CAUSES OF FAILURE
ENVIRONMENTAL
SYSTEM
OPERATION
DESIGN
MANUFACTURE
MATERIALS
MAINTENANCE
TRANSFORMER PROTECTION
FAST TRANSIENTS
LOAD REJECTION
BACKFEEDING
SHORTCIRCUITS
TRANSFORMER PROTECTION
LOAD DUTY
OVERLOADING
SWITCHING OPERATIONS
OUT-OF-PHASE SYNCHRONISATION
TRANSFORMER PROTECTION
BASIC PROTECTION
DIFFERENTIAL
RESTRICTED EARTHFAULT
OVERFLUXING
DIFFERENTIAL PROTECTION
O 0A
O
0.1 A
9A 10 A
2000 A
O
1A
9A 10 A
2000 A
B B
O
1A
9A 0A
2000 A
B B
O
9A
MAGNETISING INRUSH
TRANSIENT CONDITION - OCCURS WHEN A
TRANSFORMER IS ENERGISED
INRUSH CURRENT
V
+ m
Im
STEADY STATE
- m
TRANSFORMER PROTECTION
INRUSH CURRENT
V
+ m
Im
STEADY STATE
- m
Im
2 m
SWITCH ON AT VOLTAGE
V ZERO - NO RESIDUAL FLUX
TRANSFORMER PROTECTION
MAGNETISING INRUSH
0.5 -- 1.0 8 TO 10
1.0 -- 10 10 TO 60
> 10 60 TO 600
TRANSFORMER PROTECTION
OVERFLUXING CONDITION
DIFFERENTIAL ELEMENT SHOULD BE
BLOCKED FOR TRANSIENT OVERFLUXING-+
ADJUSTABLE CHARACTERISTIC
CT RATIO COMPENSATION
DDT 12/32
BIAS 20,30,40%
TIME DELAYED
TRANSFORMER PROTECTION
DTH 31/32
UNBIASED HIGHSET
TRANSFORMER PROTECTION
0 10 20 30 40
FAULT CURRENT (XIn)
TRANSFORMER PROTECTION
2
INST. HIGHSET
ELEMENT
0 10 20 30 40
FAULT CURRENT (XIn)
TRANSFORMER PROTECTION
MBCH
A
1/3 Cycle minimum
B
C
TRANSFORMER PROTECTION
COMPARITIVE CHARACTERISTICS
(WITHOUT HIGHSET)
6
RELAY WITH HAR.
OPERATING TIME
RESTRAINT
4
(CYCLES)
2
MBCH
0 10 20 30 40
FAULT CURRENT (XIn)
TRANSFORMER PROTECTION
3
ROLE OF BIAS
2
Differential current (x In) Operate
= I1+ I2 + I3 + I 4
1
Restrain
Setting range
(0.1 - 0.5)
0 1 2 3 4
SATURATION DETECTOR
NO SATURATION
I1
I2
I 1 + I2
I1 - I2
I1 I2
TRANSFORMER PROTECTION
SATURATION DETECTOR
NO SATURATION SATURATION DUE
TO THRO’ FAULT
I1
I2
I 1 + I2
I1 - I2
I1 I2
TRANSFORMER PROTECTION
SATURATION DETECTOR
NO SATURATION SATURATION DUE INTERNAL FAULT
TO THRO’ FAULT
I1
I2
I 1 + I2
I1 - I2
I1 I2
TRANSFORMER PROTECTION
USE OF ICT
Dy1(-30 )
Interposing CT provides
Vector correction
Yd11(+30 ) Ratio correction
Zero sequence
compensation
R
R
R
TRANSFORMER PROTECTION
Yy0 Yd11
0 87 +30
Dy11 (+30 )
Yy0 Yd1
87
0 -30
TRANSFORMER PROTECTION
33kV : 11kV
200/1 IL = 175A 10 MVA I L = 525A 400/1
+VE SEQUENCE
CURRENTS
BALANCE
REQUIRE ZERO
SEQUENCE
CURRENT
TRAPS FOR A B C
STABILITY
TRANSFORMER PROTECTION
64
64
64
TRANSFORMER PROTECTION
REF CONNECTIONS
3 Phase 3 wire
TRANSFORMER PROTECTION
REF CONNECTIONS
3 Phase 3 wire
R
CAG14
TRANSFORMER PROTECTION
REF CONNECTIONS
3 Phase 3 wire Delta winding
R
CAG14
TRANSFORMER PROTECTION
REF CONNECTIONS
3 Phase 3 wire Delta winding
R
CAG14
3 Phase 4 wire
TRANSFORMER PROTECTION
REF CONNECTIONS
3 Phase 3 wire Delta winding
R
CAG14
P2 64
P1
P2
64
P1
P2 64
P1
R R R
TRANSFORMER PROTECTION
Low frequency
High voltage Ie
Geomagnetic disturbances
Effects
Tripping of differential element (Transient overfluxing)
Damage to transformers (Prolonged overfluxing)
TRANSFORMER PROTECTION
OVERFLUXING PROTECTION
V K
f
INFLUENCING FACTORS :
VECTOR CONFIGURATION
TYPE OF EARTHING
INFEED CONDITIONS
TRANSFORMER PROTECTION
~ LOAD
CAG 37 50 51
CDG 31
CDG 31 51
64
67 N VDG 14
CDD 21
TRANSFORMER PROTECTION
3 x 51
51N
CAG 17 50 50 CAG 17
CDD 21 67 67 CDD 21
67 N 67 N
CDD 21 CDD 21
OVERLOAD PROTECTION
51 51
64
ICT
51N
50N 50
87
TRANSFORMER PROTECTION
CT REQUIREMENTS
RELAY VK > IMAG <
CT REQUIREMENTS
RELAY VK > IMAG <
CT REQUIREMENTS
RELAY VK > IMAG <
CT REQUIREMENTS
RELAY VK > IMAG <
SETTING CRITERIA
BIASED DIFF.
CURRENT PICKUP IS SET JUST ABOVE THE STANDING
UNBALANCE CURRENT DUE TO OLTC, CT MISMATCH
AND ERRORS
R IF
WORLD LEADER
IN
PROTECTION
&