You are on page 1of 3

Foundation Design Calculation

Calculations- ARU Techfor ARU Tech Structure


Structure

Jacobs Project Code. & No. : Linde Project Code & No. : Doc. No: &AG-C-CS 0301.001
DHT Project / 44LK-5100 Mahul 2 / K-02-2310A051 Issue : 03

"PRIMARY LOAD CASES"


Load Case
No. Abbreviation Load Title Explanation
1001 SW OF STRUCTURE Self weight of structure
1002 DEAD LOAD OF SECONDARY BEAMS Dead load of secondary beams, not modeled in STAAD
1003 DEAD LOAD OF GRATING ON FLOORS Dead load due to grating on floors
1004 DEAD LOAD OF SECONDARY ITEMS Dead load due to secondary items such as hand rail, stair case, ladder which are not modeled in STAAD
1005 DEAD LOAD OF FIRE PROOFING Only If required
1 DL DEAD LOAD [TOTAL] 1001+1002+1003+1004+1005
2001 LIVE LOAD ON MAIN FLOORS
2002 LIVE LOAD ON SECONDARY PLATFORMS
2 LL LIVE LOAD [TOTAL] 2001+2002
3001 EMPTY WEIGHT OF PIPING (UDL)
3002 EMPTY WEIGHT OF PIPING (CONCENTRATED)
3003 EMPTY WEIGHT OF EQUIPMENT
3 DLempty EMPTY WEIGHT OF PIPING/EQUIPMENT [TOTAL] 3001+3002+3003
4001 OPERATING WEIGHT OF PIPING (UDL)
4002 OPERATING WEIGHT OF PIPING (CONCENTRATED)
4003 OPERATING WEIGHT OF EQUIPMEMNT
4004 CABLE TRAY LOADS Loads of Cable Tray
4 DLOP OPERATING WEIGHT OF PIPING/EQUIPMENT [TOTAL] 4001+4002+4003+4004
5001 HYTROTEST WEIGHT OF PIPING (UDL)
5002 HYDROTEST WEIGHT OF PIPING (CONCENTRATED)
5003 HYDROTEST WEIGHT OF EQUIPMEMNT
5004 CABLE TRAY LOADS Loads of Cable Tray
5 DLTest HYDROTEST WEIGHT OF PIPING/EQUIPMENT [TOTAL] 5001+5002+5003+5004
6001 WIND LOAD ON STRUCTURE DUE TO SELF OBSTRUCTION IN N-S DIRECTION Wind load on structure due to self obstruction and is applied as a nodal force
6002 WIND LOAD ON PIPING IN N-S DIRECTION Consider the band width or actual pipe dia (as applicable)
6003 WIND LOAD ON EQUIPMENT IN N-S DIRECTION This load includes the push/pull force or moment due to wind
6004 WIND LOAD ON CABLE TRAY Loads of Cable Tray
6 WLN WIND IN N-S DIRECTION [WLN: N-->S] 6001+6002+6003+6004+6005
7001 WIND LOAD ON STRUCTURE DUE TO SELF OBSTRUCTION IN E-W DIRECTION Wind load on structure due to self obstruction and is applied as a nodal force
7002 WIND LOAD ON PIPING IN E-W DIRECTION Consider the band width or actual pipe dia (as applicable)
7003 WIND LOAD ON EQUIPMENT IN E-W DIRECTION This load includes the push/pull force or moment due to wind
7004 WIND LOAD ON CABLE TRAY Loads of Cable Tray
7 WLE WIND LOAD IN E-W DIRECTION [WLE: E-->W] 7001+7002+7003+7004+7005
8001 SEISMIC LOAD ON STRUCTURE & PIPING IN OPER. CONDN N-S DIRECTION
8002 SEISMIC LOAD ON EQUIPMENT IN OPER. CONDN N-S DIRECTION This load includes the push/pull force or moment due to seismic
8 EQN SEISMIC LOAD IN N-S DIRECTION [EQN: N-->S] 8001+8002
9001 SEISMIC LOAD ON STRUCTURE & PIPING IN OPER. CONDN E-W DIRECTION
9002 SEISMIC LOAD ON EQUIPMENT IN OPER. CONDN E-W DIRECTION This load includes the push/pull force or moment due to seismic
9 EQE SEISMIC LOAD IN E-W DIRECTION [EQE: E-->W] 9001+9002
10 TLN PIPE THERMAL LOAD IN N-S DIRECTION (FDN/GLOBAL DESIGN) This load include the piping thermal force during operating condition
11 TLE PIPE THERMAL LOAD IN E-W DIRECTION (FDN/GLOBAL DESIGN) This load include the piping thermal force during operating condition
12 TFN PIPE/EQUIPMENT FRICTION LOAD IN N-S DIRECTION (GLOBAL DESIGN) Friction Load of UDL & Cocentrated Load of Pipings (NSP supports, if required)
13 TFE PIPE/EQUIPMENT FRICTION LOAD IN E-W DIRECTION (GLOBAL DESIGN) Friction Load of UDL & Cocentrated Load of Pipings (NSP supports, if required)
1401 VLPR MIN. LOAD ON PIPE RACK LONG.BEAM / LOCAL MAINTAINANCE LOAD/CONTINGENCY LOAD Min Vertical load at Mid Span of Longitudinal Beams Of Pipe Rack & Lifting Load for Local design
1402 VLNSP LOAD OF MISC. PIPE SUPPORTS Vertical loads for pin, hangers, L shape, post type pipe supports
14 VL TOTAL VERTICAL LOAD (LOCAL DESIGN) 1401+1402
15 ML MAINTENANCE LOAD( BUNDLE PULL ) (FDN/GLOBAL DESIGN) Apply the horizontal force on fixed side saddle
16 WLPN LOCAL WIND LOAD ON PIPING IN N-S DIRECTION (LOCAL DESIGN) Wind Load on Pipe to be considered in Local Design (as given by piping)
17 WLPE LOCAL WIND LOAD ON PIPING IN E-W DIRECTION (LOCAL DESIGN) Wind Load on Pipe to be considered in Local Design (as given by piping)
18 EQPN LOCAL SEISMIC LOAD ON PIPING IN N-S DIRECTION (LOCAL DESIGN) Seismic Load on Pipe to be considered in Local Design (as given by piping)
19 EQPE LOCAL SEISMIC LOAD ON PIPING IN E-W DIRECTION (LOCAL DESIGN) Seismic Load on Pipe to be considered in Local Design (as given by piping)
20 TLLOCALN LOCAL PIPING LOAD IN N-S DIRECTION (LOCAL DESIGN) Anchor Forces to be considered Locally in design (as given by piping)
21 TLLOCALE LOCAL PIPING LOAD IN E-W DIRECTION (LOCAL DESIGN) Anchor Forces to be considered Locally in design (as given by piping)
22 PSV PSV LOADS (HORIZONTAL LOADS) (LOCAL DESIGN) Horizontal Loads of PSV
50 Rv RESERVE LOAD- VERTICAL DIRECTION Additional assumed loads for uncertainity in piping loads
51 RHN RESERVE LOAD- HORIZONTAL IN N-S DIRECTION Additional assumed loads for uncertainity in piping loads
52 RHE RESERVE LOAD- HORIZONTAL IN E-W DIRECTION Additional assumed loads for uncertainity in piping loads

Page 32 of 747
Client Foundation Design Calculation for ARU Tech Structure Calc. No. : .
Static Calculations- ARU Tech Structure
Project Rev. :0 .
Jacobs Project Code. & No. : Linde Project Code & No. : Doc. No: &AG-C-CS 0301.001
Proj. No. DHT Project / 44LK-5100 Mahul 2 / K-02-2310A051 Issue : 03Page______of__________ .

"LOAD COMBINATIONS FOR LIMIT STATE DESIGN" -


Load Sr. Load 1 2 3 4 5 14 6 16 7 17 8 18 9 19 10 11 20 21 12 13 15 22 50 51 52 Remarks
Conditions No. Comb DL LL DLempty DLop DLTest VL WLN WLPN WLE WLPE EQN EQPN EQE EQPE TL N TL E TL LOCALN TL LOCALE TFN TFE ML PSV RV RHN RHE
1 301 1.50 1.50 - 1.50 - - - - - - - - - - 1.50 1.50 - - 1.50 1.50 - - 1.50 1.50 1.50
OP. + LL

2 302 1.50 1.50 - 1.50 - - - - - - - - - - -1.50 -1.50 - - -1.50 -1.50 - - 1.50 -1.50 -1.50
For Global Design
3 303 1.50 1.50 - 1.50 - - - - - - - - - - -1.50 1.50 - - -1.50 1.50 - - 1.50 -1.50 1.50
4 304 1.50 1.50 - 1.50 - - - - - - - - - - 1.50 -1.50 - - 1.50 -1.50 - - 1.50 1.50 -1.50
5 305 1.20 1.20 - 1.20 - - 1.20 - - - - - - - 1.20 1.20 - - - - - - 1.20 1.20 1.20
OP+WL+L

6 306 1.20 1.20 - 1.20 - - - - 1.20 - - - - - 1.20 1.20 - - - - - - 1.20 1.20 1.20
For Global Design
L

7 307 1.20 1.20 - 1.20 - - -1.20 - - - - - - - -1.20 -1.20 - - - - - - 1.20 -1.20 -1.20
8 308 1.20 1.20 - 1.20 - - - - -1.20 - - - - - -1.20 -1.20 - - - - - - 1.20 -1.20 -1.20
9 309 1.50 - - 1.50 - - 1.50 - - - - - - - 1.50 1.50 - - - - - - 1.50 1.50 1.50
OP + WL

10 310 1.50 - - 1.50 - - - - 1.50 - - - - - 1.50 1.50 - - - - - - 1.50 1.50 1.50


For Global Design
11 311 1.50 - - 1.50 - - -1.50 - - - - - - - -1.50 -1.50 - - - - - - 1.50 -1.50 -1.50
12 312 1.50 - - 1.50 - - - - -1.50 - - - - - -1.50 -1.50 - - - - - - 1.50 -1.50 -1.50
13 313 1.50 - - 1.50 - - 1.50 - - - - - - - 1.50 1.50 - - - - - - - - -
OP + WL

Reserve

14 314 1.50 - - 1.50 - - - - 1.50 - - - - - 1.50 1.50 - - - - - - - - -


load
w/o

For Global Design


15 315 1.50 - - 1.50 - - -1.50 - - - - - - - -1.50 -1.50 - - - - - - - - -
16 316 1.50 - - 1.50 - - - - -1.50 - - - - - -1.50 -1.50 - - - - - - - - -
17 317 1.20 1.20 - 1.20 - - - - - - 1.20 - - - 1.20 1.20 - - - - - - 1.20 1.20 1.20
OP+LL+E

18 318 1.20 1.20 - 1.20 - - - - - - - - 1.20 - 1.20 1.20 - - - - - - 1.20 1.20 1.20
For Global Design
Q

19 319 1.20 1.20 - 1.20 - - - - - - -1.20 - - - -1.20 -1.20 - - - - - - 1.20 -1.20 -1.20
20 320 1.20 1.20 - 1.20 - - - - - - - - -1.20 - -1.20 -1.20 - - - - - - 1.20 -1.20 -1.20
21 321 1.50 - - 1.50 - - - 1.50 - - 1.50 1.50 - - - - - - 1.50 1.50 1.50
OP + EQ

22 322 1.50 - - 1.50 - - - - 1.50 - 1.50 1.50 - - - - - - 1.50 1.50 1.50


For Global Design
23 323 1.50 - - 1.50 - - - -1.50 - - -1.50 -1.50 - - - - - - 1.50 -1.50 -1.50
24 324 1.50 - - 1.50 - - - - -1.50 - -1.50 -1.50 - - - - - - 1.50 -1.50 -1.50
25 325 1.50 - - 1.50 - - - 1.50 - - 1.50 1.50 - - - - - - - - -
OP + EQ

Reserve

26 326 1.50 - - 1.50 - - - - 1.50 - 1.50 1.50 - - - - - - - - -


load
w/o

For Global Design


27 327 1.50 - - 1.50 - - - -1.50 - - -1.50 -1.50 - - - - - - - - -
28 328 1.50 - - 1.50 - - - - -1.50 - -1.50 -1.50 - - - - - - - - -
29 329 0.90 - 0.90 - - - 1.50 - - - - - - - - - - - - - - - - - -
Empty +

30 330 0.90 - 0.90 - - - - - 1.50 - - - - - - - - - - - - - - - -


WL

For Global Design


31 331 0.90 - 0.90 - - - -1.50 - - - - - - - - - - - - - - - - - -
32 332 0.90 - 0.90 - - - - - -1.50 - - - - - - - - - - - - - - - -
TEST + LL 33 333 1.50 1.50 - - 1.50 - - - - - - - - - - - - - For Global Design
34 334 1.20 1.20 - - 1.20 - 0.30 - - - - - - - - - - - - - - - - - -
25%WL
TEST +

35 335 1.20 1.20 - - 1.20 - - - 0.30 - - - - - - - - - - - - - - - -


LL+

For Global Design


36 336 1.20 1.20 - - 1.20 - -0.30 - - - - - - - - - - - - - - - - - -
37 337 1.20 1.20 - - 1.20 - - - -0.30 - - - - - - - - - - - - - - - -
ML+LL 38 338 1.50 1.50 1.50 - - - - - - - - - - - 1.50 - - - For Global Design
39 401 1.50 1.50 - 1.50 - 1.50 - - - - - - - - 1.50 1.50 1.50 1.50 1.50 1.50 - - 1.50 1.50 1.50
OP. + LL

40 402 1.50 1.50 - 1.50 - 1.50 - - - - - - - - -1.50 -1.50 -1.50 -1.50 -1.50 -1.50 - - 1.50 -1.50 -1.50
For Local Design
41 403 1.50 1.50 - 1.50 - 1.50 - - - - - - - - -1.50 1.50 -1.50 1.50 -1.50 1.50 - - 1.50 -1.50 1.50
42 404 1.50 1.50 - 1.50 - 1.50 - - - - - - - - 1.50 -1.50 1.50 -1.50 1.50 -1.50 - - 1.50 1.50 -1.50
43 405 1.20 1.20 - 1.20 - 1.20 1.20 1.20 - - - - - - 1.20 1.20 1.20 1.20 - - - - 1.20 1.20 1.20
OP+WL+L

44 406 1.20 1.20 - 1.20 - 1.20 - - 1.20 1.20 - - - - 1.20 1.20 1.20 1.20 - - - - 1.20 1.20 1.20
For Local Design
L

45 407 1.20 1.20 - 1.20 - 1.20 -1.20 -1.20 - - - - - - -1.20 -1.20 -1.20 -1.20 - - - - 1.20 -1.20 -1.20
46 408 1.20 1.20 - 1.20 - 1.20 - - -1.20 -1.20 - - - - -1.20 -1.20 -1.20 -1.20 - - - - 1.20 -1.20 -1.20
47 409 1.50 - - 1.50 - 1.50 1.50 1.50 - - - - - - 1.50 1.50 1.50 1.50 - - - - 1.50 1.50 1.50
OP. + WL

48 410 1.50 - - 1.50 - 1.50 - - 1.50 1.50 - - - - 1.50 1.50 1.50 1.50 - - - - 1.50 1.50 1.50
For Local Design
49 411 1.50 - - 1.50 - 1.50 -1.50 -1.50 - - - - - - -1.50 -1.50 -1.50 -1.50 - - - - 1.50 -1.50 -1.50
50 412 1.50 - - 1.50 - 1.50 - - -1.50 -1.50 - - - - -1.50 -1.50 -1.50 -1.50 - - - - 1.50 -1.50 -1.50
51 413 1.20 1.20 - 1.20 - 1.20 - - - - 1.20 1.20 - - 1.20 1.20 1.20 1.20 - - - - 1.20 1.20 1.20
OP+EQ+L

52 414 1.20 1.20 - 1.20 - 1.20 - - - 1.20 - - 1.20 1.20 1.20 1.20 1.20 1.20 - - - - 1.20 1.20 1.20
For Local Design
L

53 415 1.20 1.20 - 1.20 - 1.20 - - - - -1.20 -1.20 - - -1.20 -1.20 -1.20 -1.20 - - - - 1.20 -1.20 -1.20
54 416 1.20 1.20 - 1.20 - 1.20 - - - -1.20 - - -1.20 -1.20 -1.20 -1.20 -1.20 -1.20 - - - - 1.20 -1.20 -1.20
55 417 1.50 - - 1.50 - 1.50 - 1.50 1.50 - - 1.50 1.50 1.50 1.50 - - - - 1.50 1.50 1.50
OP + EQ

56 418 1.50 - - 1.50 - 1.50 - - 1.50 1.50 1.50 1.50 1.50 1.50 - - - - 1.50 1.50 1.50
For Local Design
57 419 1.50 - - 1.50 - 1.50 - -1.50 -1.50 - - -1.50 -1.50 -1.50 -1.50 - - - - 1.50 -1.50 -1.50
58 420 1.50 - - 1.50 - 1.50 - - -1.50 -1.50 -1.50 -1.50 -1.50 -1.50 - - - - 1.50 -1.50 -1.50
59 421 1.50 - - 1.50 - 1.50 - - - - - - - - 1.50 1.50 1.50 1.50 - - - 1.50 1.50 1.50 1.50
OP. + PSV

60 422 1.50 - - 1.50 - 1.50 - - - - - - - - -1.50 -1.50 -1.50 -1.50 - - - 1.50 1.50 -1.50 -1.50
For Local Design
61 423 1.50 - - 1.50 - 1.50 - - - - - - - - 1.50 -1.50 1.50 -1.50 - - - 1.50 1.50 1.50 -1.50
62 424 1.50 - - 1.50 - 1.50 - - - - - - - - -1.50 1.50 -1.50 1.50 - - - 1.50 1.50 -1.50 1.50
63 425 1.50 1.50 - 1.50 - 1.50 - - - - - - - - 1.50 1.50 1.50 1.50 - - - 1.50 1.50 1.50 1.50
OP. + LL +

64 426 1.50 1.50 - 1.50 - 1.50 - - - - - - - - -1.50 -1.50 -1.50 -1.50 - - - 1.50 1.50 -1.50 -1.50
PSV

For Local Design


65 427 1.50 1.50 - 1.50 - 1.50 - - - - - - - - 1.50 -1.50 1.50 -1.50 - - - 1.50 1.50 1.50 -1.50
66 428 1.50 1.50 - 1.50 - 1.50 - - - - - - - - -1.50 1.50 -1.50 1.50 - - - 1.50 1.50 -1.50 1.50

Page 33 of 747
Client Foundation Design
Static Calculation
Calculations forTech
- ARU ARUStructure
Tech Structure Calc. No. : .

Project Rev. :0 .
Jacobs Project Code. & No. : Linde Project Code & No. : Doc. No: &AG-C-CS 0301.001
DHT Project / 44LK-5100 Mahul 2 / K-02-2310A051 Issue : 03
Proj. No. Page______of__________ .

"LOAD COMBINATIONS FOR SERVICEABILITY"


Load Sr. Load 1 2 3 4 5 14 6 16 7 17 8 18 9 19 10 11 20 21 12 13 15 22 50 51 52 Remarks
Conditions No. Comb DL LL DLempty DLop DLTest VL WLN WLPN WLE WLPE EQN EQPN EQE EQPE TL N TL E TL LOCALN TL LOCALE TFN TFE ML PSV RV RHN RHE
1 601 1.00 1.00 - 1.00 - - - - - - - - - - 1.00 1.00 - - 1.00 1.00 - - 1.00 1.00 1.00
OP. + LL

2 602 1.00 1.00 - 1.00 - - - - - - - - - - -1.00 -1.00 - - -1.00 -1.00 - - 1.00 -1.00 -1.00
For Global Design
3 603 1.00 1.00 - 1.00 - - - - - - - - - - -1.00 1.00 - - -1.00 1.00 - - 1.00 -1.00 1.00
4 604 1.00 1.00 - 1.00 - - - - - - - - - - 1.00 -1.00 - - 1.00 -1.00 - - 1.00 1.00 -1.00
5 605 1.00 0.80 - 1.00 - - 0.80 - - - - - - - 1.00 1.00 - - - - - - 1.00 1.00 1.00
OP+WL+L

6 606 1.00 0.80 - 1.00 - - - - 0.80 - - - - - 1.00 1.00 - - - - - - 1.00 1.00 1.00
For Global Design
L

7 607 1.00 0.80 - 1.00 - - -0.80 - - - - - - - -1.00 -1.00 - - - - - - 1.00 -1.00 -1.00
8 608 1.00 0.80 - 1.00 - - - - -0.80 - - - - - -1.00 -1.00 - - - - - - 1.00 -1.00 -1.00
9 609 1.00 - - 1.00 - - 1.00 - - - - - - - 1.00 1.00 - - - - - - 1.00 1.00 1.00
OP + WL

10 610 1.00 - - 1.00 - - - - 1.00 - - - - - 1.00 1.00 - - - - - - 1.00 1.00 1.00


For Global Design
11 611 1.00 - - 1.00 - - -1.00 - - - - - - - -1.00 -1.00 - - - - - - 1.00 -1.00 -1.00
12 612 1.00 - - 1.00 - - - - -1.00 - - - - - -1.00 -1.00 - - - - - - 1.00 -1.00 -1.00
13 613 1.00 - - 1.00 - - 1.00 - - - - - - - 1.00 1.00 - - - - - - - - -
OP + WL

Reserve

14 614 1.00 - - 1.00 - - - - 1.00 - - - - - 1.00 1.00 - - - - - - - - -


load
w/o

For Global Design


15 615 1.00 - - 1.00 - - -1.00 - - - - - - - -1.00 -1.00 - - - - - - - - -
16 616 1.00 - - 1.00 - - - - -1.00 - - - - - -1.00 -1.00 - - - - - - - - -
17 617 1.00 0.80 - 1.00 - - - - - - 0.80 - - - 1.00 1.00 - - - - - - 1.00 1.00 1.00
OP+LL+E

18 618 1.00 0.80 - 1.00 - - - - - - - - 0.80 - 1.00 1.00 - - - - - - 1.00 1.00 1.00
For Global Design
Q

19 619 1.00 0.80 - 1.00 - - - - - - -0.80 - - - -1.00 -1.00 - - - - - - 1.00 -1.00 -1.00
20 620 1.00 0.80 - 1.00 - - - - - - - - -0.80 - -1.00 -1.00 - - - - - - 1.00 -1.00 -1.00
21 621 1.00 - - 1.00 - - - 1.00 - - 1.00 1.00 - - - - - - 1.00 1.00 1.00
OP + EQ

22 622 1.00 - - 1.00 - - - - 1.00 - 1.00 1.00 - - - - - - 1.00 1.00 1.00


For Global Design
23 623 1.00 - - 1.00 - - - -1.00 - - -1.00 -1.00 - - - - - - 1.00 -1.00 -1.00
24 624 1.00 - - 1.00 - - - - -1.00 - -1.00 -1.00 - - - - - - 1.00 -1.00 -1.00
25 625 1.00 - - 1.00 - - - 1.00 - - 1.00 1.00 - - - - - - - - -
OP + EQ

Reserve

26 626 1.00 - - 1.00 - - - - 1.00 - 1.00 1.00 - - - - - - - - -


load
w/o

For Global Design


27 627 1.00 - - 1.00 - - - -1.00 - - -1.00 -1.00 - - - - - - - - -
28 628 1.00 - - 1.00 - - - - -1.00 - -1.00 -1.00 - - - - - - - - -
29 629 1.00 - 1.00 - - - 1.00 - - - - - - - - - - - - - - - - - -
Empty +

30 630 1.00 - 1.00 - - - - - 1.00 - - - - - - - - - - - - - - - -


WL

For Global Design


31 631 1.00 - 1.00 - - - -1.00 - - - - - - - - - - - - - - - - - -
32 632 1.00 - 1.00 - - - - - -1.00 - - - - - - - - - - - - - - - -
TEST + LL 33 633 1.00 1.00 - - 1.00 - - - - - - - - - - - - - For Global Design
34 634 1.00 0.80 - - 1.00 - 0.20 - - - - - - - - - - - - - - - - - -
25%WL
TEST +

35 635 1.00 0.80 - - 1.00 - - - 0.20 - - - - - - - - - - - - - - - -


LL+

For Global Design


36 636 1.00 0.80 - - 1.00 - -0.20 - - - - - - - - - - - - - - - - - -
37 637 1.00 0.80 - - 1.00 - - - -0.20 - - - - - - - - - - - - - - - -
ML+LL 38 638 1.00 1.00 1.00 - - - - - - - - - - - 1.00 - - - For Global Design
39 701 1.00 1.00 - 1.00 - 1.00 - - - - - - - - 1.00 1.00 1.00 1.00 1.00 1.00 - - 1.00 1.00 1.00
OP. + LL

40 702 1.00 1.00 - 1.00 - 1.00 - - - - - - - - -1.00 -1.00 -1.00 -1.00 -1.00 -1.00 - - 1.00 -1.00 -1.00
For Local Design
41 703 1.00 1.00 - 1.00 - 1.00 - - - - - - - - -1.00 1.00 -1.00 1.00 -1.00 1.00 - - 1.00 -1.00 1.00
42 704 1.00 1.00 - 1.00 - 1.00 - - - - - - - - 1.00 -1.00 1.00 -1.00 1.00 -1.00 - - 1.00 1.00 -1.00

Page 34 of 747

You might also like