Report Ham Thuan Nam 10 Nos BP92 Vs Risen 445W (143 String 19)
Report Ham Thuan Nam 10 Nos BP92 Vs Risen 445W (143 String 19)
PVsyst TRIAL
Simulation variant :
Simulation parameters
Collector Plane Orientation
10 nos BP 92 vs Risen 445 (143 string 19)
Simulation date
System type
Tilt
24/09/20 11h48
PVsyst TRIAL
PV Arrays Characteristics (2 kinds of array defined)
PV module Si-mono Model RSM156-6-445M
Custom parameters definition Manufacturer Risen Energy Co., Ltd
Sub-array "Sub-array #1"
Number of PV modules In series 19 modules In parallel 98 strings
Total number of PV modules Nb. modules 1862 Unit Nom. Power 445 Wp
Array global power Nominal (STC) 829 kWp At operating cond. 737 kWp (55°C)
Array operating characteristics (50°C) U mpp 730 V I mpp 1010 A
Sub-array "Sub-array #2"
Number of PV modules In series 19 modules In parallel 45 strings
Total number of PV modules Nb. modules 855 Unit Nom. Power 445 Wp
Array global power Nominal (STC) 380 kWp At operating cond. 338 kWp (55°C)
Array operating characteristics (50°C) U mpp 730 V I mpp 464 A
PVsyst TRIAL
Total Arrays global power Nominal (STC) 1209 kWp Total 2717 modules
Module area 5894 m² Cell area 5341 m²
PVsyst TRIAL
PV Array loss factors
Thermal Loss factor Uc (const) 20.0 W/m²K Uv (wind) 0.0 W/m²K / m/s
Wiring Ohmic Loss Array#1 12 mOhm Loss Fraction 1.5 % at STC
Array#2 27 mOhm Loss Fraction 1.5 % at STC
Global Loss Fraction 1.5 % at STC
LID - Light Induced Degradation Loss Fraction 2.0 %
Module Quality Loss Loss Fraction -0.8 %
Module Mismatch Losses Loss Fraction 1.0 % at MPP
Strings Mismatch loss Loss Fraction 0.10 %
PVsyst Evaluation mode
PVSYST V6.88 24/09/20 Page 2/6
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL
PVsyst Evaluation mode
PVSYST V6.88 24/09/20 Page 3/6
PVsyst TRIAL
Inverter pack Nb. of units 10.0 Pnom total 920 kW ac
User's needs Unlimited load (grid)
Normalized productions (per installed kWp): Nominal power 1209 kWp Performance Ratio PR
7 1.0
Lc : Collection Loss (PV-array losses) 0.82 kWh/kWp/day PR : Performance Ratio (Yf / Yr) : 0.833
0.9
Ls : System Loss (inverter, ...) 0.1 kWh/kWp/day
6
Yf : Produced useful energy (inverter output) 4.58 kWh/kWp/day
0.8
[kWh/kWp/day]
5 0.7
Performance Ratio PR
PVsyst TRIAL
0.6
4
Energy
0.5
3
0.4
Normalized
2 0.3
0.2
1
0.1
0 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
0.835
0.830
0.823
0.821
May 179.6 81.51 29.20 169.5 167.4 173.6 170.1 0.830
June 168.5 73.82 28.29 155.7 153.4 160.6 157.3 0.836
July 176.6 75.58 27.86 164.1 161.6 169.3 165.9 0.836
August 172.3 80.78 27.27 165.9 163.7 171.4 167.9 0.837
September 148.6 85.04 26.61 148.6 146.6 154.5 151.4 0.843
October 154.1 76.06 26.78 162.3 160.5 167.5 164.0 0.836
November 148.6 65.45 25.91 163.5 161.8 169.3 165.7 0.838
Legends: GlobHor
DiffHor
T_Amb
135.9
1974.1
63.70
876.16
GlobEff
EArray
E_Grid
157.3
2062.9
154.0
2019.6
0.842
0.833
PVsyst TRIAL
Inverter pack Nb. of units 10.0 Pnom total 920 kW ac
User's needs Unlimited load (grid)
8000
Values from 01/01 to 31/12
7000
Energy injected into grid [kWh/day]
6000
5000
3000
2000
1000
0
0 2 4 6 8 10
Global incident in coll. plane [kWh/m².day]
PVsyst TRIAL
System Output Power Distribution
140000
Values from 01/01 to 31/12
120000
Energy injected into grid [kWh / Bin]
100000
80000
60000
20000
0
0 200 400 600 800 1000
Power injected into grid [kW]
PVsyst TRIAL
Inverter pack Nb. of units 10.0 Pnom total 920 kW ac
User's needs Unlimited load (grid)
+0.75%
-2.00%
Array nominal energy (at STC effic.)
-0.06% PV loss due to irradiance level
PVsyst TRIAL
0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage
0.00% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
-0.02% Night consumption
2020 MWh Available Energy at Inverter Output
2020 MWh Energy injected into grid
PVsyst TRIAL
PVsyst Evaluation mode
PVSYST V6.88 24/09/20 Page 6/6
PVsyst TRIAL
Inverter pack Nb. of units 10.0 Pnom total 920 kW ac
User's needs Unlimited load (grid)
The probability distribution variance is also depending on some system parameters uncertainties
PVsyst TRIAL
Specified Deviation PV module modelling/parameters 1.0 %
Inverter efficiency uncertainty 0.5 %
Soiling and mismatch uncertainties 1.0 %
Degradation uncertainty 1.0 %
Global variability (meteo + system) Variance 2.7 % (quadratic sum)
Probability distribution
PVsyst TRIAL
0.50
0.45
P50 = 2019631 kWh
0.40 E_Grid simul = 2019631 kWh
0.35
0.30
Probability
0.25
0.20
P90 = 1949900 kWh
0.15
0.05
PVsyst TRIAL
0.00
1850000 1900000 1950000 2000000 2050000 2100000 2150000 2200000
E_Grid system production kWh