Problem 2
An axially load rectangular tied column is to be designed for the following service loads:
Dead Load, D = 1500 kN
Live Load, L = 836 kN
Required Strength, U = 1.2D + 1.6L
Capacity Reduction Factor, Ø = 0.65
Effective Cover to Centroid of Steel Reinforcement = 70mm
Concrete, fc’ = 27.5 MPa
Steel, fy = 415 MPa
1. Using 3% vertical steel ratio, what is the required column width (mm) if architectural
considerations limit the width of the column in one direction to 350 mm? (Ans: 500 mm)
2. If column section = 350 x 450mm. Vertical Reinforcement consists of 16 bars.
Determine the diameter of vertical bars (mm) if the required minimum steel ratio is 3% (Ans: 25
mm)
3. If the column has circular section, determine the required minimum diameter if it is
reinforced with 8-25 mm Ø bars. (Ans: 494.70 mm)
Problem 3
A 360mm x 360mm concrete tied column is to be designed for a factored axial load of
2200 kN. Capacity reduction factor, Ø = 0.65. Use the 2010 NSCP.
Materials: Concrete, fc’ = 28 MPa
Steel, fy = 400 MPa
1. The number of pcs. 20mmØ bars for the longitudinal reinforcements is nearest to:
A. 6 B. 7 C. 8 D. 10
2. The spacing required (mm) for the 10mmØ lateral reinforcements is nearest to:
A. 300 B. 350 C. 400 D. 450
3. If 16mmØ longitudinal bars are used, how many bars are required if it will be placed
on equal number of pieces on each side of the section.
A. 8 B. 14 C. 16 D. 20
Problem 4
A 400 mm square tied RC column is to carry axial service loads of 2400 kN dead load and
790 kN live load. Assume column to be short and that any moment caused by the loads can be
neglected. Use 2010 NSCP. If fc’ = 28 MPa and fy = 415 MPa, determine:
Problem 5
A 450 mm diameter concrete spiral column is to be designed to support a factored axial
load of 3170 kN. Clear bar covering is 40mm and the aggregate size is 25 mm use the 2010
NSCP with fc’ = 28 MPa, fy = 414 MPa for the longitudinal steel, fyt = 414 MPa for the spiral
steel. Limit the gross steel percentage to 2%. Find:
1. the maximum nominal axial strength of the RC column. (Ans: 3232.29 kN)
2. the design axial strength of the column. (Ans: 2424.22 kN)
3. the minimum spiral steel ratio required for the column section. (Ans: 0.01281)
4. the recommended pitch of the spiral reinforcement. (Ans: 70 mm)
PLASTIC CENTROID
- the location of the resultant load when the column is compressed uniformly
- the reference point for eccentricity of loads
- the plastic centroid (PC) is at the geometrical center for symmetrical column section