- WORKING TENSION AT 27°C WITHOUT WIND PER CONDUCTOR / EDT (kg) 2650
- WORKING TENSION AT 10°C WITH MAX WIND PER CONDUCTOR / MWT (kg) 5550
III. INSULATOR
- TYPE 4XU160BLP
- NUMBER OF DISC 4X27
-ELECTRO- MECHANICAL STRENGHT (KN) 4X160
-MINIMUM CREEPAGE DISTANCE (mm) 525
IV. EARTHWIRES
A. OPTIC WIRE
- TYPE OPGW 100
- NUMBER 2
- WORKING TENSION AT 27°C WITHOUT WIND PER WIRE / EDT (kg) 1399
- WORKING TENSION AT 10°C WITH MAX WIND PER WIRE /MWT (kg) 2956
B. STEEL WIRE
- TYPE -
- NUMBER -
- WORKING TENSION AT 10°C WITH MAX WIND PER WIRE /MWT (kg) -
IV. DESIGN SPAN & SAG
A. BASIC SPAN (m) 450
B1. SAG ON BASIC SPAN (CONDUCTOR)
- SAG AT 27°C WITHOUT WIND (m) 15.391
- SAG AT 80°C WITHOUT WIND (m) 17.592
B2. SAG ON BASIC SPAN (STEEL WIRE)
- SAG AT 27°C WITHOUT WIND (m) -
- SAG AT 50°C WITHOUT WIND (m) -
B3. SAG ON BASIC SPAN (OPTIC WIRE)
- SAG AT 27°C WITHOUT WIND (m) 12.429
- SAG AT 10°C WITH WIND (m) 14.547
C. LOADING SPAN
1. NORMAL CONDITION
1.1 WEIGHT SPAN (m)
1.1.1 MAXIMUM
- SUSPENSION TOWER 1350
- TENSION & DEAD END TOWER 1350
1.1.2 MINIMUM
- SUSPENSION TOWER 0
- TENSION & DEAD END TOWER 0
1.1.3 UPLIFT
- SUSPENSION TOWER 0
- TENSION & DEAD END TOWER -900
1.2 WIND SPAN (m) 495
2. BROKEN WIRE CONDITION
2.1 WEIGHT SPAN (m)
2.1.1 MAXIMUM
- SUSPENSION TOWER 1350
- TENSION & DEAD END TOWER 1350
2.1.2 MINIMUM
- SUSPENSION TOWER 0
- TENSION & DEAD END TOWER 0
2.1.3 UPLIFT
- SUSPENSION TOWER -
- TENSION & DEAD END TOWER -
2.2 WIND SPAN (m) 297
V. OVERLOAD FACTORS
1. NORMAL CONDITION 1.2
2. BROKEN WIRE CONDITION 1.2
VI. UNFACTORED DESIGN LOADS
A. TOWER STRUCTURE
1. ULTIMATE WIND PRESSURES
- CONDUCTOR & GROUNDWIRE (N/m2) 1060
- INSULATOR (N/m2) 1430
- TOWER (N/m2) 2350
2. UNBALANCED LONGITUDINAL LOADS / CONDUCTOR
2.1 BROKEN WIRES
2.1.1 SUSPENSION TOWER : ONE PHASE BROKEN
- CONDUCTOR (kN) 122.1
- EARTHWIRE (kN) 22