normal
occurs even though the breaker is as far away from the currents, although currents will be considerably less
electrical center as possible. The extremely large than during an OS condition.
transient recovery voltage still appears. If the circuit
breaker has insufficient dielectric strength to withstand
this voltage, reignitions will continue until a more 5.7 Reclosing
favorable angle is reached. To interrupt at all, a
breaker must be capable of attempting interruption, When a fault persists after reclosing, the stability of the
possibly for several seconds, at each current 0. If the system will probably be jeopardized. On the other
breaker cannot perform such interruptions, tripping hand, system stability is greatly improved if the fault is

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


split so most of the generation is separated from the
major system load.
In Figure 14-11, breaker A is in a poor location for
splitting system (1) from (2), since it would dump one
unit of load on system (2), which only generates 0.4
unit of power. Splitting the system using breakers D or
E would offer a more tolerable generation/load
balance. In this scheme, system (1) need only increase
its generation from 0.6 to 0.66 to maintain frequency.
Figure 14-11 also illustrates that OS tripping is
desirable at some points, but should be blocked at
others. This selective tripping/blocking philosophy is
basic to the intelligent application of OS relaying.

6.1 Generator Out-of-Step Relaying

Generator per unit reactances have steadily increased


over the years, and inertia constants have decreased as
machine ratings have increased. This, in turn, has
reduced critical clearing times and increased the need
for the OS relaying for generators.
Loss-of-field relays, equipped with directional units
and undervoltage supervision, may provide a measure
of OS protection for generators. Viewed from the
Figure 14-10 Maximum recovery voltage on OS trip with terminals of a large modern machine, the ohms will, in
breaker at source. general, fall within the machine or unit transformer
when the machine is out of step with the system. If the
swing ohms fall within the machine for the system
temporary and does not reignite following reclosure. shown in Figure 14-11, the KLF (or KLF-1) loss-of-
Three-phase faults tend to be permanent more often field relay (40) will operate if swing ohms stay inside
than other faults. They also have the most severe effect the characteristic circle for 0.25 sec.
on stability. For this reason, reclosing is often blocked If a loss-of-field relay is used for OS sensing, the
for three-phase faults and for OS conditions, but timer must not time out for stable swings. It must
allowed for all others. operate, however, for field failure before damage (or
There appears to be no advantage to the high-speed further damage) can occur, and it must recognize the
reclosing of both terminals following an OS trip. fastest realistic swing rate. Generally, all these time
Reclosing one terminal, or preferably blocking trip- constraints can be satisfied. Figure 14-12 shows a
ping at one terminal, will facilitate system restoration. typical stable swing locus following a severe three-
The second terminal can be reclosed under synchron- phase fault.
ism-check relay supervision. If swing ohms pass through the unit transformer,
OS detection may not be possible with either a loss-of-

6 OUT-OF-STEP RELAYING

Ideally, fault relays should clear faults fast enough to


maintain stability. Also, they should not operate on
swings from which the system can recover. If a system
does go out of step, it should be split by circuit
breakers opening at a few preselected locations, in such
a way that generation and load on each side of the split
are reasonably balanced. The system should not be Figure 14-11 Generation and load distribution.

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


but rather that OS detection may be easiest at the
generating plant. Out-of-step separation would then be
accomplished by transfer-tripping, or other suitable
means, to maintain a generation/load match, as
described above.

6.2 Transmission-Line Out-of-Step Relaying

The prime criterion in OS tripping is to maintain a


generation/load match in the islands created. If such a
match were perfect, no large load shifts and load
dropping would be required. Also, little or no
generation would be dropped. To even approximate
this ideal would, in all probability, require trip-
blocking at some locations and trip initiation at others.
Distance-relay operation on OS conditions tends to
occur at locations where the relay reach settings are
longest. There are two reasons for this phenomenon.
First, the minimum system voltage during an OS
condition tends to occur in the high-impedance
segments of the system. Second, distance relays with
long reach settings, such as those on long lines, cover a
Figure 14-12 Stable swing following clearing of nearby larger area on the R-X diagram and therefore are more
three-phase fault with the KLF relays (40) likely to respond to swing conditions. Out-of-step
tripping at long-line terminals is not necessarily
conducive to ideal system splitting.
field relay or simple distance relay. Moving the
directional unit characteristic output to point G on
Figure 14-12 would substantially increase the possibi-
lity of a false trip on a stable swing, such as GCD. 7 PHILOSOPHIES OF OUT-OF-STEP
Alternatively, the time criterion could be increased to RELAYING
the point where the stable swing would not trigger
relay operation, but then the fastest out-of-step swing Certain fundamental objectives should influence the
may not be recognized. design of protection systems:
When the smaller characteristic is used as described
1. Block tripping at all locations for stable swings.
by the dotted circle of Figure 14-12, a higher degree of
2. Ensure separation for every OS condition.
security is achieved. However, it occurs at the expense
3. Effect separation at points that will leave a
of making out-of-step recognition impossible, as well
satisfactory load/generation balance in each
as losing the ability to match accurately, as described
separated area. Loads should not be inter-
in Chapter 8, the loss-of-field relay characteristic,
rupted.
steady-state stability, and minimum excitation unit
4. Block tripping or automatically reclose at one
limits for the machine.
end of any line that trips because of an OS
In general, devices applied for other functions (fault
condition.
detection, loss of field, thermal protection, etc.) are
5. Initiate tripping while the systems are less than
unsuitable for detecting OS conditions. The use of
1208 out of phase and the angle is closing in
relaying, tailored explicitly for OS detection, is the only
order to minimize breaker stress.
dependable approach, unless extensive studies demon-
6. Minimize the possibility of an OS condition
strate that other devices will suffice or instability is
occurring by
improbable.
This should not be taken to mean that generator (a) Using high-speed relaying
tripping is encouraged when OS conditions develop, (b) Using a high-speed excitation system

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


(c) Employing loss-of-field relays to remove a
unit that is drawing excessive reactive
power from the system
(d) Providing sufficient transmission capacity
(e) Tripping generators upon the loss of
critical transmission lines
(f) Applying generator braking resistors or
inserting series capacitors for critical faults
(g) Applying fast valving techniques
(h) Using an independent mechanism for each
breaker pole to downgrade faults from
three-phase to phase-to-phase
Although easily stated, these objectives are not so
readily achieved, particularly item 3 above. Figure 14-13 The concentric circle scheme for out-of-step
detection.

7.1 Utility Practice


pass from 68 to 21P. For a fault within the 21P reach,
Utility practice consists of a combination of: however, both elements operate essentially simulta-
neously. The relaying logic senses the sequence,
1. Allowing the line-protection relays to initiate identifies swing or fault, and initiates the appropriate
OS line tripping action.
2. Allowing the loss-of-field relays to initiate OS The dotted arcs of circles described as a ‘‘tomato’’
generator tripping (when the nature of the loss- characteristic represent a popular analog implementa-
of-field relay allows it) tion of the ‘‘outer’’ characteristic.
3. Restricting relay-trip sensitivity at the higher This scheme is appropriate for an OS trip-blocking
power factors function or reclose-blocking. It is not appropriate for
4. Blocking tripping on OS OS tripping, however, unless additional logic is added.
5. Blocking reclosing on OS If an external phase fault occurs close to the balance
6. Initiating tripping using relays designed for OS point of 21P, as at P in Figure 14-13, for example, the
tripping relay will respond slowly because of its low energy
There is no industry standard for protection-system level. Device 68, on the other hand, has an appreciably
design; however, once the difficult functional decisions higher energy level and operates faster than does 21P.
of ‘‘what’’ and ‘‘where’’ are made, there is reasonable Removing remote terminal infeed on external fault
consistency in the ‘‘how.’’ clearing following breaker failure can also produce
sequential operation of 68 and 21P. If the time in the
sensing logic is shorter than this operating-time
8 TYPES OF OUT-OF-STEP SCHEMES difference, a fault at P would be incorrectly identified
as an OS condition and would cause a false trip at A. If
Some typical systems used in OS relaying are described the time is increased to avoid this situation, rapid OS
here. swings would not produce OS tripping. Adding a third
concentric circle would allow better perceptive segre-
gation of swings and faults, but could introduce load
8.1 Concentric Circle Scheme ohm involvement. OS tripping can be achieved with
the two-concentric-circle scheme if the 68/21P operat-
A concentric circle scheme for OS detection on ing sequence is checked and the resetting sequence is
terminal A is shown in Figure 14-13. Customarily, an correct.
OS relay with a characteristic as shown for 68 is added For the three-terminal applications, infeed can
to a transmission-line relaying system and surrounds adversely affect OS blocking relays that use the
an over-reaching element, such as 21P. Because of concentric circle scheme if the sequential clearing of a
rotating apparatus inertia, significant time is required three-phase fault can occur. The reach-shortening
for the torque angle to advance and the swing locus to effect of the third terminal infeed can cause an internal

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


line-end fault to operate 68, but not 21P. Clearing the Another application is OS tripping on swings passing
infeed may then allow 21P to operate. This sequence beyond the reach of the line relays (on an R-X plot).
could cause undesirable OS trip-blocking at one Finally, this relay scheme is particularly well-suited for
terminal. Out-of-step blocking then should not be generator OS trip applications.
used in a three-terminal application unless remote The two-blinder scheme (Fig. 14-15) senses OS
terminal coverage can be obtained with maximum conditions by observing the operating sequence of the
infeed. outer and inner blinders. A fault produces essentially
simultaneous operation; an OS condition causes the
8.2 Blinder Scheme outer blinder to operate first, followed by operation of
the inner blinder. The two-blinder scheme allows the
One form of a blinder relay has an operating trip-area restriction of distance relays, OS trip-block-
characteristic that parallels the transmission-line plot ing, OS reclose-blocking, or OS tripping, regardless of
in an R-X diagram (Fig. 14-14). A single-blinder relay normal load-flow direction.
21B, gives the two linear characteristics shown.
An obvious application of this device is for limiting
the coverage of a distance relay in the load area. This is 9 RELAYS FOR OUT-OF-STEP SYSTEMS
a side benefit of the application of blinder OS relays.
9.1 Electromechanical Types
A single-blinder relay plus auxiliary logic can be
used for OS tripping. Its use, however, is limited to 9.1.1 KS-3 (68) OS Blocking Scheme
only those applications where OS trip-blocking of
Figure 14-16 shows the configuration for the type KS-3
phase-distance relays is not required, since swings
out-of-step blocking scheme. If ZOS operates approxi-
passing through the line section (on an R-X plot) will
mately 60 msec or more ahead of 21-2, the OS relay
cause operation of the line relays. A single blinder
operates to block all or selected tripping. The OS relay
cannot distinguish between a fault and an OS also blocks reclosing when some elements in the
condition until the resetting sequence is confirmed.
system, such as zone 1 or time trips, are allowed to
Such a scheme delays OS tripping until the swing is
operate during OS conditions.
well past the 1808 position and is returning to an in-
For faults, 21-2 trip contacts or the D0 and I0
phase condition.
contacts of the ground relay close to short out the OS
The single-blinder OS package is recommended for
unit coil, blocking pickup of the OS unit. This scheme
causing a system splitting to occur through the tripping
of a line that is protected by a phase-comparison relay.

Figure 14-14 The single blinder scheme for out-of-step Figure 14-15 The two blinder scheme for out-of-step
detection. detection. (I ¼ inner blinder, O ¼ outer blinder.)

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


Figure 14-17 The KST out-of-step tripping scheme.

maintained. The zone 2 timer would time out and


trip in the scheme shown.

9.2 Solid-State Types


Figure 14-16 The type KS-3 out-of-step blocking scheme.
9.2.1 SDBU-1 (21B), SI-T (50), ARS (94), OS
Tripping Scheme

is recommended for short-to moderate-length lines. It For the single-blinder OS tripping scheme (Fig. 14-18),
should not be used on long lines, where the load might swings from the right to left cause B1 to operate, B2 to
operate the ZOS unit. operate, B1 to reset, and then B2 to reset. It is of no
consequence whether B1 is initially operated by load
and B2 does not subsequently reset.
9.1.2 KST (68) OS Tripping Scheme
Device 50 (SI-T relay) is sensitively set and operates
Figure 14-17 illustrates the KST scheme of OS at a current level above maximum zero power factor
tripping. After sensing an OS condition in the same interchange, line charging, or transformer-magnetizing
way as the KS relay, telephone relays T1 and T2 add current. The device operates when a swing begins and
two requirements: The 21-2 relay (for example, the prohibits load pickup trip.
KD-10 phase-distance relay) must operate for 100 Thus, AND 2 operates when B1 and 50 operate with
msec, and 21-2 resets 60 msec or more ahead of ZOS. B2 reset to identify the swing origin in the positive F
On a swing, ZOS operates first to energize OS. If 21-2 region. After 4 msec, the feedback circuit holds the
does not operate before 60 msec, OS operates. Then upper input AND 2. AND 4 has an output when the
when 21-2 operates, the AR relay, T1, is energized. If swing moves between B1 and B2 to operate both
both ZOS and 21-2 remain closed for 100 msec, T1 blinders. If AND 4 output persists for 20 msec and the
operates. As the swing moves out, 21-2 resets first, swing moves across B1 to reset it, AND 6 has an
deenergizes AR, and permits the energization of T2 output. An output from AR occurs 20 msec later for
through AR back contacts if ZOS is still closed. If ZOS tripping and reclose block.
does not reset for 60 msec, T2 operates to trip and Swings originating to the left of B1 traveling left to
block reclosure as shown. right produce identical action through AND 1, AND
A fault that operates ZOS and 21-2 together (or 3, and AND 5. The restricted trip feature prevents
within approximately 60 msec) will have no effect tripping on recoverable swings. B1 and B2 may be used
because the short around the OS coil will be to supervise the tripping of a phase-distance relay.

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


Figure 14-18 The SDBU-1 out-of-step tripping scheme.

Out-of-step block of reclosing is not available with this


complement, unless OS trip is used.
The above scheme is recommended for generator
OS sensing, because its logic requires that swing ohms
emerge from the side of the relay characteristic
opposite to that from which it entered. That is, there
must be a reversal of power flow as viewed from the
machine terminals, and the reversal must occur during
high current. These two conditions will not be satisfied
unless the machine is out of step with the system. A
low-current reversal can, however, occur during
motoring.
This scheme, or its equivalent, supervised by an
over-current or distance relay, is the most secure
available for generator OS tripping. A severe but stable
swing, such as shown in Figure 14-12, cannot cause
misoperation, regardless of the timing involved in the
transient.

9.2.2 Lens Scheme


One significant variation of the blinder scheme uses a
lens and single-blinder line characteristic as described
in Figure 14-19 for out-of-step tripping. It is also
equipped with a reactance-type characteristic to
restrict the reach of the system to the desired extent.
Various areas are established (inside the lens, right of
the blinder, left of the blinder, above the reactance line, Figure 14-19 Lens scheme for out-of-step tripping GZX-
below the reactance line) and, by the addition of 104.

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


sequence and timing logic, can determine the origin relay and the point at which tripping is initiated (on the
and termination of swings and the time involved in way into the inner-blinder operating region or on the
passage, thus identifying out-of-step conditions. way out of the operating region of the outer blinder).

9.2.3 Double-Blinder OS Tripping and Blocking


10 SELECTION OF AN OUT-OF-STEP RELAY
Scheme
SYSTEM
Figure 14-20 contains the logic for out-of-step sensing
used in MDAR 2.5. 21BO and 21BI are the outer and The key ingredients in out-of-step relaying are
inner blinder units, respectively. 3fF is an input from a identification and strategy. Identification is possible
phase selector identifying the fact that no unbalanced using any of the schemes described, though a higher
fault exists (not fG, not ff, not ffG). IAL signifies order of security is mandatory for those schemes to be
that current above a preselected level exists. used for OS tripping. Also, OS identification is
The logic differentiates between a swing and fault dependent on suitable voltage and current relation-
through the sequence of operation of 21BO and 21BI. ships being present at the point of application of the
If it is a swing, the optional blocking (shown as relaying system to clearly recognize an OS condition
switches OSB1, OSB2, and OSB3) of each of three when it occurs. Strategy relates to action required once
distance units is obtained. The inner blinder supervises an OS condition has been identified. The choices are
(permits) tripping of each of the distance units to avoid OSB (out-of-step block of tripping), OST (out-of-step
any possibility of load trip not resulting from a swing trip), and OSBR (out-of-step block of reclosing).
condition. The electrical center is not a fixed point in a system.
Logic is included to permit delayed OS tripping ‘‘on Indeed, several electrical centers may be present for a
the way out’’ to minimize the possibility of breaker given swing condition. Further, the electrical center
damage during tripping or ‘‘on the way in’’ to moves as the number of generators and switching
minimize the possibility of thermal damage to a conditions vary. For the particular unstable case under
transmission line. The terms ‘‘way in’’ and ‘‘way out’’ consideration, the ohmic value (and angle) manifested
refer to the trajectory of the ohmic value seen by the at the relay location must be known with respect to

Figure 14-20 Out-of-step trip logic used in MDAR 2.5.

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.


time to assure that proper recognition is possible. In separation of the two system segments that were out of
general, a system study is required for this. synchronism. Even when ‘‘natural tripping’’ occurs (the
Out-of-step blocking is less critical than OS tripping distance relays applied for other functions operate for
in terms of identification of the swing and security. OS the OS condition), OS sensing is required to block
blocking must respond only when the blocked device reclosing. Reclosing following a legitimate OS trip is
responds. Swings producing ohmic values beyond the futile and should not be attempted.
reach of, say, a supervised zone 2 phase-distance relay Blinders aid natural tripping by providing a screen-
need not be recognized by the OS detection scheme. ing effect against undesired tripping in response to
Also, a fault appearing on the R-X diagram between large power swings that are stable. This is particularly
the characteristics of an OS relay and a phase-distance useful in long-line applications that require large
relay that is used with it can falsely identify an OS impedance settings on distance relays, making them
condition with impunity, whereas OS tripping under more susceptible to tripping on load.
the same circumstances could not be tolerated. Out-of-step relaying is as much art as science,
Stated simply, (1) OS blocking should be applied requiring a realistic appraisal of what is possible, what
when swing-produced trips are possible but are intol- is probable, and what is certain. It may, in particular
erable, and (2) OS tripping should be applied when areas of a complex system, be less expensive to
tripping will not naturally occur and tripping must take universally apply out-of-step blocking rather than to
place for an optimum generation-load match following deduce where it is needed.

Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.

You might also like