Professional Documents
Culture Documents
Transmission Lines
:STEADY-STATE OPERATION
L
Z0
(i) Mvar supplied=Mvar Absorbed=0 C
(Orange line in Voltage Profile, VS<VR, VR>0, PF<1 leading) Full Load Condition
(V) Beyond 900 MW is thermal limit of the line, Short Circuit Condition
can’t exceed beyond this point
VE
Note : I n terms of Generator quantities P sin VI cos In terms of load
X
High Voltage AC (HVAC) Transmission
220; 500 kV HVAC Transmission
Power Plant V 2
E1 X
Long Distance
Power Flow (P - Watts)
VE
E x V P sin(1 2 )
I X
X=XL-XC
Parallel
Compensation
Series Load-flow
compensation control
Real Power Output E V
x I
VE
• From P3 3 sin()
X
120 N(rpm )
By keeping rotor speed cons tan t ( N(rpm ) ), stator voltage frequency is kept cons tan t : f
Poles ( flux )
5.5 Maximum Power Flow [ Pmax ( = 900) ] P
V E
sin()
X
• The maximum power transfer is the real power output when the
V E
power angle is 90 degrees. P
max
X
VS- x VR0
I
Observe Current
Case3: Absorb Power as a Motor
direction
Case1 900>>0
Case 2 =00=1800=3600
VR VS VR2 VR
From : Q /
cos() / / VS cos() VR VRI sin
X X X
VS cos > VR
VS cos = VR
VS cos < VR
When the rotor of a synchronous generator is overexcited - given more DC excitation
(usually when the grid is lagging and in need of reactive power, i.e., inductive), it would
provide the needed reactive power to the grid. But when the rotor is underexcited - given
less DC excitation (usually when the grid is leading and has large reactive power, i.e.,
capacitive) it would absorb reactive power from the grid. In this way the reactive power is
controlled
By the increasing excitation current, the vector Ef and load current will change
When the field current is constant in the machine, Efvoltage is also constant.
Thus for the Adjustment of the active power, the torque angle should be changed.
To make bigger the angle 0 as big as ,10, the given torque to generator's shaft
should be increased and accelerated in a short time by opening the valve of the
water turbine or steam turbine
5.5 Maximum Power Flow
Transmission-line
load ability curve
for 60-Hz
overhead lines:
no series or
shunt
compensation
This value is about 4% less than that found in Example 5.4 (5974 MW), where
losses were neglected.
Example (Not in Book)
5.6 Line Loadability
In practice, power lines are not operated to deliver their
theoretical maximum power, which is based on rated terminal
voltages and an angular displacement = 90 across the line.
Figure 5.12 shows a practical line loadability curve plotted
below the theoretical steady-state stability limit. This curve is
based on the voltage-drop limit VR/VS0.95 and on a maximum
angular displacement of 30 to 350 across the line (or about 450
across the line and equivalent system reactances), in order to
maintain stability during transient disturbances. The curve is
valid for typical overhead 60-Hz lines with no compensation.
9000
9000 #500kV Lines 1 10.8 1 12
#345kV Lines 1 24.2 1 26 837
372 9000
#765kV Lines 1 4 .4 1 6
Increase Voltage Reduces lines from 26 to 6 2039
EXP 5.8 Effect of intermediate substations on number of lines for power transfer
Can five instead of six 765-kV lines transmit the required power
9000 MW, ZC=266 W, VS=1 pu, VR=0.95 pu, and =35o, 500 km
from the plant. If there are two intermediate substations that
divide each line into three 167-km line sections, and if only one
line section is out of service?
2l
2 500 X / Z C sin(l) ZC sin
X / ( 266) sin 156.35
5000 1 1 1 1 R
Req
R eq R R R 3
Combining series/parallel reactance's, X/ X/
/
X eq 2
35
the equivalent reactance of 5-lines with 3 4
1 2 / 1 X/
Xeq X 0.2167 X / 33.88
53 4 3
Long Distance
VS VR
P sin( 1 2 )
X
X
Parallel
Compensation
Series Load-flow
compensation control
Maximum power flow, discussed in Section 5.4 for lossless lines, is derived
here in terms of the ABCD parameters for lossy lines. The following notation is
used:
The complex
power
delivered to
the receiving
end is
The theoretical maximum real power delivered (or steady-state stability limit) occurs
when =Z
The second term in (5.5.6), and the fact that Z/ is larger than X/, reduce PRmax to a value
somewhat less than that given by for a lossless line.
EXAMPLE 5.5 Theoretical maximum power delivered: long line Determine the
theoretical maximum power, in MW that the line in Example 5.2 can deliver.
Assume VS = VR =765 kV.
This value is about 4% less than that found in Example 5.4 (5974 MW), where
losses were neglected.
END Transmission Lines