You are on page 1of 1

1 HOUR FIRE RATED WALL ASSEMBLY REFER TO

1 HOUR FIRE RATED WALL WALL TYPE FOR ADDITIONAL INFORMATION


1 HR FIRE RATED WALL ASSEMBLY
ASSEMBLY REFER TO WALL TYPE
REFER TO WALL TYPE
FOR ADDITIONAL INFORMATION PENETRANT TYPE A LISTED BELOW
2 A A A
FILL MATERIAL TO NOTE: SEAL THIS SIDE SMOKE TIGHT
BE FORCED INTO 1'-6" max
SECTION A-A ELEVATION

5"
ANNULUS TO

2 5/8"
REFER TO PLAN FOR WALL DIMENSIONS

max
1/4" TO 1/2" LARGER THAN OUTSIDE
PENETRANTS AS MAXIMUM EXTENT

6" MIN.
DIAMETER OF PENETRANT A
AS LISTED BELOW POSSIBLE METAL RUNNERS
METAL STUDS BEHIND GYPSUM BOARD
SEALANT TYPICAL
-
1 A BOTH ENDS

1"

1"
A A

VARIES
MAX ANULAR SPACE 3/4" NOTE: OVER 1" GAP REQUIRES
MIN ANULAR SPACE 1/4" FILL MATERIAL A MINIMUM 1/2" CROWN TO 48" MAX
SECTION A-A FORM AROUND PENETRATING ITEM AND SECTION A-A A BLOW-OUT PATCH
MIN 5/8" THICKNESS OF FILL

1"

1"
SECTION A-A LAPPING 1/4" BEYOND PERIPHERY MATERIAL APPLIED WITH THE
ANNULUS, FLUSH WITH BOTH PACK TIGHTLY WITH THERMAFIBER SAFING 2" + MAX.
SURFACES OF WALL A
ONE OR TWO LAYERS OF GYPSUM
PENETRANT TYPE BOARD AS REQUIRED FOR WALL RATING
1. PENETRANT TYPE (ONE OF THE FOLLOWING)

PRIMITIVO E. CONDE, RA ARCHITECT AR0014406 W W W . S D C O L L A B O R A T I V E . C O M


FL 33176
A A 2 6 0 0 3 9 0 2
A. MAX24" X 12" RECTANGULAR STEEL DUCT. W/ MIN 24 GAGE MAX AREA OF A. STEEL PIPE: NOMINAL 12" DIA OF SMALLER, SCHEDULED OR HEAVIER. 1. PENETRANT TYPE (ONE OR MORE, NOMINAL 1" DIA)
OPENING 325 SQ/IN W/ A MAX DIMENSION OF 25" B. CONDUIT: NOMINAL 6" DIA OR SMALLER, EMT OR STEEL CONDUIT. A. STEEL ELECTRIC TUBING MINIMUM 1/2" MAX 1" CONDUIT RIGIDLY
1. MIN. 5/8" DEPTH HILTI CP 601 S ELASTOMERIC FIRE STOP SEAL C. COPPER TUBING: NOMINAL 6" DIA OR SMALLER, TYPE L OR HEAVIER. SUPPORTED

11410 N. KENDAL DRIVE - UNIT 208 MIAMI,


2. FASTEN STEEL ANGLE L2"X 2"X 1/8" TO DUCT W/No 8 OR LARGER STEEL D. COPPER TUBING: NOMINAL 6" DIA OR SMALLER, REGULAR OS HEAVIER. ON BOTH SIDE OF WALL
SHEET METAL SCREWS. 2. FIRESTOP SYSTEM: HILTI CONSTRUCTION CHEMICALS INC: TYPE FS 605 OR 2. FIRESTOP SYSTEM: HILTI CONSTRUCTION CHEMICALS INC: TYPE FS
FS ONE SEALANT ONE SEALANT

P : 3 0 5 7 4 0 6 9 4 8
XHEZ - THROUGH-PENETRATION FIRE STOP SYSTEMS XHEZ - THROUGH-PENETRATION FIRE STOP SYSTEMS XHEZ - THROUGH-PENETRATION FIRE STOP SYSTEMS XHEZ - THROUGH-PENETRATION FIRE STOP SYSTEMS

1 Hr Fire Rating - UL Design No: W-L-2003 1Hr Fire Rating - UL Design No: W-L-1085 1 Hr Fire Rating - UL Design No: W-L-1095 2 Hr Fire Rating - Multi. Conduit / Pipe Penetrations-UL Design NO. W-L-1065
19 NTS
15 NTS
11 NTS
7 1 1/2" = 1' - 0"

1 HOUR FIRE RATED WALL 12" MAX DIA OF

DULCE M. CONDE, RA ARCHITECT AR0015803


ASSEMBLY REFER TO WALL STEEL COLLAR FABRICATED FROM FROM .016-IN. GALV. 1/2" MIN THICKNESS
APPLIED WITHIN ANNULUS OPENING. ANNULAR 1
TYPE FOR ADDITIONAL STEEL FILLED W/ NOM. .10-IN THK. WRAP STRIPS FACED ON
FLUSH WITH BOTH SIDES SPACE SHALL BE 0
INFORMATION ONE SIDE W/ ALUMINUM FOIL WRAPPED AROUND THE PIPE
OF WALL A AT THE POINT OF MAX. GAP 1/8" : NO TREATMENT OR SURFACE BEAD
MIN. 4-1/2" OF MORTAR A CONTACT TO A MAX OF USG ACOUSTICAL SEALANT
A APPLIED OF 1 1/4" OF ( NO TREATMENT REFERS TO NON-SMOKE WALLS 3 4
SEALANT TO ANNULAR SPACE OUTSIDE DIAMETER ONLY )
WITHIN ANNULUS FLUSH SEALANT AND PACKING
COMPLETELY FILL TO BE 1/2" PENETRANTS AS OF PENETRANT
WITH BOTH SIDES MATERIAL MIN 3" THK OF 4
ANNULAR SPACE MIN. TO 3/4" MAX. LISTED BELOW MAX. GAP 1/4" FILL WITH JOINT COMPOUND
OF WALL PCF MINERAL WOOL BATT
BETWEEN THE PIPE PENETRANTS AS FOR PIPES 4' SMALLER 2
AND GYPSUM BOARD MIN 3/4", MAX 1 1/4" LISTED BELOW MIN. 1/4" BEAD OF CAULK AT
A
ASSEMBLY INTERFACE CONC. SLAB
A 8" CMU ASSEMBLY 1 HOUR RATED REFER TO WALL CROSS - SECTION VIEW
AND STEEL COLLAR AND AT
INTERFACE OF STEEL SECTION A-A TYPES AND AND LIFE SAFETY PLANS FOR MAX. GAP 1/2" : FILL WITH USG ACOUSTICAL
PENETRANT TYPE A A ADDITIONAL INFORMATION
SECTION A-A LISTED BELOW COLLAR AND PIPE SEALANT REF. CEG 1-25-85 1. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR (MIN.
4-1/2" THICK) (2-HR. FIRE RATING).
ONE HOUR FIRE RATED PARTITIONS 2. CONCRETE WALL ASSEMBLY (2-HR. FIRE RATING). OWNERSHIP AND USE OF THESE
8" CMU ASSEMBLY OR 4-1/2" SLAB REFER TO WALL TYPES AND
A. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL (MIN. 8" THICK). DOCUMENTS & SPECIFICATIONS AS
SECTION A-A LIFE SAFETY PLANS FOR ADDITIONAL INFORMATION (MAX. INSTRUMENTS OF SERVICE ARE AND SHALL
B. ANY U.L. CLASSIFIED CONCRETE BLOCK WALL. REMAIN THE PROPERTY OF THE ARCHITECT
OPENING IS 8") WHETHER THE PROJECT THEY ARE MADE
1. PENETRANT TYPE (ONE OF THE FOLLOWING) 3. MINIMUM 4-3/8" THICKNESS MINERAL WOOL (MIN. 4 PCF DENSITY)
1. PENETRANT TYPE (ONE OF THE FOLLOWING) COMPRESSED 50 PERCENT.
FOR IS EXECUTED OR NOT. THEY SHALL
NOT BE USED BY THE OWNER OR OTHERS
A. NON METALLIC PIPE: POLY VINYL CHLORIDE (PVC), NOM 2" A. STEEL PIPE: NOMINAL 10" DIA OF SMALLER, SCHEDULED OR HEAVIER. ON OTHER PROJECTS OR FOR ADDITIONS
B. CONDUIT: NOMINAL 4" DIA OR SMALLER, EMT OR STEEL CONDUIT. 4. MINIMUM 1/8" (WET) THICKNESS HILTI CP 672 FIRESTOP SPRAY APPLIED TO THIS PROJECT BY OTHERS, EXCEPT BY
DIA OR SMALLER. WITHIN THE JOINT, FLUSH WITH EACH SURFACE OF WALL AND LAPPING A
C. COPPER TUBING: NOMINAL 4" DIA OR SMALLER, TYPE L OR HEAVIER. AGREEMENT IN WRITING AND WITH
B. NON METALLIC PIPE: (CPVC) PIPE, NOM 2" DIA OR SMALLER. 2. D. COPPER TUBING: NOMINAL 4" DIA OR SMALLER, REGULAR OR HEAVIER. MINIMUM 1/2" ONTO FLOOR AND WALL ON BOTH SIDES OF JOINT. APPROPRIATE COMPENSATION TO
THE ARCHITECT.
FIRESTOP SYSTEM: HILTI CONSTRUCTION CHEMICALS INC: PENETRANT TYPE (ONE OF THE FOLLOWING) A. NON-METALLIC PIPE: 6" DIA 2. FIRESTOP SYSTEM: HILTI CONSTRUCTION CHEMICALS INC:
TYPE FS 611A OR FS ONE SEALANT OR SMALLER, SCHEDULE 40 (PVC) TYPE FS 601/ FS 604/ FS ONE SEALANT
NOTE: MAXIMUM WIDTH OF JOINT = 2".

XHEZ - THROUGH-PENETRATION FIRE STOP SYSTEMS XHEZ - THROUGH-PENETRATION FIRE STOP SYSTEMS XHEZ - THROUGH-PENETRATION FIRE STOP SYSTEMS XHEZ - THROUGH-PENETRATION FIRE STOP SYSTEMS XHBN - JOINT SYSTEMS

COMMENTS
1 Hr Fire Rating - UL Design No: W-L-2098 2 Hr Fire Rating - UL Design No: C-AJ-2089 1 Hr Fire Rating - UL Design No: C-AJ-1149 UL Design NO. W-L-1087 UL System HW-D-0097 (Wall Head)
18 NTS
14 NTS
10 NTS
6 1 1/2" = 1' - 0"
3 1 1/2" = 1' - 0"

MIN 3 1/2" 1/2" MIN THICKNESS FILL


THICKNESS OF FILL MATERIAL APPLIED WITHIN

DATE
MATERIAL APPLIED ANNULUS FLUSH WITH TOP OF
WITHIN ANNULUS 2 A FLOOR OR BOTH SIDES OF A
FLUSH WITH BOTH A WALL REFER TO PLAN FOR WALL DIMENSIONS
SIDES OF WALL
PACKING MATERIAL MIN 3" GYPSUM BOARD ON METAL STUDS

REV NO.
THK OF 4 PCF MINERAL WOOL 1/4" MAX. PACK W/ DRYWALL COMPOUND
PENETRANTS AS 3 1/2" MAX BATT FOR PIPES 4' SMALLER REFER TO PLAN FOR WALL DIMENSIONS
METAL PIPE SLEEVE
LISTED BELOW DIAMETER OPENING PENETRANTS AS GYPSUM BOARD ON METAL STUDS
1 LISTED BELOW ANNULAR SPACE SHALL BE 0
1/4" MAX. PACK W/ DRYWALL COMPOUND
A AT THE POINT OF CONTACT TO
A A MAX OF 1 1/4" OF OUTSIDE PIPE METAL PIPE SLEEVE
8" CMU ASSEMBLY 1 HOUR RATED REFER TO MAX ANULAR SPACE 1 5/8"
MIN ANULAR SPACE 1/2" DIAMETER OF PENETRANT A FOAMGLASS PIPE INSULATION
WALL TYPES AND AND LIFE SAFETY PLANS PIPE
SECTION A-A FOR ADDITIONAL INFORMATION 8" CMU ASSEMBLY OR 4-1/2"
SECTION A-A PACK TIGHTLY WITH THERMAFIBER SAFING INSULATION
SECTION A-A SLAB REFER TO WALL TYPES 1" 1"
AND LIFE SAFETY PLANS FOR
ADDITIONAL INFORMATION ONE OR TWO LAYERS OF GYPSUM BOARD AS REQUIRED
FOR WALL RATING 1" 1" PACK TIGHTLY WITH THERMAFIBER SAFING INSULATION

5050 RESIDENCES
1. PENETRANT TYPE (WATER SANITARY RAIN WATER ONLY) ONE OR TWO LAYERS OF GYPSUM BOARD AS REQUIRED
1. PENETRANT TYPE (ONE OF THE FOLLOWING) A. AIR DUCT UP TO 4" X 6" FABRICATED ON No 28 MSG FOR WALL RATING
A. NON-METALLIC PIPE: 2" DIA OR SMALLER, SCHEDULE 40 (PVC) GALVANIZED SHEET METAL. PENETRANT TYPE (ONE OF THE FOLLOWING)

5050 NW 22nd Ave


(MIXED-USE)
OR (CPVC) CENTERED WITHIN OPENING. 2. 2 1/2" THERMA FIBER INSULATION A. STEEL PIPE: NOMINAL 10" DIA OF SMALLER, SCHEDULED OR HEAVIER.

PROJECT: PERMIT SET


3. 1" MIN DEEP FIRE CODE COMPOUND APPLY TO FILL GRAVITY B. CONDUIT: NOMINAL 4" DIA OR SMALLER, EMT OR STEEL CONDUIT.
2. FIRESTOP SYSTEM: HILTI CONSTRUCTION CHEMICALS INC: TYPE FLUSH WITH BOTH FACES OF WALL. C. COPPER TUBING: NOMINAL 4" DIA OR SMALLER, TYPE L OR HEAVIER.
FS 611A OR FS ONE SEALANT D. COPPER TUBING: NOMINAL 4" DIA OR SMALLER, REGULAR OR HEAVIER.

XHEZ - THROUGH-PENETRATION FIRE STOP SYSTEMS XHEZ - THROUGH-PENETRATION FIRE STOP SYSTEMS XHEZ - THROUGH-PENETRATION FIRE STOP SYSTEMS

2 Hr Fire Rating - UL Design No: C-AJ-2066 2 Hr Fire Rating - UL Design No: W-L-7002 2 Hr Fire Rating - UL Design No: C-AJ-1149 Non-Insulated Pipes Insulated Pipes
17 NTS
13 NTS
9 NTS
5 1 1/2" = 1' - 0"
2 1 1/2" = 1' - 0"
TYPE S SCREWS 6" O.C.
GENERAL NOTES JOINT AT SECOND LAYER

1. ALL THROUGH PENETRATIONS SHOWN ABOVE ARE BASED UPON SPECIFIC PRODUCTS CL OF STUDS
1/4" MAX. GAP AROUND
CAULK W/ 1/4" MIN. THK. FILL 3" MIN. 3" MIN.
AND MANUFACTURERS. FOR OTHER ACCEPTABLE MANUFACTURER'S REFER TO PROJECT PENETRATION
SPECIFICATIONS. MIN 3 1/2" THICKNESS OF MATERIAL APPLIED TO THE ANNULUS

3" 3"
A GYPSUM BOARD

3"
FILL MATERIAL APPLIED FLUSH WITH BOTH SIDES OF WALL
2. ALL ASSEMBLIES SHOWN ABOVE ARE REPRESENTATIVE ONLY FOR COMPLETE WITHIN ANNULUS FLUSH A JOINT ELECTRICAL BOXES
CONSTRUCTION REQUIREMENTS. REFER TO EACH ASSEMBLY NUMBER IN THE "UL" WITH BOTH SIDES OF WALL MIN. 1/2" WIDE .015 THK. CUT GWB. TO ALLOW 1/4" MIN OVERLAP OF FACE PLATE
OVER-SIZED HOLE IN

3" 3"
MANUAL, VOLUME 2, 1999 EDITION STEEL BANDING STRAPS
MIN. 4-1/2" BASIC PARTITION

3"
3. FOR OTHER APPLICABLE REQUIREMENTS REFER TO PROJECT SPECIFICATIONS. PENETRANTS MINERAL
3 1/2" MAX DIAMETER NOM. 1-1/2"-IN. THK. 5/8" TYPE "X" GYPSUM FLEXIBLE CONDUIT

AS NOTED
WOOL BATT

04-05-2021
OPENING AS LISTED 6 PFM CERAMIC

PROJECT NO.: 20-004-00


A BOARD LAMINATED TO

PEC/JCC
4. FOR FIRE RATED WALL ASSEMBLY TYPES BEARING UL LABEL REFER TO PARTITION BELOW INSULATION HOLES OVER 3" DIA.
BLANKET TOTALLY ONE STUD MIN. BETWEEN BOXES

DC/PEC
24" MIN.
TYPE S SCREWS WALL SURFACE HOLES UP TO 3" DIA.
TYPES. ENCAPSULATED
FLOOR OR WALL ASSEMBLY MIN. 4-1/2" MIN. 2 PER SECTION TYPICAL SECTION
WITHIN FOIL SCRIM SOUND RATED GYPSUM PARTITION WALL (SEE PARTITION TYPES
5. CONTRACTOR TO USE UL OR OTHER AGENCY APPROVED FIRE RESISTANT ASSEMBLY THICK A MIN. 6" O.C. METAL STUDS BEHIND
FACERS FOR EXACT CONSTRUCTION AND SIZES )
JOINT SYSTEM AS DETAILED. CONTRACTOR TO SUBMIT PRODUCT DATA SHEET FOR
SECTION A-A 8" CMU ASSEMBLY OR 4-1/2" SLAB REFER TO WALL NOTES:
SYSTEM TO BE USED, APPROVED MANUFACTURERS ARE HILTI (BASIS OF DESIGN), SOUND ATTENUATION INSULATION
TREMCO AND 3M . TYPES ON SHEET A-4.4 AND LIFE SAFETY PLANS 1. BUTTER BACK SIDE OF PATCH WITH JOINT COMPOUND

ISSUE DATE:
1. PENETRANT TYPE (ONE OF THE FOLLOWING) SECTION A-A A-1.3 AND A-1.4 (MAX. OPENING IS 3456 SQ. IN.) 2. LEAVE ALL SCREWS EXPOSED

DRAWN BY:
SEAL VOIDS FROM OUTSIDE AND COVER BOX W/ 1/3" MIN.

CHECKED:
A. NON-METALLIC PIPE: 2" DIA OR SMALLER, SCHEDULE 40 (PVC) 3. ONE OR TWO LAYERS OF GYPSUM BOARD AS REQUIRED FOR WALL RATING
ACOUSTICAL SEALANT (TYP.)
OR (CPVC) CENTERED WITHIN OPENING.

SCALE:
PENETRANT TYPE (ONE OF THE FOLLOWING)
2. FIRESTOP SYSTEM: HILTI CONSTRUCTION CHEMICALS INC: TYPE GENERAL NOTES:
A. STEEL AIR DUCT (MIN. 26 GA.) CARBON STEEL DUCT W/ A MAX
FS 611A OR FS ONE SEALANT 1. ALL THROUGH PENETRATIONS SHOWN ABOVE ARE BASED UPON SPECIFIC
PERIMETER DIMENSION OF 216 IN. AND A MAX DIMENSION OF 84 IN.
PRODUCTS AND MANUFACTURERS. FOR OTHER ACCEPTABLE MANUFACTURER'S REFER
TO PROJECT SPECIFICATIONS.
2. ALL ASSEMBLIES SHOWN ABOVE ARE REPRESENTATIVE ONLY FOR COMPLETE
CONSTRUCTION REQUIREMENTS. REFER TO EACH ASSEMBLY NUMBER IN THE "UL"
Fire Penetration
XHEZ - THROUGH-PENETRATION FIRE STOP SYSTEMS XHEZ - THROUGH-PENETRATION FIRE STOP SYSTEMS MANUAL,VOLUME 2, 1999 EDITION. Details

General Notes Patch Penetrations Elec. Box Back to Back Detail


16 12 8 4 1
NTS NTS NTS 1 1/2" = 1' - 0" 1 1/2" = 1' - 0"
A804