Outdoor Air Supply Comparison Local Thai Regulations vs ASHRAE

Dimension (m.)
Ambient Room Area
AREA Temp Temp Sq.m.

°C °C L W H

ASRS Cold Store 40 -25 78.0 30.2 22.7 2,332.4

Ante Room (4Ea x 5.8 sq.m.) 40 -10 23.2

Pallet Transferring & Staging 40 0-4 1,208.0


Area

Loading Docks 40 6-8 34.0


(4ea x 8.5 Sq.m.)

ESTIMATED INVESTMENT COST

ESTIMATED OPERATING COST


Ventilation System Requirements per Governing Thai RegulationsMinisterial Regulations No. 39/BC2537 (Building code)

Applied Rate Required Outdoor Equivalent


Air Flow
Description
of Reference Cooling Caapcity(kWR)
CFM/ CMH/ CFM CMH
Sq.m. Sq.m.
Outdoor air supply for 1.18 2.00 2,745.70 4,664.80 167.40
air-conditioned area (ref.
factory function)
N/A 1.77 3.00 40.97 69.60 2.25

Outdoor air supply for 2.35 4.00 2,844.12 4,832.00 134.20


air-conditioned area (ref.
factory function)
N/A 2.94 5.00 100.06 170.00 4.16

Total 5,730.85 9,736.40 301.6

104
Not Practical to Implement N/A

Use assumption 0.5 kWe per 1 kWr 2,531,088.00 THB/Yr


and consider only outdoor air supply to Cold Store only
Electrical Energy Cost Per Year =
Annual Energy Cost = (kWr*0.5*24*30*12) kWh x 3.5 THB
่ ือ มาตรฐานวิธีการตรวจสอบโรงงาน ห ้องเย็น(ประเภท หรื อชนิ ดโรงงานลำดับที่ 92)
คูม

Assumed Applied Rate Required Outdoor


Air Flow
Description
of Reference No. of CMM/ CFM/ CMH/ CMM CFM CMH
Persons Person Person Person
Outdoor air supply for 5.00 0.50 17.66 30.00 2.50 88.29 150.00
Cold room

Outdoor air supply for - 0.50 17.66 30.00 - - -


Cold room

Outdoor air supply for 15.00 0.50 17.66 30.00 7.50 264.86 450.00
Cold room

Outdoor air supply for - 0.50 17.66 30.00 - - -


Cold room

Total 10 353.147 600

Use assumption 0.5 kWe per 1 kWr and consider only outdoor air supply to Cold Store only
Electrical Energy Cost Per Year =
Annual Energy Cost = (kWr*0.5*24*30*12) kWh x 3.5 THB
ดับที่ 92) Ventilation System Requirements per ASH

People Outdoor Air Rate


Equivalent Assumed Applied Rate Required Outdoor
Air Flow
Description
Cooling Caapcity(kWR) of Reference No. of CFM/ CMH/ CFM CMH
Persons Person Person
5.67 Freezer or refrigerated 5.00 10.00 16.99 50.00 84.95
area temp < 50°F
(+10°C)
- Freezer or refrigerated - 10.00 16.99 - -
area temp < 50°F
(+10°C)
12.50 Freezer or refrigerated 15.00 10.00 16.99 150.00 254.85
area temp < 50°F
(+10°C)
- Freezer or refrigerated - 10.00 16.99 - -
area temp < 50°F
(+10°C)
18.2 Total 200 339.8

T.B.C.

85,730.40 THB/Yr Use assumption 0.5 kWe per 1 kWr

Ann
on System Requirements per ASHRAE 62.1-2007

Area Outdoor Air Rate Total


Equivalent Applied Rate Required Equivalent Cooling

Cooling Caapcity Outdoor Cooling Caapcity Capacity(kWR)


(kWR) CFM/ CMH/ Air (CMH) (kWR)
2 2
1000 ft 100 m
3.20 0 0 0 - 3.20

- 0 0 0 - -

7.08 0 0 0 - 7.08

- 0 0 0 - -

10.3 Total 0 - 10.3

T.B.C.

e assumption 0.5 kWe per 1 kWr and consider only outdoor air supply to Cold Store only 48,384.00 THB/Yr
Electrical Energy Cost Per Year =
Annual Energy Cost = (kWr*0.5*24*30*12) kWh x 3.5 THB
MR39 - BC2537 : REGULATIONS FOR NON-HIGH RISE & NON-EXTRA LARGE BUILDING
Table 5, Page 10