ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.

rvt

DESIGN
DEVELOPMENT

DALLAS COUNTY ELECTIONS


BUILDING
1460 ROUND TABLE DR
DALLAS, TX 75247

04.30.2021
PROJECT NUMBER : 20182.200

TDLR #: xxxx

architecture interiors planning graphics


8070 Park Lane, Suite 300 Dallas, Texas 75231
4/30/2021 3:47:47 PM

Tel 972.701.9000 Fax 972.991.3008


www.bokapowell.com
plotted:
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
SHEET LIST SHEET LIST

DESIGN DEVELOPMENT - 04.30.2021

DESIGN DEVELOPMENT - 04.30.2021


GENERAL CONSTRUCTION NOTES
1. ALL CONSTRUCTION WORK SHALL BE DONE IN ACCORDANCE WITH ALL APPLICABLE SYMBOLS LEGEND
BUILDING CODES AND ORDINANCES OR AGENCIES HAVING JURISDICTION OVER
SIM
THIS PROJECT. 1 DRAWING NUMBER ON SHEET
A101
2. ALL BUILDING FACILITIES AND CONDITIONS, BOTH INTERIOR AND EXTERIOR, SHALL SHEET NUMBER
BE COMPLIANT WITH THE AMERICANS WITH DISABILITIES ACT (A.D.A.) FOR ALL ABBREVIATION INDEX
ALTERATIONS, TEXAS ACCESSIBILITY STANDARDS (T.A.S.), AND ALL FEDERAL, XX WALL TAG @ AT (THE RATE OF)
STATE, AND LOCAL CODES.
AFF ABOVE FINISHED FLOOR
X KEYNOTE CL CENTER LINE SHEET SHEET
3. ESTABLISH AND MAINTAIN PROJECT SAFETY DURING CONSTRUCTION TO PROTECT NUMBER SHEET NAME NUMBER SHEET NAME
CFMF COLD FORMED METAL FRAMING
PERSONNEL, TENANTS, AND BUILDING OCCUPANTS. REQUIREMENTS INCLUDE, BUT
X WINDOW TAG EQ EQUAL
SHALL NOT BE LIMITED TO O.S.H.A. PART 1926 LATEST EDITION. architecture interiors planning graphics
EWC ELECTRIC WATER COOLER GENERAL
4. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO ELEVATION HEIGHT CHANGE FD FLOOR DRAIN A0.00 COVER SHEET X ARCHITECTURE
FDC FIRE DEPARTMENT CONNECTION 8070 Park Lane, Ste. 300 Dallas, Texas 75231
COMMENCEMENT OF WORK. IF CONFLICT OCCURS, CONTACT THE ARCHITECT. A0.01A SHEET INDEX / GENERAL NOTES X A0.10 ALTERNATES X
X COLUMN GRID BUBBLE FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET A0.21 LIFE SAFETY PLAN X A1.01 SITE PLAN X Tel 972.701.9000 Fax 972.991.3008
5. CONTRACTOR SHALL FIELD VERIFY ALL MEASUREMENTS, LOCATIONS AND
CHARACTERISTICS OF ALL WORK AND EQUIPMENT (WHETHER SUPPLIED BY THE FF FINISHED FLOOR A0.31 TAS 2012 INFORMATION X A1.11 ENLARGED SITE PLANS X
Room name ROOM NAME
FHC FIRE HOSE CABINET
www.bokapowell.com
OWNER OR OTHERS) WITH THE SUPPLIER OR MANUFACTURER PRIOR TO THE 0000A A0.32 TAS 2012 INFORMATION X A1.12 ENLARGED SITE PLANS & DETAILS X
START OF RELATED WORK. ROOM NUMBER HVAC HEATING, VENTILATING & AIR CONDITIONING A0.36 CLEAR FLOOR SPACE X A2.01 OVERALL FLOOR PLAN X
ID INSIDE DIAMETER
A0.51 PARTITION TYPES X A2.01a ENLARGED FLOOR PLAN X
6. ANY VARIATIONS FROM INDICATED DIMENSIONS OR CONDITIONS SHALL BE J-BOX JUNCTION BOX These documents are issued for pricing only
BROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT. XX NEW DOOR & DOOR NUMBER MO MASONRY OPENING A0.52 PARTITION TYPES X A2.01b ENLARGED FLOOR PLAN - UTILITY/LOADING DOCK X and are not for regulatory approval,
N/A NOT APPLICABLE A0.71 FINISH SCHEDULE X A2.01c ENLARGED FLOOR PLAN - RESTROOM/ENTRY VESTIBULE X permitting or construction.
7. NO CHANGES TO BE MADE WITHOUT APPROVAL OF THE ARCHITECT. SIM NIC NOT IN CONTRACT A0.83 EXPANSION JOINT DETAILS - ROOF X A2.10a ENLARGED ELEC PLAN X
1
DETAIL A101 SHEET NUMBER NSMF NON STRUCTURAL METAL FRAMING A0.86 STANDARD BLOCKING/BACKING DETAILS X A2.21 ROOF PLAN X Arch: Donald R. Powell, Jr. Reg. No.: 7206
8. PARTITIONS ENDING AT WINDOW MULLIONS SHALL BE ATTACHED WITH DOUBLE SECTION NTS NOT TO SCALE Arch: Chris W. Barnes Reg. No.: 10147
FACE FOAM TAPE. DO NOT SCREW INTO MULLIONS OR PENETRATE IN ANYWAY. AT A0.87 GYPSUM DETAILS X A2.30 TOILET ACCESSORIES X
DRAWING NUMBER ON SHEET OC ON CENTER Arch: John E. Orfield Reg. No.: 11164
THESE CONDITIONS, CENTERLINE OF PARTITION AND CENTERLINE OF MULLION ARE A2.41 ENLARGED ROOF PLANS X Arch: R. Andrew Bennett Reg. No.: 18129
OD OUTSIDE DIAMETER
THE SAME UNLESS OTHERWISE NOTED. OH OPPOSITE HAND CIVIL A2.67 LUMINOUS EGRESS PATH MARKINGS X
SIM
BUILDING 1 DRAWING NUMBER ON SHEET R RADIUS C04.01 DEMOLITION PLAN X A3.01 DOOR TYPES, FRAME TYPES & SCHEDULE NOTES X
9. UNDER NO CIRCUMSTANCE SHALL ANY MEASUREMENT BE SCALED FROM THE SECTION A101 RD/OD ROOF DRAIN/OVERFLOW DRAIN C05.01 DIMENSIONAL CONTROL PLAN X A4.01 EXTERIOR ELEVATIONS X
DRAWINGS WITHOUT APPROVAL OF THE ARCHITECT PRIOR TO PROCEEDING WITH SHEET NUMBER REF REFER TO REFERENCE
WORK. C06.01 PAVING PLAN X A5.11 WALL SECTIONS X
RO ROUGH OPENING client
C06.50 PAVING DETAILS X A6.01 REFLECTED CEILING PLAN X
SCBA FS SELF-CONTAINED BREATHING APPARATUS FILL STATION DALLAS COUNTY
10. PROVIDE BRACING, BLOCKING AND/OR STRUCTURE AS REQUIRED TO FACILITATE SIM C07.01 GRADING PLAN X A6.02 ENLARGED REFLECTED CEILING PLAN X
WALL 1 DRAWING NUMBER ON SHEET SF SQUARE FOOT 1460 ROUND TABLE DR
INSTALLATION OF ALL WALL AND MILLWORK MOUNTED EQUIPMENT, IN NEW AND C08.01 EXISTING DRAINAGE AREA MAP X A6.21 ENLARGED REFLECTED CEILING PLANS - VESTIBULE X
EXISTING WALLS. CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE SECTION A101 SIM SIMILAR
SHEET NUMBER SP STANDPIPE C08.02 PROPOSED DRAINAGE AREA MAP X A7.00 OVERALL FINISH PLAN X DALLAS, TX 75247
SUPPORT REQUIRED TO MAINTAIN THE INTEGRITY OF THE WALLS AND THE
SECURITY OF THE EQUIPMENT. SPC STANDPIPE CABINET C09.01 STORM SEWER PLAN X A7.02 ENLARGED FINISH PLAN X 214-653-6437
STC SOUND TRANSMISSION CLASS C11.01 EROSION CONTROL PLAN X A7.31 INTERIOR ELEVATIONS X
11. ALL WOOD BLOCKING SHALL BE FIRE RETARDANT TREATED. PROVIDE WOOD INTERIOR SHEET NUMBER TYP TYPICAL
C11.50 EROSION CONTROL DETAILS X A7.32 INTERIOR ELEVATIONS X project manager
XX/AX.X UL UNDERWRITERS LABORATORIES
BLOCKING IN ALL STUD WALLS AT MILLWORK, AND SPECIAL ITEM ANCHORING ELEVATION PRITCHARD ASSOCIATES
DRAWING NUMBER ON SHEET UNO UNLESS NOTED OTHERWISE C12.01 SIGNAGE AND STRIPING PLAN X A7.33 INTERIOR ELEVATIONS - RESTROOMS X
POINTS. WOOD BLOCKING SHALL BE MOISTURE TREATED IF LOCATED IN DAMP
LOCATIONS OR ADJACENT TO CONCRETE OR MASONRY CONSTRUCTION. IF WOOD VIF VERIFY IN FIELD A9.21 STANDARD PARKING DETAILS X 2121 NORTH AKARD ST, SUITE 100
BLOCKING IS NOT PERMITTED BY CODE, THEN METAL STRIPS SHALL BE USED. WC WATER CLOSET LANDSCAPE DALLAS, TX 75201
WH WATER HEATER L0.01 SPIL RESOURCE PLAN X PLUMBING 214-849-0011
EXTERIOR SHEET NUMBER
12. CONTRACTOR TO BE RESPONSIBLE FOR FIELD DIMENSIONS OF ALL MILLWORK, XX/AX.X
ELEVATION L1.00 TREE MITIGATION PLAN X P0.01 PLUMBING NOTES & SYMBOLS X
GLASS, DOOR OPENINGS AND OTHER STRUCTURES PRIOR TO COMMENCEMENT OF DRAWING NUMBER ON SHEET
FABRICATION. L2.00 PLANTING PLAN X P0.02 PLUMBING FIXTURE SCHEDULE X project manager
BUILDING CODE SUMMARY L2.01 PLANTING DETAILS X P2.00 UNDERFLOOR PLUMBING PLAN X JPC CONSULTING
13. ALL WORK SHALL CONFORM IN QUALITY TO ACCEPTED INDUSTRY STANDARDS. ALL L3.00 IRRIGATION PLAN X P2.01 LEVEL 01 PLUMBING PLAN X 2627 MARTIN LUTHER KING JR. BLVD.
MILLWORK SHALL CONFORM TO A.W.I. PREMIUM GRADE STANDARDS, UNLESS DRAWING VIEW NUMBER
APPLICABLE CODES: L3.01 IRRIGATION DETAILS X P3.01 PLUMBING ENLARGED PLAN X DALLAS, TX 75215
OTHERWISE NOTED. 2015 INTERNATIONAL FIRE CODE, INCLUDING APPENDIX J, WITH DALLAS AMENDMENTS P3.02 PLUMBING ENLARGED PLAN X 214-941-4297
14. THE MATERIALS USED FOR CONSTRUCTION OF SPACE SHALL NOT CONTAIN
ASBESTOS, P.C.B OR ANY OTHER HAZARDOUS MATERIALS OF ANY TYPE. 00 XXXXX
SCALE: X/X" = 1'-0"
VIEW TITLE 2015 INTERNATIONAL BUILDING CODE WITH DALLAS AMENDMENTS
2015 INTERNATIONAL PLUMBING CODE WITH DALLAS AMENDMENTS
2015 INTERNATIONAL MECHANICAL CODE WITH DALLAS AMENDMENTS
2017 NATIONAL ELECTRICAL CODE WITH DALLAS AMENDMENTS
ARCHITECTURAL DEMOLITION
AD1.01
AD2.01
DEMOLITION SITE PLAN
DEMOLITION PLAN - LEVEL 1
X
X
P5.01
P5.02
PLUMBING DETAILS - GENERAL
PLUMBING DETAILS - GENERAL
X
X m.e.p. engineer
15. MANUFACTURER'S NAME, TRADEMARK, LOGOS, ETC. SHALL NOT BE PROMINENTLY PURDY-MCGUIRE, INC.
2003 INTERNATIONAL EXISTING BUILDING CODE WITH DALLAS AMENDMENTS AD2.21 DEMOLITION ROOF PLAN X MECHANICAL
VISIBLE TO THE PUBLIC. INTERMEDIATE LANDING LANDING HEIGHT CHANGE - ARCH. ELEV. 2015 INTERNATIONAL ENERGY CONSERVATION CODE WITH DALLAS AMENDMENTS 17300 N. DALLAS PARKWAY, SUITE 3000
AD4.01 DEMOLITION ELEVATIONS X M0.01 MECHANICAL NOTES & SYMBOLS X
2015 INTERNATIONAL FUEL & GAS CODE WITH DALLAS AMENDMENTS DALLAS, TX 75248
16. ALL WALLS TO BE LAID OUT AT 90 DEGREE ANGLES, UNLESS OTHERWISE NOTED. M2.01 LEVEL 01 MECHANICAL PLAN X
2015 INTERNATIONAL GREEN CONSTRUCTION CODE WITH DALLAS AMENDMENTS 972-239-5357
SLOPE M3.01 MECHANICAL ENLARGED PLAN X
17. SCOPE OF WORK OF ALL TRADES IS TO INCLUDE ALL MATERIALS AND LABOR AS SLOPE DIRECTION (DOWN)
X" PER FT OCCUPANCY CLASSIFICATION: M3.02 MECHANICAL ENLARGED PLAN X
REQUIRED TO TOTALLY COMPLETE THE PROJECT AND BE FUNCTIONALLY MIXED USE / NON SEPARATED PER IBC 508.3
civil
CONSISTENT WITH THE DESIGN INTENT AS EXPRESSED IN THE ATTACHED M5.01 MECHANICAL DETAILS X
DOCUMENTS. M5.02 MECHANICAL DETAILS X PACHECO KOCH
DRAWING NUMBER ON SHEET BUILDING HEIGHT & STORIES: 7557 RAMBLER RD. #1400
1 STORY / 20' M6.01 MECHANICAL SCHEDULES X
18. THERMOSTATS SHALL NOT BE LOCATED IN THE CENTER OF A WALL, ON AN DALLAS, TX 75234
ACCENT/SPECIALTY WALL OR IN A LOCATION WHICH CONFLICTS WITH SHEET NUMBER
CONSTRUCTION TYPE: ELECTRICAL 972.235.3031
FURNISHINGS WITHOUT THE APPROVAL OF THE ARCHITECT. XX/XX.XX
TYPE II - B E0.01 ELECTRICAL NOTES & SYMBOLS X landscape
E2.01 LEVEL 01 ELECTRICAL PLAN X
E3.01 LEVEL 01 LIGHTING PLAN X
PACHECO KOCH
PROJECT LOCATION: E4.01 ELECTRICAL ENLARGED PLAN X
7557 RAMBLER RD. #1400
E4.02 ELECTRICAL ENLARGED PLAN X DALLAS, TX 75234
HA

972.235.3031
RR

E5.01 ELECTRICAL ONE-LINE DIAGRAM X


Y

E6.01 ELECTRICAL DETAILS X structural engineer


HI
NE

E6.02 ELECTRICAL DETAILS X


EJES INCORPORATED
S
BL

12801 N. CENTRAL EXPY, SUITE 700


VD

MEP
.

DALLAS, TX 75243
KI

MEP1.01 MEP SITE PLAN X


NG

214.3431210
.
DR

JA

MEP2.01 ROOF LEVEL MEP PLAN X


E

ME
BL

security, audio/visual
S
TA

DR

TECHNOLOGY
STEM
D

NOVOM GROUP
.
UN

T0.00 TECHNOLOGY SYMBOLS & LEGENDS X


RO

400 S. RECORD ST, SUITE 1200


OW T0.01 TECHNOLOGY SITE PLAN - BLDG.1460 X
MON

L R DALLAS, TX 75202
T0.02 TECHNOLOGY SITE PLAN - BLDG.1520 X
GA
S FW

R E T1.01 TECHNOLOGY OVERALL FLOOR PLAN X 214-882-1540


T1.02 TECHNOLOGY ENLARGED FLOOR PLAN X
Y. - I

project
JO T2.00 IDF ROOM LAYOUTS AND RACK ELEVATIONS X
H 35

HN T3.00 AUDIO-VISUAL WALL ELEVATIONS X


DALLAS COUNTY ELECTIONS BUILDING
W
.C T4.00 TECHNOLOGY RISER DIAGRAM X 1460 ROUND TABLE DR
AR DALLAS, TX 75247
PE T5.00 SECURITY DOOR DETAILS X
NT MOCKINGBIRD LN The drawings and written material herein constitute original work of the
ER T5.01 SECURITY DOOR DETAILS X
architect, and as intellectual property and instruments of service, are
FW T5.02 SECURITY CAMERA MOUNTING DETAILS X
Y. subject to copyright and may not be reproduced, distributed, published
T5.03 TECHNOLOGY WIFI MOUNTING DETAILS X or used in any way without the express written consent of the architect.
TRUE
NORTH original issue

DESIGN DEVELOPMENT 04.30.2021


revisions
LOCATION MAP
SCALE: N.T.S

title

SHEET INDEX / GENERAL


NOTES
4/30/2021 3:48:05 PM

project number 20182.200

date 04.30.2021
sheet

A0.01A
plotted:
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt

ALTERNATES
A1. BASE BID - EXISTING EXTERIOR BRICK TO REMAIN AS IS. POWER WASH AND CLEAN ALL EXTERIOR BRICK AND COPING MATERIALS.

ALTERNATE 1.1 - PAINT ALL EXTERIOR BRICK WITH ELASTOMERIC PAINT. COLOR TBD.

A2. BASE BID - PRIOVIDE PLASTIC SPEED BUMPS

ALTERNATE 2.1 - PROVIDE CONCRETE SPEED BUMPS INSTEAD OF PLASTIC SPEED BUMPS.

A3. BASE BID - NO CONNECTION TO BE MADE BETWEEN BUILDINGS.

ALTERNATE 3.1 - PROVIDE (2) 4" CONDUITS TO THE ADJACENT BUILDING 1520 ROUND TABLE DR. REFER TO TECHNOLOGY DRAWINGS FOR DETAILS

A4. BASE BID - EXISTING FLAG POLES TO REMAIN AS IS architecture interiors planning graphics
ALTERNATE 4.1 - REPLACE THE EXISTING FLAG POLE WITH NEW SPECIFICATION 8070 Park Lane, Ste. 300 Dallas, Texas 75231
ALTERNATE 4.2 - ADD AN ADDITIONAL NEW FLAG POLE (TOTAL QTY OF 2 FLAG POLES) Tel 972.701.9000 Fax 972.991.3008
A5. BASE BID - NO SCREENING OR CAGES PROVIDED AS NEW FOR ANY ROOF EQUIPMENT. www.bokapowell.com
ALTERNATE 5.1 - PROVIDE A CAGE AROUND EACH NEW ROOF TOP UNIT
These documents are issued for pricing only
A6. BASE BID - PROVIDE HORIZONTAL BLINDS, REF SPECS and are not for regulatory approval,
permitting or construction.
ALTERNATE 6.1 - REMOVE HORIZONTAL BLINDS FROM SCOPE, NO WINDOW SHADES PROVIDED
Arch: R. Andrew Bennett Reg. No.: 18129
A7. BASE BID - WAREHOUSE FLOOR TO REMAIN AS IS

ALTERNATE 7.1 - REPAIR AND FLOAT WAREHOUSE FLOOR AS REQUIRED, SEE ALLOWANCES

ALTERNATE 7.2 - SEAL WAREHOUSE CONCRETE FLOOR

A8. BASE BID - PROVIDE SECURITY FILM TO INTERIOR SIDE OF EXTERIOR GLASS SECURITY FILM TO BE LOCATED ON INTERIOR SIDE OF ALL EXTERIOR
GLASS ON LEVEL 1 & 2, INDICATED AS FL-1
owner
ALTERNATE 8.1 - REMOVE GLASS SECURITY FILM FROM SCOPE DALLAS COUNTY
600 COMMERCE, 9TH FLOOR
A9. BASE BID - PROVIDE NEW LIGHTING PROTECTION, REFER TO MEP DRAWINGS
DALLAS, TX 75202
ALTERNATE 9.1 - NO NEW LIGHTING PROTECTION REQUIRED. 214-653-6437

A10. BASE BID - WAREHOUSE WALL FINISHES TO REMAIN AS IS owner representative


PRITCHARD ASSOCIATES
ALTERNATE 10.1 - WAREHOUSE WALLS TO BE PAINTED, P-1
2121 NORTH AKARD STREET, SUITE 100
A11. BASE BID - PROVIDE GLASS MARKER BOARDS AS NOTED IN PLANS, MB-1 DALLAS, TEXAS 75201-2223
214-849-0011
ALTERNATE 11.1 - NO GLASS MARKER BOARD REQUIRED
m.e.p. engineer
A12. BASE BID - PROVIDE A PANIC BUTTON AT RECPETION 109
PURDY-MCGUIRE, INC.
ALTERNATE 12.1 - NO PANIC BUTTON REQUIRED 17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
A13. BASE BID - PROVIDE AED CABINETS AS NOTED IN PLANS
972-239-5357
ALTERNATE 13.1 - NO AED CABINETS REQUIRED
security, audio/visual
A14. BASE BID - OPEN OFFICE 118, OFFICE 119 AND CONFERENCE 120 FLOORING FINISH TO BE SEALED CONCRETE, SC-1 NOVOM GROUP
ALTERNATE 14.1 - FLOOR FINISH TO BE CPT-1 400 S. RECORD STREET, SUITE 1200
DALLAS, TX 75202
A15. BASE BID - WAITING ROOM 100, PRE-FUNCTION 110 AND BREAKROOM 104 FLOORING FINISH TO BE TERRAZZO TZ-1 214-882-1540
ALTERNATE 15.1 - FLOOR FINISH TO BE PORCELAIN TILE, PROVIDE A 8$/SF ALLOWANCE FOR MATERIAL COST ONLY
civil
ALTERNATE 15.2 - FLOOR FINISH TO BE LVT-1 PACHECO KOCH
7557 RAMBLER RD, SUITE 1400
A16. BASE BID - PROVIDE UV LIGHTING IN HVAC SYSTEM, REFER TO MEP DRAWINGS DALLAS, TX, 75231
ALTERNATE 16.1 - NO UV LIGHTING REQUIRED 972-235-3031

A17. BASE BID - PROVIDE INSULATION IN PARTITION TYPE AS NOTED IN PLANS structural engineer
L.A. FUESS PARTNERS
ALTERNATE 17.1 - NO INSULATION IN PARTITION
3333 LEE PARKWAY, SUITE 300
A18. BASE BID - PROVIDE 2" OF INSULATION ABOVE CEILING AS NOTED IN PLANS DALLAS, TX, 75219
214-871-7010
ALTERNATE 18.1 - NO INSULATION REQUIRED

A19. BASE BID - PROVIDE GLASS MARKER BOARDS AS NOTED IN PLANS, MB-1

ALTERNATE 19.1 - NO GLASS MARKER BOARD REQUIRED

A20. BASE BID - EXISTING STRUCTURE AND UNDERSIDE OF ROOF OF THE WAREHOUSE TO REMAIN AS IS.

ALTERNATE 20.1 - PAINT ALL OPEN TO STRUCTURE CEILING P-1, INCLUDING BUT NOT LIMITED TO STRUCTURE, DECK AND ANY EXISTING PLUMING
OR MECHANICAL EQUIPMENT
project
DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
DALLAS, TX 75247
ALLOWANCES
The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are
1. CONCRETE FLOOR PREP FOR WAREHOUSE - PROVIDE A $25,000 FOR CONCRETE FLOOR PREP IN
subject to copyright and may not be reproduced, distributed, published
THE WAREHOUSE AREA or used in any way without the express written consent of the architect.

2. EXTERIOR SECURITY LIGHTING - PROVIDE A $25,000 FOR ADDITIONAL EXTERIOR SITE LIGHTING original issue
NOT YET IDENTIFIED ON PLANS DESIGN DEVELOPMENT 04.30.2021

revisions

UNIT COSTS
1. FLOOR CORES/FLOOR OUTLETS - PROVIDE A UNIT COST FOR EACH FLOOR CORE AND FLOOR BOX

2. WALL OUTLETS AND DATA DROPS- PROVIDE A UNIT COST FOR EACH WALL OUTLET OR DATA DROP

3. BOLLARDS- PROVIDE A UNIT COST FOR EACH BOLLARD PROVIDED

title

ALTERNATES
4/30/2021 3:52:15 PM

project number 20182.200

date XX/XX/20XX
sheet

A0.10
plotted:
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
TRAVEL DISTANCES - LEVEL 1 LIFE SAFETY LEGEND
PATH NAME PATH SEGMENT LENGTH
FIRE RESISTANCE RATED CONSTRUCTION
CPT 1 96'-1"
MTD 1 124'-6" 1 HR FIRE PROTECTION
MTD 2 185'-9"
2 HR FIRE PROTECTION
MTD 3 364'-10"
EXIT DOOR 125C EXIT DOOR 125B 2 HR SHAFT ENCLOSURE

DOOR EXIT CAPACITY DOOR EXIT CAPACITY MEANS OF EGRESS


CLEAR WIDTH: = 80.5" CLEAR WIDTH: = 68.5" EXIT
CAPACITY: = 536 OCC EXIT CAPACITY: = 456 OCC EXIT
OCCUPANT LOAD SERVED: = 237 OCC OCCUPANT LOAD SERVED: = 202 OCC REQUIRED EXIT
architecture interiors planning graphics
EXIT
8070 Park Lane, Ste. 300 Dallas, Texas 75231
FE
ACCESS EXIT
MDF DMARC ELECTRICAL WATER FACILITIES OFFICE Tel 972.701.9000 Fax 972.991.3008
470 SF 395 SF 817 SF 530 SF 828 SF
HZ www.bokapowell.com
FE FE FE FE HORIZONTAL EXIT
FE
MTD These documents are issued for pricing only
MAXIMUM EGRESS TRAVEL DISTANCE (MTD)
and are not for regulatory approval,
permitting or construction.
CPT
COMMON PATH OF TRAVEL (CPT)
Arch: Donald R. Powell, Jr. Reg. No.: 7206
Arch: Chris W. Barnes Reg. No.: 10147
DD Arch: John E. Orfield Reg. No.: 11164
DIAGONAL DISTANCE (DD) Arch: R. Andrew Bennett Reg. No.: 18129

FE ES
EXIT SEPARATION (ES)
FE FE FE
client
FIRE PROTECTION SYSTEMS
DALLAS COUNTY
SP 1460 ROUND TABLE DR
STANDPIPE CONNECTION
DALLAS, TX 75247
SPC 214-653-6437
STANDPIPE CABINET
MTD 3 project manager
FEC
FIRE EXTINGUISHER IN CABINET
PRITCHARD ASSOCIATES
FE 2121 NORTH AKARD ST, SUITE 100
FE DALLAS, TX 75201
FE
FIRE EXTINGUISHER MOUNTED ON WALL 214-849-0011

project manager
SCBA FS
SELF-CONTAINED BREATHING APPARATUS JPC CONSULTING
FILL STATION 2627 MARTIN LUTHER KING JR. BLVD.
DALLAS, TX 75215
OCCUPANCIES 214-941-4297

m.e.p. engineer
ASSEMBLY
FE FE PURDY-MCGUIRE, INC.
RESTROOMS 17300 N. DALLAS PARKWAY, SUITE 3000
FE FE
1,020 SF
FE DALLAS, TX 75248
BUSINESS
ELECTRICAL 972-239-5357

)
0"
145 SF

1
AED

2'-
15
civil

)=
" STORAGE

/3
0'-
9 PACHECO KOCH

(1
8 IDF

S
3 7557 RAMBLER RD. #1400

.E
= 148 SF

IN
ES EXIT DOOR 104A DALLAS, TX 75234
(M
6" 972.235.3031
8'-
45

FE DOOR EXIT CAPACITY


=

landscape
DD

LOADING DOCK OFFICE CLEAR WIDTH: = 68.5"


BREAK ROOM PACHECO KOCH
520 SF CAPACITY: = 456 OCC
FE 2,820 SF
WAREHOUSE
OCCUPANT LOAD SERVED: = 202 OCC 7557 RAMBLER RD. #1400
74,439 SF DALLAS, TX 75234
972.235.3031
EXIT structural engineer

DD
59'-
3" LIFE SAFETY DATA - LEVEL 1

=8
= EJES INCORPORATED
ES

OCCUPANCY LOAD FACTOR


5' -

COMMON PATH OF TRAVEL


MINIMUM REQUIRED EXITS
12801 N. CENTRAL EXPY, SUITE 700

8"

MINIMUM EGRESS WIDTH


(M

MAX TRAVEL DISTANCE


DALLAS, TX 75243

IN
FE

.E
FE 214.3431210

OCCUPANCY LOAD
OCCUPANCY TYPE
S(
FE

1/ 3
security, audio/visual

)=

SPRINKLER
28
NOVOM GROUP

'-7
")
400 S. RECORD ST, SUITE 1200

NAME

AREA
AED EARLY VOTING BOOTH TRAINING OFFICE
E-BOOK LAB DS200 LAB
LAB
STORAGE DALLAS, TX 75202
158 SF
1,027 SF 1,023 SF 681 SF FEC 214-882-1540
1,016 SF
DD

")

A-3
'-6

EXIT project
=4

15

4")
BREAK ROOM 2,820 SF ASSEMBLY 50 57 Yes 2 8.55 250 75
7'-

5'-
)=

DALLAS COUNTY ELECTIONS BUILDING


1

=1

CIRCULATION 2,754 SF ASSEMBLY 50 56 Yes 2 8.4 250 75


3
" (M

(1/

FE 1460 ROUND TABLE DR


3)

CHECK-IN 198 SF ASSEMBLY (UNCONCENTRATED) 15 14 Yes 1 2.1 250 75


ES
I N.

(1/

POLLING AREA DS200 LAB 1,023 SF ASSEMBLY (UNCONCENTRATED) 15 69 Yes 2 10.35 250 75 DALLAS, TX 75247
IN.
ES

ES

2,956 SF
CPT 1

(M

E-BOOK LAB 1,027 SF ASSEMBLY (UNCONCENTRATED) 15 69 Yes 2 10.35 250 75


(1/

The drawings and written material herein constitute original work of the
IN.

DD
6"
3)

architect, and as intellectual property and instruments of service, are


" (M

=
EARLY VOTING BOOTH LAB 1,016 SF ASSEMBLY (UNCONCENTRATED) 15 68 Yes 2 10.2 250 75
'-

CIRCULATION
EXIT DOOR 125A
=

46

76
subject to copyright and may not be reproduced, distributed, published
15

'-11

'-3
1,188 SF POLLING AREA 2,956 SF ASSEMBLY (UNCONCENTRATED) 15 198 Yes 2 29.7 250 75
=

or used in any way without the express written consent of the architect.
'-8

"(
DD

45

MI
RESTROOMS 1,020 SF ASSEMBLY (UNCONCENTRATED) 15 69 Yes 2 10.35 250 75
")

ES = 18'- OPEN OFFICES original issue


7"

N.
=

DOOR EXIT CAPACITY ES = 20'-11" ES = 20'-11"


864 SF
DD

TRAINING ROOMS 3,345 SF ASSEMBLY (UNCONCENTRATED) 15 224 Yes 2 33.6 250 75

ES
CLEAR WIDTH: = 68.5" DESIGN DEVELOPMENT 04.30.2021

(1
WAITING AREA 1,823 SF ASSEMBLY (UNCONCENTRATED) 15 122 Yes 2 18.3 250 75

/3
CAPACITY: = 456 OCC

)=
17,982 SF 946 141.9 revisions

25
OCCUPANT LOAD SERVED: = 202 OCC CIRCULATION

'-5
2,754 SF FEC B

")
FE FEC CIRCULATION 1,188 SF BUSINESS 100 12 Yes 1 1.8 300 100
ES = 32'-7" DMARC 395 SF BUSINESS 100 4 Yes 1 0.6 300 100
OFFICE ES = 65'-11" ELECTRICAL 817 SF BUSINESS 100 9 Yes 1 1.35 300 100
4,173 SF FACILITIES OFFICE 828 SF BUSINESS 100 9 Yes 1 1.35 300 100
MTD 1

CHECK-IN WAITING AREA FIRE RISER ROOM 117 SF BUSINESS 100 2 Yes 1 0.3 300 100
198 SF 1,823 SF LOADING DOCK OFFICE 520 SF BUSINESS 100 6 Yes 1 0.9 300 100
") FIRE RISER ROOM
30'-2 MTD 2 117 SF
MDF 470 SF BUSINESS 100 5 Yes 1 0.75 300 100
=
(1/3 ) TRAINING ROOMS OFFICE 4,173 SF BUSINESS 100 42 Yes 1 6.3 300 100
S
N. E 3,345 SF OPEN OFFICES 864 SF BUSINESS 100 9 Yes 1 1.35 300 100
FE
6" (MI STORAGE
90'- TRAINING OFFICE 158 SF BUSINESS 100 2 Yes 1 0.3 300 100
= 479 SF
DD FEC WATER 530 SF BUSINESS 100 6 Yes 1 0.9 300 100 title
10,061 SF 106 15.9
S-2 LIFE SAFETY PLAN
EXIT DOOR 117 EXIT
EXIT DOOR 100 EXIT
ELECTRICAL 145 SF STORAGE 300 1 Yes 1 0.15 400 100
IDF 148 SF STORAGE 300 1 Yes 1 0.15 400 100
DOOR EXIT CAPACITY DOOR EXIT CAPACITY STORAGE 479 SF STORAGE 300 2 Yes 1 0.3 400 100
X
4/30/2021 3:48:17 PM

CLEAR WIDTH: = 68.5" CLEAR WIDTH: = 55" STORAGE 681 SF STORAGE 300 3 Yes 1 0.45 400 100
CAPACITY: = 456 OCC CAPACITY: = 366 OCC WAREHOUSE 74,439 SF WAREHOUSE 500 149 Yes 2 22.35 400 100 project number 20182.200
OCCUPANT LOAD SERVED: = 202 OCC OCCUPANT LOAD SERVED: = 162 OCC 75,892 SF 156 23.4
103,935 SF 1208 181.2 date 04.30.2021
sheet

01 LIFE SAFETY PLAN - LEVEL 1


A0.21
plotted:

SCALE: 1/16" = 1'-0"


TRUE PLAN
NORTH NORTH
CHAPTER 3: BUILDING BLOCKS

ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
302 FLOOR OR GROUND SURFACES 307 PROTRUDING OBJECTS 404 DOORS, DOORWAYS, AND GATES 405 RAMPS 407 ELEVATORS 409 PRIVATE RESIDENCE ELEVATORS

32 min 32 min 32 min


CL CL
815 815 815
4 max 2½ min
100 60 min 60 min 60 min

9 0°
½ max 64
1525 1525 1525 CL
13 2½ min
(a) (b) (c) landing ramp run landing ramp run 64

60 min
12 min

1525
hinged door sliding door folding door landing
FIGURE 302.2 CARPET PILE HEIGHT 305

X > 80
at least as wide as ramp run

2030

ramp run
FIGURE 404.2.3 CLEAR WIDTH OF DOORWAYS

X > 27
dominant direction

685

72 min
1830
of travel
18 min

48 min
1220
long dimension

60 min
1525
FIGURE 307.2 LIMITS OF PROTRUDING OBJECTS 445 (a) (b)
perpendicular to
straight change in direction
dominant direction
of travel FIGURE 405.7 RAMP LANDINGS
½ max FIGURE 409.4.6.2 LOCATION OF PRIVATE RESIDENCE
13 ELEVATOR CONTROL PANEL architecture interiors planning graphics
(a) (b)
FIGURE 302.3 ELONGATED OPENINGS IN FLOOR OR GROUND SURFACES front approach, pull side front approach, push side 12 min 12 min 410 PLATFORM LIFTS
8070 Park Lane, Ste. 300 Dallas, Texas 75231

80 min
X > 12

2030
12 max 12 max 305 305 305

685-2030
Tel 972.701.9000 Fax 972.991.3008

27-80
305 305

27 max
X > 12 12 min FIGURE 407.2.2.2 VISIBLE HALL SIGNALS

685

48 min
1220
305 305 32 min www.bokapowell.com

60 min
1525
36 min 815
(a) (b) 915
FIGURE 405.9.1 EXTENDED FLOOR OR GROUND SURFACE EDGE PROTECTION
303 CHANGES IN LEVEL
FIGURE 307.3 POST-MOUNTED PROTRUDING OBJECTS These documents are issued for pricing only
and are not for regulatory approval,
¼ max (c) (d)

2 min
permitting or construction.

51
6.4 front approach, push side, door hinge approach, pull side
provided with both closer and latch
Arch: Donald R. Powell, Jr. Reg. No.: 7206

lift mechanism
FIGURE 303.2 VERTICAL CHANGE IN LEVEL Arch: Chris W. Barnes Reg. No.: 10147
22 min

42 min
1065
platform Arch: John E. Orfield Reg. No.: 11164
560

42 min
Arch: R. Andrew Bennett Reg. No.: 18129

X < 80
X<4

54 min

1065
2030

1370
¼ 42 min

27 max
2 ½

685
6.4 1065 100
1 13
¼
6.4
FIGURE 405.9.2 CURB OR BARRIER EDGE PROTECTION FIGURE 407.2.3.1 FLOOR DESIGNATIONS ON JAMBS OF ELEVATOR
(e) (f) client
FIGURE 303.3 BEVELED CHANGE IN LEVEL hinge approach, pull side hinge approach, push side HOISTWAY ENTRANCES
DALLAS COUNTY
304 TURNING SPACE FIGURE 307.4 VERTICAL CLEARANCE
1460 ROUND TABLE DR
FIGURE 404.2.4.1 MANEUVERING CLEARANCES FIGURE 410.6 PLATFORM LIFT DOORS AND GATES DALLAS, TX 75247
406 CURB RAMPS
60 min AT MANUAL SWINGING DOORS AND GATES
214-653-6437
1525
adjoining surface maximum
slope CHAPTER 5: GENERAL SITE AND BUILDING ELEMENTS project manager

2 min
24 min

51
36 min

curb ramp slope PRITCHARD ASSOCIATES


arm

22 min

48 min
arm

308 REACH RANGES

1220
915

48 min
20 502 PARKING SPACES

1220
560 610 1 2121 NORTH AKARD ST, SUITE 100
60 min
1525

DALLAS, TX 75201
24 min
610 FIGURE 406.2 COUNTER SLOPE OF SURFACES ADJACENT TO CURB RAMPS 214-849-0011
base FIGURE 407.2.3.2 CAR DESIGNATIONS ON JAMBS OF DESTINATION
(g) (h) ORIENTED ELEVATOR HOISTWAY ENTRANCES project manager
48 max
15 min

1220
hinge approach, push side, door latch approach, pull side JPC CONSULTING
380

36 min
provided with both closer and latch
12 min
915
12 min 68 min 2627 MARTIN LUTHER KING JR. BLVD.
80 min
305 305 2030 1725 DALLAS, TX 75215
flared sides 1:10 max slope
214-941-4297
24 min 24 min

42 min
FIGURE 304.3.2 T-SHAPED TURNING SPACE

1065
54 min
1370
610 610 m.e.p. engineer

1295
51 min
1370
51 min

54 min
54 min
1295

1370
FIGURE 308.2.1 UNOBSTRUCTED FORWARD REACH
305 CLEAR FLOOR OR GROUND SPACE slope slope PURDY-MCGUIRE, INC.
17300 N. DALLAS PARKWAY, SUITE 3000
48 min 20 max >20-25 max 132 min DALLAS, TX 75248
42 min 36 min 96 min
1220 510 510-635 (i) (j) FIGURE 406.3 SIDES OF CURB RAMPS 972-239-5357
1065 915 2440 3350
latch approach, pull side, latch approach, push side
(a) (b)
door provided with closer (a) (b) car van civil
centered door side (off-centered) door
30 min

PACHECO KOCH
760

FIGURE 502.2 VEHICLE PARKING SPACES


48 max
1220

44 max

24 min 7557 RAMBLER RD. #1400


1120

48 min
1220
610 54 min
36 min at least as wide as 60 min DALLAS, TX 75234
FIGURE 305.3 CLEAR FLOOR OR GROUND SPACE curb ramp 1370 1525
915 972.235.3031
(a) (b)
landscape

full length of parking space


FIGURE 308.2.2 OBSTRUCTED HIGH FORWARD REACH PACHECO KOCH
30 min
760

60 min
(k)

1525
7557 RAMBLER RD. #1400

80 min
48 min

2030
1220

latch approach, push side,


door provided with closer DALLAS, TX 75234
48 min 972.235.3031
FIGURE 404.2.4.1 MANEUVERING CLEARANCES AT
1220 MANUAL SWINGING DOORS AND GATES (CONTINUED) structural engineer
FIGURE 406.4 LANDINGS AT THE TOP OF CURB RAMPS 36 min
48 max
1220

30 min
15 min
380

915 EJES INCORPORATED


760 36 min
(a) (b) 915 area to be 12801 N. CENTRAL EXPY, SUITE 700
(d)
forward parallel (c) marked DALLAS, TX 75243
any door location 60 min
42 min
1065
48 min
1220

FIGURE 305.5 POSITION OF CLEAR FLOOR OR GROUND SPACE any door location 36 min 214.3431210
1525
10 max 24 min 915
255 610 security, audio/visual
16 sq ft min FIGURE 502.3 PARKING SPACE ACCESS AISLE
(a) (b) 1.5 m²
FIGURE 308.3.1 UNOBSTRUCTED SIDE REACH NOVOM GROUP
X > 24

front approach side approach


610

400 S. RECORD ST, SUITE 1200

54 min
503 PASSENGER LOADING ZONES

1370
22 min DALLAS, TX 75202
1065
42 min

24 min 48 min
42 min
1065

560 610 1220 214-882-1540


48 max
1220

46 max

36 min 24 min project


1170
34 max

610
34 max

915 (c) (d)


865

865

full length of DALLAS COUNTY ELECTIONS BUILDING


pocket or hinge approach stop or latch approach (e) vehicle pull-up space

60 min
1525
FIGURE 305.7.1 MANEUVERING CLEARANCE IN AN Exception 1460 ROUND TABLE DR
ALCOVE, FORWARD APPROACH curb line
FIGURE 404.2.4.2 MANEUVERING CLEARANCES AT DOORWAYS existing elevator car configuration DALLAS, TX 75247
10 max > 10-24 max WITHOUT DOORS, SLIDING DOORS, GATES, AND FOLDING DOORS The drawings and written material herein constitute original work of the
255 255-610 architect, and as intellectual property and instruments of service, are
X > 15
380

FIGURE 407.4.1 ELEVATOR CAR DIMENSIONS subject to copyright and may not be reproduced, distributed, published
(a) (b) area to be
or used in any way without the express written consent of the architect.
18 min marked
48 min

original issue
1220

408 LIMITED-USE/LIMITED-APPLICATION ELEVATORS


60 min

FIGURE 308.3.2 OBSTRUCTED HIGH SIDE REACH 445


1525

X>8
60 min X>8 205 DESIGN DEVELOPMENT 04.30.2021
1525 CHAPTER 4: ACCESSIBLE ROUTES FIGURE 406.6 DIAGONAL OR CORNER TYPE CURB RAMPS 42 min 51 min
205 1065 revisions
FIGURE 305.7.2 MANEUVERING CLEARANCE IN AN 1295 FIGURE 503.3 PASSENGER LOADING ZONE ACCESS AISLE
ALCOVE, PARALLEL APPROACH 36 min
915
306 KNEE AND TOE CLEARANCE 403 WALKING SURFACES (a) (b)
12 min

54 min
1370

51 min
24 max 24 max pull side push side 504 STAIRWAYS

1295
305
48 min
1220

610 48 min 610


X>8
1220 205 48 min
9
30 min
760

1220 radius ½ max 30° max


32 min

36 min
32 min

230
36 min

36 min
815

915

32 min
815
915

915 13
815
(c) (b)
6 max 17-25 push side, door provided with Exception 1 (a) (b)
150 FIGURE 403.5.1 CLEAR WIDTH OF AN ACCESSIBLE ROUTE both closer and latch 36 min radius of tread edge
(a) 430-635 (b) angled riser
915 (typical for all profiles)
elevation plan
FIGURE 404.2.4.3 MANEUVERING CLEARANCES AT RECESSED title
DOORS AND GATES 15 sq ft min
FIGURE 306.2 TOE CLEARANCE (a) (b) 1.4 m²
TAS 2012 INFORMATION
60 min

8 min
1525
48 min
1220

cut through at island curb ramp at island


205 48 min

54 min
48 min

1370
1½ max 1½ max
1220 1220
38 38
30 min
760

FIGURE 406.7 ISLANDS IN CROSSING


27 min
4/30/2021 3:46:57 PM

685

9 min
42 min 42 min 36 min 36 min (a) (b) project number 20182.200
230 915 48 min
1065 1065 915 (c) (d)
X < 48 X < 48 1220
25 max curved nosing beveled nosing date 04.30.2021
1220 1220 (c)
11 min 635 (a) (b) Exception 2
280 (a) (b) 180 degree turn 180 degree turn sheet
(Exception) FIGURE 504.5 STAIR NOSINGS
elevation plan

A0.31
(c) FIGURE 408.4.1 LIMITED-USE/LIMITED-APPLICATION (LULA)
plotted:

FIGURE 403.5.2 CLEAR WIDTH AT TURN ELEVATOR CAR DIMENSIONS


FIGURE 306.3 KNEE CLEARANCE FIGURE 404.2.6 DOORS IN SERIES AND GATES IN SERIES
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
CHAPTER 7: COMMUNICATION ELEMENTS AND FEATURES

505 HANDRAILS 605 URINALS 703 SIGNS 704 TELEPHONES


18 min can be located on
CL 13½ min 13½ min any wall of shower 27 max
455 LIBRARY
345 345 685
back wall 10 max

865-965
255

34-38

16-51
865-965

5 / -2
34-38
865-965

48 max

48 max

8
1220

1220
34-38
17 max
430

66 min
1675
FIGURE 703.2.5 HEIGHT OF RAISED CHARACTERS
(a) (b) (a) (b)
wall hung type stall type without seat with seat
(a) (b) (c) distance between dots
FIGURE 608.5.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENT distance between corresponding dots in the same cell FIGURE 704.2.1.1 PARALLEL APPROACH TO TELEPHONE
stairs ramps walking surfaces FIGURE 605.2 HEIGHT AND DEPTH OF URINALS
CONTROL LOCATION in adjacent cells
607 BATHTUBS single braille
CL 15 max
FIGURE 505.4 HANDRAIL HEIGHT 60 min 27 max distance between dots cell
back wall back wall 380
blank cell space
architecture interiors planning graphics
1525 685 in the same cell
1½ min head end control head end between words 20 max
control 8070 Park Lane, Ste. 300 Dallas, Texas 75231
38 FIGURE 604.3.2 (EXCEPTION) OVERLAP OF WATER CLOSET wall end wall wall distance between corresponding raised dot 510
end wall
CLEARANCE IN RESIDENTIAL DWELLING UNITS side bac dots from one cell directly below base diameter

48 max

48 max
1220

1220
wall Tel 972.701.9000 Fax 972.991.3008

30 min

30 min
k no raised dot

760

760
wall
54 min length length of bathtub www.bokapowell.com
1370 12 min FIGURE 703.3.1 BRAILLE MEASUREMENT
12 max of bathtub (a) (b)
305 (a) (b) 305 with seat with seat
42 min removable in-tub seat permanent seat (elevation) (elevation) These documents are issued for pricing only
1065 FIGURE 704.2.1.2 FORWARD APPROACH TO TELEPHONE
back wall back wall AREA OF and are not for regulatory approval,
FIGURE 505.5 HANDRAIL CLEARANCE FIGURE 607.2 CLEARANCE FOR BATHTUBS REFUGE
15 max permitting or construction.
12 max side
305 380 side side side
wall wall wall Arch: Donald R. Powell, Jr. Reg. No.: 7206
back wall wall 705 DETECTABLE WARNINGS
1½ min

8-10 control 3/8 min Arch: Chris W. Barnes Reg. No.: 10147

840-915
38

head

33-36
205-255 end wall Arch: John E. Orfield Reg. No.: 11164

24 min
9.5

610
end wall front front Arch: R. Andrew Bennett Reg. No.: 18129
wall (c) wall (d) 3/8 min
FIGURE 604.5.1 SIDE WALL GRAB BAR AT WATER CLOSETS (b) top diameter of 50%-65% 1.6-2.4
(a) without seat with seat 9.5
elevation plan (plan) (plan) of the base diameter 41-61
0.65 min 1.6-2.4
FIGURE 505.6 HORIZONTAL PROJECTIONS BELOW FIGURE 607.4.1 GRAB BARS FOR BATHTUBS WITH PERMANENT SEATS FIGURE 608.5.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENT base diameter of 0.2
CL
41-61
36 min 17 CL CL
GRIPPING SURFACE
24 min 915 12 min 12 max 24 min 24 max CONTROL LOCATION FIGURE 703.3.2 POSITION OF BRAILLE
0.9-1.4 (23-36 mm) 5.1
CL
client
610 CL 305 305 610 610 DALLAS COUNTY
4-6¼ perimeter 609 GRAB BARS (a)
(b) 1460 ROUND TABLE DR
100-160 backwall elevation
8-10 control plan
head 4-4.8 perimeter (enlarged) DALLAS, TX 75247

840-915
33-36
205-255 end wall

24 min
end wall 100-120

610
214-653-6437
2¼ max AREA OF FIGURE 705.1 SIZE AND SPACING OF TRUNCATED DOMES
5 7 ax
m

REFUGE

12 min
57 (a) (b)

305
transfer side 2 max AREA OF
project manager

51 ax
REFUGE

2m
elevation plan 51
FIGURE 607.4.2 GRAB BARS FOR BATHTUBS WITH REMOVABLE IN-TUB SEATS PRITCHARD ASSOCIATES

60 max
707 AUTOMATIC TELLER MACHINES AND FARE MACHINES

1525
2121 NORTH AKARD ST, SUITE 100

48 min
1220
(a) (b) control end
wall CL DALLAS, TX 75201
FIGURE 505.7.2 HANDRAIL NON-CIRCULAR CROSS SECTION (a) (b)
FIGURE 604.5.2 REAR WALL GRAB BAR AT WATER CLOSETS 214-849-0011
12 min FIGURE 609.2.2 GRAB BAR NON-CIRCULAR CROSS SECTION
12 min 305 project manager
305
CL
FIGURE 703.4.1 HEIGHT OF TACTILE CHARACTERS ABOVE 1 2 3 7 8 9 JPC CONSULTING
FINISH FLOOR OR GROUND
FIGURE 607.5 BATHTUB CONTROL LOCATION
4 5 6 4 5 6 2627 MARTIN LUTHER KING JR. BLVD.

12 min
305
DALLAS, TX 75215
1½ min
608 SHOWER COMPARTMENTS 7 8 9 1 2 3
15 min

214-941-4297
48 max
380

1220

38
36 45° 18 min
915
back wall (a) (b)
455 * 0 # * 0 # m.e.p. engineer
FIGURE 505.10.1 TOP AND BOTTOM HANDRAIL EXTENSION AT RAMPS CL projecting objects recessed objects centered on
PURDY-MCGUIRE, INC.
CL
12 min 7-9 tactile characters (a) (b) 17300 N. DALLAS PARKWAY, SUITE 3000
FIGURE 609.3 SPACING OF GRAB BARS 12-key 12-key DALLAS, TX 75248
305 180-230 seat C CL control

915
L

36
wall wall 18 min ascending descending
FIGURE 604.7 DISPENSER OUTLET LOCATION 610 SEATS 972-239-5357
455

36 min
FIGURE 707.6.2 NUMERIC KEY LAYOUT

915
civil

430-485
FIGURE 703.4.2 LOCATION OF TACTILE SIGNS AT DOORS

17-19
48 min PACHECO KOCH
1220 7557 RAMBLER RD. #1400
Note: inside finished dimensions measured at the center points
of opposing sides DALLAS, TX 75234
FIGURE 608.2.1 TRANSFER TYPE SHOWER COMPARTMENT 15 min
972.235.3031
15-16

6 min
150
56 min

59 min

SIZE AND CLEARANCE


1420

1500

FIGURE 505.10.2 TOP HANDRAIL EXTENSION AT STAIRS CL 380-405 380 landscape


back wall side PACHECO KOCH
wall
7557 RAMBLER RD. #1400

30 min 30 min
X CL

760
CL not in
side pictogram DALLAS, TX 75234
wall (a) (b) 972.235.3031
field
760
X Removable Permanent Seat
60 min 60 min
60 min In-Tub Seat structural engineer
1525 1525
1525
(a) (b) Note: inside finished dimensions measured at the center FIGURE 610.2 BATHTUB SEATS FIGURE 703.6.1 PICTOGRAM FIELD EJES INCORPORATED
adult wall hung adult floor mounted water closet points of opposing sides 12801 N. CENTRAL EXPY, SUITE 700
water closet and children's water closet
Note: X = tread depth FIGURE 608.2.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENT
DALLAS, TX 75243
214.3431210

3 max
FIGURE 604.8.1.1 SIZE OF WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT SIZE AND CLEARANCE

75

3 max
FIGURE 505.10.3 BOTTOM HANDRAIL EXTENSION AT STAIRS CL

75
back wall security, audio/visual
compartment
CHAPTER 6: PLUMBING ELEMENTS AND FACILITIES alternate C entry compartment NOVOM GROUP
CL
915

door side L
36

side entry
location
wall wall 400 S. RECORD ST, SUITE 1200
602 DRINKING FOUNTAINS (a) (b)
front 36 min
rectangular L-shaped
DALLAS, TX 75202
4 max wall 915 FIGURE 703.7.2.1 INTERNATIONAL SYMBOL OF ACCESSIBILITY 214-882-1540
100 60 min
5 max 15 min FIGURE 610.3 EXTENT OF SEAT
1525
125 380 Note: inside finished dimensions measured at the center 15-16 project
4 max

points of opposing sides

1½ max
100

380-405 DALLAS COUNTY ELECTIONS BUILDING


42 min

38
1065

FIGURE 608.2.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENT 1460 ROUND TABLE DR
SIZE AND CLEARANCE DALLAS, TX 75247
back 18 seat
wall 455 wall The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are
FIGURE 602.5 DRINKING FOUNTAIN SPOUT LOCATION FIGURE 604.8.1.2 WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT DOORS subject to copyright and may not be reproduced, distributed, published
seat control FIGURE 703.7.2.2 INTERNATIONAL SYMBOL OF TTY or used in any way without the express written consent of the architect.
604 WATER CLOSETS AND TOILET COMPARTMENTS wall wall
2½ max original issue
CL CL partition partition 64
FIGURE 610.3.1 RECTANGULAR SHOWER SEAT DESIGN DEVELOPMENT 04.30.2021
6 min 6 min FIGURE 608.3.1 GRAB BARS FOR TRANSFER TYPE SHOWERS
6 max revisions
150 150 6 max 6 max 22-23

1½ max
150 150 150 560-585

38
12 min back wall back wall
9 min 6 min
230 305 150 side side
side side wall
6 max

wall wall
150

wall
6 max

6 min
6 max
150

seat seat
150

355-380

150
14-15

wall wall FIGURE 703.7.2.3 VOLUME CONTROL TELEPHONE


16-18 17-19 (a) (b) (c) (a) (b)
405-455 430-485 elevation elevation plan without seat with seat
(a) (b) adult children FIGURE 608.3.2 GRAB BARS FOR STANDARD ROLL-IN TYPE SHOWERS
wheelchair ambulatory 2½ max
6 max 6 max 15-16
accessible accessible water FIGURE 604.8.1.4 WHEELCHAIR ACCESSIBLE TOILET 64
150 150 380-405
water closets closets COMPARTMENT TOE CLEARANCE back wall (a) (b)
size distance from wall
FIGURE 604.2 WATER CLOSET LOCATION side side FIGURE 610.3.2 L-SHAPED SHOWER SEAT title
6 max
150

wall wall
611 WASHING MACHINES AND CLOTHES DRYERS FIGURE 703.7.2.4 INTERNATIONAL SYMBOL OF ACCESS TAS 2012 INFORMATION
60 min
1525

front wall FOR HEARING LOSS


FIGURE 608.3.3 GRAB BARS FOR ALTERNATE ROLL-IN TYPE SHOWERS
56 min
1420

side wall
380-915
15-36
4/30/2021 3:47:04 PM

CL 15 max
36 max

35-37 project number 20182.200


915
42 min

380
1065

890-940
date 04.30.2021
48 max
1220

60 min
38 min

(a)
965

(b) sheet
1525 top loading front loading
FIGURE 604.8.2 AMBULATORY ACCESSIBLE TOILET COMPARTMENT

A0.32
FIGURE 604.3.1 SIZE OF CLEARANCE AT WATER CLOSETS FIGURE 611.4 HEIGHT OF LAUNDRY COMPARTMENT OPENING
plotted:

FIGURE 608.5.1 TRANSFER TYPE SHOWER COMPARTMENT


CONTROL LOCATION
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
TURN SPACE CLEARANCE REQUIREMENTS TOILET ROOM CLEAR FLOOR SPACE TOILET STALL CLEAR FLOOR SPACE BATH TUB CLEAR FLOOR SPACE GENERAL NOTES
REFERENCE TEXAS ACCESSIBILITY STANDARDS SECTION 304 'TURNING SPACES' REQUIREMENTS REQUIREMENTS REQUIREMENTS
AND ANSI 117.1-2009 SECTION 304.3.
REFERENCE TEXAS ACCESSIBILITY STANDARDS SECTION 604.3 FOR SPACE REFERENCE TEXAS ACCESSIBILITY STANDARDS SECTION 604.8 'TOILET REFERENCE TEXAS ACCESSIBILITY STANDARDS SECTION 607 'BATHTUBS' AND ANSI 1. THIS SHEET IS TO BE USED FOR REFERENCE OF THE TYPICAL CLEAR FLOOR
5'-0" ALLOWANCES AND ANSI 117.1-2009 SECTION 604.3 AND CHAPTER 10. THIS COMPARTMENTS' A117.1-2009 SECTIONS 607 AND 1003.11.2.5 SPACE REQUIREMENTS. REFER TO THE TEXAS ACCESSIBILITY STANDARDS,
SECTION ILLUSTRATES THE CLEAR FLOOR SPACE REQUIREMENTS FOR TOILETS ANSI (AMERICAN NATIONAL STANDARD - ACCESSIBLE AND USABLE BUILDINGS
NOT LOCATED WITHIN TOILET STALLS. 16-18" HOLD 42" MIN. AND FACILITIES), AND OTHER APPLICABLE CODES FOR ALL ACCESSIBLE
CLEAR FLOOR SPACE REQUIREMENTS.
1. ADJACENT LAVATORIES ARE ALLOWED ALONG THE SAME WET WALL. THE

SEAT
56"x60" IS REQUIREMENT IS FOR ALL TOILETS NOT LOCATED WITHIN TOILET 2. REFERENCE THE A0 SHEET SERIES FOR ADDITIONAL ACCESSIBLE
STALLS. CONTROL WALL NOTATIONS.

2. LAVATORY AND TOILET CLEAR FLOOR SPACES MAY NOT OVERLAP. 3. NOT ALL CLEAR FLOOR SPACES APPEARING ON THIS SHEET MAY BE
APPLICABLE TO THIS PROJECT.

AT FLOOR MOUNT
AT WALL MOUNT
3. DIAGRAM WC1 ILLUSTRATES THE MINIMUM CLEAR FLOOR SPACE.

56" MIN.

59" MIN.
4. ALL DOORS TO ACCESSIBLE SPACES MUST BE 36" MINIMUM. A 32" MINIMUM
4. DIAGRAM WC2 ILLUSTRATES THE CLEAR FLOOR SPACE REQUIREMENTS CLEAR WIDTH IS REQUIRED PER THE TEXAS ACCESSIBILITY STANDARDS TAS

48" MIN.
WITH AN ADJACENT LAVATORY AND FRONT APPROACH. 404.2.3 AND ANSI 117.1-2009 SECTION 404.2.2. architecture interiors planning graphics
5. DIAGRAM WC3 ILLUSTRATES THE CLEAR FLOOR SPACE REQUIREMENTS 4" 5. THE SWING OF THE DOOR INTO A BATHROOM IS ALLOWED TO OVERLAP THE 8070 Park Lane, Ste. 300 Dallas, Texas 75231
TS1- 60" DIAMETER TURN RADIUS WITH AN ADJACENT LAVATORY AND SIDE APPROACH. MAX. CLEAR FLOOR SPACE AREA PROVIDED FOR THE FIXTURES. A 30"x48" CLEAR
FLOOR SPACE MUST BE PROVIDED OUTSIDE THE SWING OF THE DOOR TO Tel 972.701.9000 Fax 972.991.3008
6. 60" DIAMETER TURNING RADIUS IS REQUIRED. ALLOW A PERSON IN A WHEELCHAIR TO CLOSE AND OPEN THE DOOR.
60" MIN. www.bokapowell.com
7. DOORS ARE PERMITTED TO ENCROACH IN THE CLEAR FLOOR SPACE OF AN ALTERNATE DOOR LOCATION 6. ALL ACCESSIBLE ROOMS SERVED BY AN ACCESSIBLE ROUTE, EXCEPT TOILET
36" MIN.
ACCESSIBLE FIXTURE IF THERE IS A MINIMUM 30"x48" CLEAR FLOOR SPACE ROOMS AND BATHROOMS NOT REQUIRED TO COMPLY IN BOTH THE TEXAS
BEYOND THE SWING OF THE ENTRY DOOR. BA1 - 48"x60" CLEAR FLOOR SPACE AT BATH TUB WITH SEAT. FRONT APPROACH ACCESSIBILITY STANDARDS AND ANSI, MUST HAVE A TURNING SPACE AS
PRESCRIBED BY THESE CODES. REFERENCE DIAGRAMS TS1 AND TS2 OF These documents are issued for pricing only
60" MIN. 16-18" HOLD 42" MIN. THIS SHEET. and are not for regulatory approval,
60" MIN. permitting or construction.
7. CLEAR FLOOR SPACE IS MEASURED FROM THE FINISH FACE OF THE WALL OR
THE FURTHEST PROTRUDING EDGE OF COUNTER, CABINET, FIXTURE, FACE Arch: Donald R. Powell, Jr. Reg. No.: 7206
24" MIN.

SEAT
WC5 - 56" x 60" STANDARD STALL CLEAR FLOOR SPACE OF AN APPLIANCE DOOR, AND TO THE CENTERLINE OF THE APPLIANCE OR Arch: Chris W. Barnes Reg. No.: 10147
FIXTURE. Arch: John E. Orfield Reg. No.: 11164
CONTROL WALL Arch: R. Andrew Bennett Reg. No.: 18129
16-18" HOLD 42" MIN. 8. CLEAR FLOOR SPACES MAY NOT OVERLAP, AND MUST BE PART OF OR
12" MIN. 36" MIN. 12" MIN.

56" MIN.
CONNECT TO AN ACCESSIBLE ROUTE.
60" MIN. 9. APPLIANCES AND FIXTURES VARY IN CONFIGURATIONS AND DIMENSIONS.

30" MIN.
VERIFY THE APPLIANCES AND MEASUREMENTS PRIOR TO CONSTRUCTION. client
TS2 - T-SHAPED FOR 180 DEGREE TURNS
10. WALL REINFORCEMENT IS REQUIRED FOR THE GRAB BARS AND MUST BE DALLAS COUNTY

AT FLOOR MOUNTED
AT WALL MOUNTED
INSTALLED DURING CONSTRUCTION. 1460 ROUND TABLE DR

56" MIN.

59" MIN.
60" MIN. DALLAS, TX 75247
60" MIN.
30" MIN.

11. CLOSETS OR STORAGE AREAS DEEPER THAN 24" REQUIRE A 32" NOMINAL
ACCESS CLEARANCE.
214-653-6437
BA2 - 30"x60" CLEAR FLOOR SPACE AT BATH TUB WITH SEAT. PARALLEL APPROACH
WC1 - 56" x 60" CLEAR FLOOR SPACE (NO ADJACENT SINK). BOTH FRONT AND 12. CLOSETS 24" OR LESS IN DEPTH ARE CONSIDERED "REACH-IN-CLOSETS" AND project manager
SIDE APPROACH TO TOILET ALLOWED THE DOORS PROVIDED MAY BE LESS THAN 32" NOMINAL. PRITCHARD ASSOCIATES
48" MIN. 60" MIN. 15" MAX.
MAINTAIN MINIMUM 2121 NORTH AKARD ST, SUITE 100
16-18" HOLD LENGTH OF 60" AT 60" MIN.
TS3 - 30"x48" CLEAR SPACE BEYOND SWING OF DOOR WET WALL DALLAS, TX 75201
214-849-0011

36" MIN.

SEAT
project manager
CONTROL WALL JPC CONSULTING
DRINKING FOUNTAIN AND WATER COOLER 2627 MARTIN LUTHER KING JR. BLVD.
CLEARANCES DALLAS, TX 75215

48" MIN.
WC6 - 56" x 60" STANDARD STALL CLEAR FLOOR SPACE AT THE END OF ROW 12" MIN.

66" MIN.
214-941-4297

30" MIN.
REFERENCE TEXAS ACCESSIBILITY STANDARDS SECTION 602 'DRINKING
FOUNTAINS' AND ANSI 117.1 2009 SECTION 602.2
m.e.p. engineer
SINK AND LAVATORY CLEAR FLOOR SPACE PURDY-MCGUIRE, INC.
REQUIREMENTS 17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
BA3 - CLEAR FLOOR SPACE AT BATH TUB WITH PERMANENT SEAT.
REFERENCE TEXAS ACCESSIBILITY STANDARDS SECTION 606 'LAVATORIES 972-239-5357
17" - 19" 5" MAX. 15" MIN. 48" MIN. 30" MIN. AND SINKS' AREA OF FEATHERED CONCRETE
WC2 - 48" x 66" CLEAR FLOOR SPACE WITH ADJACENT SINK. FRONT TO TOILET. SINK RIM
RAMP CLEAR WIDTH DIAGRAMS CONCRETE AT EXTERIOR SIDE OF BUILDING TO BE FEATHERED UP TO FINISHED
SLAB OF BUILDING AT DOOR LOCATIONS. MAXIMUM SLOPE ALLOWED IS 1:48,
civil
PACHECO KOCH
WHEELCHAIR ACCESSIBLE

2'-0" REFERENCE TEXAS ACCESSIBILITY STANDARDS 2012, SECTION 405.3.


STANDING PERSONS

7557 RAMBLER RD. #1400


30" MIN

44" CLEAR MIN WIDTH 44" CLEAR MIN.


MAINTAIN MINIMUM
36" MAX FOR

38" - 43" FOR

16-18" HOLD LENGTH OF 60" AT BETWEEN HANDRAILS


DALLAS, TX 75234

19" MAX.
9" MIN
27" MIN

WET WALL 972.235.3031

VARIES - MAXIMUM CROSS


48" MIN. landscape

SLOPE ALLOWED 1:48


48" MIN.

34" MAX.
AREA OF PACHECO KOCH

9" MIN.
27" MIN.
8" MIN 6" MAX FEATHERED 7557 RAMBLER RD. #1400
CONCRETE
DALLAS, TX 75234
48" MIN.
56" MIN.

972.235.3031
8" MIN 6" MAX. structural engineer
30" MIN.
11" MIN. 6" WIDTH OF DOOR - MAXIMUM 24" MIN. EJES INCORPORATED
MIN.
NOTE: CENTERLINE OF CLEAR FLOOR CROSS SLOPE ALLOWED 1:48 12801 N. CENTRAL EXPY, SUITE 700
24" MAX

SPACE TO BE CENTERED WITH FIXTURE DALLAS, TX 75243


214.3431210
48" MIN.
SK1 - SINK CLEAR FLOOR SPACE REQUIREMENT
CLEAR FLOOR SPACE BEYOND DOOR SWING
48" MIN

security, audio/visual

VARIES - MAXIMUM CROSS


NOVOM GROUP

SLOPE ALLOWED 1:48


WC3 - 48" x 56" CLEAR FLOOR SPACE WITH ADJACENT SINK. SIDE APPROACH TO AREA OF
SINK RIM FEATHERED
TOILET WITHIN SLEEPING UNITS 400 S. RECORD ST, SUITE 1200
NOTE: CENTERLINE OF CONCRETE
DALLAS, TX 75202
17" MIN.

CLEAR FLOOR SPACE TO BE


19" MAX.

CENTERED WITH FIXTURE 30" MIN 214-882-1540


project
24" MAX.

8"
48" MIN.

DALLAS COUNTY ELECTIONS BUILDING

x4
DF1 - FORWARD APPROACH - FREE STANDING DRINKING FOUNTAIN OR WATER COOLER

"
34" MAX.

30
29" MIN.
1460 ROUND TABLE DR
27" MIN.

9" MIN.
6" WIDTH OF DOOR 6"
MIN. MAXIMUM CROSS SLOPE ALLOWED 1:48 MIN. DALLAS, TX 75247
NOTE: CENTERLINE OF
48" MIN.

The drawings and written material herein constitute original work of the

30"x48"
CLEAR FLOOR SPACE architect, and as intellectual property and instruments of service, are
TO BE CENTERED WITH 30" MIN. 8" MIN. 6" MAX. subject to copyright and may not be reproduced, distributed, published
FIXTURE or used in any way without the express written consent of the architect.
11" MIN.
30" MIN.
NOTE: CENTERLINE OF CLEAR FLOOR
KEYNOTE PLAN original issue
SPACE TO BE CENTERED WITH FIXTURE 30"x48" DESIGN DEVELOPMENT 04.30.2021
WC4 - 30"x48" CLEAR FLOOR SPACE AT URINAL. revisions
LA1 - LAVATORY CLEAR FLOOR SPACE REQUIREMENT A 30"x48" CLEAR FLOOR SPACE IS REQUIRED BEYOND THE SWING OF THE DOOR IN
ALL ACCESSIBLE BATHROOMS.

SHOWER STALL CLEAR FLOOR SPACE REQUIREMENTS REFRIGERATOR CLEAR FLOOR SPACE REQUIREMENTS
REFERENCE TEXAS ACCESSIBILITY STANDARDS SECTION 608 'SHOWER COMPARTMENTS' REFERENCE ANSI 117.1-2009 SECTIONS 804.5.6 AND 1003.12.5.6
CL
3'-0" 17".
CONTROL WALL 27" MAX CONTROL WALL CONTROL WALL 27" MAX
HOLD

LV1
WC1 title
3'-0"

30" MIN.

30" MIN.

CL
CLEAR FLOOR SPACE
24" MAX.
30" MIN.

30" MIN.
CLEAR FLOOR
40" MIN.

SPACE KEYNOTE
4/30/2021 3:47:09 PM

TS1 DESIGNATION
36" MIN.

36" MIN.

36" MIN.

project number 20182.200


48" MIN. 48" MIN.
date 04.30.2021
sheet
48" MIN. 60" MIN. 60" MIN. NOTE: 40 INCH CLEARANCE REQUIRED BETWEEN RF1 - REFRIGERATOR OFFSET PARALLEL APPROACH. RF2 - REFRIGERATOR PARALLEL APPROACH.
APPLIANCE AND ALL OPPOSING CABINETS, CENTERLINE OF CLEAR FLOOR SPACE MAYBE
APPLIANCES OR WALL SURFACE. THIS OFFSET OF REFRIGERATOR NO GREATER THAN 24"

A0.36
plotted:

SH1 - 36"x36" TRANSFER SHOWER PARALLEL APPROACH SH2 - 30"x60" ROLL-IN SHOWER PARALLEL APPROACH SH3 - 30"x60" ROLL-IN SHOWER W/ SEAT DIMENSION TO BE TAKEN FROM FACE OF
APPLIANCE AND EDGE OF CABINET TOP.
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt

PARTITION BLOCKING/BACKING PLATE GENERAL NOTES


1. DETAILS ON THIS SHEET INDICATE BLOCKING/BACKING PLATE TO PROVIDE FOR LIGHT, MEDIUM AND HEAVY DUTY
SUPPORT OF ELEMENTS/EQUIPMENT TO BE MOUNTED ON PARTITIONS.

2. CONTRACTOR SHALL DETERMINE TYPE AND CAPACITY OF BLOCKING/BACKING PLATE TO USE FOR EACH CONDITION ON
PROJECT AND COORDINATE THIS INFORMATION WITH THE ELEMENT/EQUIPMENT TO BE MOUNTED ON PARTITION.

3. REFER TO FLOOR PLANS AND PARTITION TYPE SHEETS FOR STUD FRAMING INFORMATION.

4. PROVIDE SAME GAGE, SIZE OF STUD AND GALVANIZING PROTECTION FOR BACKING PLATES AS REQUIRED FOR
PARTITION FRAMING UNLESS NOTED OTHERWISE. architecture interiors planning graphics
5. PROVIDE NUMBER, SIZE AND TYPE OF FASTENERS AS REQUIRED FOR EACH CONDITION UNLESS NOTED OTHERWISE. 8070 Park Lane, Ste. 300 Dallas, Texas 75231
6. PROVIDE FIRE RETARDANT TREATED WOOD BLOCKING OR NON-COMBUSTIBLE BACKING PLATE WHEN REQUIRED BY Tel 972.701.9000 Fax 972.991.3008
BUILDING CODE.
www.bokapowell.com

These documents are issued for pricing only


and are not for regulatory approval,
permitting or construction.

Arch: Donald R. Powell, Jr. Reg. No.: 7206


Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

client
DALLAS COUNTY
1460 ROUND TABLE DR
METAL STUD FRAMING DALLAS, TX 75247
214-653-6437
CONNECT TOP PLATES TO
BOTTOM OF STRUCTURE METAL STUD FRAMING
project manager
ABOVE - BOLT OR WELD AS
APPROPRIATE
PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
3" X 8" X 1/4" ANCHOR PLATE W/ DALLAS, TX 75201
(2) - 1/2" DIA. ANCHOR BOLTS PROVIDE TWO FASTENERS AT 214-849-0011
AT TOP & BOTTOM OF EACH POST EACH STUD 20 GAGE SHEET METAL PLATE -
PROVIDE TWO FASTENERS AT project manager
EACH BLOCKING AND AT STUD
JPC CONSULTING
COORDINATE TOTAL HEIGHT W/

2 1/2" X 2 1/2" X 3/16" TUBE 20 GAGE SHEET METAL BACKING


FLOOR TO FLOOR HEIGHT

SECTION POSTS & CROSSMEMBER - PLATE 2627 MARTIN LUTHER KING JR. BLVD.
WELD ALL CONNECTIONS 1 X 4 WOOD BLOCKING OR DALLAS, TX 75215
OF STRUCTURE

3/4" PLYWOOD 214-941-4297

m.e.p. engineer
PURDY-MCGUIRE, INC.
17300 N. DALLAS PARKWAY, SUITE 3000
METAL BACKING PLATE - WOOD BLOCKING - METAL DALLAS, TX 75248
972-239-5357
PROVIDE SUPPORT "ARMS" AS
REQUIRED BY ELEMENTS BEING
METAL STUD FRAME STUD FRAME CONSTRUCTION -
SUPPORTED
09 CONSTRUCTION - LIGHT DUTY
06 LIGHT DUTY civil
COORDINATE HEIGHT REQUIRED W/

SCALE: 1" = 1'-0" SCALE: 1" = 1'-0" PACHECO KOCH


CONNECT/BOLT FLOOR PLATES
ELEMENT BEING SUPPORTED

TO SLAB/STRUCTURE 7557 RAMBLER RD. #1400


DALLAS, TX 75234
972.235.3031
landscape
PACHECO KOCH
METAL STUD FRAMING NOTCH 7557 RAMBLER RD. #1400
& BEND RETURNS AS REQUIRED DALLAS, TX 75234
METAL STUD FRAMING
PROVIDE MAX 48" SPACING 972.235.3031
COORDINATE W/ STUD SPACING
structural engineer
EJES INCORPORATED
12801 N. CENTRAL EXPY, SUITE 700
NOTCH STUD BACKING PLATE DALLAS, TX 75243
FLANGES & RETURN AND PROVIDE TWO FASTENERS AT
214.3431210
MISCELLANEOUS METAL FASTEN TO METAL STUDS W/ EACH END OF EACH SEGMENT
OF BLOCKING TYPICAL
FOUR FASTENERS EACH
SUPPORT FOR ELEMENTS security, audio/visual
PROVIDE METAL RUNNER FOR NOVOM GROUP

11 OVER 4'-0" AFF


SCALE: 1 1/2" = 1'-0"
BACKING PLATE - SAME GAGE
AS STUD FRAMING
2 X 4 WOOD BLOCKING
400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
214-882-1540

METAL BACKING PLATE - project


2 1/2" X 2 1/2" X 3/16" TUBE DALLAS COUNTY ELECTIONS BUILDING
SECTION POSTS & CROSSMEMBER METAL STUD FRAME WOOD BLOCKING - METAL 1460 ROUND TABLE DR
WELD ALL CONNECTIONS DALLAS, TX 75247
CONSTRUCTION - MEDIUM STUD FRAME CONSTRUCTION -
The drawings and written material herein constitute original work of the
2 1/2" X 2 1/2" X 3/16" TUBE
SECTION "ARMS" WHERE
REQUIRED FOR SUPPORT 08 DUTY
SCALE: 1" = 1'-0" 05 MEDIUM DUTY
SCALE: 1" = 1'-0"
architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published
or used in any way without the express written consent of the architect.
original issue

DESIGN DEVELOPMENT 04.30.2021


revisions
PROVIDE SHIMS BETWEEN TUBE
SECTIONS & GYPSUM BOARD
METAL STUD FRAMING
LAVATORY/COUNTERTOP AS REQUIRED

WHERE REQUIRED TO PREVENT


DOUBLE STUDS
PROVIDE HEIGHT FOR SUPPORT OF

FASTENERS FROM DEFORMING/ METAL STUD FRAMING


BREAKING GYPSUM BOARD DOUBLE STUDS
3" X 8" X 1/4" BASE PLATE W/
(2) - 1/2" DIA. ANCHOR BOLTS
TO SLAB/STRUCTURE
2X LEDGERS - PROVIDE 3
NOTCH FRONT STUD FLANGES FASTENERS AT EACH SIDE
& RETURN AND FASTEN TO STUD
FRAMING
title
PROVIDE SHEET MTL. CLIP AT TOP PROVIDE THREE FASTENERS AT
PROVIDE MAX. 48" SPACING - ENSURE & BOTTOM OF EACH SIDE OF STUDS
& FASTEN TO STUDS & BACKER PLATE
EACH END OF EACH SEGMENT STANDARD
SPACING WORKS W/ FRAMING FOR OF BLOCKING TYPICAL
PARTITION. COORDINATE W/ PLUMBING
PROVIDE TWO METAL RUNNERS
BLOCKING/BACKING
& ELECTRICAL SERVICE. 2X6 WOOD BLOCKING -
FOR BACKING PLATE - SAME GAGE
AS STUD FRAMING
TYPICAL DETAILS
4/30/2021 3:47:24 PM

project number 20182.200

MISCELLANEOUS METAL METAL BACKING PLATE - WOOD BLOCKING - METAL date 04.30.2021
SUPPORT FOR ELEMENTS METAL STUD FRAME STUD FRAME CONSTRUCTION - sheet

10 BELOW 4'-0" AFF


07 CONSTRUCTION - HEAVY DUTY
04 HEAVY DUTY
A0.86
plotted:

SCALE: 1 1/2" = 1'-0" SCALE: 1" = 1'-0" SCALE: 1" = 1'-0"


ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
MAXIMUM SPAN
8' - 2"

2 LAYERS 5/8'' TYPE "X" GYPSUM


BOARD STRIPS FASTENED TO
REFER BELOW FOR STUD
1 HR RATED PARTITION - SAME MATERIALS
REFERENCE PLAN AND PARTITION
1 HR RATED PARTITION - TYPE 1/2"
REFERENCE PLAN AND PARTITION MAX
TYPE TYPICAL FRAMING - REF.
NON-RATED FIRE STEEL PINS AND CLINCH PARTITION TYPES FOR
EXTINGUISHER CABINET WITH SHIELDS AT 8" O.C. CONSTRUCTION DETAILS
RATED FIRE EXTINGUISHER LINER BY CABINET
CABINET WITH LINER BY MANUFACTURER
CABINET MANUFACTURER GYP BOARD ON TOP CONFIGURATION
architecture interiors planning graphics
FIRE EXTINGUISHER 2 LAYERS - 1 1/2" THICK 8070 Park Lane, Ste. 300 Dallas, Texas 75231
MINERAL WOOL BATTS
FIRE EXTINGUISHER

4'-0" AFF MAX


GYPSUM TO CONTINUE INSIDE 1 5/8" TYPE S SCREWS AT Tel 972.701.9000 Fax 972.991.3008
4'-0" AFF MAX

OF CABINET OPENING 24" O.C. VERTICALLY


ADJACENT CONSTRUCTION
TYPICAL FRAMING - REF.
www.bokapowell.com
TYPICAL FRAMING - REF.
PARTITION TYPES FOR PARTITION TYPES FOR PERIMETER CHANNEL - 20 GA.
CONSTRUCTION DETAILS CONSTRUCTION DETAILS
4" WIDE GALVANIZED These documents are issued for pricing only
SECTION STEEL STRAP - 20 GA. and are not for regulatory approval,
SECTION 2HR RATED PARTITION - permitting or construction.
2HR RATED PARTITION - REFERENCE PLAN AND PARTITION 6" WIDE GALVANIZED 20 GA.
REFERENCE PLAN AND PARTITION CABINET WIDTH METAL STUDS AT 16" O.C.
CABINET WIDTH TYPE Arch: Donald R. Powell, Jr. Reg. No.: 7206
TYPE ROUGH OPENING
ROUGH OPENING Arch: Chris W. Barnes Reg. No.: 10147
METAL CONTROL JOINT Arch: John E. Orfield Reg. No.: 11164
EACH SIDE -TAPE AND
Arch: R. Andrew Bennett Reg. No.: 18129
3 LAYERS 5/8" GYPSUM BOARD BED AS REQUIRED
DOOR TRIM
DOOR TRIM GYP BOARD ON BOTTOM CONFIGURATION
UL - I502 UL R4024 96NK13566
CLEAR GLAZING 2 LAYERS 5/8" TYPE "X" GYPSUM

ROUGH OPENING
CABINET HEIGHT
CLEAR GLAZING
ROUGH OPENING

BOARD EACH SIDE - REFERENCE client


CABINET HEIGHT

PARTITION TYPE SHEET


DOOR HANDLE DALLAS COUNTY
DOOR HANDLE 1460 ROUND TABLE DR
NON-RATED FIRE EXTINGUISHER
HORIZONTAL RATED CONSTRUCTION - 2 GYPSUM BOARD CONTROL JOINT - 2HR DALLAS, TX 75247

06 03
RATED FIRE EXTINGUISHER CABINET CABINET HOUR CEILING PARTITION 214-653-6437
SCALE: 3" = 1'-0" SCALE: 6" = 1'-0"
project manager
ELEVATION PRITCHARD ASSOCIATES
ELEVATION MOUNTING SCREWS 2121 NORTH AKARD ST, SUITE 100
MOUNTING SCREWS MAXIMUM SPAN DALLAS, TX 75201
8' - 2" 214-849-0011
1HR RATED PARTITION / 2HR
RATED PARTITION -

VERIFY
DEPTH
1HR RATED PARTITION / 2HR REFERENCE PLANS AND project manager
VERIFY

5/8'' TYPE "X" GYPSUM BOARD


DEPTH

RATED PARTITION - REFERENCE PARTITION TYPE STRIPS FASTENED TO STUDS


PLANS AND PARTITION TYPE 1/2" JPC CONSULTING
MAX. 2627 MARTIN LUTHER KING JR. BLVD.
GYPSUM TO CONTINUE INSIDE DALLAS, TX 75215
ROUGH OPENING OF CABINET OPENING REFER BELOW FOR
TYPICAL FRAMING - REF. 214-941-4297

DIMENSION
ROUGH OPENING SAME MATERIALS
DIMENSION

PARTITION TYPES FOR


TRIM
TRIM

RATED FIRE CONSTRUCTION DETAILS


NON-RATED FIRE m.e.p. engineer
EXTINGUISHER CABINET
PLAN EXTINGUISHER CABINET
PLAN PURDY-MCGUIRE, INC.
GYP BOARD ON TOP CONFIGURATION 17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
1 5/8" TYPE S SCREWS AT 972-239-5357
PERIMETER CHANNEL - 24" O.C. VERTICALLY
RATED FIRE EXTINGUISHER CABINET - NON-RATED FIRE EXTINGUISHER 20 GA. civil

10 RATED PARTITION
SCALE: 1 1/2" = 1'-0" 08 CABINET - RATED PARTITION
SCALE: 1 1/2" = 1'-0"
4" WIDE GALVANIZED
STEEL STRAP - 20 GA.
6" WIDE GALVANIZED 20
PACHECO KOCH
7557 RAMBLER RD. #1400
DALLAS, TX 75234
GA. METAL STUDS AT 972.235.3031
16" O.C.
NON-RATED PARTITION - landscape
REFERENCE PLAN AND PARTITION METAL CONTROL JOINT EACH
SIDE - TAPE AND BED AS PACHECO KOCH
TYPE
3 LAYERS 5/8" GYPSUM BOARD REQUIRED 7557 RAMBLER RD. #1400
ADJACENT CONSTRUCTION DALLAS, TX 75234
NON-RATED FIRE 972.235.3031
EXTINGUISHER CABINET GYP BOARD ON BOTTOM CONFIGURATION
UL - I501 1 LAYER 5/8" TYPE "X" GYPSUM
UL R4024 96NK13566 structural engineer
BOARD EACH SIDE - REFERENCE
PARTITION TYPE SHEET EJES INCORPORATED
12801 N. CENTRAL EXPY, SUITE 700
DALLAS, TX 75243
HORIZONTAL RATED CONSTRUCTION - 1 GYPSUM BOARD CONTROL JOINT- 1HR
4'-0" AFF MAX

FIRE EXTINGUISHER 214.3431210

TYPICAL FRAMING - REF.


PARTITION TYPES FOR
05 HOUR CEILING
SCALE: 3" = 1'-0" 02 PARTITION
SCALE: 6" = 1'-0" security, audio/visual
NOVOM GROUP
CONSTRUCTION DETAILS 400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
SECTION 214-882-1540
CABINET WIDTH project
ROUGH OPENING
DALLAS COUNTY ELECTIONS BUILDING
ADJACENT CONSTRUCTION -
REFERENCE FLOOR PLANS
1460 ROUND TABLE DR
TYPICAL FRAMING - REF.
PARTITION TYPE FOR TYPICAL FRAMING - REF. DALLAS, TX 75247
DOOR TRIM
CONSTRUCTION DETAILS PARTITION TYPE FOR The drawings and written material herein constitute original work of the
HEAD
CONSTRUCTION DETAILS architect, and as intellectual property and instruments of service, are
CLEAR GLAZING ACOUSTIC BLANKET subject to copyright and may not be reproduced, distributed, published
ROUGH OPENING

DRYWALL SCREW - TYPICAL


CABINET HEIGHT

INSULATION IN PARTITION or used in any way without the express written consent of the architect.
1/2" original issue
DOOR HANDLE FLAT PANEL TELEVISION AS
MAX. DESIGN DEVELOPMENT 04.30.2021
3"

DRYWALL J-MOLD EACH SIDE SPECIFIED CENTERED IN


NON-RATED FIRE EXTINGUISHER OPENING TO BE FLUSH WITH revisions
CABINET OUTER WALL

FIRE RATED SEALANT


EACH SIDE PROVIDE BLOCKING IN
REFER TO TV SPECS.

PARTITION FOR SUPPORT OF ACOUSTIC INSULATION AS


ELEVATION MONITOR COORDINATE W/ SCHEDULED
MOUNTING SCREWS
MONITOR DIMENSIONS
MOUNTING BRACKET
NON-RATED PARTITION -
REFERENCE PLANS AND FILL GAP W/ ACOUSTIC
VERIFY
DEPTH

PARTITION TYPE INSULATION


GLASS OR MINERAL FIBER
INSULATION ELECTRICAL/AV JUNCTION BOX
VARIES BEHIND TELEVISION REFER
3"

TO ELEVATION FOR MOUNTING title


ROUGH OPENING COORDINATE W/ TV SPECS. HEIGHT METAL CONTROL JOINT EACH
5/8" 1/2"
DIMENSION

TYPICAL FRAMING - REF. SIDE - TAPE AND BED AS GYPSUM DETAILS


TRIM

CL MIN. MAX. PARTITION TYPES FOR PARTITION AS SCHEDULED REQUIRED


NON-RATED FIRE CONSTRUCTION DETAILS REFER TO PLAN
PLAN EXTINGUISHER CABINET JAMB/SILL

5/8' TYPE "X" GYPSUM BOARD 1 LAYER 5/8" GYPSUM BOARD


UL R4024-7-8
4/30/2021 3:48:39 PM

EACH SIDE - REFERENCE EACH SIDE - REFERENCE


PLANS AND PARTITION TYPE PARTITION TYPE SHEET project number 20182.200
FOR CONSTRUCTION OF
PARTITION date 04.30.2021
NON-RATED FIRE EXTINGUISHER GYPSUM BOARD CONTROL JOINT -
sheet

09 CABINET - NON-RATED PARTITION


07 PERIMETER RELIEF DETAIL
04 TYPICAL TELEVISION NICHE SECTION
01 NON-RATED PARTITION
SCALE: 1 1/2" = 1'-0" SCALE: 6" = 1'-0" SCALE: 3" = 1'-0" SCALE: 6" = 1'-0"

A0.87
plotted:
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt

SITE DEMOLITION KEYNOTES


NUMBER KEYNOTE

0 EXCAVATE EXISTING SOIL FOR NEW LOADING DOCK


01 EXISTING PARKING SPOT/STRIPING TO BE REMOVED.
02 DEMOLISH EXISTING FENCE/CONTROLLED ACCESS GATES, TYP.
03 REMOVE PORTION OF EXISTING FENCE
04 EXISTING PAVING TO BE REMOVED
05 DEMOLISH EXISTING CONCRETE ENTRY & STAIRS
06 REMOVE EXISTING GENERATOR & MECHANICAL EQUIPMENT. GENERATOR HAS FUEL TANK THAT WILL NEED TO BE EMPTIED PRIOR TO DEMOLITION
07 DEMOLISH EXISTING BRICK WALLS, TYP
08 CUT TRENCH BETWEEM ADJACENT BUILDING TO RUN CONDUITS BETWEEN BUILDINGS, REF TO CIVIL/TECHNOLOGY FOR LOCATION architecture interiors planning graphics
09 REMOVE ALL EXISTING LIGHTING POLES
8070 Park Lane, Ste. 300 Dallas, Texas 75231
Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com

These documents are issued for pricing only


and are not for regulatory approval,
permitting or construction.

Arch: Donald R. Powell, Jr. Reg. No.: 7206


Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
KING JAMES DR. 214-653-6437

project manager
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X PRITCHARD ASSOCIATES

X X
X

2121 NORTH AKARD ST, SUITE 100

X
X

X
X
X

X
X
X

X
DALLAS, TX 75201

X
X

X
X

X
02

X
X 214-849-0011

X
X

X
X
X

X
X
X

X
X
X

X
02 project manager

X
X

X
X

06

X
X

X
X
JPC CONSULTING
X
X

X
X

X
2627 MARTIN LUTHER KING JR. BLVD.
X

X
07
X

X
X

X
DALLAS, TX 75215
X
X

X
X
X

X
X
X X X
X
X 09 214-941-4297

X
X X
X
X
m.e.p. engineer

X
X

ROU
X
X

X
X
PURDY-MCGUIRE, INC.
X

X 17300 N. DALLAS PARKWAY, SUITE 3000


01
X

X DALLAS, TX 75248

ND
X
972-239-5357
X

X
X

TABL
X

02/AD4.01
X civil
X
X

PACHECO KOCH
X

X
X

7557 RAMBLER RD. #1400


X

E
X

DALLAS, TX 75234
X
X

DR.
06 972.235.3031
X
X

X X
X
X

0 05 landscape
X

X
X

PACHECO KOCH
X
X

02 7557 RAMBLER RD. #1400


X
X

DALLAS, TX 75234
X

X X

X X X X X X X X X X X X X X X X X X X
972.235.3031
X
X

structural engineer
X

04
EJES INCORPORATED
X
X

12801 N. CENTRAL EXPY, SUITE 700


X

DALLAS, TX 75243
X

04
214.3431210
X
X

security, audio/visual
X
X

NOVOM GROUP
X

400 S. RECORD ST, SUITE 1200


X

DALLAS, TX 75202
X

01
X

214-882-1540
X
X

project
X

DALLAS COUNTY ELECTIONS BUILDING


X

1460 ROUND TABLE DR


X
X

DALLAS, TX 75247
X

The drawings and written material herein constitute original work of the
X

architect, and as intellectual property and instruments of service, are


X

subject to copyright and may not be reproduced, distributed, published


X

or used in any way without the express written consent of the architect.
X

original issue
X
X

DESIGN DEVELOPMENT 04.30.2021


X

revisions
X
X
X

01 01/AD4.01
X

X
X

X
X

EXISTING ENTRANCE
X

TO REMAIN AS IS 01 05 02
X
X

X
X

X
X

X
01
X

X
01
X
X

X
X

X
title
X

X
X

01
08
01 07 DEMOLITION SITE PLAN

X
X
X

X
X

X
03
X

X
X
4/30/2021 3:50:00 PM

X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
X

X
X
project number 20182.200

X
X
date 04.30.2021
sheet

01 DEMOLITION SITE PLAN


AD1.01
plotted:

SCALE: 1" = 30'-0"


ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
PARKING SCHEDULE SITE KEYNOTES SITE LEGEND
TYPE COUNT PERCENTAGE NUMBER KEYNOTE
PROPERTY LINE
STANDARD 378 83.8% 01 NEW CONTROLLED ACCESS GATE WITH KNOX BOX NEW CROSSWALK
HANDICAP (VAN) 2 0.4% 02 NEW CROSSWALK STRIPING FIRE LANE
HANDICAP 8 1.8% 03 NEW FIRE LANE STRIPING
ELECTRICAL CHARGING 2 0.4% 04 PROVIDE ELECTRICAL VEHICLE CHARGING STATION, REF CIVIL FOR REQUIREMENTS X EXISTING SECURITY FENCE
05 PROVIDE NEW HANDICAP SPACES HANDICAP PARKING SPOT
61 13.5%
GRAND TOTAL: 451 100.0% 06 NEW ENTRY WITH CANOPY X NEW SECURITY FENCE
07 EXISTING ENTRY, CANOPY, AND RAMP TO REMAIN. REFINISH/REPAIR EXISTING STRUCTURE AS REQUIRED.
08 NEW MONUMENT SIGN ELECTRICAL CAR CHARGING STATION
09 NEW SITE SIGN NEW LIGHT POLES
10 NEW CONCRETE, REF CIVIL FOR LOCATIONS & TYPW OF CONCRETE
11 ADDITIONAL CONCRETE TO REDUCE PONDING, THROUGHOUT. REF TO CIVIL FOR LOCATIONS
EXISTING CONCRETE
12 PROVIDE ADDITIONAL MOTION SITE LIGHTING architecture interiors planning graphics
EXISTING TREE
13 NEW SPEED BUTTONS, REFER TO ALTERNATES
14 PROVIDE NEW STANDARD PARKING SPOTS 8070 Park Lane, Ste. 300 Dallas, Texas 75231
NEW CONCRETE
15 WASH OR REFINISH EXISTING BRICK FACADES THROUGHOUT, REF ALTERNATES
16 EXISTING INLET. ROUTE AND PAVE CROSSWALK AROUND INLET TO MAINTAIN REQUIRED CROSSWALK CROSS SLOPE Tel 972.701.9000 Fax 972.991.3008
NEW TREE
17 EXISTING & NEW FLAG POLE, REF TO ALTERNATES www.bokapowell.com
18 NEW LIGHT POLES ON EXISTING BASES
19 SAW CUT IN EXISTING PAVING AS AN ALTERNATE, REFER TO TECHNOLOGY DRAWINGS
20 PIPE BOLLARD, TYP These documents are issued for pricing only
and are not for regulatory approval,
permitting or construction.

Arch: Donald R. Powell, Jr. Reg. No.: 7206


Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437
KING JAMES DR.
project manager
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X PRITCHARD ASSOCIATES

X X
X

2121 NORTH AKARD ST, SUITE 100

X
X

X
X
X

X
X

X
X X X X X X X X X X X
DALLAS, TX 75201
X

X
X

X
X

X
X

X 214-849-0011

X
X
X

X
01

X
X

X
X GENERATOR
15

X
project manager

X
X TRANSFORMER

X
X 01

X
X
X
JPC CONSULTING

X
X 2627 MARTIN LUTHER KING JR. BLVD.
X

X
X DALLAS, TX 75215
X
X
18 214-941-4297
X
X
09
m.e.p. engineer

ROU
X
X
X
PURDY-MCGUIRE, INC.
X 17300 N. DALLAS PARKWAY, SUITE 3000
11
X DALLAS, TX 75248

ND
X
X
972-239-5357

TABL
X
X civil
X

PACHECO KOCH
X

01 / A1.12
X

7557 RAMBLER RD. #1400

E
01 / A1.11
X

DALLAS, TX 75234
X

DR.
972.235.3031
X
X

landscape
X
X

14
PACHECO KOCH
X

7557 RAMBLER RD. #1400


X

10
DALLAS, TX 75234
X

972.235.3031
X
X

structural engineer
X

EJES INCORPORATED
X
X

12801 N. CENTRAL EXPY, SUITE 700


X

DALLAS, TX 75243
X

214.3431210
X
X

security, audio/visual
X
X

15
NOVOM GROUP
X

400 S. RECORD ST, SUITE 1200


X

DALLAS, TX 75202
X
X

02 214-882-1540
12
X
X

J project
X

DALLAS COUNTY ELECTIONS BUILDING


X

1460 ROUND TABLE DR


X

07 J
X

DALLAS, TX 75247
X

The drawings and written material herein constitute original work of the
X

architect, and as intellectual property and instruments of service, are


X

subject to copyright and may not be reproduced, distributed, published


X

11 or used in any way without the express written consent of the architect.
X

15 original issue
X
X

DESIGN DEVELOPMENT 04.30.2021


X

24'-0" revisions
X

8'-0" 5'-0" 8'-0" 8'-0" 5'-0" 8'-0" 8'-0" 5'-0" 8'-0" 8'-0" 5'-0" 8'-0" 8'-0" 8'-0" 8'-0"
17
X
X

08
15
X
X

X
13
X

07 05 06
X

03 13 01
X

16 02
X

X
X

X
X

04

X
X

X
X
X

X
X

X
title
X

X
X

11 19 20 SITE PLAN

X
X
X

X
X

X
X

X
X
4/30/2021 3:48:56 PM

X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
X

X
X
project number 20182.200

X
X
date 04.30.2021
sheet

01 SITE PLAN
A1.01
plotted:

SCALE: 1" = 30'-0"


TRUE PLAN
NORTH NORTH
C:\BOKAP\REVIT_PROJECTS\ARCH_20182_DALLAS_COUNTY_ELECTIONS_Alan-Macejewski.rvt

T
WA architecture interiors planning graphics
8070 Park Lane, Ste. 300Dallas, Texas 75231

GAS
8"WATER
WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT

WA
TUGT
SAN
WAT

RIM=407.78
BENCHMARK #1:

RIM=407.22
WAT SQUARE CUT
ELEV=406.47 Tel 972.701.9000Fax 972.991.3008
KING JAMES DRIVE 5'X3' BOX

WAT

ST
Δ=043°31'40" WA 3'X3' BOX

ST
T

RIM=407.15
60' Public ROW, Concrete Pavement FL(S)=399.30
R=300.00' FL10"=402.58 RIM=406.33
N01°38'55"W 670.24 FL(NE)=399.20 www.bokapowell.com

GAS
L=227.91' FL=399.73 FL10"=401.42

WAT

WA
TUGT
Concrete Walk

SAN
WA
T 24" PECAN 30'SP
CB=N 23°24'45" W POH POH POH POH POH POH POH POH POH POH POH POH POH
WW
POH POH POH POH POH POH
SAN SAN

S
CD=222.47'
SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN
SAPN T W

S
OH
GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS
T
GAS
TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG

CO

N67 40.28
SAPN
OH
5/8"FIR 24" PECAN 30'SP X-CUT SET
These documents are issued for pricing only
W
AT TGUAGS

and are not for regulatory approval,

°45
TGUAGS
RIM=406.79
ST

24" PECAN 20'SP


PO
FL18"(NE)=400.89
H
10 6 5 Conc. Pads
permitting or construction.

MH
MH

'35
FL(NW)=400.99
Manhole Pad Concrete Concrete

36" PECAN 65'SP


W
AT TGUAGS
35' BUILDING LINE Drive Drive
"SS

"E
RIM=407.06 Per Zoning A/C's
FL18"(SW)=403.16 10 PO
Transformer
H
Concrete 1/2"FIR

TUG WAT
225.5
ST

S
TGUASAN Pavement RIM=407.31 Concrete Pads
FL12"(W)=402.01 THIS SPACE RESERVED - BLDG INSPECTION
FFE= 409.40

19.7
Pavement
G

SAN
FL12"(E)=401.91
FFE= 409.36
18" PECAN 35'SP

A/C's

3"G
20
W PO
AT H
6

as
84.5

STO
S
TGUA AN
GS
FFE= 409.40
PO DP&L EASEMENT

TUG WAT
H 18 Vol. 68175, Pg. 102,
RIM=407.57

8"SS
W
AT
1/2"CIRF D.R.D.C.T. &

GAS
s
Ga Vol. 95178, Pg. 2704,
0 W 3" D.R.D.C.T.
27" PECAN 55'SP

.0 35" Concrete
PO
0
8 0'
H
Pavement RIM=407.08 client
S

TU
°1
FL12"(W)=402.18

42"
G
NO ACCESS
45
GA
FL12"(E)=402.28
DALLAS COUNTY

RC
S

TUG WAT
N

P
SAN
27
1460 ROUND TABLE DR

GAS
PO
H

179.5
STO
TU
G SAN
GA
S DALLAS, TX 75247
1/2"FIR
X
214-653-6437

6" HOLLY 15'SP

6" CREPE MYRTLE 15'SP


PO

TUG WAT
24" PECAN 40'SP

SAN
TU
G SAN
client representative

GAS
GA
S

STO
THIS SPACE RESERVED - ENGINEERING

6" HOLLY 15'SP


18"
RC
P PRITCHARD ASSOCIATES
FFE= 409.24 2121 NORTH AKARD ST, SUITE 100

TUG WAT
DALLAS, TX 75201

SAN
GAS
Δ=024°51'00"
RIM=405.99 #1460 Roundtable Drive
One Story Masonry R=924.93' 214-849-0011

STO
FL12"(SW)=402.79

8" RED OAK 20'SP


Building Area = 104,285 SF L=401.16'

30" PECAN 60'SP


Building Height = 17.6 Feet FFE= 409.48 6.5 CB=N 80°11'05" E

322.5
m.e.p. engineer
24" PECAN 40'SP

27" PECAN 55'SP


CD=398.02'

TUG WAT
7" CREPE MYRTLE 20'SP
Covered Area
420,923 SF/9.6631 AC.
27" PECAN50'SP

20.5

SAN
LOT 3, BLOCK 10/7941 PURDY-MCGUIRE, INC.
FOURTH INSTALLMENT 6.5 Brick Walls
17300 N. DALLAS PARKWAY, SUITE 3000
KINGS ROW INDUSTRIAL DISTRICT
DALLAS, TX 75248

GAS
4

36" PECAN 65'SP


Vol. 68040, Pg. 2015, DRDCT

ROUND TAncBreLteEPaD
10" CREPE MYRTLE 20'SP
STO
972-239-5357

TUG WAT
60' Public ROW, Co
RI

SAN
M
=4 36" PECAN 65'SP
FU

07 RIM=406.33
LL

FL12"(W)=403.33
O

.
civil
84
F

BT FOODS TX HOLDINGS, LLC


DE
BR

Concrete
INST. NO. 201500151904, OPRDCT
IS

30" PECAN 60'SP

GAS
12
Block 10/7941 30" PECAN 65'SP

King Row Industrial District


Pavement
RIM=406.68
FL12"(SW)=403.88
PACHECO KOCH

TUG
Fourth Installment 7557 RAMBLER RD. #1400
ST

FFE= 409.26
O

WAT
Vol. 68040, Pg. 2014, D.R.D.C.T.

8"SS
12

142.2
DALLAS, TX 75234
S4

7" CREPE MYRTLE 20'SP


36" PECAN 65'SP

48"RCP
Cantex Regal LLC RIM=406.54
4

972.235.3031
9'

Inst. 201700215989, O.P.R.D.C.T. FL12"(N)=404.24


25

GAS
13
8" CREPE MYRTLE 15'SP
"W

6' Chain Link Fence


landscape

TUG
51

vement

WAT
3.

SAN
PACHECO KOCH

RIV
73

3"Gas
36" PECAN 65'SP

36" PECAN 65'SP


7557 RAMBLER RD. #1400

E
20' FIRE LANE EASEMENT 15 FFE= 409.42 FFE= 409.46 DALLAS, TX 75234

TUG
Vol. 68196, Pg. 142 WAT

GAS
D.R.D.C.T. 972.235.3031

12"WATER
310.0

8"SS
15
structural engineer

36" PECAN 65'SP


36" PECAN 65'SP

RIM=406.09 20' FIRE LANE EASEMENT EJES INCORPORATED

TUG
Vol. 68196, Pg. 142, D.R.D.C.T.
12801 N. CENTRAL EXPY, SUITE 700

GAS
FL12"(E)=404.09

SAN
WAT
36" PECAN 65'SP

RIM=406.02 STO DALLAS, TX 75243


11
RIM=407.26 STO STO STO STO STO 17
FL12"(S)=404.22
FL12"(N)=404.02
32 H H 3
STO
5/8"FIR
214.3431210
DEMOLITION GENERAL NOTES
STO STO STO STO STO STO STO STO STO
FULL OF DEBRIS

S87°23'25"E 68
Storm Sewer
Approx. Centerline
17 RIM=406.21 RIM=406.19
security, audio/visual

BENCHMARK #2:
FL12"(S)=402.41 32 FL12"(S)=400.99 6

36" PECAN 65'SP


FL12"(N)=402.31 FL12"(N)=400.89

ELEV=
Concrete
NOVOM GROUP

SAN
WA
Metal Fence

TU
400 S. RECORD ST, SUITE 1200

408.5
X-CUT
Pavement

G
T
w/ Brick Columns

DALLAS, TX 75202

0
.50
57 8
214-882-1540
5/8"FIR 1/2"CIRF
X X X X X X X X X
S01°38'55"E 605.79

GAS

SAN
WAT
project

TUG
5/8"FIR 6' Chain Link Fence AFFIDAVIT OF FACTS YELLOW
Δ=027°39'07" Vol. 2002068, Pg. 5345
R=88.08' D.R.D.C.T.
L=42.51' Block 7941 The County of Dallas, State of Texas Block 12/7941 DALLAS COUNTY ELECTIONS BUILDING
King Row Industrial District
CB=S 15°28'28" E
Fourth Installment
Inst. 20150222226, O.P.R.D.C.T. Roundtable Addition
Vol. 74103, Pg. 1425, D.R.D.C.T. 1460 ROUND TABLE DR
CD=42.10'
Jessup Investments LLC Vol. 68040, Pg. 2015, D.R.D.C.T.
ISSUED FOR PRELIMINARY PRICING PURPOSES ONLY DALLAS, TX 75247
Inst. 201400018000, O.P.R.D.C.T.
(SUBJECT TO REVISION PRIOR TO CONSTRUCTION) The drawings and written material herein constitute original work o
architect, and as intellectual property and instruments of service, a
subject to copyright and may not be reproduced, distributed, publis
or used in any way without the express written consent of the arch
original issue
DESIGN DEVELOPMENT 04.30.2021
revisions

DALLAS COUNTY ELECTIONS BUILDING


NOT FOR CONSTRUCTION

DEMOLITION PLAN
BENC MARK DALLAS COUNTY ELECTIONS BUILDING
LOT 3, BLOCK 10/7941
SUSTAINABLE DEVELOPMENT & CONSTRUCTION
CITY OF DALLAS, DALLAS COUNTY, TEXAS
DESIGN DRAWN DATE SCALE FILE NUMBER SHEET
title
C04.01 DEMOLITION PLAN
4/22/2021 5:30:27 PM

project number 20182.200


date 04.30.2021
sheet

C04.01
plotted:
C:\BOKAP\REVIT_PROJECTS\ARCH_20182_DALLAS_COUNTY_ELECTIONS_Alan-Macejewski.rvt

architecture interiors planning graphics


8070 Park Lane, Ste. 300Dallas, Texas 75231

RIM=407.78
BENCHMARK #1:
Tel 972.701.9000Fax 972.991.3008

RIM=407.22
SQUARE CUT
ELEV=406.47
KING JAMES DRIVE

ST
Δ=043°31'40"
www.bokapowell.com

ST
R=300.00' FL10"=402.58
60' Public ROW, Concrete Pavement N01°38'55"W 670.24
L=227.91' FL10"=401.42
Concrete Walk
CB=N 23°24'45" W WW

S
CD=222.47' T W

S
T These documents are issued for pricing only

CO

N67 40.28
5/8"FIR X-CUT SET
and are not for regulatory approval,

°45
ST

10 6 5 permitting or construction.

MH
MH

'35
Manhole Pad Concrete Concrete

36" PECAN 65'SP


35' BUILDING LINE Drive Drive

"E
Per Zoning
Concrete 225.5 1/2"FIR THIS SPACE RESERVED - BLDG INSPECTION
ST

Pavement Concrete
FFE= 409.40

19.7
Pavement FFE= 409.36
18" PECAN 35'SP

20
6 84.5

FFE= 409.40
18
DP&L EASEMENT
Vol. 68175, Pg. 102,
RIM=407.57

1/2"CIRF D.R.D.C.T. &


Vol. 95178, Pg. 2704,
0 W D.R.D.C.T. client
27" PECAN 55'SP

0 .0 35" Concrete
Pavement
8 0'
S

45
°1 NO ACCESS
DALLAS COUNTY
N
27 1460 ROUND TABLE DR
DALLAS, TX 75247

179.5
1/2"FIR 214-653-6437
24" PECAN 40'SP

THIS SPACE RESERVED - ENGINEERING


client representative
PRITCHARD ASSOCIATES
FFE= 409.24
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
#1460 Roundtable Drive Δ=024°51'00"
R=924.93'
214-849-0011
One Story Masonry

8" RED OAK 20'SP


Building Area = 104,285 SF L=401.16'

30" PECAN 60'SP


Building Height = 17.6 Feet FFE= 409.48 6.5 CB=N 80°11'05" E m.e.p. engineer

322.5
24" PECAN 40'SP

27" PECAN 55'SP


CD=398.02'

7" CREPE MYRTLE 20'SP


Covered Area
420,923 SF/9.6631 AC. PURDY-MCGUIRE, INC.
27" PECAN50'SP

20.5
LOT 3, BLOCK 10/7941 17300 N. DALLAS PARKWAY, SUITE 3000
FOURTH INSTALLMENT 6.5 Brick Walls

4
KINGS ROW INDUSTRIAL DISTRICT DALLAS, TX 75248

36" PECAN 65'SP


Vol. 68040, Pg. 2015, DRDCT

RO
972-239-5357

60' Public ROW, Co


UND TAncBreLteEPaD
36" PECAN 65'SP

civil
BT FOODS TX HOLDINGS, LLC
Block 10/7941 30" PECAN 65'SP
30" PECAN 60'SP
12 Concrete
Pavement INST. NO. 201500151904, OPRDCT PACHECO KOCH
King Row Industrial District
Fourth Installment FFE= 409.26
7557 RAMBLER RD. #1400
Vol. 68040, Pg. 2014, D.R.D.C.T. 12 DALLAS, TX 75234

142.2
S4

7" CREPE MYRTLE 20'SP


972.235.3031
4

36" PECAN 65'SP


°4

Cantex Regal LLC


9'

Inst. 201700215989, O.P.R.D.C.T.


25

13
8" CREPE MYRTLE 15'SP landscape
"W

6' Chain Link Fence


51

vement
PACHECO KOCH
3.

RIVE
73

36" PECAN 65'SP


7557 RAMBLER RD. #1400
36" PECAN 65'SP
DALLAS, TX 75234
20' FIRE LANE EASEMENT FFE= 409.42 FFE= 409.46
Vol. 68196, Pg. 142
D.R.D.C.T.
15
310.0
972.235.3031
15 structural engineer

36" PECAN 65'SP


36" PECAN 65'SP

EJES INCORPORATED
20' FIRE LANE EASEMENT
Vol. 68196, Pg. 142, D.R.D.C.T. 12801 N. CENTRAL EXPY, SUITE 700
36" PECAN 65'SP DALLAS, TX 75243
11 32 H H 3 5/8"FIR 214.3431210
17

S87°23'25"E 68
17 security, audio/visual

BENCHMARK #2:
32 6
NOVOM GROUP

36" PECAN 65'SP

ELEV=408.50
GENERAL NOTES Concrete Metal Fence 400 S. RECORD ST, SUITE 1200

X-CUT
Pavement
w/ Brick Columns
DALLAS, TX 75202

.50
57 8 214-882-1540
5/8"FIR 1/2"CIRF
project
X X X X X X X X X
S01°38'55"E 605.79 YELLOW
5/8"FIR 6' Chain Link Fence AFFIDAVIT OF FACTS
Δ=027°39'07" Vol. 2002068, Pg. 5345
R=88.08' D.R.D.C.T. DALLAS COUNTY ELECTIONS BUILDING
L=42.51'
CB=S 15°28'28" E
Block 7941
King Row Industrial District
The County of Dallas, State of Texas
Inst. 20150222226, O.P.R.D.C.T.
Block 12/7941
Roundtable Addition 1460 ROUND TABLE DR
CD=42.10' Fourth Installment
Vol. 68040, Pg. 2015, D.R.D.C.T.
Vol. 74103, Pg. 1425, D.R.D.C.T.
ISSUED FOR PRELIMINARY PRICING PURPOSES ONLY DALLAS, TX 75247
Jessup Investments LLC
Inst. 201400018000, O.P.R.D.C.T. (SUBJECT TO REVISION PRIOR TO CONSTRUCTION) The drawings and written material herein constitute original work o
architect, and as intellectual property and instruments of service, a
subject to copyright and may not be reproduced, distributed, publis
or used in any way without the express written consent of the arch
original issue
DESIGN DEVELOPMENT 04.30.2021
revisions

DALLAS COUNTY ELECTIONS BUILDING


NOT FOR CONSTRUCTION

BENC MARK DIMENSIONAL CONTROL PLAN


DALLAS COUNTY ELECTIONS BUILDING
LOT 3, BLOCK 10/7941
SUSTAINABLE DEVELOPMENT & CONSTRUCTION
CITY OF DALLAS, DALLAS COUNTY, TEXAS
DESIGN DRAWN DATE SCALE FILE NUMBER SHEET
title
C05.01 DIMENSIONAL CONTROL
PLAN
4/22/2021 5:30:27 PM

project number 20182.200


date 04.30.2021
sheet

C05.01
plotted:
C:\BOKAP\REVIT_PROJECTS\ARCH_20182_DALLAS_COUNTY_ELECTIONS_Alan-Macejewski.rvt

RIM=407.78
BENCHMARK #1:

RIM=407.22
SQUARE CUT
ELEV=406.47
KING JAMES DRIVE

ST
Δ=043°31'40"

ST
R=300.00' 60' Public ROW, Concrete Pavement N01°38'55"W 670.24
L=227.91'
FL10"=402.58
FL10"=401.42
Concrete Walk
architecture interiors planning graphics
CB=N 23°24'45" W WW
8070 Park Lane, Ste. 300Dallas, Texas 75231

S
CD=222.47' T W

S
T

CO

N67 40.28
5/8"FIR X-CUT SET

Tel 972.701.9000Fax 972.991.3008

°45
ST

MH
MH

'35
Concrete Concrete
Manhole Pad 35' BUILDING LINE Drive Drive www.bokapowell.com

"E
Per Zoning
Concrete 225.5 1/2"FIR
ST
Pavement Concrete

19.7
Pavement FFE= 409.36 FFE= 409.40

6 84.5
These documents are issued for pricing only
and are not for regulatory approval,
FFE= 409.40
DP&L EASEMENT permitting or construction.
Vol. 68175, Pg. 102,
RIM=407.57

1/2"CIRF D.R.D.C.T. &


Vol. 95178, Pg. 2704,
0 W D.R.D.C.T.
.0 35" Concrete THIS SPACE RESERVED - BLDG INSPECTION
0
8 0' Pavement
S

°1 NO ACCESS
45
N

179.5
1/2"FIR

client
DALLAS COUNTY
1460 ROUND TABLE DR
FFE= 409.24 DALLAS, TX 75247
Δ=024°51'00" 214-653-6437
#1460 Roundtable Drive R=924.93'
One Story Masonry
Building Area = 104,285 SF L=401.16'
client representative
Building Height = 17.6 Feet FFE= 409.48 6.5 CB=N 80°11'05" E THIS SPACE RESERVED - ENGINEERING

322.5
420,923 SF/9.6631 AC. Covered Area CD=398.02' PRITCHARD ASSOCIATES

20.5
LOT 3, BLOCK 10/7941 2121 NORTH AKARD ST, SUITE 100
FOURTH INSTALLMENT 6.5 Brick Walls
DALLAS, TX 75201
KINGS ROW INDUSTRIAL DISTRICT
Vol. 68040, Pg. 2015, DRDCT 214-849-0011

RO
60' Public ROW, Co
m.e.p. engineer

UND TAncBreLteEPaD
Concrete
BT FOODS TX HOLDINGS, LLC PURDY-MCGUIRE, INC.
Block 10/7941 Pavement INST. NO. 201500151904, OPRDCT
King Row Industrial District 17300 N. DALLAS PARKWAY, SUITE 3000
Fourth Installment
Vol. 68040, Pg. 2014, D.R.D.C.T.
FFE= 409.26
DALLAS, TX 75248

142.2
S4

972-239-5357

Cantex Regal LLC


49

Inst. 201700215989, O.P.R.D.C.T.


'2
5

civil
"W

6' Chain Link Fence


51

vement
PACHECO KOCH
3.

RIVE
37

7557 RAMBLER RD. #1400


DALLAS, TX 75234
20' FIRE LANE EASEMENT FFE= 409.42 FFE= 409.46
Vol. 68196, Pg. 142
D.R.D.C.T. 310.0
972.235.3031
landscape
PACHECO KOCH
20' FIRE LANE EASEMENT
Vol. 68196, Pg. 142, D.R.D.C.T. 7557 RAMBLER RD. #1400
DALLAS, TX 75234
5/8"FIR 972.235.3031
structural engineer

S87°23'25"E 68

BENCHMARK #2:
EJES INCORPORATED

ELEV=408.50
Concrete Metal Fence
12801 N. CENTRAL EXPY, SUITE 700
DALLAS, TX 75243

X-CUT
Pavement
w/ Brick Columns

214.3431210

.50
CITY O DALLAS DRIVE APPROAC NOTES OR ORK IT IN PUBLIC
RIG T O AY ONLY 5/8"FIR
X X X
S01°38'55"E 605.79
X X X X X X
1/2"CIRF
YELLOW
security, audio/visual
5/8"FIR 6' Chain Link Fence AFFIDAVIT OF FACTS
Δ=027°39'07"
R=88.08'
Vol. 2002068, Pg. 5345
D.R.D.C.T. NOVOM GROUP
L=42.51' Block 7941 The County of Dallas, State of Texas Block 12/7941 400 S. RECORD ST, SUITE 1200
CB=S 15°28'28" E King Row Industrial District Inst. 20150222226, O.P.R.D.C.T. Roundtable Addition DALLAS, TX 75202
CD=42.10' Fourth Installment Vol. 74103, Pg. 1425, D.R.D.C.T.
Jessup Investments LLC Vol. 68040, Pg. 2015, D.R.D.C.T.
Inst. 201400018000, O.P.R.D.C.T.
214-882-1540
project
DALLAS COUNTY ELECTIONS BUILDING
CITY O DALLAS NOTES OR ORK IT IN PUBLIC
RIG T O AY ONLY
1460 ROUND TABLE DR
ISSUED FOR PRELIMINARY PRICING PURPOSES ONLY DALLAS, TX 75247
(SUBJECT TO REVISION PRIOR TO CONSTRUCTION) The drawings and written material herein constitute original work o
architect, and as intellectual property and instruments of service, a
subject to copyright and may not be reproduced, distributed, publis
or used in any way without the express written consent of the arch
PRIVATE PAVING GENERAL NOTES original issue
DESIGN DEVELOPMENT 04.30.2021
CITY O DALLAS SIDE ALK NOTES OR ORK IT IN PUBLIC
revisions
RIG T O AY ONLY

DALLAS COUNTY ELECTIONS BUILDING


NOT FOR CONSTRUCTION

PAVING PLAN
DALLAS COUNTY ELECTIONS BUILDING
LOT 3, BLOCK 10/7941
SUSTAINABLE DEVELOPMENT & CONSTRUCTION
CITY OF DALLAS, DALLAS COUNTY, TEXAS
DESIGN DRAWN DATE SCALE FILE NUMBER SHEET
title
C06.01 PAVING PLAN
4/22/2021 5:30:27 PM

project number 20182.200


date 04.30.2021
sheet

C06.01
plotted:
C:\BOKAP\REVIT_PROJECTS\ARCH_20182_DALLAS_COUNTY_ELECTIONS_Alan-Macejewski.rvt

architecture interiors planning graphics


8070 Park Lane, Ste. 300Dallas, Texas 75231
Tel 972.701.9000Fax 972.991.3008
www.bokapowell.com

These documents are issued for pricing only


and are not for regulatory approval,
permitting or construction.

THIS SPACE RESERVED - BLDG INSPECTION

client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437
CONCRETE PAVEMENT client representative
PAVEMENT SECTION SA ED DUMMY OINT CONNECTION E PANSION OINT THIS SPACE RESERVED - ENGINEERING

1 3 4 PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
214-849-0011
m.e.p. engineer
PURDY-MCGUIRE, INC.
17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
972-239-5357
civil
PACHECO KOCH
7557 RAMBLER RD. #1400
DALLAS, TX 75234
972.235.3031
landscape
PACHECO KOCH
7557 RAMBLER RD. #1400
CONSTRUCTION OINT ISOLATION OINT INTEGRAL CURB CONCRETE ALK DALLAS, TX 75234
5 6 7 PRIVATE 972.235.3031
structural engineer
EJES INCORPORATED
12801 N. CENTRAL EXPY, SUITE 700
DALLAS, TX 75243
214.3431210
security, audio/visual
NOVOM GROUP
400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
214-882-1540
project
DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
ISSUED FOR PRELIMINARY PRICING PURPOSES ONLY DALLAS, TX 75247
(SUBJECT TO REVISION PRIOR TO CONSTRUCTION) The drawings and written material herein constitute original work
architect, and as intellectual property and instruments of service,
subject to copyright and may not be reproduced, distributed, pub
or used in any way without the express written consent of the arc
original issue
DESIGN DEVELOPMENT 04.30.2021
revisions

DALLAS COUNTY ELECTIONS BUILDING


NOT FOR CONSTRUCTION

PAVING DETAILS
DALLAS COUNTY ELECTIONS BUILDING
LOT 3, BLOCK 10/7941
SUSTAINABLE DEVELOPMENT & CONSTRUCTION
CITY OF DALLAS, DALLAS COUNTY, TEXAS
DESIGN DRAWN DATE SCALE FILE NUMBER SHEET
title
C06.50 PAVING DETAILS
4/22/2021 5:30:27 PM

project number 20182.200


date 04.30.2021
sheet

C06.50
plotted:
C:\BOKAP\REVIT_PROJECTS\ARCH_20182_DALLAS_COUNTY_ELECTIONS_Alan-Macejewski.rvt

8"WATER
architecture interiors planning graphics

RIM=407.78
BENCHMARK #1:

RIM=407.22
SQUARE CUT
ELEV=406.47
KING JAMES DRIVE

TC 406.56
8070 Park Lane, Ste. 300Dallas, Texas 75231

G 406.51

TC 407.66
5'X3' BOX

TC 407.88

TC 407.72

TC 406.80
TC 407.03

ST
TC 406.17
TC 406.62

TC 407.40

G 407.26
Δ=043°31'40" 3'X3' BOX

G 407.29

G 407.33

G 406.64

G 406.34
G 406.22
G 406.26

G 406.95
ST

RIM=407.15
R=300.00' 60' Public ROW, Concrete Pavement N01°38'55"W 670.24 FL(S)=399.30

TC 407.58
FL10"=402.58 RIM=406.33 FL(NE)=399.20

G 407.10
407
L=227.91'
CB=N 23°24'45" W
406 FL=399.73 TC 406.52
G 406.08
FL10"=401.42
Concrete Walk Tel 972.701.9000Fax 972.991.3008
WW

S
CD=222.47' T W

S
T www.bokapowell.com

CO

N67 40.28
407 5/8"FIR 407 X-CUT SET

TC 408.42

TC 4 6.89
G 407.97

G4
G 407.97
TC 408.38

G 408.21
TC 408.77
G 408.35
G 408.73

°45
TC 408.86
TC 409.23
RIM=406.79

G 408.22
TC 408.62
ST

6 5 Conc. Pads

0
07.4
FL18"(NE)=400.89 10

G 409.20
TC 409.69

MH
MH

'35
FL(NW)=400.99

G 409.23
TC 409.68

2
Manhole Pad Concrete Concrete

36" PECAN 65'SP


35' BUILDING LINE Drive
These documents are issued for pricing only

408
"SS Drive

"E
G 407.71
TC 408.18
RIM=407.06

408
10 Per Zoning

G 408.07
TC 408.59
G 408.22
TC 408.73
FL18"(SW)=403.16
Concrete 408 1/2"FIR
and are not for regulatory approval,

G 408.76
TC 409.33
225.5
ST

RIM=407.31 Concrete
TC 407.12 Pavement permitting or construction.

409

TC 409.05
G 408.64
FL12"(W)=402.01 FFE= 409.40

19.7
G 406.45
FL12"(E)=401.91
Pavement FFE= 409.36
18" PECAN 35'SP
40

3"G
407
20

TC 408.82
7

G 408.45

TC 406.84
TC 407.50

G 406.31
G 407.03

84.5

as
THIS SPACE RESERVED - BLDG INSPECTION
FFE= 409.40

TC 407.40
G 408.77
TC 409.24

G 408.78
TC 409.25
G 408.49
TC 409.04

406

G 407.00
DP&L EASEMENT

G 408.65
TC 409.16
18 408
Vol. 68175, Pg. 102,
RIM=407.57

8"SS
1/2"CIRF D.R.D.C.T. &
as

G 408.34
TC 408.83
G Vol. 95178, Pg. 2704,

G 408.45
TC 408.95
3"

TC 407.93
408
0 W

G 407.46
G 408.49
TC 409.04
D.R.D.C.T.
27" PECAN 55'SP

0.0 35" Concrete


Pavement RIM=407.08
8 0'
408
S
TC 408.20
G 407.71

FL12"(W)=402.18
°1

42"
NO ACCESS
407
45
FL12"(E)=402.28

RCP
N
27 408
40 client

179.5
7

G 406.32
TC 406.77
408

TC 406.87
DALLAS COUNTY

G 406.30
TC 408.31
G 408.39

G 408.52
TC 408.96
1/2"FIR 408

1460 ROUND TABLE DR


40

408
24" PECAN 40'SP
9

40
7
DALLAS, TX 75247
40 40
214-653-6437

408
8
18"
8

4
RC

07

G 408.79
TC 409.37
40
P
9
40
8 FFE= 409.24
THIS SPACE RESERVED - ENGINEERING
client representative
#1460 Roundtable Drive Δ=024°51'00" PRITCHARD ASSOCIATES

TC 407.06
RIM=405.99

G 406.51
One Story Masonry R=924.93'
FL12"(SW)=402.79
2121 NORTH AKARD ST, SUITE 100

8" RED OAK 20'SP


407 Building Area = 104,285 SF L=401.16'

30" PECAN 60'SP


40
8 Building Height = 17.6 Feet FFE= 409.48 6.5 CB=N 80°11'05" E DALLAS, TX 75201

322.5
24" PECAN 40'SP

27" PECAN 55'SP


40

CD=398.02'
214-849-0011

7" CREPE MYRTLE 20'SP


9

Covered Area
420,923 SF/9.6631 AC.
27" PECAN50'SP

20.5
407
LOT 3, BLOCK 10/7941
FOURTH INSTALLMENT Brick Walls

409
KINGS ROW INDUSTRIAL DISTRICT
6.5
m.e.p. engineer
4

36" PECAN 65'SP


Vol. 68040, Pg. 2015, DRDCT

RO
408
PURDY-MCGUIRE, INC.

40

60' Public ROW, Co


8
RI
M 17300 N. DALLAS PARKWAY, SUITE 3000

UND TAncBreLteEPaD
=4 36" PECAN 65'SP
FU

RIM=406.33
0
DALLAS, TX 75248
LL

7. 40 7
40

FL12"(W)=403.33

TC 407.26

TC 407.04
O

G 407.33
TC 407.85
8

G 406.82

G 406.59
F

4
BT FOODS TX HOLDINGS, LLC
DE

407 7

GG408.90
TC 409.36
40
972-239-5357
BR

Concrete
INST. NO. 201500151904, OPRDCT
I

30" PECAN 60'SP

408.63
409.03
S

12 407
Block 10/7941 30" PECAN 65'SP Pavement
RIM=406.68

408
King Row Industrial District TC 407.53
407
FL12"(SW)=403.88
Fourth Installment
G 407.04

Vol. 68040, Pg. 2014, D.R.D.C.T.


FFE= 409.26
civil

8"SS
12

142.2
S4

7" CREPE MYRTLE 20'SP


PACHECO KOCH
4

36" PECAN 65'SP

48"RCP
°4

Cantex Regal LLC RIM=406.54


9'

G 408.56
TC 408.99
Inst. 201700215989, O.P.R.D.C.T. FL12"(N)=404.24
7557 RAMBLER RD. #1400
25

13

G 407.74
TC 408.20
8" CREPE MYRTLE 15'SP

G 407.76G 407.59
TC 408.19
G 407.06
TC 407.55
"

408
6' Chain Link Fence
W

DALLAS, TX 75234
51

vement
G 407.00
TC 407.49

G 407.45
TC 407.94
TC 408.10

G 406.80
TC 407.29
972.235.3031
3 .7

RIVE
3"Gas
3

36" PECAN 65'SP

G 407.51
TC 408.01
G 406.99
TC 407.56

40
8
408

36" PECAN 65'SP landscape

408
20' FIRE LANE EASEMENT 15 FFE= 409.42 FFE= 409.46
PACHECO KOCH
Vol. 68196, Pg. 142

TC 408.27

TC 407.68
G 407.80

G 407.21
409

D.R.D.C.T.

12"WATER
409
408
310.0
7557 RAMBLER RD. #1400

8"SS
407
15
DALLAS, TX 75234

TC 408.57
36" PECAN 65'SP
36" PECAN 65'SP

G 408.12
408
972.235.3031

TC 408.04
07 407

G 407.69
4
RIM=406.09 20' FIRE LANE EASEMENT

408
FL12"(E)=404.09 Vol. 68196, Pg. 142, D.R.D.C.T.
structural engineer
407

36" PECAN 65'SP

11 RIM=406.02
FL12"(S)=404.22 32 3 5/8"FIR
EJES INCORPORATED
H H
RIM=407.26
FULL OF DEBRIS
17 FL12"(N)=404.02
12801 N. CENTRAL EXPY, SUITE 700

S87°23'25"E 68
Storm Sewer
DALLAS, TX 75243

408
Approx. Centerline

TC 408.08
G 407.62
17 RIM=406.21 RIM=406.19

BENCHMARK #2:
408 32 6
FL12"(S)=402.41 FL12"(S)=400.99
214.3431210
40

36" PECAN 65'SP


FL12"(N)=402.31 FL12"(N)=400.89

ELEV=408.50
8

40
Concrete 7
407 Metal Fence

G 408.22
TC 408.65

X-CUT
Pavement
407 w/ Brick Columns security, audio/visual

TC 407.52
TC 407.36

TC 407.92
G 407.04
TC 407.60

G 406.84

G 407.40
G 407.14

408
NOVOM GROUP

.50
407

8
8

40
57
400 S. RECORD ST, SUITE 1200
5/8"FIR 1/2"CIRF
X X X X X X X X X
S01°38'55"E 605.79
AFFIDAVIT OF FACTS YELLOW DALLAS, TX 75202

G 408.32
G 407.67

TC 408.87
TC 408.06
G 406.97

5/8"FIR
TC 407.44

6' Chain Link Fence

G 407.97
TC 408.46
Δ=027°39'07" Vol. 2002068, Pg. 5345
R=88.08' D.R.D.C.T. 214-882-1540
L=42.51'
Block 7941 The County of Dallas, State of Texas Block 12/7941
King Row Industrial District
CB=S 15°28'28" E Inst. 20150222226, O.P.R.D.C.T. Roundtable Addition
Vol. 74103, Pg. 1425, D.R.D.C.T.
project
Fourth Installment
CD=42.10'
Jessup Investments LLC Vol. 68040, Pg. 2015, D.R.D.C.T.
GRADING & DRAINAGE GENERAL NOTES
Inst. 201400018000, O.P.R.D.C.T. DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
ISSUED FOR PRELIMINARY PRICING PURPOSES ONLY DALLAS, TX 75247
(SUBJECT TO REVISION PRIOR TO CONSTRUCTION) The drawings and written material herein constitute original work
architect, and as intellectual property and instruments of service,
subject to copyright and may not be reproduced, distributed, pub
or used in any way without the express written consent of the arc
original issue
408

DESIGN DEVELOPMENT 04.30.2021


40
8

revisions
36" PECAN 65'SP

407 7
40

DALLAS COUNTY ELECTIONS BUILDING


407
BENC MARK
RIM=406.68
NOT FOR CONSTRUCTION

GRADING PLAN
DALLAS COUNTY ELECTIONS BUILDING
G 407.74
TC 408.20

LOT 3, BLOCK 10/7941


G 407.76
TC 408.19

408

SUSTAINABLE DEVELOPMENT & CONSTRUCTION


INSET 1 CITY OF DALLAS, DALLAS COUNTY, TEXAS
DESIGN DRAWN DATE SCALE FILE NUMBER SHEET
title
C07.01 GRADING PLAN
4/22/2021 5:30:27 PM

project number 20182.200


date 04.30.2021
sheet

C07.01
plotted:
C:\BOKAP\REVIT_PROJECTS\ARCH_20182_DALLAS_COUNTY_ELECTIONS_Alan-Macejewski.rvt

architecture interiors planning graphics


8"WATER 8070 Park Lane, Ste. 300Dallas, Texas 75231

RIM=407.78
BENCHMARK #1:

RIM=407.22
SQUARE CUT
ELEV=406.47 Tel 972.701.9000Fax 972.991.3008
KING JAMES DRIVE

ST
Δ=043°31'40"

ST
R=300.00' FL10"=402.58
60' Public ROW, Concrete Pavement
407 N01°38'55"W 670.24 www.bokapowell.com
L=227.91' 406 FL10"=401.42
Concrete Walk
CB=N 23°24'45" W WW

S
CD=222.47' T W

S
T

CO

N67 40.28
407 407 X-CUT SET
5/8"FIR These documents are issued for pricing only
and are not for regulatory approval,

°45
ST
10 6 5 Conc. Pads
permitting or construction.

MH
MH

'35
Manhole Pad Concrete Concrete
35' BUILDING LINE Drive

408
"SS Drive

"E
40 8
10 Per Zoning
Concrete 408 225.5 1/2"FIR
ST

Pavement Concrete THIS SPACE RESERVED - BLDG INSPECTION

409
FFE= 409.40

19.7
Pavement FFE= 409.36
40

3"G
407
20
7

as
84.5

FFE= 409.40

406
18 408
DP&L EASEMENT
Vol. 68175, Pg. 102,
RIM=407.57

8"SS
s
1/2"CIRF D.R.D.C.T. &
Ga Vol. 95178, Pg. 2704,
3"

408
0 W D.R.D.C.T.
.0 35" Concrete
0
8 0'
408 Pavement client
S

°1

42"
NO ACCESS
407
45 DALLAS COUNTY

RCP
N
27 408
40 1460 ROUND TABLE DR

179.5
7
408
DALLAS, TX 75247
1/2"FIR 408
214-653-6437
40

408
9

40
7

40 THIS SPACE RESERVED - ENGINEERING


client representative

408
40
8
18"
PRITCHARD ASSOCIATES

4
RC

07
40
P
40
8
9
FFE= 409.24 2121 NORTH AKARD ST, SUITE 100
Δ=024°51'00"
DALLAS, TX 75201
#1460 Roundtable Drive R=924.93' 214-849-0011
One Story Masonry
40
407 Building Area = 104,285 SF L=401.16'
8 Building Height = 17.6 Feet FFE= 409.48 6.5 CB=N 80°11'05" E
m.e.p. engineer

322.5
40

CD=398.02'
9

Covered Area
420,923 SF/9.6631 AC.

20.5
407
LOT 3, BLOCK 10/7941 PURDY-MCGUIRE, INC.
FOURTH INSTALLMENT Brick Walls
17300 N. DALLAS PARKWAY, SUITE 3000

409
6.5
KINGS ROW INDUSTRIAL DISTRICT
4
Vol. 68040, Pg. 2015, DRDCT DALLAS, TX 75248

RO
408
40
972-239-5357

60' Public ROW, Co


8

UND TAncBreLteEPaD
407
40

civil
7

Concrete
BT FOODS TX HOLDINGS, LLC
Block 10/7941 12 407 INST. NO. 201500151904, OPRDCT
Pavement
PACHECO KOCH

408
King Row Industrial District 407
Fourth Installment
Vol. 68040, Pg. 2014, D.R.D.C.T.
FFE= 409.26 7557 RAMBLER RD. #1400

8"SS
12

142.2
DALLAS, TX 75234
S4
4

48"RCP
°4

Cantex Regal LLC


972.235.3031
9'

Inst. 201700215989, O.P.R.D.C.T.


25

13
"W

408
6' Chain Link Fence
landscape
51

vement
3.

PACHECO KOCH

RIVE
73

3"Gas
408
408

7557 RAMBLER RD. #1400

408
20' FIRE LANE EASEMENT
Vol. 68196, Pg. 142 15 FFE= 409.42 FFE= 409.46 DALLAS, TX 75234
972.235.3031
409

D.R.D.C.T.

12"WATER
310.0
409
408

8"SS
407
15
408
structural engineer
40
7
20' FIRE LANE EASEMENT 407 EJES INCORPORATED

408
Vol. 68196, Pg. 142, D.R.D.C.T. 12801 N. CENTRAL EXPY, SUITE 700
407

DALLAS, TX 75243
11
17
32 H H 3 5/8"FIR
214.3431210

S87°23'25"E 68
Storm Sewer

408
Approx. Centerline
17
security, audio/visual

BENCHMARK #2:
408 32 6
40

ELEV=408.50
8

Concrete 407
40
7
NOVOM GROUP
Metal Fence
400 S. RECORD ST, SUITE 1200

X-CUT
Pavement
407 w/ Brick Columns
DALLAS, TX 75202

408
.50
407

8
8
214-882-1540

40
57

5/8"FIR 1/2"CIRF
X X X X X X X X X
S01°38'55"E 605.79
5/8"FIR
Δ=027°39'07"
6' Chain Link Fence AFFIDAVIT OF FACTS
Vol. 2002068, Pg. 5345
YELLOW
project
R=88.08' D.R.D.C.T.
L=42.51' Block 7941 Block 12/7941
DALLAS COUNTY ELECTIONS BUILDING
The County of Dallas, State of Texas
CB=S 15°28'28" E King Row Industrial District
Fourth Installment
Inst. 20150222226, O.P.R.D.C.T. Roundtable Addition
Vol. 74103, Pg. 1425, D.R.D.C.T.
1460 ROUND TABLE DR
CD=42.10'
Jessup Investments LLC Vol. 68040, Pg. 2015, D.R.D.C.T. ISSUED FOR PRELIMINARY PRICING PURPOSES ONLY DALLAS, TX 75247
Inst. 201400018000, O.P.R.D.C.T. The drawings and written material herein constitute original work
(SUBJECT TO REVISION PRIOR TO CONSTRUCTION)
architect, and as intellectual property and instruments of service,
subject to copyright and may not be reproduced, distributed, pub
or used in any way without the express written consent of the arc
original issue
DESIGN DEVELOPMENT 04.30.2021
revisions

DALLAS COUNTY ELECTIONS BUILDING


NOT FOR CONSTRUCTION

EXISTING DRAINAGE AREA MAP


DALLAS COUNTY ELECTIONS BUILDING
LOT 3, BLOCK 10/7941
SUSTAINABLE DEVELOPMENT & CONSTRUCTION
CITY OF DALLAS, DALLAS COUNTY, TEXAS
DESIGN DRAWN DATE SCALE FILE NUMBER SHEET
title
C08.01 EXISTING DRAINAGE AREA
MAP
4/22/2021 5:30:27 PM

project number 20182.200


date 04.30.2021
sheet

C08.01
plotted:
C:\BOKAP\REVIT_PROJECTS\ARCH_20182_DALLAS_COUNTY_ELECTIONS_Alan-Macejewski.rvt

8"WATER

RIM=407.78
BENCHMARK #1:

RIM=407.22
SQUARE CUT
ELEV=406.47
KING JAMES DRIVE architecture interiors planning graphics

ST
Δ=043°31'40"

ST
R=300.00' FL10"=402.58
60' Public ROW, Concrete Pavement
407 N01°38'55"W 670.24
FL10"=401.42
L=227.91' 406

CB=N 23°24'45" W WW
Concrete Walk 8070 Park Lane, Ste. 300Dallas, Texas 75231

S
CD=222.47' T W

S
T
Tel 972.701.9000Fax 972.991.3008

CO

N67 40.28
407 5/8"FIR 407 X-CUT SET

°45
ST 10 6 5 Conc. Pads
www.bokapowell.com

MH
MH

'35
Manhole Pad Concrete Concrete
35' BUILDING LINE Drive

408
Drive
"SS

"E
A/C's

408
10 Per Zoning
Concrete 408 Transformer
225.5 1/2"FIR
ST

Pavement Concrete Pads

409
These documents are issued for pricing only

19.7
Pavement FFE= 409.36 FFE= 409.40
A/C's
and are not for regulatory approval,
40

3"G
407
20
7

6
permitting or construction.

a
84.5

s
FFE= 409.40

406
18 408
DP&L EASEMENT
Vol. 68175, Pg. 102,
RIM=407.57

8"SS
s
1/2"CIRF D.R.D.C.T. & THIS SPACE RESERVED - BLDG INSPECTION
Ga Vol. 95178, Pg. 2704,
3"

408
0 W D.R.D.C.T.
0 .0 35" Concrete
Pavement
8 0'
408
S

°1

42"
NO ACCESS
407
45

RCP
N
27 408
40

179.5
7
408

1/2"FIR 408
client
40

408
9

40
7
DALLAS COUNTY
40 40 1460 ROUND TABLE DR

408
8
18"
8

DALLAS, TX 75247

4
RC

07
40
P
9
40
8 FFE= 409.24 214-653-6437
Δ=024°51'00"
#1460 Roundtable Drive R=924.93' client representative
One Story Masonry THIS SPACE RESERVED - ENGINEERING
407 Building Area = 104,285 SF L=401.16'
40
8 Building Height = 17.6 Feet FFE= 409.48 6.5 CB=N 80°11'05" E PRITCHARD ASSOCIATES

322.5
40

CD=398.02' 2121 NORTH AKARD ST, SUITE 100


9

Covered Area
420,923 SF/9.6631 AC.

20.5
407
LOT 3, BLOCK 10/7941 DALLAS, TX 75201
FOURTH INSTALLMENT Brick Walls

409
KINGS ROW INDUSTRIAL DISTRICT
6.5
214-849-0011
4
Vol. 68040, Pg. 2015, DRDCT

RO
408
40
m.e.p. engineer

60' Public ROW, Co


8

UND TAncBreLteEPaD
407 PURDY-MCGUIRE, INC.
40
7

Concrete
BT FOODS TX HOLDINGS, LLC 17300 N. DALLAS PARKWAY, SUITE 3000
Block 10/7941 12 Pavement
407 INST. NO. 201500151904, OPRDCT
DALLAS, TX 75248

408
King Row Industrial District 407
Fourth Installment
Vol. 68040, Pg. 2014, D.R.D.C.T.
FFE= 409.26
972-239-5357

8"SS
12

142.2
S4

48"RCP
Cantex Regal LLC
4

civil
9'

Inst. 201700215989, O.P.R.D.C.T.


25

13
"W

408
6' Chain Link Fence
PACHECO KOCH
51

vement
7557 RAMBLER RD. #1400
3
.7

RIVE
3"Gas
3

408
DALLAS, TX 75234
408

972.235.3031

408
20' FIRE LANE EASEMENT 15 FFE= 409.42 FFE= 409.46
Vol. 68196, Pg. 142
landscape
409

D.R.D.C.T.

12"WATER
310.0
409
408

8"SS
407
15 PACHECO KOCH
40
7
408

407
7557 RAMBLER RD. #1400
20' FIRE LANE EASEMENT DALLAS, TX 75234

408
Vol. 68196, Pg. 142, D.R.D.C.T.
972.235.3031
407

11
17
32 H H 3 5/8"FIR structural engineer
EJES INCORPORATED

S87°23'25"E 68
Storm Sewer

408
Approx. Centerline
17

BENCHMARK #2:
408 32 6
12801 N. CENTRAL EXPY, SUITE 700
40

ELEV=408.50
8

Concrete 407
40
7
Metal Fence
DALLAS, TX 75243

X-CUT
Pavement
407 w/ Brick Columns 214.3431210

408
.50
407

8
8
security, audio/visual

40
57

5/8"FIR 1/2"CIRF
NOVOM GROUP
X X X X X X X X X
S01°38'55"E 605.79 YELLOW
5/8"FIR 6' Chain Link Fence AFFIDAVIT OF FACTS
Δ=027°39'07"
R=88.08'
Vol. 2002068, Pg. 5345
D.R.D.C.T. 400 S. RECORD ST, SUITE 1200
L=42.51' Block 7941 The County of Dallas, State of Texas Block 12/7941 DALLAS, TX 75202
Roundtable Addition
CB=S 15°28'28" E
CD=42.10'
King Row Industrial District
Fourth Installment
Inst. 20150222226, O.P.R.D.C.T.
Vol. 74103, Pg. 1425, D.R.D.C.T. 214-882-1540
Jessup Investments LLC Vol. 68040, Pg. 2015, D.R.D.C.T.
Inst. 201400018000, O.P.R.D.C.T. project
DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
ISSUED FOR PRELIMINARY PRICING PURPOSES ONLY DALLAS, TX 75247
(SUBJECT TO REVISION PRIOR TO CONSTRUCTION) The drawings and written material herein constitute original work
architect, and as intellectual property and instruments of service,
subject to copyright and may not be reproduced, distributed, pub
or used in any way without the express written consent of the arc
original issue
DESIGN DEVELOPMENT 04.30.2021
revisions

DALLAS COUNTY ELECTIONS BUILDING


NOT FOR CONSTRUCTION

PROPOSED DRAINAGE AREA MAP


DALLAS COUNTY ELECTIONS BUILDING
LOT 3, BLOCK 10/7941
SUSTAINABLE DEVELOPMENT & CONSTRUCTION
CITY OF DALLAS, DALLAS COUNTY, TEXAS
DESIGN DRAWN DATE SCALE FILE NUMBER SHEET
title
C08.02 PROPOSED DRAINAGE ARE
MAP
4/22/2021 5:30:27 PM

project number 20182.200


date 04.30.2021
sheet

C08.02
plotted:
C:\BOKAP\REVIT_PROJECTS\ARCH_20182_DALLAS_COUNTY_ELECTIONS_Alan-Macejewski.rvt

WA
T

architecture interiors planning graphics

GAS
8"WATER
WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT

WA
TUGT
SAN
WAT

RIM=407.78
BENCHMARK #1:

RIM=407.22
WAT SQUARE CUT

KING JAMES DRIVE ELEV=406.47


5'X3' BOX
8070 Park Lane, Ste. 300Dallas, Texas 75231

WAT

ST
Δ=043°31'40" WA 3'X3' BOX

ST
T

RIM=407.15
R=300.00' 60' Public ROW, Concrete Pavement N01°38'55"W 670.24 FL(S)=399.30
FL10"=402.58 RIM=406.33 FL(NE)=399.20
Tel 972.701.9000Fax 972.991.3008

GAS
FL10"=401.42
L=227.91' FL=399.73

WAT

WA
TUGT
Concrete Walk

SAN
WA
T
CB=N 23°24'45" W POH POH POH POH POH POH POH POH POH POH POH POH POH
www.bokapowell.com
POH POH POH POH
WW
POH POH
SAN SAN

S
CD=222.47'
SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN SAN
SAPN T W

S
OH
GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS
T
GAS
TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG TUG

CO

N67 40.28
AT
W SAPN
OH TGUAGS 5/8"FIR X-CUT SET

°45
TGUAGS
RIM=406.79
ST

PO
FL18"(NE)=400.89
H
10 6 5

MH
MH

'35
FL(NW)=400.99
Manhole Pad Concrete Concrete These documents are issued for pricing only

36" PECAN 65'SP


W
AT TGUAGS
35' BUILDING LINE Drive Drive
"SS

"E
RIM=407.06
FL18"(SW)=403.16 10
PO Per Zoning and are not for regulatory approval,
permitting or construction.
H
Concrete 1/2"FIR

TUG WAT
225.5
ST

S
TGUA AN Pavement RIM=407.31 Concrete
FL12"(W)=402.01

19.7
GS
Pavement FFE= 409.40

SAN
FL12"(E)=401.91
FFE= 409.36
18" PECAN 35'SP

3"G
20
W PO
AT H
6

as
84.5 THIS SPACE RESERVED - BLDG INSPECTION

STO
S
TGUA AN
GS
FFE= 409.40
PO DP&L EASEMENT

TUG WAT
H 18 Vol. 68175, Pg. 102,
RIM=407.57

8"SS
W
AT
1/2"CIRF D.R.D.C.T. &

GAS
G as Vol. 95178, Pg. 2704,
0 W 3" D.R.D.C.T.
27" PECAN 55'SP

.0 35" Concrete
PO
0 Pavement RIM=407.08
H
8 0'
S

TU
FL12"(W)=402.18
°1

42"
G
NO ACCESS
45
GA
FL12"(E)=402.28

RCP
S

TUG WAT
N
client

SAN
27

GAS
PO
H

179.5
DALLAS COUNTY

STO
TU S
G AN
GA

1460 ROUND TABLE DR


S
1/2"FIR
PO
DALLAS, TX 75247

TUG WAT
24" PECAN 40'SP

SAN
TU
G SAN
214-653-6437

GAS
GA
S

STO
18"
RC

FFE= 409.24
P
THIS SPACE RESERVED - ENGINEERING
client representative

TUG WAT
PRITCHARD ASSOCIATES

SAN
GAS
Δ=024°51'00"
RIM=405.99 #1460 Roundtable Drive
One Story Masonry R=924.93' 2121 NORTH AKARD ST, SUITE 100

STO
FL12"(SW)=402.79

8" RED OAK 20'SP


Building Area = 104,285 SF L=401.16' DALLAS, TX 75201

30" PECAN 60'SP


Building Height = 17.6 Feet FFE= 409.48 6.5 CB=N 80°11'05" E
214-849-0011

322.5
24" PECAN 40'SP

27" PECAN 55'SP


CD=398.02'

TUG WAT
7" CREPE MYRTLE 20'SP
Covered Area
420,923 SF/9.6631 AC.
27" PECAN50'SP

20.5

SAN
LOT 3, BLOCK 10/7941 m.e.p. engineer
FOURTH INSTALLMENT 6.5 Brick Walls
KINGS ROW INDUSTRIAL DISTRICT PURDY-MCGUIRE, INC.

GAS
4

36" PECAN 65'SP


Vol. 68040, Pg. 2015, DRDCT

ROUND TABreLteEPaD
17300 N. DALLAS PARKWAY, SUITE 3000

STO

TUG WAT
60' Public ROW, Co
RI

SAN
DALLAS, TX 75248
M
=4 36" PECAN 65'SP
FU

07 RIM=406.33
L L

FL12"(W)=403.33
972-239-5357
O

.8
F

4
BT FOODS TX HOLDINGS, LLC
DE
BR

Concrete
INST. NO. 201500151904, OPRDCT
IS

30" PECAN 60'SP

GAS
12
Block 10/7941 30" PECAN 65'SP Pavement
RIM=406.68
King Row Industrial District FL12"(SW)=403.88
civil

TUG
Fourth Installment
ST

FFE= 409.26
O

WAT
Vol. 68040, Pg. 2014, D.R.D.C.T.

8"SS
12
PACHECO KOCH

142.2
S4

7" CREPE MYRTLE 20'SP

nc

36" PECAN 65'SP


7557 RAMBLER RD. #1400

48"RCP
Cantex Regal LLC RIM=406.54
49

Inst. 201700215989, O.P.R.D.C.T. FL12"(N)=404.24


'2

GAS
13
DALLAS, TX 75234
5"

8" CREPE MYRTLE 15'SP

6' Chain Link Fence


W

TUG
972.235.3031
51

vement

WAT
3
.7

SAN
RIVE
3"Gas
3

36" PECAN 65'SP


landscape
36" PECAN 65'SP

20' FIRE LANE EASEMENT 15 FFE= 409.42 FFE= 409.46


PACHECO KOCH

TUG
Vol. 68196, Pg. 142 WAT
7557 RAMBLER RD. #1400

GAS
D.R.D.C.T.

12"WATER
310.0

DALLAS, TX 75234

8"SS
15

36" PECAN 65'SP


36" PECAN 65'SP

972.235.3031
RIM=406.09 20' FIRE LANE EASEMENT structural engineer

TUG
Vol. 68196, Pg. 142, D.R.D.C.T.

GAS
FL12"(E)=404.09

SAN
WAT
36" PECAN 65'SP
EJES INCORPORATED
RIM=406.02
12801 N. CENTRAL EXPY, SUITE 700
STO
11 FL12"(S)=404.22 32 3 5/8"FIR
17 H H
RIM=407.26 STO STO FL12"(N)=404.02 STO
DALLAS, TX 75243
STO STO STO STO STO STO STO STO STO STO STO STO
FULL OF DEBRIS

S87°23'25"E 68
Storm Sewer
Approx. Centerline
17 RIM=406.21 RIM=406.19 214.3431210

BENCHMARK #2:
FL12"(S)=402.41 32 FL12"(S)=400.99 6

36" PECAN 65'SP


FL12"(N)=402.31 FL12"(N)=400.89

ELEV=
Concrete security, audio/visual

SAN
WA
Metal Fence

TU408.5
X-CUT
Pavement

G
T
w/ Brick Columns
NOVOM GROUP

0
.50
GRADING & DRAINAGE GENERAL NOTES 57 8 400 S. RECORD ST, SUITE 1200
5/8"FIR
X X
S01°38'55"E 605.79
X X X X X X X
1/2"CIRF DALLAS, TX 75202

GAS

SAN
WAT
TUG
AFFIDAVIT OF FACTS YELLOW
5/8"FIR
Δ=027°39'07"
6' Chain Link Fence
Vol. 2002068, Pg. 5345 214-882-1540
R=88.08' D.R.D.C.T.
L=42.51' Block 7941 The County of Dallas, State of Texas Block 12/7941
Roundtable Addition
project
King Row Industrial District
CB=S 15°28'28" E Inst. 20150222226, O.P.R.D.C.T.
Fourth Installment Vol. 74103, Pg. 1425, D.R.D.C.T.
CD=42.10'
Jessup Investments LLC Vol. 68040, Pg. 2015, D.R.D.C.T. DALLAS COUNTY ELECTIONS BUILDING
Inst. 201400018000, O.P.R.D.C.T. 1460 ROUND TABLE DR
ISSUED FOR PRELIMINARY PRICING PURPOSES ONLY DALLAS, TX 75247
(SUBJECT TO REVISION PRIOR TO CONSTRUCTION) The drawings and written material herein constitute original work
architect, and as intellectual property and instruments of service,
subject to copyright and may not be reproduced, distributed, pub
or used in any way without the express written consent of the arc
original issue
DESIGN DEVELOPMENT 04.30.2021
revisions

DALLAS COUNTY ELECTIONS BUILDING


NOT FOR CONSTRUCTION

STORM SEWER PLAN


BENCHMARK: DALLAS COUNTY ELECTIONS BUILDING
LOT 3, BLOCK 10/7941
SUSTAINABLE DEVELOPMENT & CONSTRUCTION
CITY OF DALLAS, DALLAS COUNTY, TEXAS
DESIGN DRAWN DATE SCALE FILE NUMBER SHEET
title
C09.01 STORM SEWER PLAN
4/22/2021 5:30:27 PM

project number 20182.200


date 04.30.2021
sheet

C09.01
plotted:
C:\BOKAP\REVIT_PROJECTS\ARCH_20182_DALLAS_COUNTY_ELECTIONS_Alan-Macejewski.rvt

WA
T

WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT WAT

WA
WAT

RIM=407.78
BENCHMARK #1:

T
RIM=407.22
WAT SQUARE CUT
ELEV=406.47
KING JAMES DRIVE

TC 406.56
G 406.51

TC 407.66
TC 407.88

WAT
TC 407.72

TC 406.80
TC 407.03

ST
TC 406.17
Δ=043°31'40"

TC 406.62

TC 407.40

G 407.26
G 407.29

G 407.33

G 406.64

G 406.34
G 406.22
G 406.26

G 406.95
WA

ST
T
R=300.00' 60' Public ROW, Concrete Pavement N01°38'55"W 670.24 architecture interiors planning graphics

TC W
FL10"=402.58

G 407.10
407
FL10"=401.42
L=227.91' 406 TC 406.52

407.58

WA
WA
Concrete Walk

AT
T G 406.08
CB=N 23°24'45" W

T
WW 8070 Park Lane, Ste. 300Dallas, Texas 75231

S
CD=222.47' T W

S
T

CO

N67 40.28
W 407 5/8"FIR 407 X-CUT SET
Tel 972.701.9000Fax 972.991.3008
AT

TC 408.42

TC 4 .89
G 407.97

G 40
G 407.97
TC 408.38

G 408.21
TC 408.77
G 408.35
G 408.73

°45
TC 408.86
TC 409.23

G 408.22
TC 408.62
ST
6 5 Conc. Pads

07.4
10

6
G 409.20
TC 409.69
www.bokapowell.com

MH
MH

'3 5
G 409.23
TC 409.68

2
Manhole Pad Concrete Concrete

36" PECAN 65'SP


W
35' BUILDING LINE Drive

408
Drive
AT

"E
G 407.71
TC 408.18

408
Per Zoning

G 408.07
TC 408.59
G 408.22
TC 408.73
Concrete 408 1/2"FIR

G 408.76
TC 409.33
225.5
ST

TC 407.12 Pavement Concrete

409

TC 409.05
G 408.64
FFE= 409.40

19.7

WAT
G 406.45 Pavement FFE= 409.36
These documents are issued for pricing only
18" PECAN 35'SP
40

407
20

TC 408.82
W
7

G 408.45
AT

TC 406.84
TC 407.50

6 and are not for regulatory approval,


G 407.03

G 406.31
84.5

FFE= 409.40 permitting or construction.

TC 407.40
G 408.77
TC 409.24

G 408.78
TC 409.25
G 408.49
TC 409.04

G 407.00
406
DP&L EASEMENT

G 408.65
TC 409.16
18 408
Vol. 68175, Pg. 102,
RIM=407.57

WAT
D.R.D.C.T. &
AT
1/2"CIRF

G 408.34
TC 408.83
Vol. 95178, Pg. 2704,

G 408.45
TC 408.95
THIS SPACE RESERVED - BLDG INSPECTION

TC 407.93
408
0 W

G 407.46
G 408.49
D.R.D.C.T.

TC 409.04
27" PECAN 55'SP

0 .0 35" Concrete
Pavement
8 0'
408
S
TC 408.20
G 407.71

°1 NO ACCESS
407
45
N

WAT
27 408
40

179.5
7

G 406.32
TC 406.77
408

TC 406.87
G 406.30
TC 408.31
G 408.39

G 408.52
TC 408.96
1/2"FIR 408

client
40

408
24" PECAN 40'SP
9

40
7

WAT
DALLAS COUNTY
1460 ROUND TABLE DR
40

408
40
8

07 4

G 408.79
TC 409.37
40
8
40
9
FFE= 409.24
DALLAS, TX 75247
214-653-6437

WAT
Δ=024°51'00"
#1460 Roundtable Drive

TC 407.06
G 406.51
One Story Masonry R=924.93'
client representative

8" RED OAK 20'SP


407 Building Area = 104,285 SF L=401.16'

30" PECAN 60'SP


40 THIS SPACE RESERVED - ENGINEERING
8 Building Height = 17.6 Feet FFE= 409.48 CB=N 80°11'05" E
6.5
PRITCHARD ASSOCIATES

322.5
24" PECAN 40'SP

27" PECAN 55'SP


40

CD=398.02'

7" CREPE MYRTLE 20'SP


9

Covered Area
420,923 SF/9.6631 AC.
27" PECAN50'SP

2121 NORTH AKARD ST, SUITE 100

20.5

WAT
407
LOT 3, BLOCK 10/7941
FOURTH INSTALLMENT Brick Walls DALLAS, TX 75201

409
6.5

4
KINGS ROW INDUSTRIAL DISTRICT 214-849-0011

36" PECAN 65'SP


Vol. 68040, Pg. 2015, DRDCT

RO
408
40

60' Public ROW, Co


8
m.e.p. engineer

WAT
UND TAncBreLteEPaD
36" PECAN 65'SP
40 7
PURDY-MCGUIRE, INC.
40

TC 407.26

TC 407.04

G 407.33
TC 407.85
G 406.82

G 406.59
7

BT FOODS TX HOLDINGS, LLC

GG408.90
TC 409.36
Concrete
30" PECAN 60'SP
INST. NO. 201500151904, OPRDCT 17300 N. DALLAS PARKWAY, SUITE 3000

408.63
409.03
12 407
Block 10/7941 30" PECAN 65'SP Pavement

408
King Row Industrial District 407
DALLAS, TX 75248
TC 407.53
Fourth Installment
G 407.04
FFE= 409.26

WAT
Vol. 68040, Pg. 2014, D.R.D.C.T. 12
972-239-5357

142.2
S4

7" CREPE MYRTLE 20'SP


36" PECAN 65'SP


Cantex Regal LLC
4 9'

G 408.56
TC 408.99
Inst. 201700215989, O.P.R.D.C.T.
civil
25

13

G 407.74
TC 408.20
8" CREPE MYRTLE 15'SP

G 407.76G 407.59
TC 408.19
G 407.06
TC 407.55
"W

408
6' Chain Link Fence
PACHECO KOCH
51

vement
G 407.00
TC 407.49

G 407.45
TC 407.94
TC 408.10

G 406.80

WAT
TC 407.29
3.

7557 RAMBLER RD. #1400

RIV
73

36" PECAN 65'SP

G 407.51
TC 408.01
G 406.99
TC 407.56

408
408

36" PECAN 65'SP


DALLAS, TX 75234

E
408
20' FIRE LANE EASEMENT
Vol. 68196, Pg. 142 15 FFE= 409.42 FFE= 409.46 972.235.3031

TC 408.27

TC 407.68
WAT

G 407.80

G 407.21
409

D.R.D.C.T. 310.0

15
407
409
408 landscape

TC 408.57
36" PECAN 65'SP
36" PECAN 65'SP

PACHECO KOCH

G 408.12
408

7557 RAMBLER RD. #1400

TC 408.04
7
40 407

G 407.69
20' FIRE LANE EASEMENT

408
Vol. 68196, Pg. 142, D.R.D.C.T.
DALLAS, TX 75234

WAT
407

36" PECAN 65'SP

11
972.235.3031
32 H H 3 5/8"FIR
17
structural engineer

S87°23'25"E 68

408
EJES INCORPORATED

TC 408.08
G 407.62
17

BENCHMARK #2:
408 32 6
40

12801 N. CENTRAL EXPY, SUITE 700

36" PECAN 65'SP

ELEV=
8

40
Concrete 407
7
DALLAS, TX 75243

WA
Metal Fence

G 408.22
TC 408.65

408.5
X-CUT
Pavement

T
407 w/ Brick Columns

TC 407.52
TC 407.36

TC 407.92
214.3431210

G 407.04
TC 407.60

G 406.84

G 407.40
G 407.14

408

0
POLLUTION CONTROL GENERAL NOTES

.50
407

8
8

40
57

5/8"FIR
X X X X X X X X X
1/2"CIRF
security, audio/visual
S01°38'55"E 605.79

WAT
YELLOW
AFFIDAVIT OF FACTS NOVOM GROUP

G 408.32
G 407.67

TC 408.87
TC 408.06
G 406.97

5/8"FIR
TC 407.44

6' Chain Link Fence

G 407.97
TC 408.46
Δ=027°39'07" Vol. 2002068, Pg. 5345
R=88.08' D.R.D.C.T. 400 S. RECORD ST, SUITE 1200
L=42.51' Block 12/7941
Block 7941
King Row Industrial District
CB=S 15°28'28" E
The County of Dallas, State of Texas
Inst. 20150222226, O.P.R.D.C.T. Roundtable Addition DALLAS, TX 75202
Vol. 74103, Pg. 1425, D.R.D.C.T.
Jessup Investments LLC
CD=42.10' Fourth Installment
Vol. 68040, Pg. 2015, D.R.D.C.T. 214-882-1540
Inst. 201400018000, O.P.R.D.C.T.
project
DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
ISSUED FOR PRELIMINARY PRICING PURPOSES ONLY DALLAS, TX 75247
(SUBJECT TO REVISION PRIOR TO CONSTRUCTION) The drawings and written material herein constitute original work
architect, and as intellectual property and instruments of service,
subject to copyright and may not be reproduced, distributed, pub
or used in any way without the express written consent of the arc
original issue
DESIGN DEVELOPMENT 04.30.2021
revisions

DALLAS COUNTY ELECTIONS BUILDING


NOT FOR CONSTRUCTION

EROSION CONTROL PLAN


DALLAS COUNTY ELECTIONS BUILDING
LOT 3, BLOCK 10/7941
SUSTAINABLE DEVELOPMENT & CONSTRUCTION
CITY OF DALLAS, DALLAS COUNTY, TEXAS
DESIGN DRAWN DATE SCALE FILE NUMBER SHEET
title
C11.01 EROSION CONTROL PLAN
4/22/2021 5:30:27 PM

project number 20182.200


date 04.30.2021
sheet

C11.01
plotted:
C:\BOKAP\REVIT_PROJECTS\ARCH_20182_DALLAS_COUNTY_ELECTIONS_Alan-Macejewski.rvt

architecture interiors planning graphics


8070 Park Lane, Ste. 300Dallas, Texas 75231
Tel 972.701.9000Fax 972.991.3008
www.bokapowell.com

These documents are issued for pricing only


and are not for regulatory approval,
permitting or construction.

THIS SPACE RESERVED - BLDG INSPECTION

client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437

THIS SPACE RESERVED - ENGINEERING


client representative
PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
STABILI ED 214-849-0011
CONSTRUCTION m.e.p. engineer
ENTRANCE SILT ENCE DROP INLET PROTECTION
1 3 PURDY-MCGUIRE, INC.
17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
972-239-5357
civil
PACHECO KOCH
7557 RAMBLER RD. #1400
DALLAS, TX 75234
972.235.3031
landscape
PACHECO KOCH
7557 RAMBLER RD. #1400
DALLAS, TX 75234
972.235.3031
structural engineer
EJES INCORPORATED
12801 N. CENTRAL EXPY, SUITE 700
DALLAS, TX 75243
214.3431210
security, audio/visual
NOVOM GROUP
400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
214-882-1540
project
DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
ISSUED FOR PRELIMINARY PRICING PURPOSES ONLY DALLAS, TX 75247
(SUBJECT TO REVISION PRIOR TO CONSTRUCTION) The drawings and written material herein constitute original work
architect, and as intellectual property and instruments of service,
subject to copyright and may not be reproduced, distributed, pub
or used in any way without the express written consent of the arc
original issue
DESIGN DEVELOPMENT 04.30.2021
revisions

DALLAS COUNTY ELECTIONS BUILDING


CONCRETE TYPICAL SANDBAG DETAIL
AS OUT AREA 5 NOT FOR CONSTRUCTION
4
EROSION CONTROL DETAILS
DALLAS COUNTY ELECTIONS BUILDING
LOT 3, BLOCK 10/7941
SUSTAINABLE DEVELOPMENT & CONSTRUCTION
CITY OF DALLAS, DALLAS COUNTY, TEXAS
DESIGN DRAWN DATE SCALE FILE NUMBER SHEET
title
C11.50 EROSION CONTROL DETAIL
4/22/2021 5:30:27 PM

project number 20182.200


date 04.30.2021
sheet

C11.50
plotted:
C:\BOKAP\REVIT_PROJECTS\ARCH_20182_DALLAS_COUNTY_ELECTIONS_Alan-Macejewski.rvt

architecture interiors planning graphics


STOP 8070 Park Lane, Ste. 300Dallas, Texas 75231

RIM=407.78
BENCHMARK #1:
Tel 972.701.9000Fax 972.991.3008

RIM=407.22
SQUARE CUT
ELEV=406.47
KING JAMES DRIVE

ST
Δ=043°31'40"
www.bokapowell.com

ST
R=300.00' FL10"=402.58
60' Public ROW, Concrete Pavement N01°38'55"W 670.24
L=227.91' FL10"=401.42
Concrete Walk
CB=N 23°24'45" W WW

S
CD=222.47' T W

S
T These documents are issued for pricing only

CO

N67 40.28
5/8"FIR X-CUT SET
and are not for regulatory approval,

°45
ST

10 6 5 NO permitting or construction.

MH
MH

'35
Manhole Pad Concrete Concrete PARKING

36" PECAN 65'SP


35' BUILDING LINE Drive Drive ANY

"E
Per Zoning TIME
Concrete 225.5 1/2"FIR THIS SPACE RESERVED - BLDG INSPECTION
ST

Pavement Concrete
FFE= 409.40

19.7
Pavement FFE= 409.36
18" PECAN 35'SP

20
6 84.5

FFE= 409.40
18
DP&L EASEMENT
Vol. 68175, Pg. 102,
RIM=407.57

1/2"CIRF D.R.D.C.T. &


Vol. 95178, Pg. 2704,
0 W D.R.D.C.T. client
27" PECAN 55'SP

0 .0 35" Concrete
Pavement
8 0'
S

45
°1 NO ACCESS
DALLAS COUNTY
N
27 1460 ROUND TABLE DR
DALLAS, TX 75247

179.5
1/2"FIR 214-653-6437
24" PECAN 40'SP

THIS SPACE RESERVED - ENGINEERING


client representative
PRITCHARD ASSOCIATES
FFE= 409.24
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
#1460 Roundtable Drive Δ=024°51'00"
R=924.93'
214-849-0011
One Story Masonry

8" RED OAK 20'SP


Building Area = 104,285 SF L=401.16'

30" PECAN 60'SP


Building Height = 17.6 Feet FFE= 409.48 6.5 CB=N 80°11'05" E m.e.p. engineer

322.5
24" PECAN 40'SP

27" PECAN 55'SP


CD=398.02'

7" CREPE MYRTLE 20'SP


Covered Area
420,923 SF/9.6631 AC. PURDY-MCGUIRE, INC.
27" PECAN50'SP

20.5
LOT 3, BLOCK 10/7941 17300 N. DALLAS PARKWAY, SUITE 3000
FOURTH INSTALLMENT 6.5 Brick Walls

4
KINGS ROW INDUSTRIAL DISTRICT DALLAS, TX 75248

36" PECAN 65'SP


Vol. 68040, Pg. 2015, DRDCT NO

RO
PARKING 972-239-5357

60' Public ROW, Co


ANY
TIME

UND TAncBreLteEPaD
36" PECAN 65'SP

civil
BT FOODS TX HOLDINGS, LLC
Block 10/7941 30" PECAN 65'SP
30" PECAN 60'SP
12 Concrete
Pavement INST. NO. 201500151904, OPRDCT PACHECO KOCH
King Row Industrial District
Fourth Installment FFE= 409.26
7557 RAMBLER RD. #1400
Vol. 68040, Pg. 2014, D.R.D.C.T. 12 DALLAS, TX 75234

142.2
S4

7" CREPE MYRTLE 20'SP


972.235.3031
4

36" PECAN 65'SP


°4

Cantex Regal LLC


9'

Inst. 201700215989, O.P.R.D.C.T.


25

13
8" CREPE MYRTLE 15'SP landscape
"W

6' Chain Link Fence


51

vement
PACHECO KOCH
3.

RIVE
73

36" PECAN 65'SP


7557 RAMBLER RD. #1400
36" PECAN 65'SP
DALLAS, TX 75234
20' FIRE LANE EASEMENT FFE= 409.42 FFE= 409.46
Vol. 68196, Pg. 142
D.R.D.C.T.
15
310.0
972.235.3031
15 NO structural engineer

36" PECAN 65'SP


36" PECAN 65'SP

PARKING
ANY EJES INCORPORATED
TIME
20' FIRE LANE EASEMENT
Vol. 68196, Pg. 142, D.R.D.C.T. 12801 N. CENTRAL EXPY, SUITE 700
36" PECAN 65'SP DALLAS, TX 75243
11 32 H H 3 5/8"FIR 214.3431210
17

S87°23'25"E 68
17 security, audio/visual

BENCHMARK #2:
32 6
NOVOM GROUP

36" PECAN 65'SP

ELEV=408.50
Concrete Metal Fence 400 S. RECORD ST, SUITE 1200

X-CUT
Pavement
w/ Brick Columns
DALLAS, TX 75202

.50
57 8 214-882-1540
5/8"FIR 1/2"CIRF
project
X X X X X X X X X
S01°38'55"E 605.79 YELLOW
5/8"FIR 6' Chain Link Fence AFFIDAVIT OF FACTS
Δ=027°39'07" Vol. 2002068, Pg. 5345
R=88.08' D.R.D.C.T. DALLAS COUNTY ELECTIONS BUILDING
L=42.51'
CB=S 15°28'28" E
Block 7941
King Row Industrial District
The County of Dallas, State of Texas
Inst. 20150222226, O.P.R.D.C.T.
Block 12/7941
Roundtable Addition 1460 ROUND TABLE DR
CD=42.10' Fourth Installment
Vol. 68040, Pg. 2015, D.R.D.C.T.
Vol. 74103, Pg. 1425, D.R.D.C.T.
ISSUED FOR PRELIMINARY PRICING PURPOSES ONLY DALLAS, TX 75247
Jessup Investments LLC
Inst. 201400018000, O.P.R.D.C.T. (SUBJECT TO REVISION PRIOR TO CONSTRUCTION) The drawings and written material herein constitute original work o
architect, and as intellectual property and instruments of service, a
subject to copyright and may not be reproduced, distributed, publis
or used in any way without the express written consent of the arch
original issue
DESIGN DEVELOPMENT 04.30.2021
revisions

DALLAS COUNTY ELECTIONS BUILDING


NOT FOR CONSTRUCTION

BENC MARK SIGNAGE AND STRIPING PLAN


DALLAS COUNTY ELECTIONS BUILDING
LOT 3, BLOCK 10/7941
SUSTAINABLE DEVELOPMENT & CONSTRUCTION
CITY OF DALLAS, DALLAS COUNTY, TEXAS
DESIGN DRAWN DATE SCALE FILE NUMBER SHEET
title
C12.01 SIGNAGE AND STRIPING PLA
4/22/2021 5:30:27 PM

project number 20182.200


date 04.30.2021
sheet

C12.01
plotted:
C:\BOKAP\REVIT_PROJECTS\ARCH_20182_DALLAS_COUNTY_ELECTIONS_Alan-Macejewski.rvt

architecture interiors planning graphics


8070 Park Lane, Ste. 300 Dallas, Texas 75231
Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com

*VALVE/BOX REQUIREMENTS, MAX. MANIFOLDING:


- ONE 1 12" VALVE PER STANDARD VALVE BOX DBY/DBR SPLICES
- TWO 1" VALVES PER STANDARD VALVE BOX
- TWO 1 12" VALVES PER JUMBO VALVE BOX VALVE BOX, PER SPECS.
- THREE 1" VALVES PER JUMBO VALVE BOX VALVE BOX
SET BOX 2" ABOVE MULCH PER LANDSCAPE PLAN
SET BOX 2" ABOVE GRADE IN BED AREAS,
GRADE IN BED AREAS, 1" IN TURF AREAS, TYP. 2" SOIL COVER
1" IN TURF AREAS, TYP.
DBY/DBR SPLICES, TYP. DRIP TUBE STAKED AT 30" ON CENTER,
ALL LOCATIONS
client
VALVE SIZED PER PLAN
SPEARS SCH. 80 PVC
DALLAS COUNTY
SCH. 80 PVC BALL VALVE
BALL VALVE
DRIP ZONE ASSEMBLY TEES ALONG PVC HEADER
1460 ROUND TABLE DR
SCH. 80 PVC NIPPLES, DALLAS, TX 75247
12" MIN

SAME AS VALVE SIZE, TYP. SCH. 80 PVC NIPPLES,


TYP. 214-653-6437
BRICK SUPPORT, EACH SIDE, BRICK SUPPORT,
AS NEEDED TO REACH 1 PER SIDE, TYP.
CLEARANCE, TYP.
client representative
PRITCHARD ASSOCIATES
4"

2121 NORTH AKARD ST, SUITE 100


6"

3" DEPTH PEA GRAVEL DALLAS, TX 75201


PVC MAIN 214-849-0011
3" DEPTH PEA GRAVEL
WIRE IN CONDUIT UNDER LATERAL FEEDING HEADER
MAIN LINE TOP OF PIPE PAVING ONLY
AT 18" DEPTH m.e.p. engineer
WIRE IN CONDUIT UNDER
PAVING ONLY
PURDY-MCGUIRE, INC.
17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
972-239-5357

civil
AUTOMATIC SYSTEM VALVE DRIP ZONE VALVE ASSEMBLY-AT GRADE DRIP TUBE INSTALLATION - AT GRADE PACHECO KOCH
1 1 1/2" = 1'-0"
2 1 1/2" = 1'-0"
3 3" = 1'-0" 7557 RAMBLER RD. #1400
DALLAS, TX 75234
2'-0" TYP. 972.235.3031
landscape
FINISH GRADE, MULCH OR SOD POP-UP SPRAY PER LEGEND
PACHECO KOCH
BARBED FITTINGS BY MANUFACTURER, TYP. AIR RELEASE VALVE IN VALVE BOX, ONE COMPACT SOIL AROUND HEAD
PER ZONE AT HIGH CORNER, TYP.
7557 RAMBLER RD. #1400
CLASS 200 PVC HEADER, TYP.
DALLAS, TX 75234

1 "
2
FLEX PIPE ASSEMBLY
972.235.3031
4" POP-UP W/BUBBLER
PER LEGEND EACH SIDE
structural engineer
EJES INCORPORATED
MULCH LAYER
12801 N. CENTRAL EXPY, SUITE 700
DALLAS, TX 75243
214.3431210

3"
1'-4" MAX.
1'-0" MIN.
IN- LINE EMITTER TUBING.
SPACING PER LEGEND
security, audio/visual
COMPACT SOIL
NOVOM GROUP

1'-4" MAX.
1'-0" MIN.
AROUND HEAD
FLEX PIPE ASSEMBLY 400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
DRIP INDICATOR
214-882-1540
HEAD
project
FROM VALVE
INSTALL DRIP RINGS AT FLUSH VALVE FOR MANUAL FLUSH, DALLAS COUNTY ELECTIONS BUILDING
TREE TRUNKS, TYP. ONE END OF EXHAUST HEADER, TYP. CLASS 200 1460 ROUND TABLE DR
PVC LATERAL LINES
DALLAS, TX 75247
CLASS 200 PVC
LATERAL LINES The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published
DRIP ZONE TYPICAL ENLARGEMENT SPRAY HEAD / ROTATOR HEAD BUBBLER HEAD or used in any way without the express written consent of the architect.
4 3/8" = 1'-0"
5 3" = 1'-0"
6 1 1/2" = 1'-0"
original issue
DESIGN DEVELOPMENT 04.30.2021
revisions

VALVE BOX

SET BOX 1/4" ABOVE SOD


CLEAR

FINISH GRADE
2"-4"

QUICK COUPLER

18" #5 REBAR SET 12" MIN.


INTO DISTURBED SOIL

3" DPETH PEA GRAVEL

BRICK SUPPORT,
1 PER SIDE, TYP.

(2) SCREW CLAMPS, TYP.

EXISTING MAIN LINE


title

SPEARS 3/4" SCH. 80 SWING


JOINT RISER ASSEMBLY
IRRIGATION DETAILS
4/22/2021 5:30:27 PM

project number 20182.200


QUICK COUPLER VALVE
7 1 1/2" = 1'-0" date 04.30.2021
sheet

L3.01
plotted:
C:\BOKAP\REVIT_PROJECTS\ARCH_20182_DALLAS_COUNTY_ELECTIONS_Alan-Macejewski.rvt

architecture interiors planning graphics


8070 Park Lane, Ste. 300 Dallas, Texas 75231
Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com

SOIL GENERAL NOTES SOIL RESOURCE LEGEND


1. A SOIL RESOURCE ASSESSMENT IS REQUIRED IN CONJUNCTION WITH THE
INSTALLATION OF LEGACY TREES. SOIL AMENDMENT ZONE
(SOIL AMENDMENT OR TREATMENT
2. THE RANGES FOR PHYSICAL, CHEMICAL, AND BIOLOGICAL INDICATORS OF WITH MINIMAL DISTURBANCE)
SOIL QUALITY FOR URBAN TREES IS DETERMINED FROM THE ISA BEST
MANAGEMENT PRACTICES FOR SOIL MANAGEMENT FOR URBAN TREES, OR IN CONSTRUCTION ZONE
ANOTHER PUBLICATION APPROVED BY THE BUILDING OFFICIAL. (WHERE CONSTRUCTION TRAFFIC
3. PLANTING AREA REQUIREMENTS:
AND STAGING WILL BE ALLOWED) client
STOCKPILING ZONE
DALLAS COUNTY
·· FOR EACH SMALL TREE INSTALLATION, A MIN. OF 24 INCHES OF SOIL
DEPTH AND 25 SQUARE FEET OF OPEN SOIL AREA (TOTAL OF 50 CUBIC (STOCKPILING FOR TOPSOIL AND 1460 ROUND TABLE DR
IMPORTED SOIL AMENDMENTS)
FEET) MUST BE PROVIDED. DALLAS, TX 75247
·· FOR EACH LARGE OR MEDIUM TREE INSTALLATION, A MIN. OF 36 INCHES 214-653-6437
OF SOIL DEPTH AND 160 SQUARE FEET OF OPEN SOIL AREA (TOTAL OF
480 CUBIC FEET) MUST BE PROVIDED.
client representative
·· NON-LEGACY TREES MAY SHARE OPEN SOIL AREAS. PRITCHARD ASSOCIATES
·· LARGE TREES AND MEDIUM TREES MUST BE PLANTED A MIN. OF FOUR 2121 NORTH AKARD ST, SUITE 100
FEET FROM PAVEMENT. DALLAS, TX 75201
·· THE PLANTING AREAS MUST HAVE NATIVE SOILS, PREPARED SOILS, OR 214-849-0011
STRUCTURAL SOILS, AND MAY INCLUDE PERMEABLE PAVEMENT, SIDEWALK
SUPPORT, AND SOIL CELLS. m.e.p. engineer
·· REQUIRED AREAS FOR PLANT MATERIALS MUST BE PROTECTED FROM PURDY-MCGUIRE, INC.
VEHICULAR TRAFFIC THROUGH THE USE OF CONCRETE CURBS, WHEEL
STOPS, OR OTHER PERMANENT BARRIERS. . 17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
972-239-5357

GA
WAT

TUAGT
W
WAT WAT

SAN
S
WAT WAT
WAT WAT
civil
WAT WAT
WAT WAT

RIM=407.22
WAT WAT
WAT WAT
WAT
WAT 8"WATER
PACHECO KOCH

WAT

ST
RIM=407.78

WAT

KING JAMES DRIVE 7557 RAMBLER RD. #1400

GA
WAT

ST

WA
TUGT
SAN
S
WA
FL10"=401.42
POH POH POH POH
SAN
DALLAS, TX 75234
972.235.3031
T POH SAN
FL10"=402.58 POH POH POH SAN SAN W TUG
LINE / LIMIT OF WORK
SAN
WW
ARTIFICIAL LOT
POH GAS TUG

S
POH POH SAN SAN TUG GAS TUG
POH POH SAN SAN GAS TUG GAS TUG
WAT

POH SAN GAS TUG


POH POH POH
SAN SAN SAN
GAS TUG GAS TUG GAS TUG T

landscape
WA POH POH GAS TUG GAS TUG

CO
T SAN SAN SAN
GAS T TUG GAS TUG GAS TUG
GAS TUG
S

GAS TUG
SAPN
OH
GAGS TUG GAS TUG

PACHECO KOCH
TU
SAPN
OH TGUAGS
W

MH
MH
AT
TGUAGS
10
6
5
7557 RAMBLER RD. #1400

TUG WA
PO
ST

DALLAS, TX 75234
H

SAN

T
972.235.3031
TGUAS

3"G
G
EXISTING
W
"SS
AT
10

as
PO
H
EQUIPMENT SOIL AMENDMENT ZONE
YARD structural engineer
ST

S
TGUA AN
GS
20

TUG WAT
SOIL AMENDMENT ZONE EJES INCORPORATED

8"SS
STO

PO
H
W

GAS
AT

S
TGUA AN SOIL AMENDMENT ZONE 12801 N. CENTRAL EXPY, SUITE 700
GS 18
PO DALLAS, TX 75243

42"
H
RIM=407.57

214.3431210

RCP

TUG WAT
SOIL AMENDMENT ZONE

SAN
s
Ga
3"

GAS
security, audio/visual
PO S
H

TU

NO ACCESS
G

NOVOM GROUP
GA

ARTIFICIAL LOT LINE / LIMIT OF WORK

27
S

STO

TUG WAT
400 S. RECORD ST, SUITE 1200

SAN
PO
H SA GAS

GAS
DALLAS, TX 75202
TU
G
N

18"
RCP 214-882-1540
EXISTING BUILDING
STO

TUG WAT
project
TU

CONSTRUCTION
G

STOCKPILING

SAN
STAGING ZONE

GAS
ZONE DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
DALLAS, TX 75247
STO

TUG WAT
SAN
The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published

GAS
or used in any way without the express written consent of the architect.

TUG WAT
SOIL AMENDMENT ZONE original issue

SAN
4

DESIGN DEVELOPMENT 04.30.2021

ROUND TAB
STO

revisions

GAS

TUG WAT
ARTIFICIAL LOT LINE / LIMIT OF WORK

8"SS
12
SOIL AMENDMENT ZONE SOIL AMENDMENT ZONE

48"RCP
ST
O

12

GAS

TUG
LE DRIVE
WAT
SAN
13

3"Gas

TUG
WAT

GAS

12"WATER
8"SS
15
RK
OF WO

15

TUG
SAN
WAT
GAS
ARTIFICIAL LOT LINE / LIMIT OF WORK
IM IT

STO
/ L

H 3
H
LINE

STO
32 STO
STO STO
STO
STO
11
IAL LOT

STO
17 STO STO STO
STO STO STO STO STO 6
Storm Sewer
Approx. Centerline 32
17 title

WAT
SAN

TUG
ARTIFIC

SOIL RESOURCE PLAN


8

57

GAS

WAT
SAN

TUG
X X
X X
X X
X X
X
4/22/2021 5:30:27 PM

project number 20182.200

date 04.30.2021
sheet
SOIL RESOURCE PLAN
1 1" = 40'-0"

L0.01
plotted:
C:\BOKAP\REVIT_PROJECTS\ARCH_20182_DALLAS_COUNTY_ELECTIONS_Alan-Macejewski.rvt

architecture interiors planning graphics


8070 Park Lane, Ste. 300 Dallas, Texas 75231
Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com

TREE MITIGATION NOTES EVAPORATION. 


1. PROCEDURES REQUIRED PRIOR TO CONSTRUCTION: THE FOLLOWING PROCEDURES SHALL BE D. ALL TREES DIRECTLY ADJACENT TO BUILDINGS SHOULD BE PRUNED FOR CANOPY 4. TREES THAT WERE PREVIOUSLY IRRIGATED SHALL BE IRRIGATED DURING CONSTRUCTION.
FOLLOWED ON ALL TYPES OF CONSTRUCTION PROJECTS. RAISING TO PROVIDE A MINIMUM OF 4 TO 6 FEET OF CLEARANCE OVER THE THEY SHALL RECEIVE A MIN. OF ONE INCH OF WATER PER WEEK FROM THE COMBINATION OF
BUILDINGS AS WELL AS CANOPY REDUCTION PRUNING TO PROVIDE A MINIMUM OF RAINFALL AND IRRIGATION. TREES WITH ROOT-DAMAGE SHALL RECEIVE TWO INCHES OF
A. DURING PRE-CONSTRUCTION, TREES TO BE REMOVED SHOULD BE REMOVED 2 FEET CLEARANCE AWAY FROM THE SIDES OF BUILDINGS. WATER PER WEEK FROM COMBINATION OF RAINFALL AND IRRIGATION.
FROM THE SITE IN A MANNER TO AVOID INJURY TO REMAINING TREES,
INCLUDING THE REMOVAL OF STUMPS AND/OR ROOT SYSTEMS. HEAVY 2. THE FOLLOWING ACTIVITIES ARE PROHIBITED WITHIN THE LIMITS OF THE CRITICAL ROOT 5. CONTRACTOR RESPONSIBLE FOR ANY DAMAGE TO TREES THAT ARE TO REMAIN.
EQUIPMENT SHALL NOT ENCROACH ON THE ROOT SYSTEMS OF TREES TO BE ZONE OF ANY PROTECTED TREE SUBJECT TO THE REQUIREMENTS OF THE CITY ORDINANCE. CONTRACTOR TO INSTALL NEW TREE OF EQUIVALENT SIZE IF DAMAGED DURING
RETAINED OR OTHER TREES OF HIGH VALUE. IF NECESSARY, TREES SHOULD BE CONSTRUCTION.
REMOVED MANUALLY WITH CHAIN SAWS, AND STUMPS SHOULD BE GROUND A. MATERIAL STORAGE: NO MATERIALS INTENDED FOR USE IN CONSTRUCTION OR WASTE
OUT INSTEAD OF USING HEAVY EQUIPMENT. MATERIALS ACCUMULATED DUE TO EXCAVATION OR DEMOLITION SHALL BE PLACED client
WITHIN THE LIMITS OF THE CRITICAL ROOT ZONE OF ANY PROTECTED TREE.
B. CRITICAL ROOT ZONES SHALL BE ESTABLISHED AND MAINTAINED FOR ALL TREES DALLAS COUNTY
TO BE CONSERVED ON A CONSTRUCTION SITE. THIS AREA MAY BE ADJUSTED FOR
EXISTING BUILDINGS, WALKWAYS, AND ROADS BY PERMISSION OF OWNER.
B. EQUIPMENT CLEANING/LIQUID DISPOSAL: NO EQUIPMENT SHALL BE CLEANED OR OTHER 1460 ROUND TABLE DR
LIQUIDS DEPOSITED OR ALLOWED TO FLOW OVERLAND WITHIN THE LIMITS OF THE
BARRICADES SHALL BE 4 FOOT HIGH ORANGE VINYL CONSTRUCTION FENCE.
CRITICAL ROOT ZONE OF A PROTECTED TREE. THIS INCLUDES, WITHOUT LIMITATION, DALLAS, TX 75247
SIGNS, IN ENGLISH AND SPANISH SHALL BE PLACED VISIBLE FROM ALL
DIRECTIONS, ALONG THE FENCE TO INFORM WORKERS OF THE PURPOSE OF THE PAINT, OIL, SOLVENTS, ASPHALT, CONCRETE, MORTAR OR SIMILAR MATERIALS. 214-653-6437
BOUNDARY. THE BARRIER AND PROPER SIGNAGE SHALL BE INSTALLED PRIOR TO
ANY SITE PREPARATION AND SHALL BE MAINTAINED THROUGHOUT ALL PHASES OF C. TREE ATTACHMENTS: NO SIGNS, WIRES OR OTHER ATTACHMENTS, OTHER THAN THOSE A
THE CONSTRUCTION PROJECT. EROSION AND SEDIMENT CONTROL BARRIERS PROTECTIVE NATURE, SHALL BE ATTACHED TO ANY PROTECTED TREE. client representative
SHALL BE INSTALLED OR MAINTAINED IN A MANNER WHICH DOES NOT RESULT IN
SOIL BUILDUP WITHIN THE TREE DRIP LINE. APPLY 4 INCHES OF COURSE MULCH D. GRADE CHANGES: NO GRADE CHANGES SHALL BE ALLOWED WITHIN THE LIMITS OF THE PRITCHARD ASSOCIATES
WITHIN PROTECTION AREAS TO HELP REDUCE MOISTURE STRESS AND REDUCE CRITICAL ROOT ZONE OF ANY PROTECTED TREE UNLESS ADEQUATE CONSTRUCTION 2121 NORTH AKARD ST, SUITE 100
MAINTENANCE. METHODS ARE APPROVED BY THE LANDSCAPE ARCHITECT.
DALLAS, TX 75201
C. WHERE EXCAVATIONS ARE PERFORMED WITHIN THE ROOT ZONE OF TREES, E. IMPERVIOUS PAVING: NO PAVING WITH ASPHALT, CONCRETE OR OTHER IMPERVIOUS 214-849-0011
TRENCHING SHOULD BE PERFORMED MANUALLY, OR BY USING A VIBRATORY MATERIALS THAT MAY REASONABLY BE EXPECTED TO KILL A TREE SHALL BE PLACED
PLOW, DIRECTIONAL BORER, OR BY AIR SPADING. BACKHOES SHALL NOT BE WITHIN THE LIMITS OF CRITICAL ROOT ZONE OF A PROTECTED TREE EXCEPT AS
USED TO RIP ROOTS AT CONSIDERABLE DISTANCES FROM THE POINT OF OTHERWISE ALLOWED IN THE CITY ORDINANCE. m.e.p. engineer
EXCAVATION. WHEN TRENCHING OR MODIFICATION OF THE ROOT ZONE
ENCROACHES HEAVILY ONTO ESTABLISHED TREES, A ROOT PRUNING METHOD 3. PROHIBITED ACTIVITIES IN DRIP-LINE: NO HEAVY EQUIPMENT, INCLUDING BUT NOT LIMITED
PURDY-MCGUIRE, INC.
SHOULD BE EMPLOYED WHERE THE ROOTS ARE EXPOSED AND TRIMMED WITH TO TRUCKS, TRACTORS, TRAILERS, BULLDOZERS, BOBCAT TRACTORS, TRENCHERS, 17300 N. DALLAS PARKWAY, SUITE 3000
PROPER PRUNING TOOLS SEVERAL INCHES TO THE SIDE OF THE TRENCH NOTE: OWNER TO PAY FOR REMAINING INCHES TO CITY TREE REFORESTATION FUND.
COMPRESSORS, AND HOISTS, SHALL BE ALLOWED INSIDE THE DRIP-LINE OF ANY PROTECTED
BORDERING THE TRUNK OF THE AFFECTED TREE. TEARING OF ROOTS IS TO BE
TREE ON ANY CONSTRUCTION SITE WITHOUT THE SPECIFIC APPROVAL OF THE LANDSCAPE
DALLAS, TX 75248
AVOIDED. SUPPLEMENTAL IRRIGATION SHALL START IF NEEDED. ANY ROOTS
EXPOSED BY CONSTRUCTION ACTIVITY SHALL BE PRUNED FLUSH TO THE SOIL
ARCHITECT. 972-239-5357

GA
WAT
AND SEALED USING LAC BALSAM. BACKFILL ROOT AREAS WITH GOOD QUALITY

TUAGT
W
WAT WAT

SAN
S
WAT
4. TREES THAT WERE PREVIOUSLY IRRIGATED SHALL BE IRRIGATED DURING CONSTRUCTION. WAT WAT
WAT
TOP SOIL AS SOON AS POSSIBLE (I.E. WITHIN THE SAME WORKDAY). IF ROOTS civil
WAT WAT
WAT WAT

RIM=407.22
WAT
ARE NOT BACKFILLED WITHIN THIS TIME, THEY SHALL BE COVERED WITH WAT WAT
WAT WAT

ORGANIC MATERIAL SUCH AS COMPOSTED MULCH TO A DEPTH OF 4 INCHES, WAT 8"WATER


PACHECO KOCH

WAT

ST
RIM=407.78

WAT
WHICH WILL REDUCE TEMPERATURE AND MINIMIZE WATER LOSS DUE TO
EVAPORATION.  7557 RAMBLER RD. #1400

GA
IVE
KING JAMES DRment
W AT

ST
#9

WA
TUGT
SAN
S
#11
60' Public ROW, Concrete Pave
#10 24" PECAN
FL10"=401.42
POH POH DALLAS, TX 75234
WA
24" PECAN 24" PECAN POH POH SAN
972.235.3031
T POH SAN
FL10"=402.58 POH POH POH
SAN SAN SAN W TUG
POH WW GAS TUG

S
ARTIFICIAL LOT TLINE / LIMIT OF WORK
POH POH SAN SAN TUG GAS TUG
POH POH SAN SAN GAS TUG GAS TUG
WAT

POH POH SAN SAN GAS TUG GAS TUG


POH POH SAN SAN GAS TUG GAS TUG

landscape
WA POH POH GAS TUG GAS TUG

CO
T SAN SAN SAN
GAS T TUG GAS TUG GAS TUG
GAS TUG
S

GAS TUG
SAPN
OH
GAGS TUG GAS TUG

PACHECO KOCH
TU
SAPN
OH TGUAGS
W

MH
MH
AT
TGUAGS
10
6
5
7557 RAMBLER RD. #1400

TUG WA
PO
ST

DALLAS, TX 75234
H

SAN

T
972.235.3031
TGUAS

3"G
G
EXISTING
W
"SS
AT
10

as
PO
H
EQUIPMENT
YARD structural engineer
ST

S
TGUA AN
GS
20

TUG WAT
EJES INCORPORATED

8"SS
STO

PO
H
W

GAS
AT

S
TGUA AN 12801 N. CENTRAL EXPY, SUITE 700
GS 18
PO DALLAS, TX 75243

42"
H
RIM=407.57

214.3431210

RCP

TUG WAT
SAN
s
Ga
3"

GAS
security, audio/visual
PO S
H

TU

NO ACCESS
G

#8 NOVOM GROUP
GA

#15
ARTIFICIAL LOT LINE / LIMIT OF WORK

27
S

40" PECAN
STO

6" HOLLY

TUG WAT
400 S. RECORD ST, SUITE 1200

SAN
PO
H SA GAS

GAS
DALLAS, TX 75202
TU
G
N

#14
6" HOLLY
18"
RCP 214-882-1540
EXISTING BUILDING
STO

TUG WAT
project
TU
G

SAN
#4

GAS
30" PECAN DALLAS COUNTY ELECTIONS BUILDING
#5 #3 #12 1460 ROUND TABLE DR
8" RED OAK 36" PECAN 6" CRAPE MYRTLE
DALLAS, TX 75247
STO

TUG WAT
#6

SAN
The drawings and written material herein constitute original work of the
6" RED OAK
architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published
#13

GAS
or used in any way without the express written consent of the architect.

ROUND TAB
TREE PROTECTION FENCE 10" CRAPE MYRTLE

TUG WAT
60' Public RO
REF. DETAILS 1 & 2 /L2.01 original issue

SAN
4

#2 DESIGN DEVELOPMENT 04.30.2021


STO

36" PECAN
revisions

W, Concrete
GAS

TUG WAT
ARTIFICIAL LOT LINE / LIMIT OF WORK

LE
#7

8"SS
12
7" CRAPE MYRTLE TREE PROTECTION FENCE REF.

Pa
DRIV
DETAILS 1 & 2 /L2.01

48"RCP

vem
Block 10/7941
ST
O

King Row Industrial District 12

GAS

ent
Fourth Installment

TUG
Vol. 68040, Pg. 2014, D.R.D.C.T.
#1

WAT
6" CRAPE
13 MYRTLE

SAN
Cantex Regal LLC

3"Gas
Inst. 201700215989, O.P.R.D.C.T.

TUG
WAT

GAS

12"WATER
8"SS
15
RK
OF WO

15

TUG
SAN
WAT
GAS
ARTIFICIAL LOT LINE / LIMIT OF WORK
IM IT

STO
/ L

H 3
H
LINE

STO
32 STO
STO STO
STO
STO
11
IAL LOT

STO
17 STO STO STO
STO 6
TREE MITIGATION LEGEND
STO STO STO
STO
Storm Sewer
Approx. Centerline 32
17 title

WAT
SAN

TUG
ARTIFIC

TREE TO REMAIN
TREE MITIGATION PLAN
8

57
TREE TO BE REMOVED

GAS

WAT
SAN

TUG
X X
X X
X X
X X
X
AFFIDAVIT OF FACTS
4/22/2021 5:30:27 PM

Vol. 2002068, Pg. 5345


TREE PROTECTION FENCE
D.R.D.C.T.
project number 20182.200
Block 12/7941
The County of Dallas, State of Texas Roundtable Addition
Inst. 20150222226, O.P.R.D.C.T. Vol. 74103, Pg. 1425, D.R.D.C.T.
Block 7941
King Row Industrial District
date 04.30.2021
Fourth Installment
Vol. 68040, Pg. 2015, D.R.D.C.T. sheet
Jessup Investments LLC

TREE MITIGATION PLAN


1 1" = 40'-0"

L1.00
plotted:
C:\BOKAP\REVIT_PROJECTS\ARCH_20182_DALLAS_COUNTY_ELECTIONS_Alan-Macejewski.rvt

architecture interiors planning graphics


8070 Park Lane, Ste. 300 Dallas, Texas 75231
Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com

PLANT SCHEDULE REFERENCE NOTES SCHEDULE PLANTING GENERAL NOTES


2021-04-23 08:07 2021-04-23 08:08
TREES BOTANICAL / COMMON NAME SIZE/COND. REMARKS SYMBOL DESCRIPTION DETAIL 1. ALL PLANTS SHALL BE SET OUT FOR APPROVAL BY THE OWNER'S
JB2 JUNIPERUS VIRGINIANA `BURKII` B&B 3" CAL, SINGLE, STRAIGHT LEADER, REPRESENTATIVE PRIOR TO INSTALLATION.
BURK EASTERN RED CEDAR MATCHING 1 GRAVEL, 1" NATIVE GRAVEL, DFW STONE SUPPLY 7/L2.01
2. FINE GRADING SHALL BE PERFORMED IN ALL AREAS TO BE LANDSCAPED. FINE
LD LAGERSTROEMIA INDICA `DYNAMITE` 30 GAL 3" CAL, MULTI-STEM, FULL, MATCHING 2 COBBLE, 2-4" SIZE, COLORADO RIVER ROCK, DFW STONE SUPPLY 7/L2.01 GRADING SHALL INCLUDE THE REMOVAL OF DEBRIS, ROCKS, ETC. FROM THE
DYNAMITE CRAPE MYRTLE OR APPROVED EQUAL SITE AND INSURE POSITIVE DRAINAGE IN ALL AREAS.

QV2 QUERCUS VIRGINIANA B&B 4" CAL, SINGLE, STRAIGHT LEADER, 3 COBBLE, ARKANSAS RIVER ROCK, 3-4" SIZE, DFW STONE SUPPLY 7/L2.01 3. THE CONTRACTOR SHALL LOCATE ALL UTILITIES AND EASEMENTS IN THE FIELD
LIVE OAK MATCHING OR APPROVED EQUAL PRIOR TO COMMENCEMENT OF WORK. CONTRACTOR IS RESPONSIBLE FOR
ANY DAMAGE TO UTILITIES DURING THE COURSE OF CONSTRUCTION. client
UP ULMUS PARVIFOLIA B&B 4" CAL, SINGLE, STRAIGHT LEADER, 4 STEEL EDGING 6/L2.01
LACEBARK ELM FULL, MATCHING 4. WRITTEN DIMENSIONS SHALL GOVERN OVER SCALED DIMENSIONS.
DALLAS COUNTY
1460 ROUND TABLE DR
SHRUBS BOTANICAL / COMMON NAME SIZE SPACING REMARKS 5. THE CONTRACTOR SHALL REFER TO THE SPECIFICATIONS FOR ADDITIONAL DALLAS, TX 75247
AE2 ASPIDISTRA ELATIOR 3 GAL 30" o.c. FULL, MATCHING INFORMATION AND REQUIREMENTS ASSOCIATED WITH THE LANDSCAPE AND
CAST IRON PLANT ACCESSORIES. 214-653-6437
BSB BUXUS X `GREEN MOUNTAIN` 7 GAL 36" o.c. FULL, MATCHING 6. ALL PLANT MATERIALS SHALL MEET ANSI Z60.1 STANDARDS FOR CALIPER,
GREEN MOUNTAIN BOXWOOD HEIGHT AND ROOT BALL SIZE. ANY MATERIALS THAT DO NOT MEET OR EXCEED client representative
SUCH STANDARDS SHALL BE REJECTED AND REPLACED AT THE CONTRACTOR'S PRITCHARD ASSOCIATES
ID ILEX CORNUTA `DWARF BURFORD` 7 GAL 36" o.c. FULL, MATCHING EXPENSE.
DWARF BURFORD HOLLY 2121 NORTH AKARD ST, SUITE 100
7. BALLED AND BURLAPPED TREES SHALL HAVE THE TOP HALF OF THE WIRE DALLAS, TX 75201
JH JUNIPERUS HORIZONTALIS 3 GAL 36" o.c. FULL, MATCHING BASKET REMOVED. THE BURLAP SHALL BE REMOVED TO THE GREATEST
BLUE RUG JUNIPER EXTENT POSSIBLE, USING A KNIFE TO CUT AND REMOVE THE BOTTOM HALF 214-849-0011
UNDER THE WIRE BASKET THAT REMAINS.
JT JUNIPERUS SCOPULORUM `SKYROCKET` 10 GAL 36" o.c. FULL, MATCHING, 8FT HT @ PLANTING
SKYROCKET JUNIPER 8. QUANTITIES ARE SHOWN FOR CONVENIENCE ONLY. CONTRACTOR IS m.e.p. engineer
RESPONSIBLE FOR VERIFYING ALL QUANTITIES PURDY-MCGUIRE, INC.
JN JUNIPERUS VIRGINIANA `BRODIE` 10 GAL 60" o.c. FULL, MATCHING, 5-6FT HT @ PLANTING
BRODIE JUNIPER 17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
MC2 MUHLENBERGIA LINDHEIMERI 3 GAL 36" o.c. FULL, MATCHING
LENDHEIMER MUHLY 972-239-5357
GROUND COVERS BOTANICAL / COMMON NAME SIZE SPACING REMARKS
NT NASSELLA TENUISSIMA 4"POT 18" o.c. FULL, MATCHING
civil
MEXICAN FEATHER GRASS T
WA
PACHECO KOCH
LD MC2
SOD/SEED BOTANICAL / COMMON NAME SIZE SPACING REMARKS 2 15 7557 RAMBLER RD. #1400

GA
WAT
VISIBILITY TRIANGLE

WA
TUGT
WAT WAT

SAN
CD CYNODON DACTYLON SOD SOLID, ROLLED TIGHT, SAND FILLED DALLAS, TX 75234

S
WAT
QV2 WAT JT
WAT WAT WAT

MC2
KING JAMES DRIVE
WAT
BERMUDA GRASS JOINTS, 100% WEED, PEST AND
WAT
WAT
NEW GATE ACCESS 22

RIM=407.22
972.235.3031
WAT
WAT WAT
32
WAT
3
DISEASE FREE 8"WATER
WAT
REF. CIVIL DWGS. VISIBILITY TRIANGLE
JN JT
WAT

WAT

ST
RIM=407.78

WAT
ID ID
24 24 MC2 9 17
JT
landscape

GA
WAT
JB2

ST
36 15'-0" 15'-0"

TUGT
WA
SAN
S
30'-0" QV2 MC2 5 FL10"=401.42 48 PACHECO KOCH
LD 2 1 5
POH
MC2
WA POH POH SAN
1
POH
30'-0" 7557 RAMBLER RD. #1400
T POH SAN
SAN W
FL10"=402.58 2 POH POH SAN TUG
12
POH SAN
POH WW GAS TUG

S
POH SAN GAS TUG
4 POH POH SAN SAN GAS TUG TUG
POH SAN GAS TUG X-CUT SET
DALLAS, TX 75234
WAT

POH SAN GAS TUG


POH POH POH
SAN SAN SAN
GAS TUG GAS TUG GAS TUG T
POH

30'-0"
WA POH GAS TUG GAS TUG
30'-0"

CO
T

15'-0"
T SAN SAN GAS TUG GAS TUG
SAN GAS TUG
972.235.3031
GAS TUG
S

GAS TUG

15'-0"
SAPN
OH TUG GAS TUG
ARTIFICIAL LOT LINE/
GAGS
TU
SAPN
OH TGUAGS 5/8"FIR
LIMIT OF WORK
W
structural engineer

MH
MH
AT 5
6
TGUAGS
10

TUG WA
PO
ST

EJES INCORPORATED
H
1/2"FIR

SAN
4

T
3 12801 N. CENTRAL EXPY, SUITE 700
TGUAS
3

3"G
3 ID
W G
"SS EXISTING EQUIPMENT
AT
10

as
PO
H 36 YARDS NT DALLAS, TX 75243
0"
NEW GATE ACCESS 12'-
ST

32
S
TGUA AN
GS
REF. CIVIL DWGS. 20
MC2 214.3431210

TUG WAT
8"SS
10 TRANSFORMER & GENERATOR
STO

PO
H
W

GAS
REF. MEP DWGS.
AT

S
TGUA AN UP security, audio/visual
GS 18
2

6'-0
PO
NOVOM GROUP

42"
H
RIM=407.57

NT MONUMENT SIGN,

"

RCP
NT

TUG WAT
1/2"CIRF
153 CD 4 REF. ARCH. DWGS. 400 S. RECORD ST, SUITE 1200
201

SAN
s
Ga 2,493 sf
3"

GAS
NT 2 DALLAS, TX 75202
PO S

UP
H

319 214-882-1540
TU

NO ACCESS 1
G
GA

ARTIFICIAL LOT LINE / LIMIT OF WORK

27
JT
S

4
STO

DUMPSTER, REF. 19

TUG WAT
ARCH DWGS project

SAN
PO

CD
H SA GAS

GAS
BSB
TU

1,089 sf DALLAS COUNTY ELECTIONS BUILDING


G
N

32 ALIGN W/ 18"
1/2"FIR
LOADING DOCK, EXISTING
RCP 1460 ROUND TABLE DR
REF. CIVIL DWGS
EXISTING BUILDING AE2 PLANTER DALLAS, TX 75247
STO

UP

TUG WAT
22
TU
G

WALL, REF.

SAN
1 The drawings and written material herein constitute original work of the

GAS
STRUCTURAL DWGS.
MC2 architect, and as intellectual property and instruments of service, are
EXISTING OVERHEAD 16 subject to copyright and may not be reproduced, distributed, published
EXISTING TREES TO REMAIN CANOPY or used in any way without the express written consent of the architect.
JH
STO

TUG WAT
TP
40 4 original issue

SAN
9.
CD 4
07
AE2

ROUND TAB
1,572 sf 13 DESIGN DEVELOPMENT 04.30.2021
ALIGN W/
EXISTING
revisions

GAS
JT PLANTER

TUG WAT
TP
EXISTING SIGNIFICANT 13 ID

SAN
40
8.
47 4
TREE TO REMAIN 16
BSB
STO

24 JN

GAS
NT UP 6
90 1

TUG WAT
CD

LE DRIVE
ARTIFICIAL LOT LINE / LIMIT OF WORK
3,651 sf

8"SS
TP40

12 NT
8.17

128

48"RCP
Block 10/7941 CD
ST
O

King Row Industrial District 12

GAS
Fourth Installment
1,798 sf
UP

TUG
Vol. 68040, Pg. 2014, D.R.D.C.T. 2
1

WAT
TP
4

SAN
07 13
Cantex Regal LLC .8

3"Gas
Inst. 201700215989, O.P.R.D.C.T.
9
NT BUILDING WALL & SIGNAGE,
210 NT REF. ARCH DWGS
101
BUILDING ENTRY,

TUG
UP BUILDING ENTRY,
WAT

GAS
REF. ARCH DWGS

12"WATER
1 REF. ARCH DWGS
TP408.37

8"SS
15
RK
OF WO

15

TUG
SAN
WAT
GAS
ARTIFICIAL LOT LINE / LIMIT OF WORK
TP407.48

IM IT

STO
title
L

5/8"FIR
/

H 3
H
LINE

PLANTING PLAN
STO
32 STO
STO STO
STO
STO
11
IAL LOT

STO
17 STO STO STO
STO STO STO STO STO 6
Storm Sewer
Approx. Centerline 32
TP407.45

17

WAT
SAN

TUG
ARTIFIC
4/22/2021 5:30:27 PM

8 project number 20182.200


57
1/2"CIRF

WAT
GAS

SAN

TUG
X X
YELLOW
date 04.30.2021
X X
X X
X X
X
AFFIDAVIT OF FACTS
5/8"FIR Vol. 2002068, Pg. 5345
5/8"FIR
D.R.D.C.T. sheet
PLANTING PLAN Block 12/7941

1 Roundtable Addition

L2.00
The County of Dallas, State of Texas
Block 7941 Inst. 20150222226, O.P.R.D.C.T. Vol. 74103, Pg. 1425, D.R.D.C.T.
1" = 40'-0"
plotted:
C:\BOKAP\REVIT_PROJECTS\ARCH_20182_DALLAS_COUNTY_ELECTIONS_Alan-Macejewski.rvt

architecture interiors planning graphics


8070 Park Lane, Ste. 300 Dallas, Texas 75231
Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com

LIMITS OF DRIP-LINE

3 "x 4" STEEL EDGING (BLACK),


6'-8' O.C. 16
LOCATED ON PLANTER BED SIDE,
TYP
TACK WELD CORNERS AND JOINTS,
SPOT SPRAY PAINT WHERE NEEDED
MINIMUM LIMITS OF WITH BLACK ENAMEL
CRITICAL ROOT ZONE
RADIUS = 1 FT. PER INCH client
OF TRUNK DIAMETER
DALLAS COUNTY
CRITICAL ROOT ZONE
PROTECTED TREE TO TOP OF SOD LAYER 1460 ROUND TABLE DR
REMAIN
MULCH
DALLAS, TX 75247
DRIPLINE OF TREE
ORANGE TOPSOIL 214-653-6437
CONSTRUCTION FENCE
TREE PROTECTION FENCING;
PREPARED SOIL IN client representative
RE: DET. 4 / THIS SHEET PLANTING AREAS
PRITCHARD ASSOCIATES
EXISTING TREE TO REMAIN METAL T-POST (DIRECT 2121 NORTH AKARD ST, SUITE 100
4'-0" MIN.

BURIED 24" MIN)


DALLAS, TX 75201
NOTE: STEEL EDGE SHALL CREATE 214-849-0011
A CLEAN SEPARATION BETWEEN
AREAS & SHALL CREATE SMOOTH,
EVEN LINES (AS INDICATED ON m.e.p. engineer
NOTE: TREE PROTECTION FENCING SHALL BE THE PLANS) PURDY-MCGUIRE, INC.
PLACED AT OR BEYOND THE DRIP LINE OR
CRITICAL ROOT ZONE, WHICHEVER IS 17300 N. DALLAS PARKWAY, SUITE 3000
GREATER. DALLAS, TX 75248
972-239-5357

TREE PROTECTION FENCING - PLAN VIEW TREE PROTECTION FENCING STEEL EDGING AT PLANTING civil
1 N.T.S
2 3/4" = 1'-0" 6 1 1/2" = 1'-0" PACHECO KOCH
7557 RAMBLER RD. #1400
DALLAS, TX 75234
972.235.3031
landscape
SPACING PER
SHRUB PER PLAN OR PACHECO KOCH
PLANTING PLAN PLANT SCHEDULE 7557 RAMBLER RD. #1400
EDGE OF ROOT BALL
DALLAS, TX 75234
MULCH WITHIN AREA REF. PLANS FOR ADJ. 972.235.3031
OF EXCAVATION CONDITION
FILTER FABRIC,
structural engineer
STAKES COMPACTED
SUBGRADE TURNED UP AT EDGES EJES INCORPORATED
PAVING, REF. COBBLE, 3" DEPTH, REF. 12801 N. CENTRAL EXPY, SUITE 700
EDGE OF HOLE
PLANS FOR PLANS FOR TYPE
3"

TYPE
DALLAS, TX 75243
SLOPE 214.3431210
9"

security, audio/visual
MAX.

NOVOM GROUP
2"
1

400 S. RECORD ST, SUITE 1200


DALLAS, TX 75202
PLANTING SOIL IN SHRUB BEDS: SHREDDED BARK 214-882-1540
1. EXCAVATE EXISTING SOILS 4" BELOW MULCH LAYER
ADJACENT CURB OR SIDEWALK project
2. ADD 3" COMPOST & TILL INTO 6" EXISTING
SOILS, CREATING 9" PLANTING SOIL DALLAS COUNTY ELECTIONS BUILDING
3. ADD 3" MULCH AFTER PLANTING 1460 ROUND TABLE DR
DALLAS, TX 75247
The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are
TYP. SHRUB PLANTING COBBLE subject to copyright and may not be reproduced, distributed, published
4 1" = 1'-0"
7 1" = 1'-0"
or used in any way without the express written consent of the architect.
original issue
DESIGN DEVELOPMENT 04.30.2021
12 GA. BRAIDED WIRE,
TYP. ALLOW FOR 6" OF revisions
HORIZONTAL MOVEMENT
IN ANY ONE DIRECTION

6' STEEL T-POSTS (3),


SPRAY PAINT BLACK
SET TREE PLUMB
LEAVE TRUNK FLARE
EXPOSED, SET ROOT
BALL 2" ABOVE
FINISHED GRADE
TURF, REF. PLANTING PLANS
3" SHREDDED MULCH FOR TYPE
AS SPECIFIED

BACKFILL WITH SOIL


FROM TREE PIT
1"

EXCAVATION, TAMP
LIGHTLY & WATER IN
4"

6" LIFTS

TREE PIT MINIMUM 2X


WIDTH OF ROOT BALL
SCARIFY EDGES
TAMPED MOUND EXISTING SOIL
UNDISTURBED SOIL TOPSOIL PREP: title
1. FINISH GRADE TOPSOIL BY REMOVING STONES LARGER
THAN 1" IN ANY DIMENSION AND STICKS, ROOTS, RUBBISH,
AND OTHER EXTRANEOUS MATTER TO LEGALLY DISPOSE OF PLANTING DETAILS
THEM OFF OWNER'S PROPERTY.
2. ADD 1" COMPOST ON THE SURFACE, THEN TILL TO 4" DEPTH
3. INSTALL SOD AS SHOWN, REF. PLANTING PLANS FOR TYPE
4/22/2021 5:30:27 PM

CANOPY TREE PLANTING SOIL PROFILE FOR SOD project number 20182.200
3 3/4" = 1'-0"
5 1 1/2" = 1'-0"
date 04.30.2021
sheet

L2.01
plotted:
C:\BOKAP\REVIT_PROJECTS\ARCH_20182_DALLAS_COUNTY_ELECTIONS_Alan-Macejewski.rvt

architecture interiors planning graphics


8070 Park Lane, Ste. 300 Dallas, Texas 75231
Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com

IRRIGATION SCHEDULE IRRIGATION MODIFICATION NOTES


BODY.
SYMBOL MANUFACTURER/MODEL/DESCRIPTION RAIN BIRD R-VAN24 1804-SAM-P45 THE CONTRACTOR SHALL VISIT THE SITE & DOCUMENT THE EXISTING
POC
24 ADJ 24 F TURF ROTARY, 17`-24` 45-270 DEGREES AND 360 POINT OF CONNECTION 2" IRRIGATION SYSTEM TO A LEVEL SUFFICIENT TO DETERMINE:
RAIN BIRD 1804-PRS 5 SERIES MPR DEGREES. HAND ADJUSTABLE MULTI-STREAM ROTARY EXISTING IRRIGATION METER
Q H F TURF SPRAY 4.0" POP-UP SPRINKLER WITH CO-MOLDED W/1800 TURF SPRAY BODY ON 4.0" POP-UP, WITH CHECK 1. THAT THE BACKFLOW PREVENTION DEVICE ON THE EXISTING SYSTEM IS
WIPER SEAL. 1/2" NPT FEMALE THREADED INLET. VALVE AND 45 PSI IN-STEM PRESSURE REGULATOR. 1/2" IRRIGATION LATERAL LINE: PVC CLASS 200 SDR 21 FUNCTIONAL. IF NOT, HE SHALL PROVIDE A NEW ONE.
PRESSURE REGULATING. NPT FEMALE THREADED INLET. ONLY LATERAL TRANSITION PIPE SIZES 1" AND ABOVE ARE
INDICATED ON THE PLAN, WITH ALL OTHERS BEING 3/4" IN 2. THAT THE EXISTING CONTROLLER CAN ACCOMMODATE NEW ZONES OR
RAIN BIRD 1804-PRS 8 SERIES MPR RAIN BIRD 1804-PRS-1400 FLOOD 1401 SIZE. EXISTING ZONES MODIFIED WITHIN TCEQ DESIGN CRITERIA TO
Q T H F TURF SPRAY 4.0" POP-UP SPRINKLER WITH CO-MOLDED
1401 1402 1404 1408
FLOOD BUBBLER 4.0" POPUP WITH PRESSURE ACCOMMODATE EXISTING ZONES. PROVIDE NEW CONTROLLER IS client
WIPER SEAL. 1/2" NPT FEMALE THREADED INLET. REGULATING DEVICE. IRRIGATION MAINLINE: PVC SCHEDULE 40 NECESSARY.
PRESSURE REGULATING. DALLAS COUNTY
PIPE SLEEVE: PVC CLASS 200 SDR 21 3. IF EXISTING RAIN/FREEZE SENSOR IS PRESENT & FUNCTIONAL. IF NOT,
PROVIDE ONE COMPATIBLE WITH CONTROLLER.
1460 ROUND TABLE DR
RAIN BIRD 1804-PRS 10 SERIES MPR SYMBOL MANUFACTURER/MODEL/DESCRIPTION 2 SIZES LARGER THAN PIPE WITHIN.
Q T H F TURF SPRAY 4.0" POP-UP SPRINKLER WITH CO-MOLDED Valve Callout
DALLAS, TX 75247
4. WHAT MANUFACTURER IS CURRENTLY IN USE & PROVIDE SAME BRAND OF
WIPER SEAL. 1/2" NPT FEMALE THREADED INLET. RAIN BIRD XCZ-100-PRB-LC Valve Number
EQUIPMENT TO MODIFIED ZONES.
214-653-6437
PRESSURE REGULATING. WIDE FLOW DRIP CONTROL KIT, FOR LIGHT COMMERCIAL # # Valve Flow
USES. 1" PEB VALVE, WITH 1" PRESSURE REGULATING
RAIN BIRD 1804-PRS 15 SERIES MPR 40PSI BASKET FILTER. 0.3GPM TO 20GPM. #" Valve Size client representative
Q T H TQ F TURF SPRAY 4.0" POP-UP SPRINKLER WITH CO-MOLDED CONTRACTOR SHALL: PRITCHARD ASSOCIATES
WIPER SEAL. 1/2" NPT FEMALE THREADED INLET. RAIN BIRD XCZ-150-PRB-COM
PRESSURE REGULATING. HIGH FLOW CONTROL ZONE KIT, FOR LARGE COMMERCIAL 1. FOLLOW ALL TCEQ IRRIGATION REQUIREMENTS & STANDARDS. 2121 NORTH AKARD ST, SUITE 100
DRIP ZONES. 1-1/2" PESB VALVE WITH TWO 1" PRESSURE
RAIN BIRD 1804-PRS ADJ REGULATING (40PSI) QUICK-CHECK BASKET FILTERS. 2. PROVIDE LAMINATED 8 21" X 11" AS-BUILT OF THE FINISHED/MODIFIED DALLAS, TX 75201
4 6 8 10
TURF SPRAY 4.0" POP-UP SPRINKLER WITH CO-MOLDED FLOW RANGE: 15-40GPM. SYSTEM. 214-849-0011
12 15 18 WIPER SEAL. 1/2" NPT FEMALE THREADED INLET.
PRESSURE REGULATING. AREA TO RECEIVE DRIPLINE 3. DEMONSTRATE TO AN OWNER'S REPRESENTATIVE THAT THE IRRIGATION
RAIN BIRD XFS-06-12 SYSTEM IS FULLY FUNCTIONAL AND RUNNING PROPERLY PRIOR TO FINAL m.e.p. engineer
RAIN BIRD R-VAN14 1804-SAM-P45 XFS SUB-SURFACE PRESSURE COMPENSATING DRIPLINE ACCEPTANCE AND BEGINNING OF THE WARRANTY PERIOD
14 ADJ 14 F TURF ROTARY, 8`-14` 45-270 DEGREES AND 360 W/COPPER SHIELD TECHNOLOGY. 0.6 GPH EMITTERS AT PURDY-MCGUIRE, INC.
DEGREES. HAND ADJUSTABLE MULTI-STREAM ROTARY 12" O.C. LATERALS SPACED AT 18" APART, WITH EMITTERS 4. PROVIDE THAT ALL TRENCHING WITHIN DRIP LINE OF EXISTING TREES SHALL 17300 N. DALLAS PARKWAY, SUITE 3000
W/1800 TURF SPRAY BODY ON 4.0" POP-UP, WITH CHECK OFFSET FOR TRIANGULAR PATTERN. UV RESISTANT. BE DONE WITH HAND TOOLS AND SHALL NOT CUT ANY ROOT OVER 3"
VALVE AND 45 PSI IN-STEM PRESSURE REGULATOR. 1/2" SPECIFY XF INSERT FITTINGS. DIAMETER. DALLAS, TX 75248
NPT FEMALE THREADED INLET. 972-239-5357
5. EXAMINE THE PLANS IN THEIR ENTIRETY TO DETERMINE THE APPROXIMATE
RAIN BIRD R-VAN18 1804-SAM-P45 SYMBOL MANUFACTURER/MODEL/DESCRIPTION LOCATION OF EXISTING AND PROPOSED UTILITIES. HE SHALL ALSO
18 ADJ 18 F TURF ROTARY, 13`-18` 45-270 DEGREES AND 360 CONTACT THE APPROPRIATE AUTHORITY TO MARK UTILITIES ON THE SITE. civil
DEGREES. HAND ADJUSTABLE MULTI-STREAM ROTARY RAIN BIRD PGA GLOBE THE IRRIGATION CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGES
W/1800 TURF SPRAY BODY ON 4.0" POP-UP, WITH CHECK 1", 1-1/2" ELECTRIC REMOTE CONTROL VALVE, GLOBE. TO UTILITIES ON THE SITE CAUSED BY HIS WORK. PACHECO KOCH
VALVE AND 45 PSI IN-STEM PRESSURE REGULATOR. 1/2" 7557 RAMBLER RD. #1400

GA
WAT
RAIN BIRD 44-LRC

TUAGT
W
WAT
NPT FEMALE THREADED INLET.
WAT

SAN
DALLAS, TX 75234

S
WAT WAT
WAT WAT
1" BRASS QUICK-COUPLING VALVE, WITH WAT WAT
WAT WAT

RIM=407.22
972.235.3031
WAT WAT
CORROSION-RESISTANT STAINLESS STEEL SPRING, WAT WAT
WAT
8"WATER
LOCKING THERMOPLASTIC RUBBER COVER, AND 2-PIECE
WAT

WAT

ST
RIM=407.78

WAT
BODY. landscape

GA
KING JAMES DRIVE
WAT

ST

WA
TUGT
SAN
S
WA 60' Public ROW, Concrete Pavement
FL10"=401.42
POH POH POH POH
SAN
PACHECO KOCH
7557 RAMBLER RD. #1400
POH SAN
ARTIFICIAL LOT LINE / LIMIT OF WORK
T
FL10"=402.58 POH POH POH
SAN SAN SAN W TUG
POH WW GAS TUG

S
POH POH SAN SAN TUG GAS TUG
POH SAN GAS TUG
POH SAN GAS TUG X-CUT SET
DALLAS, TX 75234
WAT

POH SAN GAS TUG


POH POH SAN SAN GAS TUG GAS TUG T
T LOT LINE / LIMIT OF WORK
P OH POH POH SAN GAS TUG GAS TUG
ARTIFICIAL
WA GAS TUG

CO
T SAN SAN GAS TUG GAS TUG
SAN GAS TUG
972.235.3031
GAS TUG
S

POC
GAS TUG
SAPN
OH
GAGS TUG GAS TUG
TU
SAPN
OH TGUAGS 5/8"FIR
W
structural engineer

MH
MH
AT 5
6
TGUAGS
10 2"

TUG WA
PO
ST

H
MODIFY EXISTING 1/2"FIR
EJES INCORPORATED

SAN
IRRIGATION AS NEEDED

T
12801 N. CENTRAL EXPY, SUITE 700
TGUAS

3"G
W G
AT
"S S
10

as
PO
CONTRACTOR TO LOCATE
H
11 19.5 EXISTING SLEEVES DALLAS, TX 75243
ST

S
112"
TGUA AN
GS
20 214.3431210

TUG WAT
4

8"SS
27.8
STO

PO
H
2
W

GAS
112" 10.0
AT

S
TGUA AN 17.0 10 security, audio/visual
GS 18 1" 1"
PO
NOVOM GROUP

42"
H
RIM=407.57

RCP

TUG WAT
1/2"CIRF
3 13.3 400 S. RECORD ST, SUITE 1200

SAN
s
Ga
3" 112"

GAS
DALLAS, TX 75202
PO S
H

214-882-1540
TU

NO ACCESS
G
GA

ARTIFICIAL LOT LINE / LIMIT OF WORK

27
S

STO

TUG WAT
project

SAN
PO
H SA AS

GAS
5
TU

12.0 DALLAS COUNTY ELECTIONS BUILDING


G
N
G

1/2"FIR
1" 18"
RCP 1460 ROUND TABLE DR

ARTIFICIAL LOT LINE / LIMIT OF WORK


EXISTING BUILDING DALLAS, TX 75247
STO

TUG WAT
6 23.0

SAN
112" The drawings and written material herein constitute original work of the

GAS
architect, and as intellectual property and instruments of service, are
EXISTING OVERHEAD subject to copyright and may not be reproduced, distributed, published
7 9.57 CANOPY or used in any way without the express written consent of the architect.
1"
STO

TUG WAT
original issue

SAN
MODIFY EXISTING
CONTRACTOR TO LOCATED IRRIGATION AS NEEDED DESIGN DEVELOPMENT 04.30.2021
EXISTING SLEEVE
revisions

GAS

ROU

TUG WAT
60

SAN
' Public ROW
4

ND T,ACoBncLreEte PaDvement
STO

8 11.8

GAS
1"

TUG WAT
ARTIFICIAL LOT LINE / LIMIT OF WORK

8"SS
12
EXISTING TREES TO REMAIN EXISTING SIGNIFICANT 9 31.2

48"RCP
Block 10/7941 TREE TO REMAIN

RIVE
ST

112"
O

King Row Industrial District 12

GAS
Fourth Installment

TUG
Vol. 68040, Pg. 2014, D.R.D.C.T.

WAT
SAN
13
Cantex Regal LLC

3"Gas
Inst. 201700215989, O.P.R.D.C.T.

BUILDING ENTRY,

TUG
BUILDING ENTRY,
WAT

GAS
REF. ARCH DWGS

12"WATER
REF. ARCH DWGS

8"SS
15
ORK
IT OF W

15

TUG
SAN
WAT
GAS
ARTIFICIAL LOT LINE / LIMIT OF WORK
IM

STO
title
L

5/8"FIR
/

H 3
H
E

IRRIGATION PLAN
STO
IN

32 STO
STO
L LOT L

STO STO
STO
11 17 STO STO STO
STO
STO STO STO STO STO 6
Storm Sewer
Approx. Centerline 32
RTIFICIA

17

WAT
SAN

TUG
4/22/2021 5:30:27 PM

8 project number 20182.200


57
1/2"CIRF

WAT
GAS

SAN

TUG
X X
YELLOW
date 04.30.2021
X X
X X
X X
X
AFFIDAVIT OF FACTS
5/8"FIR Vol. 2002068, Pg. 5345
5/8"FIR
D.R.D.C.T. sheet
IRRIGATION PLAN Block 12/7941

1 Roundtable Addition

L3.00
The County of Dallas, State of Texas
Block 7941 Inst. 20150222226, O.P.R.D.C.T. Vol. 74103, Pg. 1425, D.R.D.C.T.
1" = 40'-0"
plotted:
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
EDGE OF SLAB WHERE SHOWN ON STRUCTURAL DECK
PARTITION GENERAL NOTES
CAP WITH GYPSUM BOARD PLAN STRUCTURAL DECK
01 / A0.51 1. PARTITION TYPES SHOWN MAY OR MAY NOT BE USED IN THE PROJECT.
STRUCTURAL DECK REFERENCE THE FLOOR PLANS FOR PARTITION TYPE DESIGNATIONS
HEAD
PROVIDE CLIP ANGLE CONNECTION AT USED.
SEALANT EACH SIDE SCHEDULED PARTITION TYPE
TUBE TO RUNNER SEALANT
2. PARTITION THICKNESS SHOWN IN SCHEDULES REFLECT OVERALL WALL
ASSEMBLY WIDTH.
CEILING AS SCHEDULED
METAL STUD FRAMING WITH GYPSUM LEAD LINING OPTION -
BOARD APPLIED 3. UL ASSEMBLY NUMBER IS BASED ON THE MOST CURRENT EDITION OF
HEAD HEAD CEILING AS SCHEDULED PLAN HEIGHT PER PHYSICIST'S REPORT
SHAFT LINER HEAD THE FIRE RESISTANCE DIRECTORY

ACOUSTICAL BLANKET 4. PROVIDE TYPE "X" GYPSUM BOARD AT ALL FIRE RESISTIVE
3" x 3" x 3/16" STEEL TUBE @ 4' - 0" ACOUSTICAL BLANKET INSULATION
INSULATION AS INDICATED CONSTRUCTION LOCATIONS
O.C. WELDED TO 3" x 8" x 3/16" SECURITY MESH OPTION -
BASE PLATE SILL FULL HEIGHT
REMARK 1.

C-H METAL STUD FRAMING 5. IN LIEU OF GYPSUM BOARD, PROVIDE TILE BACKER PANELS OR CEMENT
PLAN PLAN PLAN BOARD WHERE WALL FINISH IS SCHEDULED TO BE TILE. PROVIDE
METAL STUD FRAMING WITH GYPSUM MOLD/MILDEW-RESISTANT GYPSUM BOARD AT ALL OTHER LOCATIONS
(2) 1/2" ø x 3" LONG EXPANSION DOUBLE LAYER OF GYPSUM BOARD BOARD APPLIED WHERE WALL SURFACES ARE WITH-IN 48" OF A WATER SOURCE AND
ANCHORS AT EACH BASE PLATE FINISH FLOOR AS SCHEDULED architecture interiors planning graphics
FOR FULL HEIGHT OF ALL WALLS AND CEILINGS ENCLOSING
SEALANT RESTROOMS, MECHANICAL ROOMS, JANITOR CLOSETS OR SIMILAR
AREAS PRONE TO HIGH HUMIDITY AND/OR MOISTURE.
8070 Park Lane, Ste. 300 Dallas, Texas 75231
SILL SILL SILL SEALANT EACH SIDE
SEALANT EACH SIDE LEAD LINING 'X' L SECURITY MESH 'X' M
FINISH FLOOR AS SCHEDULED LEAD LINED GYPSUM BOARD SECURITY MESH ADDED TO 6. WHERE PARTITIONS CALL FOR SEALANT; PROVIDE FIRE-RATED
Tel 972.701.9000 Fax 972.991.3008
1/2"

ADDED TO ONE SIDE - REFERENCE EXTERIOR SIDE OF METAL STUD

1/2"
SEALANT AT ALL FIRE RESISTANCE RATED PARTITIONS AND
03 / A0.51 PHYSICIST'S REPORT FOR HEIGHT BEFORE APPLYING GYPSUM ACOUSTICAL SEALANT AT ALL OTHER NON-RATED PARTITIONS. www.bokapowell.com
FINISH FLOOR AS SCHEDULED EDGE OF SLAB WHERE SHOWN ON FINISH FLOOR AS SCHEDULED AND THICKNESS OF LEAD LINING BOARD
PLAN
LOW PARTITION J SHAFT WALL - 2 HOUR F FULL HEIGHT PARTITION C These documents are issued for pricing only
and are not for regulatory approval,
PARTITION SYMBOL USE
PART. STUD SIDE ONE SIDE TWO
TYPE WDTH (LAYERS)MTRL (LAYERS)MTRL
PART.
THICK
FIRE ACOU STC
RTG UL # INSL # REM
PART. STUD SIDE ONE SIDE TWO
TYPE WDTH (LAYERS)MTRL (LAYERS)MTRL
PART.
THICK
FIRE ACOU STC
RTG UL # INSL # REM
PART. STUD SIDE ONE SIDE TWO
TYPE WDTH (LAYERS)MTRL (LAYERS)MTRL
C1 3 5/8" (1) 5/8" GYP (1) 5/8" GYP
PART.
THICK
4 7/8"
FIRE ACOU STC
RTG UL # INSL
-0- - -
# REM
- -
06 PARTITION OPTIONS
SCALE: 1 1/2" = 1'-0"
PARTITION TYPE
permitting or construction.

Arch: Donald R. Powell, Jr. Reg. No.: 7206


C2 3 5/8" (1) 5/8" GYP (1) 5/8" GYP 4 7/8" -0- - 3 1/2" - - X1 Arch: Chris W. Barnes Reg. No.: 10147
C3 3 5/8" (1) 5/8" TYPE X (1) 5/8" TYPE X 4 7/8" 1 HR U465 - - - Arch: John E. Orfield Reg. No.: 11164
C4 6" (1) 5/8" GYP (1) 5/8" GYP 7 1/4" -0- - - - - PARTITION IN PLAN Arch: R. Andrew Bennett Reg. No.: 18129
C5 6" (1) 5/8" TYPE X (1) 5/8" TYPE X 7 1/4" 1 HR - - - -
CL
PARTITION TYPE
REMARKS: 1. PARTITION HEIGHT TO BE X' - XX" REMARKS: REMARKS: client
LINE OF
X1 D FURR OUT OR FRAMED PARTITION DALLAS COUNTY
MULLION BELOW
ADDED TO BASIC PARTITION TYPE
1460 ROUND TABLE DR
REFER PLAN PARTITION IN PLAN DALLAS, TX 75247

6" MIN.
214-653-6437

PARTITION TYPE project manager


X1 L PARTITION OPTION - LEAD LINING (L), SECURITY PRITCHARD ASSOCIATES
EDGE OF SLAB WHERE SHOWN ON STRUCTURAL DECK 2121 NORTH AKARD ST, SUITE 100
STRUCTURAL DECK MESH (M), REFERENCE DETAIL 06
PLAN
01 / A0.51 DALLAS, TX 75201
STRUCTURAL DECK BRACE TO STRUCTURE @ 4' - 0" O.C. 214-849-0011
PARTITION IN PLAN
SEALANT EACH SIDE MAXIMUM AND AT EACH SIDE OF ALL
SEALANT OPENINGS WITH METAL STUDS project manager

6"
MATCHING PARTITION FRAMING
JPC CONSULTING
CEILING AS SCHEDULED
2627 MARTIN LUTHER KING JR. BLVD.
HEAD CEILING AS SCHEDULED HEAD SHAFT LINER
HEAD ACOUSTICAL INSULATION TO 4' - 0"
EACH SIDE OF PARTITION WHEN
REFERENCE DETAIL 04 FOR
SIMILAR NOTES AND
RATED WALL LEGEND DALLAS, TX 75215
INDICATED FOR PARTITION DIMENSIONS. UNLESS NOTED 3-HR FIRE RESISTANT 1 HIGHEST 214-941-4297
ACOUSTICAL BLANKET OTHERWISE.
ACOUSTICAL BLANKET 2-HR FIRE RESISTANT SMOKE BARRIER 2
INSULATION AS INDICATED
INSULATION CEILING AS SCHEDULED m.e.p. engineer
PARTITION DETAIL AT OFFSET 2-HR FIRE RESISTANT PURDY-MCGUIRE, INC.
C-H METAL STUD FRAMING PLAN 3
PLAN PLAN ACOUSTICAL BLANKET 2-HR FIRE RESISTANT SHAFT WALL 17300 N. DALLAS PARKWAY, SUITE 3000

05 MULLION
METAL STUD FRAMING WITH GYPSUM
BOARD APPLIED
INSULATION AS INDICATED DALLAS, TX 75248
LAYER OF GYPSUM BOARD 1-HR FIRE RESISTANT SMOKE BARRIER 4
METAL STUD FRAMING WITH GYPSUM SCALE: 3" = 1'-0" 972-239-5357
BOARD APPLIED 1-HR FIRE RESISTANT
SEALANT SILL 5 civil
SILL SEALANT EACH SIDE SILL 1-HR FIRE RESISTANT SHAFT WALL
SEALANT EACH SIDE PACHECO KOCH
FINISH FLOOR AS SCHEDULED

1/2"
NON-RATED SMOKE RESISTANT 6 7557 RAMBLER RD. #1400
1/2"

FINISH FLOOR AS SCHEDULED DALLAS, TX 75234


FINISH FLOOR AS SCHEDULED 03 / A0.51 EDGE OF SLAB WHERE SHOWN ON NON-RATED 7 LOWEST
PLAN 972.235.3031
WINDOW MULLION
FULL HEIGHT PARTITION H SHAFT WALL - 1 HOUR E PARTIAL HEIGHT PARTITION B CL
LINE OF MULLION
PARTITION INTERSECTION PRIORITY
landscape
HIGHER PRIORITY PACHECO KOCH
PART. STUD SIDE ONE SIDE TWO PART. FIRE ACOU STC PART. STUD SIDE ONE SIDE TWO PART. FIRE ACOU STC PART. STUD SIDE ONE SIDE TWO PART. FIRE ACOU STC BELOW
TYPE WDTH (LAYERS)MTRL (LAYERS)MTRL THICK RTG UL # INSL # REM TYPE WDTH (LAYERS)MTRL (LAYERS)MTRL THICK RTG UL # INSL # REM TYPE WDTH (LAYERS)MTRL (LAYERS)MTRL THICK RTG UL # INSL # REM CONSTRUCTION JOINT 7557 RAMBLER RD. #1400
H1 3 5/8" (2) 5/8" GYP (2) 5/8" GYP 6 1/8" -0- - 3 1/2" - - B1 2 1/2" (1) 5/8" GYP (1) 5/8" GYP 3 3/4" -0- - - - - PREFINISH METAL CAP; DALLAS, TX 75234
B5 6" (1) 5/8" GYP (1) 5/8" GYP 7 1/4" -0- - - - - FINISH TO MATCH 972.235.3031
LOWER PRIORITY
WINDOW SYSTEM
structural engineer
EJES INCORPORATED
12801 N. CENTRAL EXPY, SUITE 700
ADHESIVE RUBBER DALLAS, TX 75243
GASKET
REMARKS: REMARKS: REMARKS: 214.3431210

STRUCTURAL DECK security, audio/visual


PARTITION AS SCHEDULED CONTINUOUS ANGLE WITH 3/8"
NOVOM GROUP
THICK SPONGE NEOPRENE FACING 400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
REFERENCE PLANS 3/4" - 1" AIR SPACE 214-882-1540
NOTE: PROVIDE ADHESIVE RUBBER GASKET CONNECTION TO MULLION. DO
NOT SCREW OR DRILL INTO WINDOW MULLION. TYPICAL AT ALL DRYWALL PARTITION TRACK
TO MULLION CONNECTIONS project
STRUCTURAL DECK STRUCTURAL DECK STRUCTURAL DECK PARTITION AS SCHEDULED DALLAS COUNTY ELECTIONS BUILDING
01 / A0.51 01 / A0.51 1460 ROUND TABLE DR
SEALANT EACH SIDE
SEALANT
BRACE TO STRUCTURE AT 4' - 0" O.C.
MAXIMUM AND AT EACH SIDE OF ALL
OPENINGS WITH METAL STUDS
MATCHING PARTITION FRAMING
04 PARTITION DETAIL - JAMB
SCALE: 3" = 1'-0"
NOTE: TYPICAL HEAD DETAIL AT ALL SOUND BARRIER CEILING
DALLAS, TX 75247
The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published
METAL STUD GUSSETS AT
QUARTER POINTS or used in any way without the express written consent of the architect.
HEAD CEILING AS SCHEDULED
original issue
HEAD
CEILING AS SCHEDULED
HEAD CEILING AS SCHEDULED ACOUSTICAL INSULATION TO 4' - 0" SOUND (ACOUSTICAL) DESIGN DEVELOPMENT 04.30.2021
EACH SIDE OF PARTITION WHEN

ACOUSTICAL BLANKET
INSULATION AS INDICATED
ACOUSTICAL BLANKET
INSULATION AS INDICATED
INDICATED FOR PARTITION
J-MOLD AT TOP OF GYPSUM BOARD 02 PARTITION DETAIL - HEAD
SCALE: 3" = 1'-0"
revisions

COMPRESSIBLE GASKET PARTITION AS


PLAN PLAN PLAN SCHEDULED
METAL STUD FRAMING WITH GYPSUM
METAL STUD FRAMING WITH BOARD APPLIED ACOUSTICAL BLANKET
GYPSUM BOARD APPLIED INSULATION AS INDICATED CONCRETE SLAB / METAL DECK -
REFER STRUC.
METAL STUD FRAMING WITH GYPSUM GYPSUM PANEL CANT
SILL SILL BOARD APPLIED SCREWED TO VERTICAL PROVIDE FIRE RESISTANCE
SILL SEALANT
SEALANT EACH SIDE STUDS (ONLY AT SYSTEM IN METAL DECK FLUTES
1/2"

SEALANT EACH SIDE HORIZONTAL AT FIRE RATED PARTITIONS


1/2"
1/2"

PROJECTIONS IN 20 GAGE SHEET METAL WITH


FINISH FLOOR AS SCHEDULED FINISH FLOOR AS SCHEDULED FINISH FLOOR AS SCHEDULED ELEVATOR HOISTWAYS FASTENERS AT METAL DECK

TO 1" FOR DEFLECTION


GREATER THAN 2") CONDITIONS

PROVIDE 3/4"
title
CHASE PARTITION G FURR OUT PARTITION D CEILING HEIGHT PARTITION A CONTINUOUS SEALANT AT EACH

PART. STUD SIDE ONE SIDE TWO PART. FIRE ACOU STC PART. STUD SIDE ONE SIDE TWO PART. FIRE ACOU STC PART. STUD SIDE ONE SIDE TWO PART. FIRE ACOU STC FIRE SEALANT
SIDE, FIRE RESISTANCE SYSTEM
SEALANT AT FIRE RATED PARTITIONS
PARTITION TYPES
TYPE WDTH (LAYERS)MTRL (LAYERS)MTRL THICK RTG UL # INSL # REM TYPE WDTH (LAYERS)MTRL (LAYERS)MTRL THICK RTG UL # INSL # REM AS REQUIRED
TYPE WDTH (LAYERS)MTRL (LAYERS)MTRL THICK RTG UL # INSL # REM CHANNEL DEFLECTION TRACK -
G1 2 1/2" (1) 5/8" GYP (1) 5/8" GYP 11 3/4" -0- - 2 1/2" - 1. D2 2 1/2" - (1) 5/8" GYP 3 1/8" -0- - - - - CONTINUOUS , MATCH STUD GAUGE
60°

1/2"
G4 6" (1) 5/8" GYP (1) 5/8" GYP 2' - 3 1/4" -0- - 3 1/2" - 1. D5 6" - (1) 5/8" GYP 6 5/8" -0- - - - -
2" MIN.
4/30/2021 3:47:37 PM

EDGE OF STRUCTURE PARTITION TRACK


OPENING PARTITION AS SCHEDULED project number 20182.200

NOTE: DO NOT ATTACH GYPSUM BOARD TO TOP TRACK TO ALLOW FOR date 04.30.2021
DEFLECTION. THIS IS TYPICAL AT NON-LOAD BEARING METAL STUD
PARTITIONS. sheet
REMARKS: 1. PROVIDE TILE BACKER PANELS IN LIEU OF GYP. BOARD AT WET REMARKS: REMARKS:
WALLS AND TILE LOCATIONS.
03 ELEVATOR SHAFT SILL DETAIL
01 PARTITION DETAIL - HEAD
A0.51
plotted:

SCALE: 3" = 1'-0" SCALE: 3" = 1'-0"


ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
STRUCTURAL DECK STRUCTURAL DECK
01 / A0.51
SIM. SEALANT 01 / A0.51 SEALANT EACH SIDE
SIM.

6"
STOP GYPSUM BOARD 6" ABOVE CEILING AS SCHEDULED
CEILING ON ONE SIDE

HEAD HEAD ACOUSTICAL BLANKET


CEILING AS SCHEDULED INSULATION EACH SIDE

ACOUSTICAL BLANKET 1 " AIR SPACE


INSULATION AS INDICATED
PLAN PLAN
METAL STUD FRAMING,
METAL STUD FRAMING WITH GYPSUM STAGGERED WITH GYPSUM BOARD architecture interiors planning graphics
BOARD APPLIED APPLIED EACH SIDE
8070 Park Lane, Ste. 300 Dallas, Texas 75231
SILL SILL
SEALANT EACH SIDE SEALANT EACH SIDE Tel 972.701.9000 Fax 972.991.3008

1/2"
1/2"
www.bokapowell.com
FINISH FLOOR AS SCHEDULED FINISH FLOOR AS SCHEDULED

SMOKE PARTITION Q DEMISING PARTITION M These documents are issued for pricing only
and are not for regulatory approval,
PART. STUD SIDE ONE SIDE TWO PART. FIRE ACOU STC PART. STUD SIDE ONE SIDE TWO PART. FIRE ACOU STC
permitting or construction.
TYPE WDTH (LAYERS)MTRL (LAYERS)MTRL THICK RTG UL # INSL # REM TYPE WDTH (LAYERS)MTRL (LAYERS)MTRL THICK RTG UL # INSL # REM
Arch: Donald R. Powell, Jr. Reg. No.: 7206
Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

REMARKS: REMARKS: client


DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437

project manager
REFERENCE PLANS PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
STRUCTURAL DECK STRUCTURAL DECK DALLAS, TX 75201
214-849-0011
SEALANT
project manager
JPC CONSULTING
CEILING AS SCHEDULED 2627 MARTIN LUTHER KING JR. BLVD.
DALLAS, TX 75215
HEAD HEAD 214-941-4297
FURRING CHANNELS @ 2' - 0" O.C.
HORIZONTALLY
CAST-IN-PLACE CONCRETE WALL - m.e.p. engineer
REFERENCE STRUCTURAL PURDY-MCGUIRE, INC.
GYPSUM BOARD APPLIED
17300 N. DALLAS PARKWAY, SUITE 3000
PLAN PLAN DALLAS, TX 75248
EXISTING OR INSTALLED SOLID 972-239-5357
PARTITION / WALL
civil
SILL SILL PACHECO KOCH
SEALANT
7557 RAMBLER RD. #1400

1/2"
DALLAS, TX 75234
FINISH FLOOR AS SCHEDULED FINISH FLOOR AS SCHEDULED 972.235.3031
landscape
CAST-IN-PLACE CONCRETE P FURR OUT FRAMING PARTITION L PACHECO KOCH
PART. STUD SIDE ONE SIDE TWO PART. FIRE ACOU STC PART. STUD SIDE ONE SIDE TWO PART. FIRE ACOU STC 7557 RAMBLER RD. #1400
TYPE WDTH (LAYERS)MTRL (LAYERS)MTRL THICK RTG UL # INSL # REM TYPE WDTH (LAYERS)MTRL (LAYERS)MTRL THICK RTG UL # INSL # REM
DALLAS, TX 75234
L1 7/8" - (1) 5/8" GYP 1 1/2" -0- - - - -
972.235.3031
structural engineer
EJES INCORPORATED
12801 N. CENTRAL EXPY, SUITE 700
DALLAS, TX 75243
214.3431210
REMARKS: 1. IBC TABLE 720.1(2); ITEM NUMBER 4-1.1 REMARKS:
2. STC OF 50 OR GREATER, PER THICKNESS - 4" - 49 security, audio/visual
6" - 55, 8" - 58 NOVOM GROUP
400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
214-882-1540

STRUCTURAL DECK
project
STRUCTURAL DECK
DALLAS COUNTY ELECTIONS BUILDING
01 / A0.51 SEALANT EACH SIDE
1460 ROUND TABLE DR
FIRE RESISTANCE SYSTEM DALLAS, TX 75247
SEALANT AS REQUIRED
The drawings and written material herein constitute original work of the
RESILIENT CHANNELS @ 2' - 0" O.C. architect, and as intellectual property and instruments of service, are
HORIZONTALLY subject to copyright and may not be reproduced, distributed, published
STEEL ANGLES AND ATTACHMENT - or used in any way without the express written consent of the architect.
REFERENCE STRUCTURAL
HEAD HEAD CEILING AS SCHEDULED original issue

DESIGN DEVELOPMENT 04.30.2021


BOND BEAM ACOUSTICAL BLANKET
revisions
INSULATION
CONCRETE MASONRY UNIT METAL STUD FRAMING WITH GYPSUM
PLAN GROUT & VERTICAL REINFORCING - PLAN BOARD APPLIED
REFERENCE STRUCTURAL
HORIZONTAL REINFORCING SECOND LAYER GYPSUM BOARD
WHERE INDICATED
SILL DOWEL AND VERTICAL REINFORCING - SILL
REFERENCE STRUCTURAL SEALANT EACH SIDE

1/2"
FINISH FLOOR AS SCHEDULED FINISH FLOOR AS SCHEDULED

CONCRETE MASONRY PARTITION N ACOUSTICAL PARTITION K title


PART. STUD SIDE ONE SIDE TWO
TYPE WDTH (LAYERS)MTRL (LAYERS)MTRL
PART.
THICK
FIRE ACOU STC
RTG UL # INSL # REM
PART. STUD SIDE ONE SIDE TWO
TYPE WDTH (LAYERS)MTRL (LAYERS)MTRL
PART.
THICK
FIRE ACOU STC
RTG UL # INSL # REM PARTITION TYPES
N1 8" - - 7 5/8" -0- - - - 1.
4/30/2021 3:47:19 PM

project number 20182.200

date 04.30.2021
REMARKS: 1. STC CAN BE ADJUSTED UP TO 48 IF ALL CELLS ARE FILLED REMARKS: 1. FOR 1-HR USE UL# U451. 2. FOR 2-HR USE UL# U453 sheet
WITH GROUT & REINFORCED W/ #5 BARS, REFER STRUCTURAL.

A0.52
plotted:
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
FINISH SCHEDULE
MARK MANUFACTURER STYLE COLOR SIZE LOCATION NAME PHONE NOTES

ACCOUSTIC CEILING TILE


ACT-1 ARMSTRONG FINE FISSURED WHITE 2X2 OVERALL

ACOUSTIC CEILING SYSTEM


ACS-1 ARMSTRONG ACOUSTIBUILT SEAMLESS WHITE BREAKROOM TO BE PAINTED P-6

ALUMINUM
AL-1 MULLIONS, MISC ALUMINUM
AL-2 LOADING DOCK CANOPIES

ALUMINUM COMPOSITE METAL


ACM-1 REF SPECS REF SPECS LIGHT GREY REF TO PLANS/ELEVATIONS FOR PANEL SIZES NEW ENTRY CANOPY
ACM-2 REF SPECS REF SPECS DARK GREY REF TO PLANS/ELEVATIONS FOR PANEL SIZES NEW ENTRY CANOPY
architecture interiors planning graphics
BRICK 8070 Park Lane, Ste. 300 Dallas, Texas 75231
BK-1 - - - USED TO REFINISH PATCHED AREAS IN FACADE - - REUSE EXISTING BRICK FROM FACADE DEMO TO FILL IN PATCHED AREAS,
REF TO ELEVATIONS Tel 972.701.9000 Fax 972.991.3008

CARPET www.bokapowell.com
CPT-1 MANNINGTON CENTERFIELD IV CATCHER 34012 24 X 24 OPEN OFFICE ALTERNATIVE

CERAMIC TILE
CT-1 DALTILE PORTFOLIO IRON GREY PF06 2 X 2 MOSAIC RESTROOM WALL
CT-2 DALTILE COLOR WHEEL - LINEAR CURRANT SH17 4X8 PREFUNCTION
CT-3 DALTILE COLOR WHEEL - LINEAR 0190 ARTIC WHITE 3.5 X 12 TRAINING ROOM/BREAKROOM
CT-4 DALTILE COLOR WHEEL - LINEAR 1174 SEA BREEZE 4X8 BREAKROOM
CT-5 DALTILE COLOR WHEEL LINEAR 0180 CHALKBOARD 4X8 BREAKROOM

CONCRETE MASONRY UNIT Date 1


CMU-1 REF SPECS REF SPECS REF SPECS REF SPECS TRASH ENCLOSURE

CORNER GUARD
owner
CG-1 KOROSEAL KOROGUARD GW15 VINYL CORNER 1-1/2" OVERALL DALLAS COUNTY
GUARD 600 COMMERCE, 9TH FLOOR
DALLAS, TX 75202
GLASS 214-653-6437
GL-1 TRULITE (OR EQUAL) REF SPECS REF SPECS NEW ENTRY & NEW EXTERIOR WINDOWS
owner representative
LUXURY VINYL TITLE PRITCHARD ASSOCIATES
LVT-1 ARTISTEK BY METROFLOR AMERICAN PLANK BUCKBOARD 73346 6 X 36 TRAINING ROOM, CLASSROOMS 2121 NORTH AKARD STREET, SUITE 100
LVT-2 ARTISTEK BY METROFLOR AMERICAN PLANK CHERRY PINE 71006 6 X 36 TRAINING ROOM, CLASSROOMS DALLAS, TEXAS 75201-2223
214-849-0011
MARKER BOARD
MB-1 ASI VISUAL DISPLAYS PORCELAIN SURFACES WHITE HIGH-GLOSS 021" THICKNESS CONFERENCE, POLLING, TRAINING REFER TO ALTERNATES m.e.p. engineer
PURDY-MCGUIRE, INC.
PAINT
P-1 SHERWIN WILLIAMS EGGSHELL WHITE FLOUR SW7102 EGGSHELL RESTROOM
17300 N. DALLAS PARKWAY, SUITE 3000
P-2 SHERWIN WILLIAMS EGGSHELL SKY HIGH SW6504 OVERALL
DALLAS, TX 75248
P-3 SHERWIN WILLIAMS EGGSHELL TANAGER SW6601 ACCENT 972-239-5357
P-4 SHERWIN WILLIAMS EGGSHELL BLUE CHIP SW6959 ACCENT
P-5 SHERWIN WILLIAMS FLAT WHITE FLOUR SW7102 CEILING
security, audio/visual
P-6 SHERWIN WILLIAMS FLAT TANAGER SW6601 CEILING CLOUDS NOVOM GROUP
400 S. RECORD STREET, SUITE 1200
PLASTIC LAMINATE DALLAS, TX 75202
PL-1 WILSONART STANDARD LAMINATE BRAZIL WOOD 7946-38 TRAINING ROOM 214-882-1540
PL-2 NEVAMAR TEXTURERED WILD OATS MATRIX MR7002T COPY/PRINT
PL-3 NEVAMAR TEXTURED EISKAFFE WZ0056T COPY/PRINT civil
PL-4 NEVAMAR TEXTURED WHITE ESSENCE ES7001T BREAKROOM PACHECO KOCH
7557 RAMBLER RD, SUITE 1400
PORCELAIN TILE DALLAS, TX, 75231
PT-1 DALTILE PORTFOLIO DOVE GREY PF04 12 X 24 RESTROOM FLOOR 972-235-3031

SEALED CONCRETE structural engineer


SC-1 PER SPECIFICATIONS - - - L.A. FUESS PARTNERS
3333 LEE PARKWAY, SUITE 300
SECURITY FILM
DALLAS, TX, 75219
FL-1 SECURITY FILM MEETS GSA PROTECTION - - INTERIOR FACE OF ALL EXTERIOR GLAZING SEE ALTERNATES
STANDARDS OF LEVEL 3A
214-871-7010

SOLID SURFACE
SS-1 CORIAN QUARTZ COARSE CARRARA RECEPTION/TRAINING
SS-2 CORIAN QUARTZ SNOW FLURRY BREAKROOM/RESTROOM
SS-3 CORIAN QUARTZ STORM GREY LEATHERED BREAKROOM ISLAND

TERRAZZO
TZ-1 ANDREOLA TERRAZZO AND RESTORATION MATCH EXISTING LIGHT GREY OVERALL PLATE # - 2796-19-CI-16
project
TZ-2 ANDREOLA TERRAZZO AND RESTORATION MATCH EXISTING DARK GREY ACCENT PLATE # 2856-19
TZ-3 ANDREOLA TERRAZZO AND RESTORATION MATCH EXISTING RED ACCENT PLATE # 2832-19
DALLAS COUNTY ELECTIONS BUILDING
TZ-4 ANDREOLA TERRAZZO AND RESTORATION MATCH EXISTING BLUE ACCENT PLATE # 2795-19-EPIV-109
1460 ROUND TABLE DR
DALLAS, TX 75247
VINYL COMPOSITION TILE The drawings and written material herein constitute original work of the
VCT-1 ARMSTRONG FLOORING IMPERIAL TEXTURE 51904 STERLING 12 X 12 STORAGE architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published
or used in any way without the express written consent of the architect.
WALK OFF MAT
original issue
WM-1 MOHAWK GROUP FIRST STEP II TILE - QL315 OBSIDIAN - 989 VESTIBULE
DESIGN DEVELOPMENT 04.30.2021
WINDOW FILM
FL-1 revisions
1 Revision 1 Date 1

APPLIANCE SCHEDULE
TAG Type Comments MANUFACTURER MODEL NO.

APL-1 MICROWAVE WHIRLPOOL WMC50522AS


APL-2 REFRIDGERATOR WHIRLPOOL WRF555SDH
APL-3 UNDERCOUNTER ICE MACHINE SUMMIT BIM44GADA

title

FINISH SCHEDULE
4/30/2021 3:50:08 PM

project number 20182.200

date XX/XX/20XX
sheet

A0.71
plotted:
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
ROOF EXPANSION JOINT COVER GENERAL NOTES
1. ROOF EXPANSION JOINT COVER DETAILS ON THIS SHEET ARE BASED ON PRODUCTS PRODUCED BY
CONSTRUCTION SPECIALTIES, C/S WHERE NOTED. PRODUCTS BY ONE OF THE OTHER MANUFACTURERS
LISTED IN THE SPECIFICATIONS ARE ACCEPTABLE AS LONG AS THEY ARE COMPARABLE TO THE ONES
SHOWN ON THIS SHEET AND PERFORM IN A SIMILAR MANNER.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL CONSTRUCTION DETAILS, LEAVE OUTS,
GROUT POCKETS, CONNECTIONS, FASTENERS AND SEALANTS.

3. WHERE REQUIRED BY ADJACENT CONDITIONS, PROVIDE CONTINUATION OF AIR/MOISTURE BARRIER AND


INSTALL COMPRESSIBLE BATT INSULATION IN JOINT CONDITIONS WHERE REQUIRED.

4. WHERE EXPANSION JOINTS ARE INSTALLED IN FIRE RATED CONSTRUCTION, PROVIDE MANUFACTURER'S
STANDARD FIRE BARRIER ASSEMBLY WITH A RATING NOT LESS THAN THAT OF ADJACENT
CONSTRUCTION.
architecture interiors planning graphics
5. WHERE EXPANSION JOINTS INTERSECT OR MEET OTHER EXPANSION JOINTS, PROVIDE MANUFACTURER'S
STANDARD JOINT TRANSITION ASSEMBLY COMPLETE WITH MITERED CORNERS, FIELD SPLICES, FIELD 8070 Park Lane, Ste. 300 Dallas, Texas 75231
FORMED SECONDARY SEALS AND OTHER ACCESSORY MATERIALS TO PROVIDE A COMPLETE
INSTALLATION. Tel 972.701.9000 Fax 972.991.3008
6. DETAILS SHOW STANDARD SYSTEMS IN A ROOF TO ROOF, ROOF TO WALL OR PARAPET TO PARAPET www.bokapowell.com
CONDITION. WHERE REQUIRED, PROVIDE MANUFACTURER'S SYSTEM TO MAKE ROOF TO PARAPET,
PARAPET TO CORNER OR PARAPET TO WALL TRANSITION WITH A SIMILAR MODEL MODIFIED FOR THAT
CONDITION. DETAILS INDICATE THE APPROPRIATE
These documents are issued for pricing only
MODEL NUMBER FOR THOSE CONDITIONS.
and are not for regulatory approval,
7. PROVIDE APPROPRIATE FASTENERS, EXPANSION ANCHORS, SLEEVES, GROUT, SEALANT AND OTHER permitting or construction.
ACCESSORIES AS REQUIRED FOR A COMPLETE ASSEMBLY.
Arch: Donald R. Powell, Jr. Reg. No.: 7206
Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437

project manager
PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
214-849-0011

project manager
JPC CONSULTING
2627 MARTIN LUTHER KING JR. BLVD.
DALLAS, TX 75215
214-941-4297

m.e.p. engineer
PURDY-MCGUIRE, INC.
17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
972-239-5357

civil
PACHECO KOCH
7557 RAMBLER RD. #1400
DALLAS, TX 75234
972.235.3031
landscape
PACHECO KOCH
7557 RAMBLER RD. #1400
DALLAS, TX 75234
972.235.3031
structural engineer
EJES INCORPORATED
12801 N. CENTRAL EXPY, SUITE 700
DALLAS, TX 75243
214.3431210

security, audio/visual
NOVOM GROUP
400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
214-882-1540
project
DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
DALLAS, TX 75247
The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published
or used in any way without the express written consent of the architect.
original issue
TWO PIECE METAL EJ COVER
MATCH COPING FINISH AND INSTALL DESIGN DEVELOPMENT 04.30.2021
W/ GAPS FOR MOVEMENT AS SHOWN revisions

6" - 12" PREFINISHED METAL COPING


SYSTEM, INSTALL W/ SEALANT
1/2" 2" - 4" 1/2"
JOINT WIDTH JOINT WIDTH JOINT WIDTH SELF ADHERED WP MEMBRANE
LEAVE BACKING ON MIDDLE PORTION
AND FORM BELLOW AT JOINT

SELF ADHERED WP MEMBRANE


UNDERLAYMENT

WOOD BLOCKING AS DETAILED


ON PARAPET SECTION
title

COLD FORMED METAL FRAMING EXPANSION JOINT DETAILS -


AT PARAPET
THERMAL INSULATION AS DETAILED ROOF
4/30/2021 3:51:59 PM

project number 20182.200

date 04.30.2021
EXTERIOR PARAPET sheet
EXPANSION JOINT 2-INCH TO
A0.83
plotted:

01 4-INCH COPING TO COPING


SCALE: 6" = 1'-0"
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
DEMOLITION LEGEND DEMOLITION PLAN KEYNOTES
NUMBER KEYNOTE
EXISTING CONSTRUCTION TO REMAIN
01 ALL RAISED ACCESS FLOOR TO BE DEMOLISHED
02 EXISTING WALL TO BE DEMOLISHED AS REQUIRED FOR NEW
NEW CONSTRUCTION OPENING.
03 EXISTING RAMP, STEPS AND EXTERIOR ELEVATED SLAB TO BE
DEMOLISHED
EXISTING CONSTRUCTION TO BE REMOVED 04 DEMOLISH ALL EXISTING PLUMBING FIXTURES, TOILET
ACCESSORIES AND TOILET PARTITIONS
EXISTING DOOR TO REMAIN 05 DEMOLISH FLOOR FINISH BACK TO TOPPING SLAB
06 DEMOLISH WALL FINISH AND WALL BASE
07 EXISTING RAMP, GAURDRAILS AND STEPS TO REMAIN
EXISTING DOOR AND FRAME TO BE REMOVED 08 DEMOLISH EXISTING CEILINGS, LIGHT FIXTURES AND CEILING
DEVICES
AREA NOT INCLUDED IN SCOPE OF WORK 16 15 13 14 12 11 10 9 8 7 6 5 4 3 2 1 architecture interiors planning graphics
8070 Park Lane, Ste. 300 Dallas, Texas 75231
AREAS OF ABATEMENT, ABATEMENT AND A
DEMOLISHION IN THESE AREAS ARE TO BE
PROVIDED BY OWNER CONTRACTOR Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com

B These documents are issued for pricing only


and are not for regulatory approval,
permitting or construction.
05 06 08
Arch: Donald R. Powell, Jr. Reg. No.: 7206
Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

C client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437

project manager

02/AD4.01
PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
D 214-849-0011
05 06 08 project manager
JPC CONSULTING
2627 MARTIN LUTHER KING JR. BLVD.
05 06 08
DALLAS, TX 75215
214-941-4297
02
m.e.p. engineer
PURDY-MCGUIRE, INC.
E 17300 N. DALLAS PARKWAY, SUITE 3000
01 DALLAS, TX 75248
03 972-239-5357

civil
02
04 PACHECO KOCH
05 06 08 7557 RAMBLER RD. #1400
04 DALLAS, TX 75234
972.235.3031

F landscape
PACHECO KOCH
7557 RAMBLER RD. #1400
DALLAS, TX 75234
972.235.3031
structural engineer
EJES INCORPORATED
12801 N. CENTRAL EXPY, SUITE 700
05 06 08 DALLAS, TX 75243
05 06 08 214.3431210
G
security, audio/visual
NOVOM GROUP
400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
214-882-1540
04
project
DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
H DALLAS, TX 75247
07 The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published
05 06 08 or used in any way without the express written consent of the architect.
original issue

DESIGN DEVELOPMENT 04.30.2021


revisions
05 06 08

I
02

02

title
J DEMOLITION PLAN - LEVEL 1
02
07
01/AD4.01

X
4/30/2021 3:51:50 PM

project number 20182.200

date 04.30.2021

01 DEMOLITION PLAN - LEVEL 1


SCALE: 1/16" = 1'-0"
sheet

TRUE PLAN

AD2.01
plotted:

NORTH NORTH
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
DEMOLITION ROOF KEYNOTES
NUMBER KEYNOTE

01 PREPARE EXISTING ROOF TO RECEIVE RECOVERY BOARD AND NEW TPO ROOF SYSTEM, AS REQUIRED
02 REMOVE EXISTING EQUIPMENT AND PRE EXISTING CURBS TO RECEIVE NEW EQUIPMENT, AS REQUIRED

16 15 13 14 12 11 10 9 8 7 6 5 4 3 2 1
architecture interiors planning graphics
8070 Park Lane, Ste. 300 Dallas, Texas 75231
A
Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com

B These documents are issued for pricing only


and are not for regulatory approval,
permitting or construction.

Arch: Donald R. Powell, Jr. Reg. No.: 7206


Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

C client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437

project manager

02/AD4.01
PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
D 214-849-0011

project manager
JPC CONSULTING
2627 MARTIN LUTHER KING JR. BLVD.
DALLAS, TX 75215
214-941-4297

m.e.p. engineer
PURDY-MCGUIRE, INC.
E 17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
972-239-5357

civil
PACHECO KOCH
7557 RAMBLER RD. #1400
DALLAS, TX 75234
01
972.235.3031

F landscape
PACHECO KOCH
02 7557 RAMBLER RD. #1400
DALLAS, TX 75234
972.235.3031
structural engineer
EJES INCORPORATED
12801 N. CENTRAL EXPY, SUITE 700
DALLAS, TX 75243
214.3431210
G
security, audio/visual
NOVOM GROUP
400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
214-882-1540
project
DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
H DALLAS, TX 75247
The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published
or used in any way without the express written consent of the architect.
original issue

DESIGN DEVELOPMENT 04.30.2021


revisions

title
J DEMOLITION ROOF PLAN
01/AD4.01
4/30/2021 3:51:42 PM

project number 20182.200

date 04.30.2021
sheet

01 DEMOLITION ROOF PLAN


AD2.21
plotted:

SCALE: 1/16" = 1'-0"


ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
DEMOLITION ELEVATION KEYNOTES
NUMBER KEYNOTE

01 DEMOLISH EXISTING BRICK WALLS. EXISTING BRICK TO BE REUSED, REF TO FINISH SCHEDULE.

architecture interiors planning graphics


8070 Park Lane, Ste. 300 Dallas, Texas 75231
Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com

These documents are issued for pricing only


and are not for regulatory approval,
permitting or construction.

Arch: Donald R. Powell, Jr. Reg. No.: 7206


Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437

project manager
PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
214-849-0011

project manager
JPC CONSULTING
2627 MARTIN LUTHER KING JR. BLVD.
DALLAS, TX 75215
B E 214-941-4297

8'-0" 5'-8 5/8" 1'-7 3/8" 8'-0" 9'-4" 8'-0" 1'-4" 3'-4" m.e.p. engineer
PURDY-MCGUIRE, INC.
ROOF
17300 N. DALLAS PARKWAY, SUITE 3000
EL. 117'-0" DALLAS, TX 75248
972-239-5357

civil

7'-0"
PACHECO KOCH
7557 RAMBLER RD. #1400
DALLAS, TX 75234
972.235.3031

2'-10"
landscape
PACHECO KOCH
7557 RAMBLER RD. #1400
01 01 01
DALLAS, TX 75234
972.235.3031

7'-2"
01
structural engineer
EJES INCORPORATED
LEVEL 1 12801 N. CENTRAL EXPY, SUITE 700
EL. 100'-0" DALLAS, TX 75243
214.3431210

security, audio/visual
ENLARGED DEMOLITION NOVOM GROUP
400 S. RECORD ST, SUITE 1200
02 ELEVATION - LOADING DOCK
SCALE: 1/4" = 1'-0"
DALLAS, TX 75202
214-882-1540
project
DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
DALLAS, TX 75247
The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are
4 3 2 subject to copyright and may not be reproduced, distributed, published
or used in any way without the express written consent of the architect.
6" 18'-6" 2'-5 7/8" 20'-0 1/8" original issue

DESIGN DEVELOPMENT 04.30.2021


ROOF
EL. 117'-0" revisions
2'-0"
5'-0"

01
10'-0"

01 title

DEMOLITION ELEVATIONS

LEVEL 1
EL. 100'-0"
4/30/2021 3:51:56 PM

project number 20182.200

date 04.30.2021
sheet
ENLARGED DEMOLITION
01 ELEVATION - ENTRY
AD4.01
plotted:

SCALE: 1/4" = 1'-0"


ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt

architecture interiors planning graphics


8070 Park Lane, Ste. 300 Dallas, Texas 75231
Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com

These documents are issued for pricing only


and are not for regulatory approval,
permitting or construction.

Arch: Donald R. Powell, Jr. Reg. No.: 7206


Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437

project manager
PRITCHARD ASSOCIATES
16 2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
214-849-0011

project manager
PROVIDE NEW, ISLOTED CONCRETE FLOOR 4' IN LENGTH
FROM EXISTING BUILDING FLOOR LINE SEPARATED BY JPC CONSULTING
AN EXPANSION JOINT TO AVOID INTERFERRING WITH 2627 MARTIN LUTHER KING JR. BLVD.
EXISTING BUILDING FOUNDATION/STRUCTURE. TYPICAL DALLAS, TX 75215
CONCRETE WALL BELOW FOR LOADING DOCK.
214-941-4297
19'-5 1/4" 5'-0" 4'-0" m.e.p. engineer
PURDY-MCGUIRE, INC.
17300 N. DALLAS PARKWAY, SUITE 3000
PIPE GUARD RAIL DALLAS, TX 75248
972-239-5357

civil
PACHECO KOCH

12'-4"
7557 RAMBLER RD. #1400
DALLAS, TX 75234
972.235.3031
landscape
PACHECO KOCH
7557 RAMBLER RD. #1400

CL
DALLAS, TX 75234
972.235.3031
structural engineer
EJES INCORPORATED
12801 N. CENTRAL EXPY, SUITE 700
DALLAS, TX 75243
214.3431210

40'-0"
15'-4"
security, audio/visual
E NOVOM GROUP
CONTINUOUS TRENCH DRAIN 400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
214-882-1540
project

CL
DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
DOCK BUMPER, REF SPECS DALLAS, TX 75247
The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are

02/A4.01
subject to copyright and may not be reproduced, distributed, published

12'-4"
or used in any way without the express written consent of the architect.
original issue

DESIGN DEVELOPMENT 04.30.2021


PIPE GUARD RAIL
revisions
409'-3"

PIPE BOLLARD, TYP.

1'-0"
407'-0"

4'-0"
CL
4'-0"
RAMP DOWN

title
25'-6"
ENLARGED SITE PLANS
4/30/2021 3:50:27 PM

project number 20182.200

date 04.30.2021
ENLARGED SITE PLAN - sheet

01 LOADING DOCK
A1.11
plotted:

SCALE: 1/4" = 1'-0"


ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt

3/8" THICK STEEL PLATE EMBEDDED


1'-4" ANCHOR AT 2'-0" O.C. VERTICALLY
8'-4" TALL CONCRETE FILLED
6"X6"X1/2" PAINTED STEEL POST
WITH CAP - FILL WITH CONCRETE
2 1/2"x 2 1/2"x 1/4" STEEL ANGLE
GATE FRAME

PRE-FINISHED FORMED METAL

3"
WALL PANEL
BARREL HINGE, KING ARCHITECTURAL
METAL MODEL #44-2000-KONG architecture interiors planning graphics
CMU WALL 8070 Park Lane, Ste. 300 Dallas, Texas 75231
1 1/2" X 1 1/2" X 3/16" CROSS Tel 972.701.9000 Fax 972.991.3008
BRACE ANGLE PRE FORMED PANEL
www.bokapowell.com
2"X2" TUBE FRAME BEYOND
13 GATE-HINGE
SCALE: 1 1/2" = 1'-0"
These documents are issued for pricing only
and are not for regulatory approval,
permitting or construction.

Arch: Donald R. Powell, Jr. Reg. No.: 7206

8'-0" GATE HEIGHT

8'-0" GATE HEIGHT


SLOPE Arch: Chris W. Barnes Reg. No.: 10147
CAST STONE CAP - RAKE HEAD
1" THICK CORREGATED JOINTS 1/2" DEEP AND FILL Arch: John E. Orfield Reg. No.: 11164
METAL PANEL INFILL WITH SEALANT, PROVIDE Arch: R. Andrew Bennett Reg. No.: 18129

4"
3"
DRIPS AT EACH SIDE
14 GAUGE BENT PLATE MASONRY ANCHOR FOR CAP
ANGLES TO HOLD METAL
DRIP
PANEL INFILL IN PLACE - client
FASTEN TO FRAME WITH
SELF-TAPPING SCREWS DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437
2"x2"x3/16" TUBE FRAME
project manager

8'-0" MIN @ TRANSFORMER, TRASH ENCLOSURE, AND GENERATOR WALLS


FOR GATE - ALL FOUR

COORDINATE FINAL HEIGHT WITH EQUIPMENT INSTALLATION DETAILS


SIDES PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100

9" N.T.S.
9" GAP
N.T.S.
DALLAS, TX 75201
GRADE GRADE ELASTOMERIC COATING AT
FACE OF CMU (BOTH SIDES)
214-849-0011

project manager
8" CMU BLOCK WALL WITH
PRE FORMED PANEL - GATE VERTICAL REINFORCING -
REFER STRUCTURE
JPC CONSULTING
2627 MARTIN LUTHER KING JR. BLVD.

10 SECTION
SCALE: 6" = 1'-0"
DALLAS, TX 75215
214-941-4297

m.e.p. engineer
PURDY-MCGUIRE, INC.
17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
972-239-5357
2" x2"x1/4" STEEL
1/2" GAP
ANGLE FRAME civil
DIAGONAL STEEL PACHECO KOCH
BRACING ANGLE 7557 RAMBLER RD. #1400
PRE-FINISHED DALLAS, TX 75234
FORMED METAL 972.235.3031
WALL PANEL CONCRETE FOUNDATION
landscape

3"
AND SLAB- COORDINATE
1/2" DIAMETER WITH STRUCTURAL & CIVIL, PACHECO KOCH
STEEL BENT ROD SLOPE SLAB TO DRAIN
7557 RAMBLER RD. #1400
WITH FLANGE
SEALANT BACKER ROD DALLAS, TX 75234
1/4" STEEL PLATE
WITH 3/4" DIAMETER
AND 3/4" JOINT FILLER 972.235.3031
HOLE structural engineer
1/4" STEEL PLATE EJES INCORPORATED
WITH 1" DIAMETER
HOLE FOR PAD LOCK 12801 N. CENTRAL EXPY, SUITE 700
PRE FORMED PANEL GATE - ENCLOSURE WALL SECTION - DALLAS, TX 75243
1/2" DIAMETER STEEL 214.3431210
CANE BOLT

1/4" STEEL PLATE


12 LATCH/KEEPER
SCALE: 3" = 1'-0" 9 CMU
SCALE: 1" = 1'-0" security, audio/visual
NOVOM GROUP
WITH 3/4" DIAMETER
HOLE 400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
214-882-1540
2"X2" TUBE FRAME BEYOND
25'-4" project
1 1/2" X 1 1/2" X 3/16" CROSS 5" 11'-7" 11'-7" 5" DALLAS COUNTY ELECTIONS BUILDING
6" DIA. SCHEDULE 40 PIPE BRACE ANGLE 1460 ROUND TABLE DR
BOLLARD - FILL WITH 3,000 PSI BRICK/ CMU 3'-8" 4'-3" 4'-3" 3'-8"
CONCRETE AND ROUND TOP ENCLOSURE WALLS
DALLAS, TX 75247
CL CL CL CL CL CL CL

10/A1.12
14 GAUGE BENT PLATE WITH CAST STONE CAP The drawings and written material herein constitute original work of the
2"x2" STEEL TUBE FRAME
ANGLES TO HOLD METAL architect, and as intellectual property and instruments of service, are
PAINT BOLLARD WITH WHITE subject to copyright and may not be reproduced, distributed, published
6" DIAMETER STEEL

5"
TRAFFIC PAINT PANEL INFILL IN PLACE -

CL
POST, SET IN 3'-6" DEEP BOL BOL BOL BOL or used in any way without the express written consent of the architect.
FASTEN TO FRAME WITH
SELF-TAPPING SCREWS CONCRETE FOOTING original issue

3'-8"
2"X1" STEEL ANGLE
3' - 0"

3"x 3"x 1/2" ANGLE DESIGN DEVELOPMENT 04.30.2021


WELDED TO POST 1" DEEP CORRUGATED
2"x2"x3/16" TUBE FRAME revisions

CL
METAL PANEL BOL BOL BOL
1' - 6" SEALANT AND BACKER ROD FOR GATE - ALL FOUR
HINGES, WELD
DUMPSTER DUMPSTER

CLEAR
13'-4"
12'-0"
SIDES
BETWEEN FRAME & PADLOCK AND HASP

5'-0"
3/4" 9
JOINT FILLER - COORDINATE WITH CIVIL ANGLE
1 1/2"x 1 1/2"x 1/4" CROSS
A1.12 N.I.C. N.I.C.
8'-0"

CONCRETE PAVING - REFER CIVIL BRACE ANGLE, 1 PER


BOL BOL

CL
FOR THICKNESS, REINFORCING AND 13/A1.12 DOOR BOL
9" GAP

CONSTRUCTION DETAILS
N.T.S.

12/A1.12
EMBEDDED METAL SLEEVE 3/4" DIAMETER CANE
WITH FLUSH SPRING DUST- BOLTS, DRILL 2" DEEP
PROOF STRIKE HOLES IN PAVEMENT

1'-0"
COMPACTED SUBGRADE PER GEOTECH FOR CANE BOLTS AT
BOTH CLOSED & OPEN BOL BOL
3' - 0"

POSITION
STRUCTURAL SLAB, REFER EQ EQ title
9"

STRUCTURAL
CONCRETE FOOTING
ENLARGED SITE PLANS &
8" DEPTH

03/A1.12
N.T.S.

CONCRETE FOOTING

HEADED STUDS (4) 1/2" DIA.


DETAILS
3'-6" DEEP

WELD TO BASE OF BOLLARD REFER STRUCTURAL FOR 3/4" GAP


REINFORCEMENT SIZE AND BETWEEN GATES
SPACING
4/30/2021 3:50:33 PM

6"

project number 20182.200

date 04.30.2021

PRE FORMED PANEL - CANE DUMPSTER ENCLOSURE - DOUBLE sheet

08 SLAB - ON - GRADE BOLLARD


11 BOLT
03 GATE ELEVATION
01 BAY - BARREL HINGES
A1.12
plotted:

SCALE: 1" = 1'-0" SCALE: 6" = 1'-0" SCALE: 1/2" = 1'-0" SCALE: 1/4" = 1'-0"
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt GENERAL NOTES
1. REFER TO A0 SHEET SERIES FOR PARTITION TYPES.

2. REFER TO A3 SHEET SERIES FOR DOOR & FRAME TYPES, DOOR SCHEDULE
& DETAILS

3. REFER TO A0 SHEET SERIES FOR TYPICAL BLOCKING & GYPSUM BOARD


DETAILS.

4. DIMENSIONS ARE TO INSIDE FACE OF CURTAINWALL / STOREFRONT


MULLIONS AND TO FACE OF GYPSUM BOARD AT INTERIOR LOCATIONS 16 15 13 14 12 11 10 9 8 7 6 5 4 3 2 1
UNLESS NOTED OTHERWISE.

5. ALL DOOR FRAMES (HINGE SIDE) TO BE 3-INCHES FROM ADJACENT


PERPENDICULAR PARTITIONS, UNLESS NOTED OTHERWISE.
01 / A2.01b
architecture interiors planning graphics

X
6. ALL PARTITIONS TO BE XX UNLESS NOTED OTHERWISE.
8070 Park Lane, Ste. 300 Dallas, Texas 75231
A

X
FACILITIES Tel 972.701.9000 Fax 972.991.3008
MDF DMARC WATER OFFICE
PLAN KEY NOTES
X

X
156 157 ELEC 159 160 www.bokapowell.com
158

X
1 VENDING MACHINE BY OWNER
B These documents are issued for pricing only
OPERABLE PARTITION, MODERNFOLD DOOR and are not for regulatory approval,
2
ACOUSTI-SEAL ENCORE SYSTEM, STC 52 permitting or construction.

3 WINDOW 5'W X 4'H IN AN ALUMINUM FRAME Arch: Donald R. Powell, Jr. Reg. No.: 7206
Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
4 PROVIDE AED CABINET AS AN ALTERNATE Arch: R. Andrew Bennett Reg. No.: 18129

5 WALL INSULATION TO BE REMOVED FROM


PARTITION TYPE AS AN ALTERNATE.

C client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437

project manager
PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
D 214-849-0011
02 / A2.01b project manager
JPC CONSULTING
2627 MARTIN LUTHER KING JR. BLVD.
DALLAS, TX 75215
214-941-4297

m.e.p. engineer
PURDY-MCGUIRE, INC.
E 17300 N. DALLAS PARKWAY, SUITE 3000
01 / A2.01a DALLAS, TX 75248
MEN'S 972-239-5357
ELEC RESTROOM
107 105 civil
WOMEN'S PACHECO KOCH
RESTROOM 7557 RAMBLER RD. #1400
IDF
106
108 DALLAS, TX 75234
972.235.3031
LOADING
F landscape
DOCK
OFFICE PACHECO KOCH
180 7557 RAMBLER RD. #1400
DALLAS, TX 75234
972.235.3031
structural engineer
BREAKROOM
104 EJES INCORPORATED
12801 N. CENTRAL EXPY, SUITE 700
WAREHOUSE
125 DALLAS, TX 75243
214.3431210
G
security, audio/visual
NOVOM GROUP
MEN'S
RESTROOM 400 S. RECORD ST, SUITE 1200
123 CORRIDOR STORAGE DALLAS, TX 75202
102 103 214-882-1540
WOMEN'S TRAINING
COPIER
project
RESTROOM OFFICE DALLAS COUNTY ELECTIONS BUILDING
124 111a 1460 ROUND TABLE DR
H ELEC IDF
122 121
DALLAS, TX 75247
EARLY The drawings and written material herein constitute original work of the
105
VOTING TRAINING architect, and as intellectual property and instruments of service, are
E-BOOK BOOTH OPEN POLLING subject to copyright and may not be reproduced, distributed, published
OFFICE CONFERENCE AREA
119 LAB DS200 LAB LAB OFFICES or used in any way without the express written consent of the architect.
120 101
114 113 112 111 original issue
CORRIDOR
117 DESIGN DEVELOPMENT 04.30.2021
revisions
PRE-FUNCTION
110

I COPIER

TRAINING
OPEN TRAINING
OFFICE 116
115
118

WAITING
AREA
100

STORAGE/RECEPTION
109 VESTIBULE STORAGE
126 127 title
J OVERALL FLOOR PLAN

X
4/30/2021 3:48:24 PM

project number 20182.200

OVERALL FLOOR PLAN - date 04.30.2021

01 LEVEL 1 sheet

A2.01
SCALE: 1/16" = 1'-0"
plotted:

TRUE PLAN
NORTH NORTH
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
PLAN KEY NOTES
X 5 4 3 2 1
02 / A2.01c
CG CG
1 VENDING MACHINE BY OWNER
C1 MEN'S
C2
OPERABLE PARTITION, MODERNFOLD DOOR ELEC RESTROOM
2
ACOUSTI-SEAL ENCORE SYSTEM, STC 52 107 105

3 WINDOW 5'W X 4'H IN AN ALUMINUM FRAME


107
4 PROVIDE AED CABINET AS AN ALTERNATE
108 C1
5 WALL INSULATION TO BE REMOVED FROM IDF
PARTITION TYPE AS AN ALTERNATE. 108
WOMEN'S
C2
C1 RESTROOM L1 C2
106 architecture interiors planning graphics
CG

104c 8070 Park Lane, Ste. 300 Dallas, Texas 75231


L1 L1
Tel 972.701.9000 Fax 972.991.3008
F L1 CG
CG CG
www.bokapowell.com

WAREHOUSE 125a 104b


These documents are issued for pricing only
125 CG
and are not for regulatory approval,
permitting or construction.

Arch: Donald R. Powell, Jr. Reg. No.: 7206


Arch: Chris W. Barnes Reg. No.: 10147

03/A7.32
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

L1

05/A7.32
04/A7.32
BREAKROOM
C2 104 client
DALLAS COUNTY
C1
CG
1460 ROUND TABLE DR
CG
DALLAS, TX 75247
214-653-6437

project manager
G CG
CG L1 L1
11 10 9 8 7 6 PRITCHARD ASSOCIATES
L1
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
104a 214-849-0011
8'-0"
03 / A2.01c project manager

117b
CG CG
1
CG
JPC CONSULTING
MEN'S
C3
CG 2627 MARTIN LUTHER KING JR. BLVD.
RESTROOM 103a DALLAS, TX 75215
123 WAREHOUSE
C4
C1
214-941-4297
C3 125 CORRIDOR STORAGE
102 103
m.e.p. engineer
C2 PURDY-MCGUIRE, INC.
L1
17300 N. DALLAS PARKWAY, SUITE 3000

101c
L1 DALLAS, TX 75248

103
WOMEN'S 113c 112c 972-239-5357
TRAINING
RESTROOM OFFICE
124 111a C1 civil
L1 C2
L1 L1 L1 PACHECO KOCH
H L1 7557 RAMBLER RD. #1400
ELEC IDF
DALLAS, TX 75234

111a
122 121 L1
C2
EARLY
CG
972.235.3031
122 121 VOTING
CG
E-BOOK BOOTH C2 landscape
LAB DS200 LAB LAB TRAINING
114 113 OPEN PACHECO KOCH
112
C2 OFFICES 7557 RAMBLER RD. #1400
3 OFFICE CONFERENCE 16 C2 C2 C3 111
C1 POLLING DALLAS, TX 75234
119 120 AREA 972.235.3031
C2 101
structural engineer
120a

EJES INCORPORATED
120b
119

CORRIDOR
117 12801 N. CENTRAL EXPY, SUITE 700
DALLAS, TX 75243
C3 C2 C2 C3 214.3431210
C2
114a

111
security, audio/visual
114b
113a
2'-0 7/8"

112b
113b
112a
CG CG
C2
NOVOM GROUP
118b 02/A7.32 PRE-FUNCTION
118a 03a/A7.31 03b/A7.31 400 S. RECORD ST, SUITE 1200
110
D2 110b DALLAS, TX 75202
L1 L1 110a L1 L1
CG CG 214-882-1540
C3
116b

115b
116a

115a
CG CG CG CG CG CG CG CG CG CG

109
I CG
CG CG
L1
project
DALLAS COUNTY ELECTIONS BUILDING
C2 C3 C2 C2 C2 C2
OPEN C2 C2 C2 1460 ROUND TABLE DR
01/A7.32
OFFICE DALLAS, TX 75247

101b
101a
CG
118 The drawings and written material herein constitute original work of the
C2 architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published

02/A7.31

01/A7.31
C1 or used in any way without the express written consent of the architect.
original issue
C1
TRAINING TRAINING WAITING DESIGN DEVELOPMENT 04.30.2021
116 115 AREA
revisions
100
2

STORAGE/RECEPTION
109

STORAGE
VESTIBULE 127
126

J
117a

title

01/A4.01
ENLARGED FLOOR PLAN
4/30/2021 3:50:18 PM

X
01 / A2.01c project number 20182.200

date 04.30.2021
sheet

01 ENLARGED FLOOR PLAN


A2.01a
plotted:

SCALE: 1/8" = 1'-0"


TRUE PLAN
NORTH NORTH
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt

architecture interiors planning graphics


8070 Park Lane, Ste. 300 Dallas, Texas 75231
Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com

These documents are issued for pricing only


and are not for regulatory approval,
permitting or construction.
16
Arch: Donald R. Powell, Jr. Reg. No.: 7206
Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437

125e
project manager
PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
E
214-849-0011

project manager

125f
JPC CONSULTING
2627 MARTIN LUTHER KING JR. BLVD.
DALLAS, TX 75215
214-941-4297

m.e.p. engineer
PURDY-MCGUIRE, INC.
17300 N. DALLAS PARKWAY, SUITE 3000

125g
DALLAS, TX 75248
972-239-5357

3 civil
125d
PACHECO KOCH
7557 RAMBLER RD. #1400

180
DALLAS, TX 75234
C2
972.235.3031
F LOADING landscape
DOCK
OFFICE PACHECO KOCH
180 7557 RAMBLER RD. #1400
DALLAS, TX 75234
972.235.3031
structural engineer
EJES INCORPORATED
12801 N. CENTRAL EXPY, SUITE 700
DALLAS, TX 75243
214.3431210

security, audio/visual
NOVOM GROUP
ENLARGED PLAN - LOADING 400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202

TRUE PLAN
02 DOCK OFFICE
SCALE: 1/8" = 1'-0"
214-882-1540
project
NORTH NORTH DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
DALLAS, TX 75247
The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published
or used in any way without the express written consent of the architect.
original issue
14 12 11 10 9 8 7 6 5 4 3
DESIGN DEVELOPMENT 04.30.2021
revisions

X
125b

160b

125c
157b

158b

158a
FACILITIES
MDF DMARC ELEC WATER OFFICE
156 157 158 159 160

C2 H1

C2 ?
title
157a

C1 C2
160a
159

B ENLARGED FLOOR PLAN -


156

UTILITY/LOADING DOCK
4/30/2021 3:50:23 PM

project number 20182.200

date 04.30.2021
sheet

01 ENLARGED PLAN - UTILITY

A2.01b
SCALE: 1/8" = 1'-0"
plotted:

TRUE PLAN
NORTH NORTH
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
11 10
CG

C3

02/A7.33

05/A7.33
SIM OH

SIM OH
03/A7.33 C3
SIM OH
C2

C1

123
C2
C1
CG
C2

architecture interiors planning graphics

G1 8070 Park Lane, Ste. 300 Dallas, Texas 75231

CG Tel 972.701.9000 Fax 972.991.3008


C1
www.bokapowell.com

124
C2
C1
These documents are issued for pricing only

05/A7.33
02/A7.33
03/A7.33 and are not for regulatory approval,
permitting or construction.
C3 01/A7.33 C2
Arch: Donald R. Powell, Jr. Reg. No.: 7206
Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

ENLARGED PLAN - OFFICE


03 RESTROOMS
SCALE: 1/4" = 1'-0"
client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437
4 3
project manager
PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
C1 C2 01/A7.33 C1
C2

02/A7.33
SIM OH
SIM OH DALLAS, TX 75201

05/A7.33
SIM OH
214-849-0011

project manager
06/A7.33 JPC CONSULTING
C1 C2 2627 MARTIN LUTHER KING JR. BLVD.

105
C1
DALLAS, TX 75215
CG 214-941-4297
C2
m.e.p. engineer
PURDY-MCGUIRE, INC.
17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
G4 972-239-5357
CG

civil

106
C1 C2
C1 PACHECO KOCH
7557 RAMBLER RD. #1400

05/A7.33
DALLAS, TX 75234

02/A7.33
01/A7.33 972.235.3031
C2 landscape
C2 03/A7.33 C2
PACHECO KOCH
7557 RAMBLER RD. #1400
CG DALLAS, TX 75234
972.235.3031
structural engineer
ENLARGED PLAN - PUBLIC
EJES INCORPORATED

02 RESTROOMS
SCALE: 1/4" = 1'-0"
12801 N. CENTRAL EXPY, SUITE 700
DALLAS, TX 75243
214.3431210

security, audio/visual
3 2 1 NOVOM GROUP
16'-0" 6" 400 S. RECORD ST, SUITE 1200
CL DALLAS, TX 75202
2'-11 3/4" 5'-0 1/4" 5'-0 1/4" 2'-11 3/4"
214-882-1540
01
project
A5.11
DALLAS COUNTY ELECTIONS BUILDING
100a 1460 ROUND TABLE DR
DALLAS, TX 75247

3'-11"
The drawings and written material herein constitute original work of the
STORAGE architect, and as intellectual property and instruments of service, are
VESTIBULE

7'-10 7/8"
127 subject to copyright and may not be reproduced, distributed, published

CL
126 or used in any way without the express written consent of the architect.
original issue

3'-11 7/8"
1'-6" 6'-4 1/2"
DESIGN DEVELOPMENT 04.30.2021

1'-0 1/2"
100
J revisions

8 1/4"

1'-5 1/8"
412'-1"

7'-6 1/2"
411'-3"

4'-3"
9'-5 5/8" 1" / 12"
RAMP DOWN

1'-7 3/4"
02

CL
A5.11
17'-2 3/8"

409'-3" 412'-1"

4'-3"
1" / 12"
6" 1'-0"

408'-0 1/2"
RAMP DOWN title

ENLARGED FLOOR PLAN -


5'-6 1/2"

RESTROOM/ENTRY
VESTIBULE

X
4/30/2021 3:50:39 PM

project number 20182.200


6" 1'-0" 2'-0" 1'-0" 11'-0" 1'-0" 2'-6" 1'-0" 5'-0" 9'-6" 4'-6"
date 04.30.2021
12'-0 1/8" 2'-6" 5'-6" 10'-0"
1'-6" CL 20'-0" CL CL CL sheet

01 ENLARGED PLAN - ENTRY


A2.01c
plotted:

SCALE: 1/4" = 1'-0"


ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
5 4 3 2 1
ELEC PLAN KEY NOTES X

1 RECEPTACLE SHALL BE FOR TV. COORDINATE MOUNTING HEIGHT WITH ?


?
OWNER/ARCHITECT BEFORE INSTALLATION
ELEC
2 POWER FOR MOTORIZED SCREEN. COORDINATE HEIGHT WITH INSTALLER. 107

3 SEE TECHNOLOGY DRAWINGS FOR ADDITIONAL POWER REQUIREMENTS

3
IDF
108

WOMEN'S RESTROOM
106

architecture interiors planning graphics


8070 Park Lane, Ste. 300 Dallas, Texas 75231
F Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com
1
WAREHOUSE
125
These documents are issued for pricing only
and are not for regulatory approval,
permitting or construction.

Arch: Donald R. Powell, Jr. Reg. No.: 7206


Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

BREAKROOM
104

client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437
G project manager
11 10 9 8 7 6 PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
214-849-0011

project manager
MEN'S RESTROOM
123
JPC CONSULTING
2627 MARTIN LUTHER KING JR. BLVD.
WAREHOUSE
DALLAS, TX 75215
125
CORRIDOR STORAGE 214-941-4297
102 103

m.e.p. engineer
PURDY-MCGUIRE, INC.
17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
WOMEN'S RESTROOM
972-239-5357
124

1 civil
J PACHECO KOCH
H 7557 RAMBLER RD. #1400
ELEC
122
IDF
121
3
EARLY VOTING BOOTH
DALLAS, TX 75234
LAB
112 972.235.3031

E-BOOK LAB DS200 LAB


landscape
114 113
CONFERENCE
1
POLLING AREA
101
PACHECO KOCH
120
TRAINING OPEN
OFFICES 7557 RAMBLER RD. #1400
111
OFFICE
119
DALLAS, TX 75234
972.235.3031
J
structural engineer
CORRIDOR EJES INCORPORATED
117
12801 N. CENTRAL EXPY, SUITE 700
1 1 1 DALLAS, TX 75243
214.3431210

PRE-FUNCTION
110
security, audio/visual
NOVOM GROUP
400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
214-882-1540
I
project
1 1 DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
OPEN OFFICE
118 DALLAS, TX 75247
The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are
1 1 subject to copyright and may not be reproduced, distributed, published
2 or used in any way without the express written consent of the architect.
2
original issue
TRAINING TRAINING
116 115 DESIGN DEVELOPMENT 04.30.2021
revisions
WAITING AREA
100

STORAGE/RECEPTION
109

1 1

title

ENLARGED ELEC PLAN

X
4/30/2021 3:51:02 PM

project number 20182.200

ENLARGED ELEC PLAN - date 04.30.2021

01 OFFICE
SCALE: 1/8" = 1'-0"
sheet

A2.10a
plotted:

TRUE PLAN
NORTH NORTH
ROOF SUB CONTRACTOR INFORMATION:
ROOF KEYNOTES
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
ILIFF INC.
ZACH WARNICK NUMBER KEYNOTE
214.886.3968
ZWARNICK@ILIFFINC.COM
01 PROVIDE CAGE WITH LOCKING GATE FOR ROOF TOP UNIT, TYP., REFER TO ALTERNATES
02 EXISTING SKYLIGHT WITH NEW GUARD RAIL AND GATE
03 OVERHEAD DOOR CANOPY
04 PROVIDE OVERFLOW DRAINS 2' O.C. OF EXISTING ROOF DRAINS, REF PLUMBING
05 EXISTING ROOF HATCH
06 PROVIDE RECOVERY BOARD OVER EXISTING ROOF. NEW TPO ROOFING SYSTEM TO BE INSTALLED ON RECOVERY BOARD. SLOPE TPO ROOF
TO EXISTING ROOF DRAINS & NEW OVERFLOW DRAINS
11 07 PROVIDE TPO WALKWAY MATS, TYP
16 15 13 14 12 10 9 8 7 08 6 ROOF EXPANSION
PROVIDE 5 4 EXISTING 3
JOINT. MATCH 2 LOCATION 1
EXPANSION JOINT

16 15 13 14 12 11 10 9 8 7 6 5 4 3 2 1
architecture interiors planning graphics
8070 Park Lane, Ste. 300 Dallas, Texas 75231
A A
Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com

B B These documents are issued for pricing only


and are not for regulatory approval,
permitting or construction.

Arch: Donald R. Powell, Jr. Reg. No.: 7206


Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129
X X X

X
X
C C

X
X X X client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437
X X
project manager

X
PRITCHARD ASSOCIATES

X
01
08 2121 NORTH AKARD ST, SUITE 100
A0.83

X
DALLAS, TX 75201

X
D D 214-849-0011

X
X X

project manager
JPC CONSULTING
2627 MARTIN LUTHER KING JR. BLVD.
DALLAS, TX 75215
214-941-4297

m.e.p. engineer
PURDY-MCGUIRE, INC.
E E 17300 N. DALLAS PARKWAY, SUITE 3000
03 DALLAS, TX 75248
02/A4.01

972-239-5357

civil
04 PACHECO KOCH
02 7557 RAMBLER RD. #1400
06 DALLAS, TX 75234
972.235.3031

F
X X
F landscape

X
X X X

X
PACHECO KOCH

X
X

X
7557 RAMBLER RD. #1400

X
X
DALLAS, TX 75234

X
X

X X X

972.235.3031
X
X X

07 02 structural engineer
EJES INCORPORATED
2'-0"
12801 N. CENTRAL EXPY, SUITE 700
DALLAS, TX 75243
214.3431210
G G
security, audio/visual
NOVOM GROUP
400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
X X X X
214-882-1540

X
X
01
project

X
X

X
X
01
A0.83
DALLAS COUNTY ELECTIONS BUILDING

X
X
1460 ROUND TABLE DR

X
X
H X X
H DALLAS, TX 75247

X
X
X

X X X X
X
X

The drawings and written material herein constitute original work of the
08 architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published
X
X

or used in any way without the express written consent of the architect.
X

X X
original issue

DESIGN DEVELOPMENT 04.30.2021


revisions

I I
05

01 / A2.41 title
J J ROOF PLAN
01/A4.01 K
L

X
4/30/2021 3:51:28 PM

project number 20182.200


2.2 2.1 1.3 1.2
date 04.30.2021
sheet

01 ROOF PLAN
A2.21
plotted:

SCALE: 1/16" = 1'-0"


TRUE PLAN
NORTH NORTH
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt

GENERAL TOILET ACCESSORY NOTES

4'-11"
1. THE ATTACHED DIAGRAMS ARE FOR MOUNTING THE REFERENCED
MANUFACTURER'S PRODUCT TO MEET TAS/ADA REQUIREMENTS.

2'-6"
CONTRACTOR SHALL COORDINATE AND MODIFY MOUNTING HEIGHTS IF
FF FF PRODUCTS ARE USED BY OTHER APPROVED MANUFACTURERS.

2. ALL STAINLESS STEEL ACCESSORIES ARE TO BE BRUSHED SATIN FINISH


UNLESS NOTED OTHERWISE.
TA-02A TA-03A
3. REFER TO INTERIOR ELEVATION SHEETS AND ENLARGED FLOOR PLANS
WASTE RECEPTACLE PAPER TOWEL DISPENSER/ FOR LOCATIONS OF TOILET ACCESSORIES.
SURFACE MOUNTED WASTE RECEPTACLE
SEMI-RECESSED architecture interiors planning graphics
4. PROVIDE ADEQUATE BLOCKING WITHIN PARTITIONS FOR SUPPORT OF
ACCESSORIES AS REQUIRED. REFER TO THE i0 or A0 SHEET SERIES FOR 8070 Park Lane, Ste. 300 Dallas, Texas 75231
ASI ASI BLOCKING/BACKING DETAILS.
0473 04697-4
Tel 972.701.9000 Fax 972.991.3008
5. COORDINATE FINISHES OF SPACES WITH INSTALLATION OF ACCESSORIES
AND ENSURE THICKNESS OF TILE, TRIM, BASES DO NOT CONFLICT WITH www.bokapowell.com
THE PERFORMANCE OF THE ACCESSORY BEING MOUNTED.

These documents are issued for pricing only


and are not for regulatory approval,

6'-2"

6'-2"
LAVATORY

2'-6"
permitting or construction.
COUNTER

REFER
FF

ELEV
Arch: Donald R. Powell, Jr. Reg. No.: 7206
FF F FF Arch: Chris W. Barnes Reg. No.: 10147
F Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129
TA-04C TA-05A TA-05B TA-09A

SOAP DISPENSER STAINLESS STEEL STAINLESS STEEL TOILET TISSUE


LAVATORY MOUNTED FRAME MIRROR FRAME MIRROR DISPENSER-
DOUBLE ROLL client
SURFACE MOUNTED DALLAS COUNTY
KOHLER ASI BOBRICK
K-1995 0620-24 B-165 2460 1460 ROUND TABLE DR
BOBRICK DALLAS, TX 75247
B-2740
214-653-6437

project manager
PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
214-849-0011

project manager
JPC CONSULTING
2627 MARTIN LUTHER KING JR. BLVD.
DALLAS, TX 75215
214-941-4297

m.e.p. engineer
PURDY-MCGUIRE, INC.
17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
972-239-5357

civil
PACHECO KOCH
8" 7557 RAMBLER RD. #1400
DALLAS, TX 75234

3'-0"

3'-0"
2'-6"

972.235.3031
FF FF FF
landscape
PACHECO KOCH
TA-09L TA-10A TA-10B
7557 RAMBLER RD. #1400
DALLAS, TX 75234
TOILET TISSUE SEAT COVER DISPENSER SEAT COVER DISPENSER
DISPENSER- SURFACE MOUNTED SURFACE MOUNTED 972.235.3031
JUMBO ROLL structural engineer
SURFACE MOUNTED
BOBRICK BOBRICK
EJES INCORPORATED
BOBRICK B-221 B-4221 12801 N. CENTRAL EXPY, SUITE 700
B-2892 DALLAS, TX 75243
214.3431210

security, audio/visual
1'-0" 3'-6" 1'-0" 3'-6"
NOVOM GROUP
MIN
400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
2'-10"

2'-10"
214-882-1540
FF FF
project
DALLAS COUNTY ELECTIONS BUILDING
TA-13B TA-13C
1460 ROUND TABLE DR
DALLAS, TX 75247
AMBULATORY STALL ACCESSIBLE TOILET
GRAB BARS SEPARATE GRAB BARS The drawings and written material herein constitute original work of the
CONCEALED MOUNTING CONCEALED MOUNTING architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published
BOBRICK BOBRICK or used in any way without the express written consent of the architect.
B-6806x42 (2) B-6806x42, B-6806x36 original issue

DESIGN DEVELOPMENT 04.30.2021


revisions

6'-0"

6'-0"

6'-0"
4'-0"

FF FF FF FF

TA-15E TA-16A TA-16B TA-16C

SINGLE ROBE HOOK UTILITY SHELF W/ UTILITY SHELF W/ STAINLESS STEEL


SURFACE MOUNTED MOP/BROOM HOLDER MOP/BROOM HOLDER, MOP/BROOM HOLDER title
DRYING ROD
BOBRICK BOBRICK BOBRICK BOBRICK
TOILET ACCESSORIES
B-7671 B-239 B-224 B-223
4/30/2021 3:47:51 PM

project number 20182.200

date 04.30.2021
sheet

A2.30
plotted:
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt

architecture interiors planning graphics


8070 Park Lane, Ste. 300 Dallas, Texas 75231
Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com

These documents are issued for pricing only


and are not for regulatory approval,
permitting or construction.

Arch: Donald R. Powell, Jr. Reg. No.: 7206


Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437

project manager
PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
214-849-0011

project manager
JPC CONSULTING
2627 MARTIN LUTHER KING JR. BLVD.
DALLAS, TX 75215
214-941-4297

m.e.p. engineer
PURDY-MCGUIRE, INC.
17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
972-239-5357

civil
PACHECO KOCH
7557 RAMBLER RD. #1400
DALLAS, TX 75234
972.235.3031
landscape
PACHECO KOCH
7557 RAMBLER RD. #1400
DALLAS, TX 75234
972.235.3031
structural engineer
EJES INCORPORATED
12801 N. CENTRAL EXPY, SUITE 700
DALLAS, TX 75243
214.3431210

security, audio/visual
NOVOM GROUP
400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
214-882-1540
project
DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
DALLAS, TX 75247
The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published
or used in any way without the express written consent of the architect.
original issue

DESIGN DEVELOPMENT 04.30.2021


revisions

3 2 1

2'-0 3/8"
11'-0 1/4"
422'-3"

title

5'-5 7/8"
ENLARGED ROOF PLANS

6" 3'-6" 16'-0" 22'-0"


4/30/2021 3:51:32 PM

project number 20182.200

date 04.30.2021
ENLARGED ROOF PLAN - sheet

01 ENTRY CANOPY
SCALE: 1/8" = 1'-0"

A2.41
plotted:
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt 1024.2.6 DOORS FROM EXIT ENCLOSURES. DOORS THROUGH WHICH OCCUPANTS 1024.2.4.2 WALL-MOUNTED DEMARCATION LINES. PERIMETER DEMARCATION LINES SHALL 1024.2.1 STEPS. A SOLID AND CONTINUOUS STRIPE SHALL BE APPLIED TO THE
WITHIN AN EXIT ENCLOSURE MUST PASS IN ORDER TO COMPLETE THE EXIT PATH
SHALL BE PROVIDED WITH MARKINGS COMPLYING WITH SECTIONS 1024.2.6.1
THROUGH 1024.2.6.3.
BE PLACED ON THE WALL WITH THE BOTTOM EDGE OF THE STRIPE NO MORE
THAN 4 INCHES (102 MM) ABOVE THE FINISHED FLOOR. AT THE TOP OR BOTTOM
OF THE STAIRS, DEMARCATION LINES SHALL DROP VERTICALLY TO THE FLOOR WITHIN
2 INCHES (51 MM) OF THE STEP OR LANDING EDGE. DEMARCATION LINES ON WALLS
HORIZONTAL LEADING EDGE OF EACH STEP AND SHALL EXTEND FOR
THE FULL LENGTH OF THE STEP. OUTLINING STRIPES SHALL HAVE A
MINIMUM HORIZONTAL WIDTH OF 1 INCH (25 MM) AND A MAXIMUM
WIDTH OF 2 INCHES (51 MM). THE LEADING EDGE OF THE STRIPE SHALL
LUMINOUS EGRESS PATH
1024.2.6.1 EMERGENCY EXIT SYMBOL. THE DOORS SHALL BE IDENTIFIED BY A LOW-LOCATION
LUMINOUS EMERGENCY EXIT SYMBOL COMPLYING WITH NFPA 170. THE EXIT SYMBOL
SHALL BE A MINIMUM OF 4 INCHES (102 MM) IN HEIGHT AND SHALL BE MOUNTED ON
THE DOOR, CENTERED HORIZONTALLY, WITH THE TOP OF THE SYMBOL NO HIGHER
SHALL TRANSITION VERTICALLY TO THE FLOOR AND THEN EXTEND ACROSS THE
FLOOR WHERE A LINE ON THE FLOOR IS THE ONLY PRACTICAL METHOD OF OUTLINING
THE PATH. WHERE THE WALL LINE IS BROKEN BY A DOOR, DEMARCATION LINES ON
WALLS SHALL CONTINUE ACROSS THE FACE OF THE DOOR OR TRANSITION TO THE
BE PLACED AT A MAXIMUM OF 1/2 INCH (13 MM) FROM THE LEADING
EDGE OF THE STEP AND THE STRIPE SHALL OVERLAP THE LEADING EDGE
OF THE STEP BY NOT MORE THAN1/2 INCH (13 MM) DOWN THE VERTICAL
FACE OF THE STEP.
MARKINGS
THAN 18 INCHES (457 MM) ABOVE THE FINISHED FLOOR. FLOOR AND EXTEND ACROSS THE FLOOR IN FRONT OF SUCH DOOR.
EXCEPTION: THE MINIMUM WIDTH OF 1 INCH (25 MM) SHALL NOT APPLY
EXCEPTION: DEMARCATION LINES SHALL NOT EXTEND IN FRONT OF EXIT DOORS
THAT LEAD OUT OF AN EXIT ENCLOSURE AND THROUGH WHICH OCCUPANTS MUST
TO OUTLINING STRIPES LISTED IN ACCORDANCE WITH UL 1994. INTERNATIONAL BUILDING CODE IBC - CHAPTER
TRAVEL TO COMPLETE THE EXIT PATH. 10 MEANS OF EGRESS SECTION 1024: LUMINOUS
EGRESS PATH MARKINGS
architecture interiors planning graphics

BUILDING OCCUPANCY CLASSIFICATIONS 8070 Park Lane, Ste. 300 Dallas, Texas 75231

REQUIRED TO PROVIDE LUMINOUS EGRESS PATH Tel 972.701.9000 Fax 972.991.3008

MARKINGS www.bokapowell.com

1024.1 GENERAL. APPROVED LUMINOUS EGRESS PATH MARKINGS DELINEATING THE EXIT PATH
SHALL BE PROVIDED IN BUILDINGS OF: These documents are issued for pricing only
GROUPS A - ASSEMBLY and are not for regulatory approval,
B - BUSINESS permitting or construction.
E - EDUCATION
I - INSTITUTIONAL Arch: Donald R. Powell, Jr. Reg. No.: 7206
M - MERCANTILE, AND Arch: Chris W. Barnes Reg. No.: 10147
R-1 - TRANSIENT RESIDENTIAL (HOTELS, MOTELS) Arch: John E. Orfield Reg. No.: 11164
HAVING OCCUPIED FLOORS LOCATED MORE THAN 75 FEET (22 860 MM) ABOVE Arch: R. Andrew Bennett Reg. No.: 18129
THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS IN ACCORDANCE WITH
SECTIONS 1024.1 THROUGH 1024.5.

client
DALLAS COUNTY
LOCATIONS REQUIRING EGRESS PATH MARKINGS 1460 ROUND TABLE DR
WITHIN THOSE BUILDING OCCUPANCIES DALLAS, TX 75247
FIGURE 1024.2.6.1 EMERGENCY EXIT SYMBOL FIGURE 1024.2.1 LEADING EDGE OF STEP REQUIRING MARKINGS
214-653-6437

AND LANDING FOR SI: 1 INCH = 25.4 MM. 1024.2 MARKINGS WITHIN EXIT ENCLOSURES. EGRESS PATH MARKINGS SHALL BE PROVIDED
project manager
FIGURE 1024.2.4.2 PERIMETER DEMARCATION 1024.2.2 LANDINGS. THE LEADING EDGE OF LANDINGS SHALL BE MARKED WITH A
IN EXIT ENCLOSURES, INCLUDING VERTICAL EXIT ENCLOSURES AND EXIT PASSAGEWAYS,
IN ACCORDANCE WITH SECTIONS 1024.2.1 THROUGH 1024.2.6.
PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
LINES–WALL MOUNTED OPTION STRIPE CONSISTENT WITH THE DIMENSIONAL REQUIREMENTS FOR STEPS.
INTERIORS OF EXIT STAIRWAYS FOR ALL FLOORS
DALLAS, TX 75201
1024.2.3 HANDRAILS. ALL HANDRAILS AND HANDRAIL EXTENSIONS SHALL BE MARKED INTERIORS OF EXIT RAMPS FOR ALL FLOORS 214-849-0011
WITH A SOLID AND CONTINUOUS STRIPE HAVING A MINIMUM WIDTH OF 1 INTERIORS OF EXIT PASSAGEWAYS FOR ALL FLOORS
1024.2.6.2 DOOR HARDWARE MARKINGS. DOOR HARDWARE SHALL BE MARKED WITH NO LESS INCH (25 MM). THE STRIPE SHALL BE PLACED ON THE TOP SURFACE OF THE (STAIR TRANSFER CORRIDORS) project manager
THAN 16 SQUARE INCHES (406 MM2) OF LUMINOUS MATERIAL. THIS MARKING SHALL BE HANDRAIL FOR THE ENTIRE LENGTH OF THE HANDRAIL, INCLUDING
LOCATED BEHIND, IMMEDIATELY ADJACENT TO OR ON THE DOOR HANDLE AND/OR EXTENSIONS AND NEWEL POST CAPS. WHERE HANDRAILS OR HANDRAIL 1024.1 EXCEPTIONS: JPC CONSULTING
ESCUTCHEON. WHERE A PANIC BAR IS INSTALLED, SUCH MATERIAL SHALL BE NO LESS EXTENSIONS BEND OR TURN CORNERS, THE STRIPE SHALL NOT HAVE A GAP 1. LUMINOUS EGRESS PATH MARKINGS SHALL NOT BE REQUIRED ON THE LEVEL 2627 MARTIN LUTHER KING JR. BLVD.
THAN 1 INCH (25 MM) WIDE FOR THE ENTIRE LENGTH OF THE ACTUATING BAR OR OF MORE THAN 4 INCHES (102 MM). OF EXIT DISCHARGE IN LOBBIES THAT SERVE AS PART OF THE EXIT PATH IN DALLAS, TX 75215
TOUCHPAD. ACCORDANCE WITH SECTION 1027.1, EXCEPTION 1. 214-941-4297
EXCEPTION: THE MINIMUM WIDTH OF 1 INCH (25 MM) SHALL NOT APPLY TO 2. LUMINOUS EGRESS PATH MARKINGS SHALL NOT BE REQUIRED IN AREAS OF OPEN
1024.2.6.3 DOOR FRAME MARKINGS. THE TOP AND SIDES OF THE DOOR FRAME SHALL BE MARKED OUTLINING STRIPES LISTED IN ACCORDANCE WITH UL 1994. PARKING GARAGES THAT SERVE AS PART OF THE EXIT PATH IN ACCORDANCE WITH
WITH A SOLID AND CONTINUOUS 1 INCH TO 2 INCH (25 MM TO 51 MM) WIDE STRIPE. SECTION 1027.1, EXCEPTION 3. m.e.p. engineer
WHERE THE DOOR MOLDING DOES NOT PROVIDE SUFFICIENT FLAT SURFACE ON WHICH
TO LOCATE THE STRIPE, THE STRIPE SHALL BE PERMITTED TO BE LOCATED ON THE WALL
PURDY-MCGUIRE, INC.
SURROUNDING THE FRAME. 17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
DEFINITION OF LUMINOUS EGRESS PATH 972-239-5357

MARKING MATERIAL civil


PACHECO KOCH
1024.3 UNIFORMITY. PLACEMENT AND DIMENSIONS OF MARKINGS SHALL BE 7557 RAMBLER RD. #1400
CONSISTENT AND UNIFORM THROUGHOUT THE SAME EXIT ENCLOSURE.
DALLAS, TX 75234
1024.4 SELF-LUMINOUS AND PHOTOLUMINESCENT. LUMINOUS EGRESS 972.235.3031
PATH MARKINGS SHALL BE PERMITTED TO BE MADE OF ANY MATERIAL,
INCLUDING PAINT, PROVIDED THAT AN ELECTRICAL CHARGE IS NOT REQUIRED landscape
TO MAINTAIN THE REQUIRED LUMINANCE. SUCH MATERIALS SHALL INCLUDE, PACHECO KOCH
BUT ARE NOT LIMITED TO, SELF-LUMINOUS MATERIALS AND PHOTOLUMINESCENT
MATERIALS. MATERIALS SHALL COMPLY WITH EITHER:
7557 RAMBLER RD. #1400
FIGURE 1024.2.3 HANDRAIL MARKINGS 1. UL 1994; OR DALLAS, TX 75234
2. ASTM E 2072, EXCEPT THAT THE CHARGING SOURCE SHALL BE 1 972.235.3031
FOOT-CANDLE (11 LUX) OF FLUORESCENT ILLUMINATION FOR 60
MINUTES, AND THE MINIMUM LUMINANCE SHALL BE 30 MILLICANDELAS structural engineer
1024.2.4 PERIMETER DEMARCATION LINES. STAIR LANDINGS AND OTHER FLOOR AREAS PER SQUARE METER AT 10 MINUTES AND 5 MILLICANDELAS PER SQUARE EJES INCORPORATED
METER AFTER 90 MINUTES.
FIGURE 1024.2.4.3 PERIMETER DEMARCATION WITHIN EXIT ENCLOSURES, WITH THE EXCEPTION OF THE SIDES OF STEPS,
SHALL BE PROVIDED WITH SOLID AND CONTINUOUS DEMARCATION LINES ON
12801 N. CENTRAL EXPY, SUITE 700
1024.5 ILLUMINATION. EXIT ENCLOSURES WHERE PHOTOLUMINESCENT EXIT PATH DALLAS, TX 75243
LINES–OPTIONS AT DOORS INTO EXIT THE FLOOR OR ON THE WALLS OR A COMBINATION OF BOTH. THE STRIPES SHALL
BE 1 TO 2 INCHES (25 MM TO 51 MM) WIDE WITH INTERRUPTIONS NOT EXCEEDING MARKINGS ARE INSTALLED SHALL BE PROVIDED WITH THE MINIMUM MEANS OF 214.3431210
EGRESS ILLUMINATION REQUIRED BY SECTION 1006 FOR AT LEAST 60 MINUTES
ENCLOSURES 4 INCHES (102 MM).
PRIOR TO PERIODS WHEN THE BUILDING IS OCCUPIED.
security, audio/visual
EXCEPTION: THE MINIMUM WIDTH OF 1 INCH (25 MM) SHALL NOT APPLY TO
OUTLINING STRIPES LISTED IN ACCORDANCE WITH UL 1994. NOVOM GROUP
400 S. RECORD ST, SUITE 1200
1024.2.4.3 TRANSITION. WHERE A WALL-MOUNTED DEMARCATION LINE TRANSITIONS TO A 1024.2.4.1 FLOOR-MOUNTED DEMARCATION LINES. PERIMETER DEMARCATION LINES DALLAS, TX 75202
FLOOR-MOUNTED DEMARCATION LINE, OR VICE VERSA, THE WALL-MOUNTED SHALL BE PLACED WITHIN 4 INCHES (102 MM) OF THE WALL AND SHALL EXTEND
DEMARCATION LINE SHALL DROP VERTICALLY TO THE FLOOR TO MEET A COMPLEMENTARY TO WITHIN 2 INCHES (51 MM) OF THE MARKINGS ON THE LEADING EDGE OF
214-882-1540
EXTENSION OF THE FLOOR-MOUNTED DEMARCATION LINE, THUS FORMING A CONTINUOUS LANDINGS. THE DEMARCATION LINES SHALL CONTINUE ACROSS THE FLOOR IN
MARKING. FRONT OF ALL DOORS.
project
DALLAS COUNTY ELECTIONS BUILDING
1024.2.5 OBSTACLES. OBSTACLES AT OR BELOW 6 FEET 6 INCHES (1981 MM) IN HEIGHT AND EXCEPTION: DEMARCATION LINES SHALL NOT EXTEND IN FRONT OF EXIT 1460 ROUND TABLE DR
PROJECTING MORE THAN 4 INCHES (102 MM) INTO THE EGRESS PATH SHALL BE OUTLINED DOORS THAT LEAD OUT OF AN EXIT ENCLOSURE AND THROUGH WHICH
WITH MARKINGS NO LESS THAN 1 INCH (25 MM) IN WIDTH COMPRISED OF A PATTERN OF OCCUPANTS MUST TRAVEL TO COMPLETE THE EXIT PATH.
DALLAS, TX 75247
ALTERNATING EQUAL BANDS, OF LUMINESCENT LUMINOUS MATERIAL AND BLACK, WITH The drawings and written material herein constitute original work of the
THE ALTERNATING BANDS NO MORE THAN 2 INCHES (51 MM) THICK AND ANGLED AT 45 architect, and as intellectual property and instruments of service, are
DEGREES (0.79 RAD). OBSTACLES SHALL INCLUDE, BUT ARE NOT LIMITED TO, STANDPIPES, subject to copyright and may not be reproduced, distributed, published
HOSE CABINETS, WALL PROJECTIONS AND RESTRICTED HEIGHT AREAS. HOWEVER, SUCH or used in any way without the express written consent of the architect.
MARKINGS SHALL NOT CONCEAL ANY REQUIRED INFORMATION OR INDICATORS INCLUDING, original issue
BUT NOT LIMITED TO, INSTRUCTIONS TO OCCUPANTS FOR THE USE OF STANDPIPES.
DESIGN DEVELOPMENT 04.30.2021
revisions

title
FIGURE 1024.2.6 EXAMPLES OF EXIT DOOR TO LUMINOUS EGRESS PATH
EXTERIOR OPTIONS FOR SI: 1 INCH = 25.4 MM. MARKINGS
4/30/2021 3:47:55 PM

project number 20182.200

date 04.30.2021
FIGURE 1024.2.5 OBSTACLE MARKINGS FIGURE 1024.2.4.1 PERIMETER DEMARCATION
sheet
FOR SI: 1 INCH = 25.4 MM; LINES–FLOOR MOUNTED OPTION
1 SQUARE INCH = 645.16 MM FOR SI: 1 INCH= 25.4 MM.
A2.67
plotted:
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
DOOR SCHEDULE
DOOR FRAME
DOOR DETAIL FIRE Forearm HARDWARE GENERAL NOTES - FRAME TYPES
NUMBER WIDTH HEIGHT THICKNESS TYPE MATERIAL FINISH GLAZING TYPE MATERIAL FINISH HEAD JAMB SILL RATING Card Reader Pull SET NOTES
1. PROVIDE TEMPERED OR SAFETY GLAZING IN OPENINGS WHERE
REQUIRED BY CODE OR BY AUTHORITY HAVING JURISDICTION.
LEVEL 1
100 10'-0" 10'-0" 1 3/4" SLD1 TEMP - No No 2. SET WINDOW SUB-SILLS IN CONTINUOUS BED OF SEALANT.
100a 10'-0" 10'-0" 1 3/4" SLD1 TEMP - No No
3. SPACE ANCHORS FOR DOOR FRAMES NO MORE THAN 16" O.C. MAX.
101a 6'-0" 8'-10" 1 3/4" FL/FL SCW ST - 2 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No
101b 6'-0" 8'-10" 1 3/4" FL/FL SCW ST - 2 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No 4. PROVIDE 3 HINGES FOR DOORS UNDER 7'-6" HIGH AND 4 HINGES
101c 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No FOR DOORS BETWEEN 7'-6" AND 9'-0" HIGH. DOORS ABOVE 9'-0"
103 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No HIGH SHALL HAVE 5 HINGES.
103a 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No
5. VERIFY HEAD HEIGHTS OF OPENINGS ON THE EXTERIOR AND
104a 6'-0" 7'-0" 1 3/4" FL/FL SCW ST - 2 AL AN 06/A3.06 05/A3.06 04/A3.06 20 MIN No No INTERIOR ELEVATIONS. INFORM ARCHITECT OF DISCREPANCIES
104b 6'-0" 7'-0" 1 3/4" FL/FL SCW ST - 2 AL AN 06/A3.06 05/A3.06 04/A3.06 20 MIN No No PRIOR TO PROCEEDING.
104c 3'-0" 7'-0" 1 3/4" FL - - No No architecture interiors planning graphics
105 6'-0" 7'-0" 1 3/4" FL/FL - - No No 6. ALL INTERIOR GLAZING SHALL BE 1/4" CLEAR GLASS UNLESS
NOTED OTHERWISE. ALL EXTERIOR GLAZING SHALL BE 1" 8070 Park Lane, Ste. 300 Dallas, Texas 75231
105 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No
INSULATED GLASS UNLESS NOTED OTHERWISE.
106 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No
107 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No 7. INSTALL FIRE-RATED GLAZING AND FRAMES FOR RATED OPENINGS,
Tel 972.701.9000 Fax 972.991.3008
108 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No WHERE REQUIRED BY CODE.
www.bokapowell.com
109 6'-0" 7'-0" 1 3/4" FL/FL SCW ST - 2 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No
8. PROVIDE KNOX BOX AT GATE OR DOOR OPENINGS AS REQUIRED
110a 6'-0" 7'-0" 1 3/4" FL/FL SCW ST - 2 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No BY FIRE MARSHALL.
110b 6'-0" 7'-0" 1 3/4" FL/FL SCW ST - 2 AL AN 06/A3.06 05/A3.06 04/A3.06 20 MIN No No These documents are issued for pricing only
111 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 20 MIN No No 9. ALUMINUM WINDOW WALL SUPPLIER SHALL BE RESPONSIBLE FOR and are not for regulatory approval,
111a 3'-0" 7'-0" 1 3/4" NL SCW ST - 3 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No PROVIDING PROPER THICKNESS OF FRAMING MEMBERS, permitting or construction.
INCLUDING INTERNAL STRUCTURAL FRAMING AS MAY BE
112a 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 20 MIN No No
REQUIRED, BASED UPON LAYOUT SHOWN AND AS PER APPLICABLE Arch: Donald R. Powell, Jr. Reg. No.: 7206
112b 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 20 MIN No No BUILDING CODES. Arch: Chris W. Barnes Reg. No.: 10147
112c 3'-0" 7'-0" 1 3/4" FL - - No No Arch: John E. Orfield Reg. No.: 11164
113a 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 20 MIN No No 10. PROVIDE SEALS IN LIEU OF SILENCERS WHERE REQUIRED FOR Arch: R. Andrew Bennett Reg. No.: 18129
113b 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 20 MIN No No FIRE RATED CONDITIONS.
113c 3'-0" 7'-0" 1 3/4" FL - - No No
113d 3'-0" 7'-0" 1 3/4" FL SCW PT - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 20 MIN
114a 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 20 MIN No No
114b 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 20 MIN No No
GENERAL NOTES - DOORS & LITES client
DALLAS COUNTY
115a 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 20 MIN No No 1. PROVIDE TEMPERED OR SAFETY GLAZING IN OPENINGS WHERE 1460 ROUND TABLE DR
115b 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 20 MIN No No REQUIRED BY CODE OR BY AUTHORITY HAVING JURISDICTION.
DALLAS, TX 75247
116a 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 20 MIN No No
2. VERIFY HEAD HEIGHTS OF OPENINGS ON THE EXTERIOR AND 214-653-6437
116b 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 20 MIN No No
INTERIOR ELEVATIONS. INFORM ARCHITECT OF DISCREPANCIES
117a 6'-0" 7'-0" 1 3/4" FL/FL - - No No PRIOR TO PROCEEDING. project manager
117b 6'-0" 7'-0" 1 3/4" FL/FL SCW ST - 2 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No
118a 6'-0" 7'-0" 1 3/4" FL/FL SCW ST - 2 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No 3. ALL INTERIOR GLAZING SHALL BE 1/4" CLEAR GLASS UNLESS PRITCHARD ASSOCIATES
118b 6'-0" 7'-0" 1 3/4" FL/FL SCW ST - 2 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No NOTED OTHERWISE. ALL EXTERIOR GLAZING SHALL BE 1" 2121 NORTH AKARD ST, SUITE 100
INSULATED TINTED GLASS UNLESS NOTED OTHERWISE. DALLAS, TX 75201
119 3'-0" 7'-0" 1 3/4" NL SCW ST - 3 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No
120a 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No 4. ALL INTERIOR HOLLOW METAL GLAZING SYSTEMS SHALL HAVE 214-849-0011
120b 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No GLASS AND GLAZING STOPS ON HALLYWAY OR MORE "PUBLIC"
121 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No SIDE OF FRAME. project manager
122 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No
5. ALL FIRE AND/OR SMOKE RATED DOORS SHALL HAVE SEALS, BE
JPC CONSULTING
123 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No SELF CLOSING AND HAVE MAXIMUM UNDERCUT OF 3/4" PER NFPA 2627 MARTIN LUTHER KING JR. BLVD.
124 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No 80. IF DOORS ARE EQUIPED WITH HOLD-OPEN FEATURE, THEY DALLAS, TX 75215
125a 6'-0" 7'-0" 1 3/4" FL/FL SCW ST - 2 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No SHALL BE TIED TO THE FIRE/MASS NOTIFICATION SYSTEM AND 214-941-4297
SHALL AUTOMATICALLY CLOSE UPON THE DETECTION OF SMOKE.
125b 7'-0" 7'-0" 1 3/4" FL/FL - - No No
125c 6'-0" 7'-0" 1 3/4" FL/FL - - No No 6. ALL DOOR HARDWARE SETS SHALL BE CODED AND/OR KEYED IN m.e.p. engineer
125d 3'-0" 7'-0" 1 3/4" FL - - No No ACCORDANCE WITH BUILDING REQUIREMENTS. SECURITY CODES PURDY-MCGUIRE, INC.
125e 8'-0" 10'-0" 1 3/4" SDO - - No No AND/OR KEYS SHALL BE DELIVERED TO OWNER PROPERLY TESTED 17300 N. DALLAS PARKWAY, SUITE 3000
125f 8'-0" 10'-0" 1 3/4" SDO - - No No AND/OR TAGGED. QUANTITY OF MASTER AND PASS KEYS SHALL BE
COORDINATED WITH OWNER. DALLAS, TX 75248
125g 8'-0" 10'-0" 1 3/4" SDO - - No No 972-239-5357
156 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No 7. EXTERIOR HOLLOW METAL DOORS, AND FRAMES, SHALL BE
157a 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No PAINTED TO MATCH ADJACENT WALL SURFACE. civil
157b 6'-0" 7'-0" 1 3/4" FL/FL - - No No
8. NOT ALL DOOR OR FRAME TYPES SHOWN ARE USED. VERIFY DOOR PACHECO KOCH
158a 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No
AND FRAME TYPES WITH DOOR SCHEDULE. 7557 RAMBLER RD. #1400
158b 6'-0" 7'-0" 1 3/4" FL/FL - - No No
DALLAS, TX 75234
159 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No 9. COORDINATE COLOR AND FINISH OF DOORS AND FRAMES WITH
160a 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No INTERIOR ELEVATIONS AND INTERIOR FINISH SCHEDULE. IF NOT 972.235.3031
NOTED, COLOR SHALL MATCH ADJACENT WALL SURFACE.
160b 6'-0" 7'-0" 1 3/4" FL/FL - - No No landscape
180 3'-0" 7'-0" 1 3/4" FL SCW ST - 1 AL AN 06/A3.06 05/A3.06 04/A3.06 - No No 10. PROVIDE PROTECTED OPENINGS, AS REQUIRED BY CODE, WHERE PACHECO KOCH
OPENINGS ARE LOCATED IN A SMOKE AND/OR FIRE RESISTANCE 7557 RAMBLER RD. #1400
ROOF RATED WALL/PARTITION AND AS INDICATED IN THE DOOR
SCHEDULE. CONTRACTOR SHALL NOTIFY ARCHITECT OF ANY DALLAS, TX 75234
R100 2'-2" 8'-0" 1 3/4" FL - - No No
AMBIGUITIES PRIOR TO ORDERING/INSTALLING DOOR, FRAMES, 972.235.3031
R201 2'-2" 8'-0" 1 3/4" FL - - No No
GLAZING AND/OR HARDWARE FOR CLARIFICATION.
R202 2'-2" 8'-0" 1 3/4" FL - - No No structural engineer
R203 2'-2" 8'-0" 1 3/4" FL - - No No EJES INCORPORATED
R204 2'-2" 8'-0" 1 3/4" FL - - No No 12801 N. CENTRAL EXPY, SUITE 700
R205
R206
2'-2"
2'-2"
8'-0"
8'-0"
1 3/4"
1 3/4"
FL
FL
-
-
-
-
No
No
No
No
NOTES FOR DOOR SCHEDULE DALLAS, TX 75243
214.3431210
1. PROVIDE POWER SOURCE, CONTROLLER & CONNECTIONS TO
KEYPAD/CARD READER. security, audio/visual
2. MAGNETIC HOLD OPEN TIED TO FIRE ALARM/MASS NOTIFICATION NOVOM GROUP
SYSTEM TO ACTIVATE/RELEASE UPON AN ALARM. 400 S. RECORD ST, SUITE 1200
3. PART OF MANUFACTURERES STANDARD ALUMINUM GLAZING
DALLAS, TX 75202
SYSTEM USING TYPICAL DETAILS BY MANUFACTURER. 214-882-1540

FRAME TYPES 4.

5.
SELF CLOSING DOOR.

PROVIDE MAXIMUM 3/4" UNDERCUT PER NFPA 80.


project
DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
SCHEDULED SIDE DALLAS, TX 75247
SCHEDULED WIDTH SCHEDULED WIDTH SCHEDULED WIDTH LITE WIDTH The drawings and written material herein constitute original work of the
2" TYP.

2" TYP.
2" TYP.

architect, and as intellectual property and instruments of service, are


2" TYP. 2" TYP. 2" TYP.
TYPICAL DOOR PLACEMENT subject to copyright and may not be reproduced, distributed, published
or used in any way without the express written consent of the architect.
original issue
SCHEDULED HEIGHT

SCHEDULED HEIGHT

SCHEDULED HEIGHT

7" MAX. AT EXIT STAIRS DESIGN DEVELOPMENT 04.30.2021


revisions

3" TO FRAME

1 - SINGLE 2 - PAIR 3 - SINGLE W/ 4 - EXISTING NOTE:


SIDELITE REFERENCE TAS 404 DOORS,
DOORWAYS, AND GATES FOR
ADDITIONAL CLEARANCES

DOOR TYPES DOOR SCHEDULE ABBREVIATIONS


title
AL ALUMINUM
SCHEDULED WIDTH SCHEDULED WIDTH SCHEDULED WIDTH SCHEDULED WIDTH SCHEDULED WIDTH
AL/GL
AN
ALUMINUM/GLASS
ANODIZED
DOOR TYPES, FRAME TYPES
GL GLASS & SCHEDULE NOTES
4"

HCW HOLLOW CORE WOOD


HM HOLLOW METAL
4" 4"
SCHEDULED HEIGHT

SCHEDULED HEIGHT

SCHEDULED HEIGHT

SCHEDULED HEIGHT

LAM LAMINATED GLASS


4/30/2021 3:47:44 PM

SCHEDULED HEIGHT

PATCH PANEL FOR


MAG LOCK/STOP
N/A NOT APPLICABLE project number 20182.200
BOTTOM RAIL P PAINT
BOTTOM
CYLINDER SENSORED PL PLASTIC LAMINATE CLAD date 04.30.2021
PATCH PANELS
LOCK AS RAIL SCW SOLID CORE WOOD
FOR PIVOTS
SCHEDULED ST STAIN sheet
TYPICAL
10"

TEMP TEMPERED/SAFETY GLAZING

A3.01
TINT TINTED GLASS
plotted:

FG - FULL GLASS FL - FLUSH GL - ALL GLASS CDO - OVERHEAD COILING OFS - OVERHEAD FIRE SHUTTER WD WOOD
WD/LV WOOD/LOUVER
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt

architecture interiors planning graphics


8070 Park Lane, Ste. 300 Dallas, Texas 75231
Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com

These documents are issued for pricing only


and are not for regulatory approval,
permitting or construction.

Arch: Donald R. Powell, Jr. Reg. No.: 7206


Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437

project manager
PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
214-849-0011

project manager
JPC CONSULTING
2627 MARTIN LUTHER KING JR. BLVD.
DALLAS, TX 75215
214-941-4297

m.e.p. engineer
PURDY-MCGUIRE, INC.
17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
972-239-5357

civil
PACHECO KOCH
7557 RAMBLER RD. #1400
DALLAS, TX 75234
972.235.3031
landscape
PACHECO KOCH
7557 RAMBLER RD. #1400
DALLAS, TX 75234
E 972.235.3031
structural engineer
EJES INCORPORATED
9' - 8 5/8" 5' - 7 3/8" 17' - 4" 7' - 0" 12801 N. CENTRAL EXPY, SUITE 700
ROOF DALLAS, TX 75243
EL. 117'-0" 214.3431210

420'-3" security, audio/visual


NOVOM GROUP
?, ? 400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202

10'-0"
214-882-1540
GUARD RAIL, TYP.
LEVEL 1 project
EL. 100'-0"
DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
DALLAS, TX 75247
The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published
or used in any way without the express written consent of the architect.
original issue

02 ELEVATION - LOADING DOCK


SCALE: 1/8" = 1'-0"
DESIGN DEVELOPMENT
revisions
04.30.2021

4 3 2 1
CL CL CL
6" 5'-0" 5'-0" 5'-0" 3'-6" 1' - 5 7/8" 2' - 0 1/8" 15' - 11 3/4" 2' - 0 1/4"
ROOF
EL. 117'-0"
ALUMINUM COMPOSITE
METAL, ACM-2
title

GLASS, GL-1 EXTERIOR ELEVATIONS


10'-0"

BRICK, BK-1

LEVEL 1
4/30/2021 3:49:03 PM

EL. 100'-0"
project number 20182.200

date 04.30.2021
sheet

01 ELEVATION - NEW ENTRY


A4.01
plotted:

SCALE: 1/8" = 1'-0"


ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt

ALUMINUM COMPOSITE
METAL, ACM-2

architecture interiors planning graphics


8070 Park Lane, Ste. 300 Dallas, Texas 75231
Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com

These documents are issued for pricing only


and are not for regulatory approval,
permitting or construction.

ALUMINUM COMPOSITE Arch: Donald R. Powell, Jr. Reg. No.: 7206


METAL, ACM-1 Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

client
DALLAS COUNTY
1460 ROUND TABLE DR

03 ENTRY CANOPY - AXON


SCALE:
DALLAS, TX 75247
214-653-6437

project manager
PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
3 01
2 1 DALLAS, TX 75201
A5.11
214-849-0011

project manager
ROOF
EL. 117'-0" JPC CONSULTING
2627 MARTIN LUTHER KING JR. BLVD.
DALLAS, TX 75215
422'-3" 214-941-4297

m.e.p. engineer
ALUMINUM COMPOSITE PURDY-MCGUIRE, INC.
METAL, ACM-1
17300 N. DALLAS PARKWAY, SUITE 3000
ALUMINUM COMPOSITE DALLAS, TX 75248
METAL, ACM-2 972-239-5357
415'-3"
civil
PACHECO KOCH
412'-1"
7557 RAMBLER RD. #1400
BRICK, BK-1
DALLAS, TX 75234
411'-3" 972.235.3031
LEVEL 1 landscape
409'-3" EL. 100'-0" PACHECO KOCH
7557 RAMBLER RD. #1400
DALLAS, TX 75234
972.235.3031
structural engineer
EJES INCORPORATED
12801 N. CENTRAL EXPY, SUITE 700
WALL SECTION - ENTRY DALLAS, TX 75243
214.3431210

02 CANOPY
SCALE: 1/4" = 1'-0" security, audio/visual
NOVOM GROUP
400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
214-882-1540
J
project
18'-6" DALLAS COUNTY ELECTIONS BUILDING
CL 1460 ROUND TABLE DR
13'-0 3/8"
DALLAS, TX 75247
02 The drawings and written material herein constitute original work of the
A5.11 architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published
ROOF or used in any way without the express written consent of the architect.
EL. 117'-0"
original issue

DESIGN DEVELOPMENT 04.30.2021


422'-3" revisions

ALUMINUM COMPOSITE
METAL, ACM-1
419'-3"

GLASS, GL-1
412'-1"

title

LEVEL 1
EL. 100'-0"
WALL SECTIONS
407'-3"
4/30/2021 3:49:15 PM

project number 20182.200

date 04.30.2021
sheet
WALL SECTION - ENTRY
01 CANOPY
A5.11
plotted:

SCALE: 1/4" = 1'-0"


ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt REFLECTED CEILING PLAN GENERAL NOTES
1. CEILING, LIGHT FIXTURES AND OTHER ITEMS SHALL BE LOCATED PER THE ARCHITECT'S
REFLECTED CEILING PLANS. USE EXTREME CARE IN COORDINATING WORK OF VARIOUS
TRADES TO FIT THE PATTERN SHOWN. IF CONFLICT OCCURS BETWEEN MECHANICAL AND
LIGHT FIXTURE ABOVE CEILING, CONTACT THE ARCHITECT PRIOR TO PROCEEDING.

2. REFER TO REFLECTED CEILING LEGEND FOR FIXTURE TYPES.

3. INSTALL AND ANCHOR ALL LIGHT FIXTURES PER MANUFACTURER'S REQUIREMENTS.


16 15 13 14 12 11 10 9 8 7 6 5 4 3 2 1
4. PROVIDE AND INSTALL SMOKE DETECTORS, EXIT SIGNS, FIRE ALARM STROBES, FIRE ALARM
SPEAKERS AND EMERGENCY EGRESS LIGHTING AS REQUIRED TO MEET ALL LOCAL, STATE AND
NATIONAL CODES.

5. ALL WORK SHALL CONFORM TO ALL APPLICABLE CODES, AGENCIES AND AUTHORITIES WITH
A 10'-0"
JURISDICTION. HB HB HB HB HB HB HB HB

MDF
OTS OTS
DMARC OTS ELEC WATER
A1 A1
FACILITIES OFFICE
A1 A1
HB HB HB HB
architecture interiors planning graphics
4 156 157 4 158
OTS
159 4 160 ACT-1
6. CLEAN, REPAIR, REPLACE AND REPAINT ANY GRID THAT IS DAMAGED DURING CONSTRUCTION. 4
HB HB HB HB HB HB HB HB A1 A1 A1 A1 8070 Park Lane, Ste. 300 Dallas, Texas 75231
7. CONTRACTOR SHALL FURNISH LABOR AND MATERIALS NECESSARY TO PROVIDE FOR
INSTALLATION OF SPRINKLER HEAD(S) TO MAINTAIN COVERAGE OF SPACE PER CODE B Tel 972.701.9000 Fax 972.991.3008
REQUIREMENTS. NO SPRINKLER HEADS SHALL BE LOCATED WITHIN ONE FOOT OF A PARTITION
AND NO SPRINKLER ESCUTCHEON SHALL TOUCH THE CEILING GRID. HB HB HB HB HB HB HB HB HB HB HB HB HB HB HB
www.bokapowell.com
8. REPLACE ALL DAMAGED, SCUFFED, CHIPPED OR SOILED CEILING TILE.
These documents are issued for pricing only
9. IT IS THE CONTRACTOR'S RESPONSIBILITY TO SURVEY ALL EXISTING ABOVE CEILING
and are not for regulatory approval,
CONDITIONS AND NOTIFY THE ARCHITECT IN WRITING OF ANY CONFLICTS THAT WOULD
PREVENT THIS DESIGN FROM BEING BUILT. THIS INCLUDES, BUT IS NOT LIMITED TO SPRINKLER permitting or construction.
PIPES, DUCTWORK, AND STRUCTURE.
HB HB HB HB HB HB HB HB HB HB HB HB HB HB HB Arch: Donald R. Powell, Jr. Reg. No.: 7206
10. ALL GYP BD SOFFITS INDICATED ON THIS PLAN SHALL MATCH EXISTING ON THE HORIZONTAL Arch: Chris W. Barnes Reg. No.: 10147
AND VERTICAL SURFACES OF THE SOFFIT UNLESS OTHERWISE NOTED. Arch: John E. Orfield Reg. No.: 11164
C Arch: R. Andrew Bennett Reg. No.: 18129
11. CEILING HEIGHT TO BE 10'-0" UNLESS NOTED OTHERWISE.

HB HB HB HB HB HB HB HB HB HB HB HB HB HB HB

client
DALLAS COUNTY
1460 ROUND TABLE DR
HB HB HB HB HB HB HB HB HB HB HB HB HB HB HB
DALLAS, TX 75247
214-653-6437

D project manager
REFLECTED CEILING PLAN LEGEND PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
HB HB HB HB HB HB HB HB HB HB HB HB HB HB HB
EXISTING 24" X 48" LAY-IN CEILING GRID; TILE S TO MATCH EXISTING DALLAS, TX 75201
4
214-849-0011
NEW BUILDING 24" X 24" CEILING TILE AND GRID. OTS project manager
HB HB HB HB HB HB HB HB HB HB HB HB HB HB HB
JPC CONSULTING
BLDG STANDARD 2 X 4 FLUORESCENT LIGHT FIXTURE, TO MATCH EXISTING 2627 MARTIN LUTHER KING JR. BLVD.
DALLAS, TX 75215
BLDG STANDARD 2 X 2 FLUORESCENT FLIGHT FIXTURE, TO MATCH EXISTING E 01 / A6.02 214-941-4297

m.e.p. engineer
BLDG STANDARD RECESSED DOWNLIGHT FIXTURE, TO MATCH EXISTING HB HB HB HBWAREHOUSE HB HB HB HB HB HB HB HB
125 PURDY-MCGUIRE, INC.
17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
REFLECTED CEILING PLAN KEY NOTES X HB
972-239-5357
HB HB HB HB HB HB HB HB HB HB HB

1 OPERABLE PARTITION WALL TRACK civil


A1 A1 PACHECO KOCH
2 CEILING MOTORIZED SCREEN. COORDINATE HEIGHT F LOADING DOCK
OFFICE 7557 RAMBLER RD. #1400
WITH TECHNOLOGY. 180
A1 A1 DALLAS, TX 75234
3 10'-0" 972.235.3031
CEILING MOUNTED PROJECTOR. REFER TO MEP P-1
DRAWINGS FOR LOCATION AND ELECTRICAL HB HB HB HB HB HB HB HB HB HB HB
REQUIREMENTS.
A1 A1
landscape
BOTTOM OF STRUCTURE TO BE SPRAYED WITH
PACHECO KOCH
4
INTERIOR LATEX DRY-FOG TO MATCH P-5 7557 RAMBLER RD. #1400
DALLAS, TX 75234
5 HORIZONTAL WINDOW SHADES, REFER TO
SPECIFICATION. SEE ALTERNATES
972.235.3031
HB HB HB HB HB HB HB HB HB HB HB HB structural engineer
LIGHTS TO BE ON DIMMERS AND CONTROLS
6
SHOULD ALLOW FOR FULL DIMMING
G EJES INCORPORATED
12801 N. CENTRAL EXPY, SUITE 700
7 PROVIDE OVERHEAD COILING SECURITY DALLAS, TX 75243
GATE
214.3431210
8 PROVIDE INSULATION ABOVE THE
CEILING, REFER TO ALTERNATES
HB HB HB HB HB HB HB HB HB HB
security, audio/visual
NOVOM GROUP
400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
214-882-1540
H
HB HB HB HB HB
project
LIGHTING SCHEDULE DALLAS COUNTY ELECTIONS BUILDING
TYPE MANUFACTURER PRODUCT 1460 ROUND TABLE DR
HB DAY-BRITE FBY24L840-UNV DALLAS, TX 75247
A1 DAY-BRITE 2FGG42B835-A-D-UNV-DIM The drawings and written material herein constitute original work of the
B1 LIGHTOLIER 6RN / Z6RDL20835WOCDZ10U architect, and as intellectual property and instruments of service, are
HB HB HB HB HB
subject to copyright and may not be reproduced, distributed, published
D1 DAY-BRITE FSSEZ440L835-UNV
or used in any way without the express written consent of the architect.
C MERCURY LIGHTING MLS3-D1-48"-625-625-35K-HTA-1%-1C-U
original issue
E JUNO TRAC-MASTER ONE CIRCUIT TRAC SYSTEM - T SERIES
E ILLUMINATION RYLIE SERIES LED MEDIUM CYLINDER TRACK HEAD I DESIGN DEVELOPMENT 04.30.2021
F METALUX 4' LED LENSED FIXTURE revisions
G USAI LIGHTING BLSD5 PENDANT HB HB HB HB HB
J AXIS LIGHTING WALL WASH PERFEKT
K

HB HB HB HB HB

title

REFLECTED CEILING PLAN


4/30/2021 3:48:33 PM

project number 20182.200


REFLECTED CEILING PLAN -
date 04.30.2021

TRUE PLAN
01 LEVEL 1
SCALE: 1/16" = 1'-0" sheet

NORTH NORTH

A6.01
plotted:
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
REFLECTED CEILING PLAN KEY NOTES X

1 OPERABLE PARTITION WALL TRACK MEN'S RESTROOM


105
E
B1 B1 B1 B1
2 CEILING MOTORIZED SCREEN. COORDINATE HEIGHT 9'-0"
WITH TECHNOLOGY. OTS 4 P-5 B1 B1
ELEC
107

3 CEILING MOUNTED PROJECTOR. REFER TO MEP B1 B1 B1 B1

DRAWINGS FOR LOCATION AND ELECTRICAL E 9'-0"


REQUIREMENTS.
B1 B1

4 BOTTOM OF STRUCTURE TO BE SPRAYED WITH


E
INTERIOR LATEX DRY-FOG TO MATCH P-5

ALIGN
OTS IDF 4 B1 B1 B1 B1
5 HORIZONTAL WINDOW SHADES, REFER TO 108
9'-0"
SPECIFICATION. SEE ALTERNATES B1 B1

E
B1 P-5 B1 WOMEN'S RESTROOM B1 B1

6 LIGHTS TO BE ON DIMMERS AND CONTROLS 106

SHOULD ALLOW FOR FULL DIMMING architecture interiors planning graphics


9'-0"
7 PROVIDE OVERHEAD COILING SECURITY B1 B1 B1 B1 B1 B1 G G 8070 Park Lane, Ste. 300 Dallas, Texas 75231
GATE
F 5 Tel 972.701.9000 Fax 972.991.3008
8 PROVIDE INSULATION ABOVE THE
CEILING, REFER TO ALTERNATES B1 www.bokapowell.com
G G G G G
BREAKROOM
104

2'-0" 9'-6" 4'-0" 8'-6" 2'-8" 8'-6" 2'-8" 8'-6" These documents are issued for pricing only
and are not for regulatory approval,
B1
B1 B1 B1 B1
permitting or construction.
7
9'-0" 9'-0" Arch: Donald R. Powell, Jr. Reg. No.: 7206
Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
B1
B1 B1 B1 Arch: R. Andrew Bennett Reg. No.: 18129

P-4
B1

P-5 ACS-1 ACS-1 ACS-1


P-6 P-6 P-6
B1
client
B1 B1 B1 B1
DALLAS COUNTY
7'-0" 1460 ROUND TABLE DR
OTS 5 DALLAS, TX 75247
B1 6
G G G G 4 G 214-653-6437
G project manager
PRITCHARD ASSOCIATES
B1 G G G G G
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
214-849-0011
8'-0"

7" 7'-5 3/8"


B1 B1 B1 B1 B1 P-5 B1
project manager
9'-0" J JPC CONSULTING
B1 B1 B1 B1
MEN'S RESTROOM
123
2627 MARTIN LUTHER KING JR. BLVD.
B1
DALLAS, TX 75215
B1 B1 A1 A1 A1 A1
B1 P-5 B1 B1 214-941-4297
10'-0" ACT-1
9'-0" STORAGE

B1
103 m.e.p. engineer
B1
PURDY-MCGUIRE, INC.
B1 B1 A1 A1 A1 A1
B1 B1 B1 17300 N. DALLAS PARKWAY, SUITE 3000
WOMEN'S RESTROOM P-5 DALLAS, TX 75248
124
9'-0" A1 CORRIDOR
102
972-239-5357
B1 B1 B1 B1
TRAINING OFFICE A1 A1 A1 A1 A1
B1
B1
C C C C C C C C C
111a
C C civil
8
OTS OTS ACT-1 PACHECO KOCH
H C C C C C C C C 6 C A1 C C 7557 RAMBLER RD. #1400
ELEC IDF
122 121
E E E E
A1 A1 A1 A1 A1
DALLAS, TX 75234
B1 B1
4 4 C C C C C C C C ACT-1 C C C 972.235.3031
ACT-1 ACT-1 ACT-1
EARLY VOTING BOOTH
landscape
C C
E-BOOK LAB C C C
DS200 LAB C C C C C C
LAB
114 113
112 PACHECO KOCH
A1
CONFERENCE 10'-0" 10'-0" 10'-0" 10'-0" A1 A1 10'-0" A1 A1 A1
120
10'-0"
B1
C 6 C C C 6 C C C C C C
TRAINING OPEN
OFFICES C C
B1 7557 RAMBLER RD. #1400
OFFICE
6 111 ACT-1 DALLAS, TX 75234
119 8'-6" POLLING AREA

8 8 C C C C C C C C C C C C
101
972.235.3031
A1
A1 A1 A1 6 A1 A1
structural engineer
B1 B1

CORRIDOR
C C C C C C C C C C C C
EJES INCORPORATED
117
10'-0" 12801 N. CENTRAL EXPY, SUITE 700
C C C C C C C C C C C C
DALLAS, TX 75243
A1 A1 A1 A1
B1 B1
A1 A1 A1 A1 A1 214.3431210
ACT-1 10'-0" security, audio/visual
ACT-1 PRE-FUNCTION
110 NOVOM GROUP
A1 A1 A1 A1
B1
B1 B1 B1
7'-6" B1 B1 B1 B1 B1 B1 B1 B1 B1
B1 B1
A1 A1 A1 A1 A1 400 S. RECORD ST, SUITE 1200
P-6 P-6 7'-6"
DALLAS, TX 75202
I 214-882-1540
A1 A1 A1 project
A1 A1 A1 A1 A1
B1 B1
A1
A1 A1 5
DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
C C C C C C C C 2'-0" DALLAS, TX 75247
OPEN OFFICE P-5
118
A1 A1 A1 A1
The drawings and written material herein constitute original work of the
10'-0" B1
C C C C C C C C
B1 B1 B1
F F
B1 B1 B1
architect, and as intellectual property and instruments of service, are
A1 A1
9'-0" 25'-7 3/8" 9'-0" subject to copyright and may not be reproduced, distributed, published
1 2 P-5
2 6 or used in any way without the express written consent of the architect.
C C C C C C ACT-1 C C
7'-9" original issue
A1 A1 A1 A1 F F
TRAINING TRAINING
116 3 115 3 6 8'-0" DESIGN DEVELOPMENT 04.30.2021
B1
C C C C 9'-6" C C C C
B1 B1 B1 WAITING AREA 6 B1 B1 B1
100
10'-0" 10'-0"
A1 A1
revisions
ACT-1 ACT-1
STORAGE/RECEPTION F F
C C C C C C C C
109 8'-6" 5
01 / A6.21
A1 A1 A1 A1 8'-6"
B1 B1 B1 B1
C C C C C C C C
A1 A1

C C C C C C C C

A1 A1 A1 A1
B1 B1 B1 B1
C C C C C C C C A1
A1
5

title

ENLARGED REFLECTED
CEILING PLAN
4/30/2021 3:50:51 PM

11 10 9 8 7 6 5 4 3 2 1 project number 20182.200

date 04.30.2021
ENLARGED REFLECTED sheet

01 CEILING PLAN
A6.02
plotted:

SCALE: 1/8" = 1'-0"


TRUE PLAN
NORTH NORTH
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt

architecture interiors planning graphics


8070 Park Lane, Ste. 300 Dallas, Texas 75231
Tel 972.701.9000 Fax 972.991.3008
www.bokapowell.com

These documents are issued for pricing only


and are not for regulatory approval,
permitting or construction.

Arch: Donald R. Powell, Jr. Reg. No.: 7206


Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437

project manager
PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
214-849-0011

project manager
JPC CONSULTING
2627 MARTIN LUTHER KING JR. BLVD.
DALLAS, TX 75215
214-941-4297

m.e.p. engineer
PURDY-MCGUIRE, INC.
17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
972-239-5357

civil
PACHECO KOCH
7557 RAMBLER RD. #1400
DALLAS, TX 75234
972.235.3031
landscape
PACHECO KOCH
7557 RAMBLER RD. #1400
3 2 1 DALLAS, TX 75234
20'-0" 972.235.3031
2'-0 1/8" 4'-0"
CL
4'-0"
CL
4'-0"
CL
4'-0" 2'-0" structural engineer
CL
2'-0"
CL
2'-0"
CL
2'-0"
CL
2'-0"
CL B1 B1 B1
EJES INCORPORATED
12801 N. CENTRAL EXPY, SUITE 700
01 108'-0" DALLAS, TX 75243
A5.11
214.3431210
OTS
security, audio/visual

4'-0"
NOVOM GROUP
STORAGE
400 S. RECORD ST, SUITE 1200

7'-11 5/8"
127

DALLAS, TX 75202

CL
B1

E
4
E
214-882-1540
project
J DALLAS COUNTY ELECTIONS BUILDING

2'-0 3/8"

2'-0 3/8"
1460 ROUND TABLE DR

2'-9 1/8" 1'-4 1/8"

2'-9 1/8" 11 7/8"


DALLAS, TX 75247
111'-0" The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published

CL

CL
or used in any way without the express written consent of the architect.

2'-9"

2'-9"
original issue

11'-0 1/4"

11'-0CL1/4"
02
DESIGN DEVELOPMENT 04.30.2021

CL
A5.11
110'-0" revisions

2'-9"

2'-9"
16'-6 1/8"

CL

CL
2'-9 1/8"

2'-9 1/8"
5'-5 7/8"

5'-5 7/8"
5'-5 7/8" 12'-0 1/8" 2'-6" title
10'-0"
2'-0" 2'-0" 4'-0"
CL 4'-0" 4'-0" 4'-0"
CL 2'-0" 2'-0" 2'-0" 2'-0" 2'-0" 2'-0" 2'-0" 2'-0" 2'-0" 2'-0" 2'-0"
CL CL CL CL CL CL
CL
CL CL CL CL CL
CL
CL CL CL
ENLARGED REFLECTED
4'-0" 16'-0" 22'-0" CEILING PLANS - VESTIBULE
42'-0"
4/30/2021 3:51:21 PM

project number 20182.200

ENLARGED REFLECTED date 04.30.2021


CEILING PLAN - ENTRY sheet

01 CANOPY
A6.21
plotted:

SCALE: 1/4" = 1'-0"


TRUE PLAN
NORTH NORTH
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt GENERAL INTERIOR FINISH PLAN NOTES
THE FOLLOWING NOTES ARE GENERAL AND ARE APPLICABLE WHEREVER THE SUBJECT MATTER
OCCURS. REFERENCE THE GENERAL PROJECT NOTES ON i0 SHEET SERIES AND NUMBERED
NOTES ON THIS SHEET FOR ADDITIONAL DIRECTIONS WHICH ARE SPECIFIC TO PARTICULAR 16 15 13 14 12 11 10 9 8 7 6 5 4 3 2 1
LOCATIONS. LIMITS OF WORK WILL VARY BY DISCIPLINE. COORDINATE ALL DISCIPLINES FOR
LIMITS OF WORK.

1. NO SUBSTITUTIONS OR CHANGES TO FINISH MATERIALS ARE TO BE MADE WITHOUT PRIOR


WRITTEN APPROVAL OF ARCHITECT.

X
2. SUBMIT 12"x12" FINISH SAMPLES FOR APPROVAL FOR ALL PAINTED SURFACES AND STAIN
GRADE MATERIALS TO THE ARCHITECT. ALL OTHER SPECIFIED MATERIALS SHALL BE A

X
SUBMITTED AT AN APPROPRIATE SIZE TO VERIFY SPECIFICATION FOR APPROVAL PRIOR TO
MATERIAL ORDER.

X
3. ALL WORK SHALL CONFORM TO ALL APPLICABLE CODES, AGENCIES AND AUTHORITIES WITH
JURISDICTION. architecture interiors planning graphics

X
4. ALL PAINTED PARTITIONS SHALL RECEIVE PRIMER AND TWO COATS FINISH PAINT. CAULK B 8070 Park Lane, Ste. 300 Dallas, Texas 75231
ALL JOINTS PRIOR TO PAINTING.
MDF DMARC ELEC WATER FACILITIES OFFICE Tel 972.701.9000 Fax 972.991.3008
5. TOUCH UP OR REPAINT AFTER COMPLETION OF CONSTRUCTION OF SPACE TO A FINISH 156 157 158 159 160
ACCEPTABLE TO ARCHITECT. F SC-1 F SC-1 F SC-1 F SC-1 F SC-1 www.bokapowell.com
W P-2 W P-2 W P-2 W P-2 W P-2
6. IT IS THE INTENT OF THE DRAWINGS THAT ALL EXPOSED SURFACES SHALL RECEIVE B RB-1 B RB-1 B RB-1 B RB-1
B RB-1
FINISHES AS INDICATED UNLESS SPECIFICALLY NOTED OTHERWISE. ANY SURFACE WHICH
DO NOT HAVE A SPECIFIC SCHEDULED FINISH OR ARE NOT SCHEDULED TO REMAIN These documents are issued for pricing only
UNFINISHED, SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND FINISHED and are not for regulatory approval,
PER ARCHITECT'S DIRECTION. permitting or construction.

7. ALL TRANSITIONS OCCURING AT DOORS SHALL OCCUR AT THE CENTERLINE OF THE DOOR. Arch: Donald R. Powell, Jr. Reg. No.: 7206
C Arch: Chris W. Barnes Reg. No.: 10147
8. SCRIBE ALL FINISHED MILLWORK TO WALLS, PARTITIONS AND CEILINGS, PROVIDE SCRIBE Arch: John E. Orfield Reg. No.: 11164
MOULDING TO FINISH ALL MILLWORK TO WALLS, PARTITIONS AND CEILINGS. Arch: R. Andrew Bennett Reg. No.: 18129

9. REFER TO ELEVATIONS AND DETAILS FOR FINISHES NOT INDICATED ON FINISH PLAN.

10. ALIGN ALL WALL GROUT JOINTS WITH FLOOR GROUT JOINTS UNLESS NOTED OTHERWISE.
client
11. ALIGN FULL FLOOR TILES WITH NEW WALL PARTITIONS. REFER TO FINISH PLANS FOR TILE
START POINTS.
DALLAS COUNTY
1460 ROUND TABLE DR
12. ALL FINISH FLOOR MATERIAL TO STOP AT EDGE/TOE SPACE OF MILLWORK, CASEWORK. DALLAS, TX 75247
D 214-653-6437
13. TAPE AND BED ALL CORE WALLS THAT FACE TENANT IMPROVEMENT AREA, TYPICAL.

14. REFER TO i7 SHEET SERIES FOR FLOOR TRANSITION DETAILS. project manager
PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
DALLAS, TX 75201
214-849-0011
FINISH PLAN KEY NOTES X
project manager
1 1/8" ZINC STRIPS TO BE INSTALLED AT EVERY TERRAZZO TRANSITION JPC CONSULTING
E WAREHOUSE 2627 MARTIN LUTHER KING JR. BLVD.
2 ALL EXISITNG WALLS TO BE PAINTED P-1, SEE ALTERNATES 125 DALLAS, TX 75215
F SC-1 01 / A7.02 214-941-4297
3 FLOORING TO BE SEALED CONCRETE, SEE ALTERNATES W P-2 2
B RB-1 m.e.p. engineer
4 FLOORING TO TERRZZO, SEE ALTERNATES PURDY-MCGUIRE, INC.
17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
972-239-5357
LOADING DOCK OFFICE
F 180
civil
F SC-1 PACHECO KOCH
2 W P-2 7557 RAMBLER RD. #1400
B RB-1 DALLAS, TX 75234
972.235.3031
landscape
PACHECO KOCH
7557 RAMBLER RD. #1400
DALLAS, TX 75234
G 972.235.3031
structural engineer
EJES INCORPORATED
12801 N. CENTRAL EXPY, SUITE 700
DALLAS, TX 75243
214.3431210

COPIER
security, audio/visual
NOVOM GROUP
400 S. RECORD ST, SUITE 1200
H DALLAS, TX 75202
214-882-1540
project
DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
DALLAS, TX 75247
The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published
or used in any way without the express written consent of the architect.
I COPIER

original issue

DESIGN DEVELOPMENT 04.30.2021


revisions

X
title

OVERALL FINISH PLAN

01 OVERALL FINISH PLAN


SCALE: 1/16" = 1'-0"
4/30/2021 3:52:09 PM

TRUE PLAN project number 20182.200


NORTH NORTH
date 04.30.2021
sheet

A7.00
plotted:
MEN'S RESTROOM
105

ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt
F PT-1
FINISH PLAN KEY NOTES X 5 4 W CT-1/P-1
3 2 1
B PTB-1
1 1/8" ZINC STRIPS TO BE INSTALLED AT EVERY TERRAZZO TRANSITION
ELEC
107
2 ALL EXISITNG WALLS TO BE PAINTED P-1, SEE ALTERNATES
F SC-1
W P-1
3 FLOORING TO BE SEALED CONCRETE, SEE ALTERNATES B RB-1

FL-1
4 FLOORING TO TERRZZO, SEE ALTERNATES

CT-1
IDF
108
F SC-1
W P-1
B RB-1
architecture interiors planning graphics
WOMEN'S RESTROOM 8070 Park Lane, Ste. 300 Dallas, Texas 75231
106
F F PT-1 Tel 972.701.9000 Fax 972.991.3008
W CT-1/P-1
B PTB-1
www.bokapowell.com

These documents are issued for pricing only


and are not for regulatory approval,
permitting or construction.
01
Arch: Donald R. Powell, Jr. Reg. No.: 7206
Arch: Chris W. Barnes Reg. No.: 10147

FL-1
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

P-2
BREAKROOM
104
F TZ-1,2,3,4
W P-2,5 client
B RB-1 DALLAS COUNTY
04 1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437

G project manager
11 10 9 8 7 6 PRITCHARD ASSOCIATES
MEN'S RESTROOM 2121 NORTH AKARD ST, SUITE 100
123 DALLAS, TX 75201
F PT-1 214-849-0011
W CT-1/P-1
B PTB-1 WAREHOUSE project manager
125 JPC CONSULTING
F SC-1
2627 MARTIN LUTHER KING JR. BLVD.
W P-2 CORRIDOR
B RB-1 102
DALLAS, TX 75215
F TZ-1,4 STORAGE 214-941-4297
W P-2 103
B RB-1 F VCT-1 m.e.p. engineer
CT-1

W P-2 PURDY-MCGUIRE, INC.


B RB-1 17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248
WOMEN'S RESTROOM
124 972-239-5357
F PT-1 MB-1
W CT-1/P-1 civil

10'-0"
ELEC IDF
B PTB-1
122 121
PACHECO KOCH
H F SC-1 F SC-1
7557 RAMBLER RD. #1400
W P-1 W P-1 DALLAS, TX 75234
B RB-1 B RB-1 972.235.3031
landscape
OFFICE MB-1 E-BOOK LAB DS200 LAB EARLY VOTING BOOTH LAB TRAINING OPEN OFFICES
PACHECO KOCH
119 114 113 112 111 POLLING AREA 7557 RAMBLER RD. #1400
CONFERENCE
F SC-1 120 F LVT-1 F LVT-1 F LVT-1 F LVT-1 101 DALLAS, TX 75234
W P-1
F SC-1
W P-2 W P-2 W P-2 W P-2 F LVT-1,2 972.235.3031
B RB-2 CORRIDOR B RB-1 B RB-1 B RB-1 B RB-1 01 W P-2
W P-1 structural engineer
117 B RB-1
3 3 B RB-2 10'-0"
F TZ-1 EJES INCORPORATED
W P-2 12801 N. CENTRAL EXPY, SUITE 700
B RB-1 DALLAS, TX 75243
10'-0" 214.3431210
LVT-2
PRE-FUNCTION security, audio/visual
110 LVT-1
F TZ-1,3 NOVOM GROUP
TZ-1 W P-2 TZ-4 400 S. RECORD ST, SUITE 1200
TZ-3 01 04
B RB-1
ALIGN
DALLAS, TX 75202
214-882-1540
I 3 2'-0" project

10'-0"
LVT-1 2'-0" DALLAS COUNTY ELECTIONS BUILDING

FL-1
OPEN OFFICE
7'-0"

118 1460 ROUND TABLE DR


F SC-1 P-3 P-3 DALLAS, TX 75247
W P-1 The drawings and written material herein constitute original work of the
B RB-1 architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published
or used in any way without the express written consent of the architect.
TRAINING TRAINING WAITING AREA
116 115 TZ-1 original issue
100
F LVT-1,2 F LVT-1,2 01 DESIGN DEVELOPMENT 04.30.2021
MB-1

LVT-2 F TZ-1,2,3,4

MB-1
MB-1

W P-2,3/WC-1 W P-2,3/WC-1 W P-2


B RB-1 B RB-1 revisions
B RB-1
TZ-3

FL-1
04
STORAGE/RECEPTION
109 TZ-2
F CPT-1 STORAGE
W P-2 127
WC-1 WC-1 B RB-1 F VCT-1
7'-0"

W P-2
LVT-1 FL-1 FL-1 B RB-1
J
VESTIBULE
126 title
F WM-1
W - ENLARGED FINISH PLAN
B -
4/30/2021 3:49:39 PM

X
project number 20182.200

date 04.30.2021

ENLARGED FINISH PLAN - sheet

01 OFFICE SPACE
A7.02
plotted:

SCALE: 1/8" = 1'-0"


ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt

PAINT, P-3

7'-6"
CERAMIC TILE, CT-2
architecture interiors planning graphics
8070 Park Lane, Ste. 300 Dallas, Texas 75231
Tel 972.701.9000 Fax 972.991.3008
RUBBER BASE, RB-1
www.bokapowell.com
4 7/8" 9'-8"

These documents are issued for pricing only


ELEVATION - PRE-FUNCTION and are not for regulatory approval,
permitting or construction.

03b 173 - SOUTH


SCALE: 1/2" = 1'-0" Arch: Donald R. Powell, Jr. Reg. No.: 7206
Arch: Chris W. Barnes Reg. No.: 10147
Arch: John E. Orfield Reg. No.: 11164
Arch: R. Andrew Bennett Reg. No.: 18129

client
DALLAS COUNTY
1460 ROUND TABLE DR
DALLAS, TX 75247
214-653-6437
CERAMIC TILE, CT-2
project manager
PRITCHARD ASSOCIATES
2121 NORTH AKARD ST, SUITE 100
?, ? PAINT,
PAINT,
PAINT,P-3
P-3
P-3 DALLAS, TX 75201
7'-6"

214-849-0011

project manager
JPC CONSULTING
2627 MARTIN LUTHER KING JR. BLVD.
DALLAS, TX 75215
214-941-4297
RUBBER BASE, RB-1
4'-0 5/8" 4 7/8" m.e.p. engineer
PURDY-MCGUIRE, INC.
ELEVATION - PRE-FUNCTION 17300 N. DALLAS PARKWAY, SUITE 3000
DALLAS, TX 75248

03a 173 - SOUTH


SCALE: 1/2" = 1'-0"
972-239-5357

civil
PACHECO KOCH
7557 RAMBLER RD. #1400
PAINT, P-5 DALLAS, TX 75234
972.235.3031
landscape
PACHECO KOCH
SAFETY SAFETY 7557 RAMBLER RD. #1400
GLASS GLASS PAINT, P-2 DALLAS, TX 75234
972.235.3031
structural engineer
EJES INCORPORATED
SOLID SURFACE, SS-1 12801 N. CENTRAL EXPY, SUITE 700
8"

DALLAS, TX 75243
214.3431210
PLASTIC LAMINATE, PL-3
2'-10"

security, audio/visual
NOVOM GROUP
RUBBER BASE, RB-2 400 S. RECORD ST, SUITE 1200
DALLAS, TX 75202
1 1/2" 6'-1 1/2" 1'-6" 4'-6 7/8" 1'-6" 1 1/2"
214-882-1540
ELEVATION - RECEPTION 161 - project

02 EAST
SCALE: 1/2" = 1'-0"
DALLAS COUNTY ELECTIONS BUILDING
1460 ROUND TABLE DR
DALLAS, TX 75247
The drawings and written material herein constitute original work of the
architect, and as intellectual property and instruments of service, are
subject to copyright and may not be reproduced, distributed, published
or used in any way without the express written consent of the architect.
original issue

DESIGN DEVELOPMENT 04.30.2021


PAINT, P-5 revisions

SAFETY GLASS SAFETY GLASS

SOLID SURFACE, SS-1

PAINT, P-2 title

INTERIOR ELEVATIONS
3'-6"

2'-10"

RUBBER BASE, RB-1


4/30/2021 3:49:47 PM

1 1/2" 3'-10 1/2" 1 1/2" 5'-9" 1 1/2"


project number 20182.200

ELEVATION - WAITING AREA date 04.30.2021

01 171 - WEST sheet

A7.31
SCALE: 1/2" = 1'-0"
plotted:
ARCH_20182_DALLAS_COUNTY_ELECTIONS_detached.rvt

architecture interiors planning graphics

SOLID SURFACE, SS-3 8070 Park Lane, Ste. 300 Dallas, Texas 75231