Product description
Rectifier DPR 300B/600B
Our InD, OutD and HelpD series are designed to complement each
other. InD stands for indoor power systems, while OutD solutions
are created for demanding outdoor use. HelpD is our global support
team; its task is to make everything easy for you.
3791363100_00
www.deltapowersolutions.com Smarter. Greener. Together.
Table of contents
1 About the rectifier ............................................................................................... 2
2 Feature overview ................................................................................................ 3
3 Functional description ........................................................................................ 4
3.1 Input voltage range .................................................................................. 4
3.2 AC input.................................................................................................... 5
3.2.1 DPR 300B-48 ............................................................................. 5
3.2.2 DPR 600B-48 ............................................................................. 5
3.3 Output characteristics .............................................................................. 5
3.4 Output voltage .......................................................................................... 6
3.5 Output current .......................................................................................... 6
3.6 Over-voltage protection OVP ................................................................... 6
3.7 Load sharing............................................................................................. 6
3.8 Cooling ..................................................................................................... 7
3.9 Thermal management .............................................................................. 7
4 Mechanical description ....................................................................................... 8
4.1 Front panel ............................................................................................... 8
4.2 Rectifier installation .................................................................................. 8
4.3 Configuration ............................................................................................ 8
4.4 Rectifier status indicators ......................................................................... 9
The rectifiers do not contain any user serviceable parts. A faulty rectifier module must be
replaced as a complete unit.
Note! DPR 300B-48 and DPR 600B-48 are not intended to be used in mixed
systems. The two models do not work in parallel operation.
If the input voltage exceeds the nominal input voltage upper limit, the rectifier continues
operating without power factor correction (PFC). If the input voltage rises above the
maximum input voltage limit, the rectifier switches off.
The rectifier has protection against AC mains voltage in the range of 300 V to 320 V for
less than 30 seconds. The rectifier is not working but safe. Exposure to AC over-voltage
for greater voltages, or for a longer period may cause rectifier failure.
If the input voltage falls below the nominal input voltage lower limit, the rectifier continues
to operate with a lower output current. If the input voltage falls below the minimum input
voltage limit, the rectifier switches off.
The rectifier switches on when the input voltage is within the input voltage limits.
3.2 AC input
The rectifier has two inbuilt AC fuses in the Line and Neutral path.
Fuse rating: 8 A time lag T Littelfuse 215 series
The fuses are not field replaceable. The rectifier must be sent to repair in case an internal
fuse trips due to internal failure.
The rectifier has two inbuilt AC fuses in the Line and Neutral path.
Fuse rating: 8 A time lag T Littelfuse 215 series
The fuses are not field replaceable. The rectifier must be sent to repair in case an internal
fuse trips due to internal failure.
DPR 600B-48: The factory setting for the output current limit is 14 ADC.
Combining OVP with a current measuring condition allows selectivity for rectifiers
connected in parallel to ensure that only the affected rectifier is shut down.
Disconnecting the mains supply voltage for approximately 2 seconds resets the rectifier
after an OVP shutdown.
Thermal management protects the rectifier against overheating by reducing the output
current limit to limit internal temperature, as shown in Figure 5 and Figure 6.
To protect against interrupted air flow and fan failure, the rectifier is shut down as soon as
the internal temperature reaches a critical value. If the temperature returns to within
normal limits, the rectifier restarts automatically. If the airflow is interrupted or the fan fails,
the rectifier recognizes several unsuccessful restart attempts within a short period. In that
case the rectifier remains shut down and generates an alarm.
4.3 Configuration
On installation to a system with an ORION/PSC 3 controller, the rectifier is automatically
configured. In systems without a controller the rectifier operates with the factory-set
standard configuration.
LED “OK” blinks (200 ms on/200 ms off) and an alarm is given if:
LED “OK” flashes (20 ms on/1000 ms off) and an alarm is given if:
• The input voltage is out of range, but auxiliary supply is still working.
• The rectifier is not enabled.
• The rectifier is switched off and controlled by the ORION/PSC 3 controller.
3791134300_03
*3791134300*