Professional Documents
Culture Documents
System Stability and Out-of-Step Relaying: W. A. Elmore
System Stability and Out-of-Step Relaying: W. A. Elmore
2 STEADY-STATE STABILITY
3 TRANSIENT STABILITY
moves in phase position with respect to VU, the apparent fully cleared) appears to be a three-phase fault. The
impedance viewed by the relay (VR/IR) will change with location of this apparent fault is at the electrical center
time, producing a trajectory on an R-X (resistance- of the system. If this apparent impedance enters the
reactance) diagram such as that of Figure 14-6c. operating area of a distance relay, it will operate.
With the depressed voltage and large current, this If VR and VU are not supported at full value, their
swing condition (long after the fault has been success- ratio is influential in determining the locus on the R-X
Figure 14-7 Source angle relationship for swing trip on the Figure 14-8 Effect of OS swings on various line relaying
system of Figure 14-6. systems.
With the two system segments 1808 apart at the instant 5.6 Overcurrent Relays
of interruption, a theoretical undamped recovery
voltage of four times normal is possible. Figure 14-9 Figure 14-6 can be used to illustrate the conditions
describes this phenomenon with the breaker at the encountered by phase-overcurrent units during swings.
electrical center of the system. At current 0, where Assume, for example, that an instantaneous over-
interruption takes place, the voltage on each side of the current unit set for 2.5 times full load were used in a
breaker must settle at a new value. In the process of line connecting Vs and Vu, and that ZS þ ZL þ ZU
getting there, overshoot takes place as a result of the equals 0.765 per unit on the full-load base. During an
presence of inductance and distributed capacitance in OS condition, the instantaneous unit would operate
the system. Recovery voltage is the voltage across the because the current reaches at least 2.61 (2/0.765) times
breaker contacts following current interruption. full load when VU lags by 1808. Swings during stable
Figure 14-10 shows that this identical phenomenon conditions will also result in higher than normal
occurs even though the breaker is as far away from the currents, although currents will be considerably less
electrical center as possible. The extremely large than during an OS condition.
transient recovery voltage still appears. If the circuit
breaker has insufficient dielectric strength to withstand
this voltage, reignitions will continue until a more 5.7 Reclosing
favorable angle is reached. To interrupt at all, a
breaker must be capable of attempting interruption, When a fault persists after reclosing, the stability of the
possibly for several seconds, at each current 0. If the system will probably be jeopardized. On the other
breaker cannot perform such interruptions, tripping hand, system stability is greatly improved if the fault is
6 OUT-OF-STEP RELAYING
Figure 14-14 The single blinder scheme for out-of-step Figure 14-15 The two blinder scheme for out-of-step
detection. detection. (I ¼ inner blinder, O ¼ outer blinder.)
is recommended for short-to moderate-length lines. It For the single-blinder OS tripping scheme (Fig. 14-18),
should not be used on long lines, where the load might swings from the right to left cause B1 to operate, B2 to
operate the ZOS unit. operate, B1 to reset, and then B2 to reset. It is of no
consequence whether B1 is initially operated by load
and B2 does not subsequently reset.
9.1.2 KST (68) OS Tripping Scheme
Device 50 (SI-T relay) is sensitively set and operates
Figure 14-17 illustrates the KST scheme of OS at a current level above maximum zero power factor
tripping. After sensing an OS condition in the same interchange, line charging, or transformer-magnetizing
way as the KS relay, telephone relays T1 and T2 add current. The device operates when a swing begins and
two requirements: The 21-2 relay (for example, the prohibits load pickup trip.
KD-10 phase-distance relay) must operate for 100 Thus, AND 2 operates when B1 and 50 operate with
msec, and 21-2 resets 60 msec or more ahead of ZOS. B2 reset to identify the swing origin in the positive F
On a swing, ZOS operates first to energize OS. If 21-2 region. After 4 msec, the feedback circuit holds the
does not operate before 60 msec, OS operates. Then upper input AND 2. AND 4 has an output when the
when 21-2 operates, the AR relay, T1, is energized. If swing moves between B1 and B2 to operate both
both ZOS and 21-2 remain closed for 100 msec, T1 blinders. If AND 4 output persists for 20 msec and the
operates. As the swing moves out, 21-2 resets first, swing moves across B1 to reset it, AND 6 has an
deenergizes AR, and permits the energization of T2 output. An output from AR occurs 20 msec later for
through AR back contacts if ZOS is still closed. If ZOS tripping and reclose block.
does not reset for 60 msec, T2 operates to trip and Swings originating to the left of B1 traveling left to
block reclosure as shown. right produce identical action through AND 1, AND
A fault that operates ZOS and 21-2 together (or 3, and AND 5. The restricted trip feature prevents
within approximately 60 msec) will have no effect tripping on recoverable swings. B1 and B2 may be used
because the short around the OS coil will be to supervise the tripping of a phase-distance relay.