Boq Preparation considerations:

Module consideration:

Each switch will occupy one module place.


Each Regulator will occupy one module space.
Each socket will occupy one/two module space.anyway we dont have any
celling fans in this building.

Switches consideration:

for lighting switches - consider 6A module switches.


for lighting board sockets consider 16A Switches.

socket consideration:

At each room lighting board consider one 6/16A Socket with switch.

At each equipment testing socket - consider one socket and switch.

Industrial Grade socket :

for 3 phase sockets - 32A,125A COnsider for each room as follows

Room-1 1No - 32A, 1nO - 125A


Room-2 2Nos -32A 1nO - 125A
IGBT Centre 1No -125A 1nO 32A

Air condition :

at each Air condition: take one number MCB/switch and socket near to
Air condition level
Exhaust Fan:

cosnider exhaust fan for toilet rooms

Wire and conduits:

for tube lights and CFL Consider 1.5 sq.mm

for Air condition take 4.0 sq.mm

power cables

cosnider suitable for 32A,125A as per attached catalogue in mail,


consider 1.1KV,XLPE 4C Cables ,with proper de rating(check de rating
table at last in cable catalogue),
consider current rating in duct.

PVC Pipes :

1)consider dia of the pipe such that only 40% of area shall be fill.
2)for power cable conduit - which is run through at floor level
(marked in yellow colour in auto cad drawing)
3)for lighting & Air condition consider at light point level(around
2.7 mtrs height)(marked in blue colour in auto cad )

check the excel sheet made for quality control lab(attaching in mail)

for better under standing root please refer


Distribution Board Design:

Incomer : Consider MCCB, its Rating will be frrezed later


Out goings: 1) for testing sockets (32A,125A RCCB Feeders) consider
32A,125A 4P MCCB at distribution board level.
2) for Air conditioner loads for each two 2 nos of Air
conditioners ,take one DP MCB (Refer central lab SLD)
3) for Lighting loads

a) store room+ store cabin room - 1 DP MCB


b) IGBT centre + MSDS ROOM - 1DP MCB
c) Room-1 &2 -1 DP MCB
d) corridor + toilet - 1 DP MCB

FINAL OUTPUTS REQUIRMENT:

1)BOQ
2)LIGHTING LAYOUT (ONLY SHOWS THE PROVISION OF ALL
FIXTURES,ACs,sockets)
3)conduit layout at floor level rooting arrangment
4)conduit layout at fixture level rooting arrangment
5)Power distribution SLD

please use the layers option for each drawing (2,3,4 shall be in same
drawing but as per drawing requirment layers will be change)( please
refer central layout drawing as attached)