Professional Documents
Culture Documents
4800-T
MODEL – 10K BOP TEST STATION
MANUFACTURED FOR
JOHN ENERGY
MANUFACTURED BY - -
API LICENSE 16D-0028
Consolidated Pressure Control, LLC
7614 Bluff Point • Houston TX 77086 DATED MANUFACTURE
02/12
281-893-5900 Voice • 281-893-5901 FAX
Www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
TABLE OF CONTENTS
2
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
SALES DATA
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
3
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
7614 Bluff Point
Houston, TX 77086
1.3 (1) 0-‐10 K “Barton” Chart recorder w\ chart and pen kit (contains 100 charts & 6 pens)
1.5
Medium
pressure
needle
valves
for
bleeding
and
isolating
system,
medium
pressure
flow
and
discharge
fittings
&
check
valve.
(Parker
Brand
valves
&
fittings
only
to
be
used.)
1.6
Low
pressure
ball
valves
for
supply
fluid
inlet,
both
air
pumps,
and
air
inlet.
(Parker
Brand
vales
&
fittings
only
to
be
used.)
1.10 Quick connects for test hose to unit, and adapter for test hose “M” to ½” NPT
1.11 80 gallon test fluid reservoir with graduated level indication, volume to be in gallons
Standard
Int’l
Terms:
50%
down
payment
with
placement
of
order,
balance
due
at
shipment
(DESIGN FROM API SPEC 16D)
4
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Design Plan
Order Date: February 2012 Received: February 2012
Design verification
Calculation Method A Ryan Inderwiesen 02/12 ____________________
5
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
CERTIFICATIONS
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
6
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
CERTIFICATE OF
CONFORMANCE
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
7
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Certifications
Certificate of Compliance
Unit Serial Number: 4800-T
Manufactured: 02/12
This 10,000-PSI - Hydraulic Test Unit was assembled under the direction of
Quality Control personnel familiar with current Quality Management System
and Manufacturing Specifications. All items and materials used in manufac-
ture have been found to be compliant with the order and applicable require-
ments.
Upon completion of assembly this unit was tested within the prescribed Oper-
ating Pressure noted on the order data. This unit has completed and “passed”
the Factory Acceptance Testing and is certified suitable for operation.
T. Thornhill - Q A
Test Unit BOP Control System Design Book- Rev 1 - 03312011
QA - Accepted / Approved
(DESIGN FROM API SPEC 16D)
8
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
API CERTIFICATE
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
9
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Certifications
API Certificate
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
10
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
ISO CERTIFICATE
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
11
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Certifications
ISO Certificate
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
12
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
CERTIFICATE OF
WARRANTY
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
13
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Certifications
Warranty
Certificate of Warranty
This BOP Control System (aka Unit) is warranted to be free from defects in manufacture
and operation for a maximum period of one year after the time of installation. The war-
ranty coverage period is not to exceed 18 months after manufacture date. CPC may at its
discretion replace or repair defective parts as needed with either entire systems/assem-
blies or with spare and repairs kits.
If the Unit is serviced or tampered with or has been improperly installed or commissioned
by persons or agencies other than certified Consolidated Pressure Control (CPC) techni-
cians and service crews or ‘authorized’ agents then this warranty may be considered void.
Damage to parts through normal or anticipated wear and tear or use may is exempt from
coverage. Any and all parts and systems that are to be considered for warranty and re-
placement must be returned to CPC for evaluation.
CPC cannot be held responsible or bound for any damages resulting from mismatched
electrical installation or negligence and or lack of proper service and maintenance to or
misuse of the Unit and attached devices. CPC cannot be held liable for time lost, down-
time, or other such losses due to equipment failures or downtime after the Unit has left
our facilities. Other restrictions and limitations may apply. Please contact CPC if unclear
about your warranty.
DESCRIPTION: BOP-10KTP-TEST-PUMP
SERIAL NUMBER: 4800-T
MANUFACTURE DATE: FEBRUARY 2012
Test Unit BOP Control System Design Book- Rev 1 - 03312011
T. Thornhill - Q A
(DESIGN FROM API SPEC 16D)
QA - Accepted / Approved
14
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
CERTIFICATE OF
ORIGIN
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
15
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Certifications
Origin
CERTIFICATE OF ORIGIN
This document is to hereby state that the below listed items have
been manufactured and or assembled in the United States with legally
available consumable that are acceptable to the governing guidelines
as required from the United States and other regulatory agencies..
To the best of our knowledge, all statements made above are true and
accurate.
T. Thornhill - Q A
Test Unit BOP Control System Design Book- Rev 1 - 03312011
QA - Accepted / Approved
(DESIGN FROM API SPEC 16D)
16
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
FACTORY
ACCEPTANCE &
HYDROSTATIC
TEST CERTS
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
17
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Certifications
Factory Acceptance & Hydrostatic Test Certificate
Factory Acceptance & Hydrostatic Test Certificate
Description: 10K Hydrostatic Test Unit
Serial Number: 4800-T
This Hydrostatic Test Unit has been inspected and tested by qualified
technicians under the guidance of CPC’s Quality Assurance department
and to applicable current Factory Acceptance Test standards which com-
ply with and exceed industry requirements. This system has been visually
and functionally tested and has been found to be in working and good
order. Hydrostatic Testing was performed to the unit in various loads and
time to pressure of 10,000K-PSI throughout the system to ensure integ-
rity. The 10,000 PSI calibrated gauge supplied on test unit is found to be
compliant by Consolidated Pressure Control and is suitable for operation.
This unit has been found to be in good and working condition and is giv-
en a grade of “Pass” for testing purposes. Hydrostatic test results follow
T. Thornhill - Q A
QA - Accepted / Approved
Tim Thornhill
API / ISO Coordinator
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
18
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Certifications
Hydrostatic Test Results
T. Thornhill - Q A
Test Unit BOP Control System Design Book- Rev 1 - 03312011
QA - Accepted / Approved
(DESIGN FROM API SPEC 16D)
19
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Certifications
Test Unit BOP Control System Design Book- Rev 1 - 03312011
T. Thornhill - QA
T. Thornhill - Q A
(DESIGN FROM API SPEC 16D)
QA - Accepted / Approved
QA - Accepted / Approved
20
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
SECTION 4
DRAWINGS
Drawings and Calculations to Document
Compliance to Specifications
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
21
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
S/N 4800-T BOP Test Unit MFG : 02/12
John Energy
4 3 2 1
22
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
40.00
D D
C C
56.25
B B
DRAWN
rinderwiesen 5/11/2011 Consolidated Pressure Control
CHECKED
33.25 GK 5/11/2011 TITLE
A QA A
MFG 10,000 PSI Test Unit
APPROVED
GL 5/11/2011 SIZE DWG NO REV
C 10KTP-2AP-0 00
SCALE
SHEET 1 OF 1
4 3 2 1
(DESIGN FROM API SPEC 16D)
Test Unit BOP Control System Design Book- Rev 1 - 03312011
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
INSTALLATION
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
23
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Installation
This model test unit has been tested and shipped with an approved and rated test hose; so when moving
the Test Unit toward the test area be sure to position the unit close enough to allow all the needed hoses to
reach all connections that will be utilized during the testing phase.
Locate and position the unit in safe area as not to interfere with other operations. Keep the unit clear of
areas where water/liquid run-off and leakage may be considered an issue. Make sure the Test Unit is care-
fully seated on a level surface prior to connecting and or using the device.
On this kind of Hydrostatic test unit there is one (1) slot/ hole cut into the top frame to allow safer and sim-
plified moving/arrangement of this unit prior to and after use. It can be easily identified viewing the main
gauge on the unit,with the slot/ hole directly behind it. Using this is the recommended manner to move the
equipment at any time. Never allow any person to stand, move or work underneath or on the equipment or
in any area that it may fall onto while it is raised or in motion. Never attempt to power-up or run the unit
when positioning, suspending, or moving the Test Unit. If and when hoisting/lifting always make certain
there is a trained spotter dedicated to aiding the crane/hoist operator.
Always inspect the lifting equipment to insure it is without damage and that all points are firmly connected
and remain connected during the hoisting/suspension process.
Once the unit is in place, make certain that there is adequate room all the way around the equipment to
allow for access to the Test Unit as well as safe passage for exit in the event of an emergency. Verify that
the test hose is capable of reaching the targets it must mate with and the test unit simultaneously. Remove
all rigging from test unit and any clutter in the area.
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
24
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Installation
Closed Valves
This Hydrostatic Test Unit is equipped with many valves. The operator should set and or tighten all valves
in or to the close position before performing any procedures below to verify all the valves have been
closed (Shown in Figure 2). Valves being closed are as followed: High/Low Pressure Isolation Valves,
Fluid/Air Inlet Valves and Dump Valve. Doing this will allow smoother installation and operation for your
Hydrostatic test unit and devices being tested.
25
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Installation
Opened Valves
This Hydrostatic Test Unit is equipped with many valves. The operator should set and or loosen all speci-
fied valves into the open position before performing any procedures below to verify all the necessary
valves have been open (Shown in Figure 3). Valve being open is as followed: Test Isolation (Bleeder)
Valve. Doing this will allow smoother installation and operation for your Hydrostatic test unit and devices
being tested.
26
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
INSPECTION &
PREPARATION
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
27
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Inspection & Preparation
The Dirty Dump port (Shown as port B in Figure 4) needs to be faced away from the work area and into a
safe area to discharge the fluid during the testing process. If environmental contaminants are likely to be
present in the discharge a hose should be ran to an environmentally safe receptacle with adequate capacity
to capture all discharged fluid both during and after the testing process.
Fluid/Hose Connections
Connect a third hose/line to the 1” NPT
Air Inlet port. (Shown as C in Figure 4) A C
A. Test Line Connection from Test Unit
(OUT)
Run a clean fluid supply line to the test 15,000 PSI High Pressure
Male Quick Disconnect !
unit and connect it to the 3/4” NPT (Nipple No Check 9/16 MP QD Male; affixed into HC MF9-BH 9/16 Bulk Head)
Supply Line port (shown as D in Figure B B. Dirty Dump from Test Unit (OUT)
Low Pres. 1/2” NPT D
4). Be sure to have an in-line valve be- C. Fluid Intel to Test Unit (IN)
tween the supply and the port to allow Low Pres. 1/2“ NPT
convenient access to turn the supply on D. Air Inlet to Test Unit (IN)
After the Plumbing aspects have been
connected and checked appropriately
the operator is then ready to perform
the routine inspection and preparation
procedures prior to operation.
Figure 4 - Hoses
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
28
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Inspection & Preparation
29
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Inspection & Preparation
Rupture Disc
A.
Rupture Disc: 12,500 PSI
30
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
OPERATION
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
31
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Operation
Introduction
This portable test unit is capable of hydrostatically testing a BOP stack and other such devices to pressure
of up to 15,000 PSI. This unit is designed to use an external fluid/water supply and it requires a High Pres-
sure/Volume and Low Pressure/Volume Air Pump power source to obtain the PSI required. The unit uses
a sequence of valves to obtain the required PSI and then lock the pressure into the item(s) to be tested. An
onboard chart recorder will record the tested pressures with a wheel graph.
The photo illustration on page 10 (Figure 8) shows a breakdown of the primary elements on the Test Unit
which the operator will use during the testing process.
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
32
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Operation
I
J K
O
Test Unit BOP Control System Design Book- Rev 1 - 03312011
N
(DESIGN FROM API SPEC 16D)
33
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Operation - Pre-Test
1. Make sure all the Valves are set in Closed settings except Test Isolation (bleeder) Valve,
which will remain open during testing operation. (Refer to Figure 9 steps 1 thru 3 below and
the “Installation” section for valve location.)
Warning - Do Not Over Tighten the “Dump Valve” (blue handle).
Tighten only to 7.5 ft/lbs MAX.
3. The operator needs to be sure all steps are completed in the “Inspection” Section.
4. If Recording this Test, insert a new 20,000 PSI Chart into the recorder, turn the recorder “On” to
the correct time scenario, uncap the recorder pen, lock the chart, close the recorder door.
ALWAYS TURN THE POWER OFF TO THE CHART RECORDER WHEN COMPLETE.
5. Once all the above have been completed correctly the operator may begin the test.
OPEN POSITION TEST UNIT TOP VIEW
ROTATED 100%
CLOCKWISE TEST PRESSURE ISOLATION VALVE
TEST PRESSURE ISOLATION VALVE
HIGH PRESSURE PUMP ONE
STEP 1
LOW PRESSURE PUMP TWO * NORMALLY CLOSED*
AIR INLET * NORMALLY CLOSED*
OPEN
OPEN
OPEN CLOSE
CLOSE
CLOSE
GAUGE
UP FAST, SO GRADUALLY INCREASE TO REACH
(KEEP OPEN DURING PRESSURE UP) PRESSURE)
STEP 2
FLUID INLET
TO
TO
CL
C
LA
AV
VE
E
EN
EN
NE
EE
ERS
RS
7.5 ft./lbs. To Seat under Pressure 7.5 ft./lbs. To Seat under Pressure
Test Unit BOP Control System Design Book- Rev 1 - 03312011
CLOCKWISE COUNTER-CLOCKWISE
(DESIGN FROM API SPEC 16D)
34
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Operation - Testing
1. Make sure the Air Inlet is still open. (Shown as D in Figure 8)
2. With the Fluid Inlet (Shown as G in Figure 8) open and test connection hooked to devices being
tested, the fluid will fill the cavity. This may take a little while depending upon the fluid volume
of the device to be tested.
3. Once devices have reached volume needed, and the operator verifies the Isolation “Bleeder” Test
Valve (Shown as M in Figure 8) is still open from the pre-test, the operator will then proceed to
pressure air up from pumps.
4. Engage and hold open the Low Pressure, High Volume (Pump 2 Shown as C in Figure 8) until it
reaches the flow rate cut off. Keep open until desired pressure is reached through next step.
5. Gradually open the High Pressure, Low Volume (Pump 1 Shown as A in Figure 8) The opera
tor must be precise in pressure cut off or Rupture Disc (Shown as L in figure 8) will rupture. DO
NOT PRESSURE OVER 15K. CPC recommends increasing pressure in cycles to acquire exact
pressure.
6. The Test Pressure Gauge in the middle of test unit (Shown as B in Figure 8) should be displaying
the correct test pressure.
7. After the desired pressure is reached, turn both pump valves in the closed position.
8. Once the Test Pressure Gauge reads the correct pressure the operator can then lock and allow the
Chart Recorder (Shown as I in Figure 8) to document the results of the pressure test for
the appropriate/required time frame.
35
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
OPEN POSITION TEST UNIT TOP VIEW
ROTATED 100% TEST PRESSURE ISOLATION VALVE TEST PRESSURE ISOLATION VALVE
CLOCKWISE LOW PRESSURE PUMP TWO HIGH PRESSURE PUMP ONE
* NORMALLY CLOSED*
* NORMALLY CLOSED*
AIR INLET
OPEN CLOSE
STEP 5
OPEN OPEN
CLOSE
PRESSURE CLOSE
GAUGE
-OPEN ONLY WHEN LOW PRESSURE PUMP IS
-OPEN AFTER AIR INLET LINE IS CONNECTED -OPEN AFTER AIR INLET LINE IS CONNECTED AT MAX PRESSURE (THIS PUMP WILL PRESSURE
AND TEST IS BEING PERFORMED UP FAST, SO GRADUALLY INCREASE TO REACH
AND WHEN TEST IS BEING PERFORMED ON BOP
PRESSURE)
(KEEP OPEN DURING PRESSURE UP)
-CLOSE ONLY DURING HOOK UP AND WHEN NO
TEST IS BEING PERFORMED. THIS WILL PREVENT - CLOSE WHEN TEST PRESSURE IS REACHED
STEP 4
DEBRIS FROM REACHING AIR FILTRATION/LUBRICATOR - CLOSE WHEN NO AIR IS NEEDED OR AND WHEN NO AIR IS NEEDED OR WHEN
OPERATOR IS FINISHED PRESSURING OPERATOR IS FINISHED PRESSURING
STEP 1
TEST UNIT TEST UNIT
AU
AU
FLUID INLET
TO
TO
CL
CL
AV
AV
STEP 2
E
E
EN
EN
OPEN CLOSED OPEN CLOSED
STEP 3
GI
GI
NE
NE
ER
ER
S
S
-CLOSE ONLY DURING FULL TEST OPERATION
- THIS VALVE REMAINS OPEN ALWAYS DURING
OPEN OPERATION
-OPEN AFTER TEST IS COMPLETE TO RELEASE
FLUID FROM UNIT AND PREVENT DEBRIS FROM
REACHING TEST PRESSURE GAUGE/CHART - CLOSE ONLY TO PREVENT WASHOUT
CLOSE
7.5 ft./lbs. To Seat under Pressure 7.5 ft./lbs. To Seat under Pressure
DO NOT OVER TIGHTEN DO NOT OVER TIGHTEN
CLOCKWISE COUNTER-CLOCKWISE
TEST OPERATIONS
Figures 10 - Testing Device Through Test Unit
OPEN POSITION TEST UNIT TOP VIEW
ROTATED 100%
CLOCKWISE
TEST PRESSURE ISOLATION VALVE
LOW PRESSURE PUMP TWO
STEP 7 TEST PRESSURE ISOLATION VALVE
HIGH PRESSURE PUMP ONE
* NORMALLY CLOSED*
* NORMALLY CLOSED*
AIR INLET
OPEN OPEN
OPEN CLOSE
CLOSE CLOSE
PRESSURE
GAUGE
-OPEN ONLY WHEN LOW PRESSURE PUMP IS
-OPEN AFTER AIR INLET LINE IS CONNECTED -OPEN AFTER AIR INLET LINE IS CONNECTED AT MAX PRESSURE (THIS PUMP WILL PRESSURE
AND TEST IS BEING PERFORMED UP FAST, SO GRADUALLY INCREASE TO REACH
AND WHEN TEST IS BEING PERFORMED ON BOP
PRESSURE)
(KEEP OPEN DURING PRESSURE UP)
-CLOSE ONLY DURING HOOK UP AND WHEN NO
TEST IS BEING PERFORMED. THIS WILL PREVENT - CLOSE WHEN TEST PRESSURE IS REACHED
STEP 6
DEBRIS FROM REACHING AIR FILTRATION/LUBRICATOR - CLOSE WHEN NO AIR IS NEEDED OR AND WHEN NO AIR IS NEEDED OR WHEN
OPERATOR IS FINISHED PRESSURING OPERATOR IS FINISHED PRESSURING
TEST UNIT TEST UNIT
FLUID INLET
TO
TO
C
CL
LA
AV
VE
E
EN
EN
NE
NE
E
ER
RS
Test Unit BOP Control System Design Book- Rev 1 - 03312011
7.5 ft./lbs. To Seat under Pressure 7.5 ft./lbs. To Seat under Pressure
DO NOT OVER TIGHTEN DO NOT OVER TIGHTEN
CLOCKWISE COUNTER-CLOCKWISE
RIGGING DOWN –
BLEEDING DOWN
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
37
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Rigging Down Operation -
Bleeding-Off / Releasing Pressure After Testing
After the test is complete, prior to disconnecting any lines/hoses, it important to properly and safely bleed
the system of any pressure to avoid injury. The following steps (illustrated in Figure 11) are the safest
means to accomplish this.
1. Stop Chart Recorder and turn off. (Shown as I in Figure 8) Be sure to remove the chart recorder graph,
mark it/identify it as necessary.
2. Close both Air (Shown as D in Figure 8) and Fluid (Shown as G in Figure 8) Inlets. This allows fluid/
air to stop continuing through test unit and testing device.
3. Close Isolation Test ”Bleeder” Valve (Shown as M in Figure 8). This is so no fluid will bleed back into
test unit.
4. Slowly open Dirty Dump (Drain) Valve (Show as O in Figure 8) to release fluid from both the test unit
and testing device.
System should be bleeding down. Once pressure on the gauge(s) reads zero PSI (0 PSI) it will be safe
begin disconnecting hoses.
If you are to retest another unit start at and follow the step in Pre-Test Operations.
OPEN POSITION TEST UNIT TOP VIEW
ROTATED 100% TEST PRESSURE ISOLATION VALVE TEST PRESSURE ISOLATION VALVE
CLOCKWISE LOW PRESSURE PUMP TWO HIGH PRESSURE PUMP ONE
* NORMALLY CLOSED*
* NORMALLY CLOSED*
AIR INLET
OPEN OPEN
OPEN CLOSE
CLOSE CLOSE
PRESSURE
GAUGE
-OPEN ONLY WHEN LOW PRESSURE PUMP IS
-OPEN AFTER AIR INLET LINE IS CONNECTED -OPEN AFTER AIR INLET LINE IS CONNECTED AT MAX PRESSURE (THIS PUMP WILL PRESSURE
AND TEST IS BEING PERFORMED UP FAST, SO GRADUALLY INCREASE TO REACH
AND WHEN TEST IS BEING PERFORMED ON BOP
PRESSURE)
(KEEP OPEN DURING PRESSURE UP)
-CLOSE ONLY DURING HOOK UP AND WHEN NO
TEST IS BEING PERFORMED. THIS WILL PREVENT - CLOSE WHEN TEST PRESSURE IS REACHED
DEBRIS FROM REACHING AIR FILTRATION/LUBRICATOR - CLOSE WHEN NO AIR IS NEEDED OR AND WHEN NO AIR IS NEEDED OR WHEN
OPERATOR IS FINISHED PRESSURING OPERATOR IS FINISHED PRESSURING
TEST UNIT TEST UNIT
STEP 3
AU
AU
FLUID INLET
TO
TO
C
C
LA
LA
VE
VE
EN
EN
OPEN
NE
NE
ER
ER
S
S
STEP 4
- THIS VALVE REMAINS OPEN ALWAYS DURING
-OPEN AFTER TEST IS COMPLETE TO RELEASE OPERATION
FLUID FROM UNIT AND PREVENT DEBRIS FROM
REACHING TEST PRESSURE GAUGE/CHART - CLOSE ONLY TO PREVENT WASHOUT
Test Unit BOP Control System Design Book- Rev 1 - 03312011
7.5 ft./lbs. To Seat under Pressure 7.5 ft./lbs. To Seat under Pressure
DO NOT OVER TIGHTEN DO NOT OVER TIGHTEN
CLOCKWISE COUNTER-CLOCKWISE
(DESIGN FROM API SPEC 16D)
38
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
MAINTENANCE
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
39
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Maintenance
Daily/Per Use
Inspect and clean the “Y”strainer feeding into fluid inlet. (Shown as H.in Fig 8)
40
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
GLOSSARY
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
41
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
GLOSSARY
A
Accumulator - A pressure vessel charged with non-reactive or inert gas used to store
hydraulic fluid under pressure for operation of blowout preventors.
Annular BOP - A device with a generally toroidal shaped steel - reinforced elastomer
packing element that is hydraulically operated to close and seal around any drill pipe
size to provide full closure of the wellbore.
Backup - An element or system intended to be used only in the event that the prima-
ry element or system is non-functional.
Blind Ram BOP - A BOP having rams which seal against each other to close the well-
bore in the absence of any pipe.
BOP (Blowout Preventer) - A device that allows the well to be sealed to confine the
well fluids to the wellbore.
BOP Closing Ration (Ram BOP) - A dimensionless factor equal to the area of the pis-
ton operator divided by the area of the ram shaft.
Test Unit BOP Control System Design Book- Rev 1 - 03312011
BOP stack - The assembly of well control equipment including BOPs, spools, valves,
and nipples connected to the top of the casing head.
(DESIGN FROM API SPEC 16D)
BOP Stack Maximum Rated Wellbore Pressure - The pressure containment rating of
the ram BOPs in a stack.
42
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
GLOSSARY
C
Central Control Unit (CCU) - The central control point for control and monitoring sys-
tem functions and communications.
Check Valve - A valve that allows flow through it in one direction only
Choke Line - A high pressure line connected below a BOP to transmit well fluid flow
to the choke manifold during well control operations.
Choke and Kill Valves - BOP stack-mounted valves that are connected below selected
BOPs to allow access to the wellbore to either choke or kill the well.
Control Fluid - Hydraulic oil, water based fluid, or gas which, under pressure, pilots
the operation of control valves or directly operates functions.
Control Hose Bundle - A group of pilot and/or supply and/or control hoses assem-
bled into a bundle covered with an outer protective sheath.
Control Line - A flexible hose or rigid line that transmits control fluid.
Control Manifold - The assemblage of valves, regulators, gauges and piping used to
regulate pressures and control the flow of hydraulic power fluid to operate system
functions.
Control Pod - The assemblage of valves and pressure regulators which respond to
Test Unit BOP Control System Design Book- Rev 1 - 03312011
control signals to direct hydraulic power fluid through assigned porting to operate
functions.
(DESIGN FROM API SPEC 16D)
Control Valve (Surface Control System) - A valve mounted on the hydraulic manifold
which directs hydraulic power fluid to the selected function (such as annular BOP
close) while simultaneously venting the opposite function (annular BOP open.)
43
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
GLOSSARY
D
Disconnect - Unlatch and separation of the BOP stack connector from the wellhead
Discrete Hydraulic Control System - A system utilizing pilot hoses to transmit hy-
draulic pressure signals to activate pilot-operated valves assigned to functions.
Diverter - A device attached to the wellhead or marine riser to close the vertical flow
path and direct well flow (typically shallow gas) into a vent line away from the rig.
Diverter Panel - A panel that is dedicated to the diverter and flow line system func-
tions.
Drive-off - An unintended lateral move of a dynamically position vessel off its location
driven by the vessel’s main propulsion or station keeping thrusters.
Function - Operation of a BOP, choke or kill valve or other component, in one direc-
Test Unit BOP Control System Design Book- Rev 1 - 03312011
tion (example, closing the blind rams is a function, opening the blind rams is a sepa-
rate function).
G - None
(DESIGN FROM API SPEC 16D)
44
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
GLOSSARY
H
Interflow - The control fluid lost (vented) during the travel of the piston in a control
valve during the interval when the control valve’s inlet and vent points are temporar-
ily interconnected.
Jumper - A segment of hose or cable used to make a connection such as a hose reel
junction box to the control manifold.
Junction Box (J-box) (hydraulic or pneumatic) - A bolt-on plate having multiple stab-
type terminal fittings used for quick connection of the multi-hose bundle to a pod,
hose reel or manifold.
Kill Line - A high-pressure line from the mud pumps to a connection below a BOP
that allows fluid to be pumped into the well or annulus with the BOP closed during
well control operations.
Limit Switch - A hydraulic, pneumatic or electrical switch that indicates the motion
or position of a device.
M
Manifold - An assemblage of pipe, valves, and fittings by which fluid from one or more
sources is selectively directed to various systems or components.
Master Panel (Hydraulic or Electric) - The panel mounted in close proximity to the
primary power fluid supply. All control functions are operable from this panel in-
cluding all required regulators, gauges, meters, audible alarms, and visible alarms.
Test Unit BOP Control System Design Book- Rev 1 - 03312011
Mini or Auxiliary Remote Panel (Tool pusher’s Panel) - Full or limited function panel
mounted in a remote location for use as an emergency backup. Mixing System - A
system that mixes a measured amount of water soluble lubricant and, optionally, gly-
col to feed water and delivers it to a storage tank or reservoir.
(DESIGN FROM API SPEC 16D)
45
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
GLOSSARY
N - None
O - None
Pilot Fluid - Control fluid that is dedicated to the pilot supply system.
Pilot Line - A line that transmits pilot fluid to operate a control valve.
Pipe Ram BOP - A hydraulically operated assembly typically having two opposed ram
assemblies that move inward to close on pipe in the wellbore and seal the annulus.
Pipe Rams - Rams whose ends are contoured to seal around pipe to close the annular
space.
Potable Water - A water supply that is acceptable pure for human consumption.
Note: On an offshore rig, it is usually produced by water makers and used as supply
water for mixing control fluid for a subsea control system.
sure) on pilot lines such that hydraulic signal transmission time is reduced.
Pressure Vessel - For BOP control systems, a pressure vessel is a container for the
(DESIGN FROM API SPEC 16D)
46
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
GLOSSARY
Q
Ram BOP - A blowout preventer that uses rams to seal off pressure in the wellbore.
Rated Working Pressure - The maximum internal pressure that equipment is de-
signed to contain or control under normal operating conditions.
Reaction Time - The actual time elapsed between initiations of a command to comple-
tion of the function.
Reel (hose or cable) - A reel, usually power driven, that stores, pays-out and takes-up
umbilicals, either control hose bundles or electrical cables.
Relief Valve - A device that is built into a hydraulic or pneumatic system to relieve
(dump) any excess pressure.
Response Time - The time elapsed between activation of a function at any control
panel and complete operation of the function.
(DESIGN FROM API SPEC 16D)
47
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
GLOSSARY
Reservoir - A storage tank for BOP control system fluid.
Return-To-Reservoir Circuit - A hydraulic control circuit in which spent fluid is re-
turned to the reservoir.
Rig Floor Panel (Driller’s Panel) - The BOP control panel mounted near the driller’s
position on the rig floor.
Shared - An element or system that may be used for more than one purpose.
Shear Ram BOP (blind/shear rams) - Rams having cutting blades that will shear
tubular that may be in the wellbore. Shearing blind rams additionally close and seal
against the pressure below. Casing shear rams are designed specifically to shear
casing, and may not seal the well bore.
Shuttle Valve - A valve with two or more supply ports and only one outlet port. Note:
When fluid is flowing through one of the supply ports the internal shuttle seals off
the other inlet port(s) and allows flow to the outlet port only.
Solenoid Valve-An electrical coil operated valve which controls a hydraulic or pneu-
matic function or signal.
Spent Fluid - Hydraulic control fluid that is vented from a function control port when
the opposite function is operated.
Stored Hydraulic Fluid Volume - The fluid volume recoverable from the accumulator
system between the systems rated working pressure and the pre-charge pressure.
System Rated Working Pressure - The maximum design pressure at which control
fluid is stored in the accumulator assembly.
Test Pressure - The pressure at which the component or system is tested to verify
Test Unit BOP Control System Design Book- Rev 1 - 03312011
48
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
GLOSSARY
Type Certification Testing - Testing by a manufacturer of a representative specimen
(or prototype) of a product which qualifies the design and, therefore, validates the
integrity of other products of the same design, materials and manufacture.
Umbilical - A control hose bundle or electric cable used to control subsea functions.
Usable Hydraulic Fluid - The fluid volume recoverable from the accumulator system
between the systems rated working pressure and the minimum operating pressure.
Vent Position - The position of a control valve that vents spent fluid to ambient or to
the reservoir.
Volumetric Efficiency (VE) - The ratio of deliverable fluid volume to total gas volume of
a bottle, based on design conditions and calculation method (see 4.2.3.1. in API 16D).
W
Watch Circle - The rig offset perimeter around the well location for which special
procedures are to be initiated to prepare to disconnect the drilling riser or actually
implement the disconnect to prevent damage due to excessive offset.
X - None
Y - None
Z - None
Note: All of the following definitions can be found in API 16D. The above defini-
tions are applicable to Consolidated Pressure Control, LLLP.
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
49
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
The information provided in this document is meant to be used as a guideline for op-
eration of the equipment within a safe measure of operation. Ultimately it is the op-
erator’s responsibility to insure that safety of persons and equipment are considered
at all times with the operation of this equipment. If any item is suspected of being
faulty it is imperative that the unit is shut down and removed from operation until
the equipment has been properly repaired and serviced with equipment that is rated
to handle the working pressures of the test unit. Never modify or alter the unit in any
manner.
This document and the data and content it provides are meant to be used as a refer-
ence. Changes and modifications to this documentation may be made but it is the
Test Unit BOP Control System Design Book- Rev 1 - 03312011
operators responsibility to ensure that they are using the most current set of data
related to the test unit.
(DESIGN FROM API SPEC 16D)
Consolidated Pressure Control, LLLP cannot be held responsible for any injury or
damages that may occur from misuse, neglect, improper maintenance, modification,
alteration or improper handling and use of the test unit.
50
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
KEY COMPONENTS
PARTS
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
NEEDLE
VALVE
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
52
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Needle Valves
Medium Pressure
SM Series
Pressures to 20,000 psi (1379 bar)
Medium Pressure
(DESIGN FROM API SPEC 16D)
www.autoclave.com
53
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Tube Pressure
Outside Rating
Diameter Orifice psi (bar)
Size Connection Size Rated @ Room
Inches Type Inches (mm) Cv* Temperature**
Notes:
* CV values shown are for 2-way straight valve pattern. For 2-way
angle patterns, increase CV value 50%. (Based on water)
6
POWDER COATED
STAINLESS STEEL
HANDLE 5 Regulating Stem
Number of turns open
LOW FRICTION
ALUMINUM ONE PIECE NON-ROTATING
BRONZE PACKING STEM
GLAND
4
LOCKING DEVICE
3
ANTI-EXTRUSION
BACK-UP RINGS
ADJUSTABLE PACKING
2
BELOW THREADS
COLD WORKED
TYPE 316 SS
BODY IN FIVE
1 Vee Stem
PATTERNS
0
MEDIUM
PRESSURE
CONED-AND-THR
10 20 30 40 50 60 70 80 90 100
EADED
CHOICE OF VEE
OR REGULATING
METAL-TO-METAL
SEATING
CONNECTIONS
% of rated Cv
STEM TIP
20SM 4 07 1 XX
Valve Outside Diameter Stem/Seat Body Options
Series Tube Size Type Pattern
For extreme
4-1/4” 07 - non-rotating 1 - two-way straight
temperature and other
Test Unit BOP Control System Design Book- Rev 1 - 03312011
10SM 6-3/8” Vee stem (on-off service) 2 - two-way angle options, see
20SM 9-9/16” 08 - non-rotating 3 - three-way, two on pressure Valve Options.
12-3/4” regulating stem (tapered tip
4 - three-way, one on pressure
16-1” for regulating and shutoff)
5 - three-way, two stem
87 - Vee stem with replaceable seat
manifold valve
(DESIGN FROM API SPEC 16D)
2 All general terms and conditions of sale, including limitations of our liability, apply to all products and services sold.
54
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Valve Options Valve Maintenance
Extreme Temperatures Repair Kits: add “R” to the front of valve catalog
Standard Autoclave valves with Teflon packing may be operated from number for proper repair kit.
0°F (-17.8°C) to 450°F (232°C). High temperature packing and/or (Example: R20SM4071)
extended stuffing box are available for service from -423°F (-252°C) Valve Bodies: Valve bodies are available. Order using the eight (8)
to 1200°F (649°C) by adding the following suffixes to catalog order digit part number found on the valve drawing or
number. contact your Sales Representative for information.
TG standard valve with Teflon glass packing to 600°F (316°C).
GY standard valve with graphite braided yarn packing to 800°F (427°C).
Consult your Autoclave representative for pricing on repair kits and valve
Note: 3/4” rated 8000 psi (552 bar) and 1” rated 6000 psi (412 bar) maxi-
bodies. Refer to the Tools, Installation, Operation and Maintenance section for
mum with graphite yarn packing. proper maintenance procedures.
HT extended stuffing box valve with graphite braided yarn packing
to 1200°F (649°C).
Note: Caution should be exercised in proper selection of medium pressure tub-
B standard valve with cryogenic trim materials and Teflon packing to
ing based on actual operating conditions. Two tubing series available in some
-100°F (-73°C). sizes: 15,000 psi (1034 bar) and 20,000 psi (1380 bar).
LT extended stuffing box valve with Teflon packing and cryogenic
trim materials to -423°F (-252°C).
K anti-vibration collet and gland assembly
See needle valve options for stem and seat coating for erosive service.
2-Way Straight
20SM4071 VEE 1/4 0.125 2.00 1.00 0.38 1.62 1.19 2.00 3.00 0.75 0.22 4.69 0.62 0.38 0.75
20SM4081 REG (6.35) (3.18) (50.80) (25.40) (9.65) (41.15) (30.23) (50.80) (76.20) (19.05) (5.59) (119.13) (15.75) (9.65) (19.05)
20SM6071 VEE 3/8 0.219 2.00 1.00 0.47 1.62 1.19 2.00 3.00 0.75 0.22 4.63 0.62 0.38 0.75
20SM6081 REG (9.53) (5.56) (50.80) (25.40) (11.94) (41.15) (30.23) (50.80) (76.20) (19.05) (5.59) (117.48) (15.75) (9.65) (19.05)
20SM9071 VEE 9/16 0.312 2.50 1.25 0.53 2.38 1.75 2.88 4.00 1.00 0.34 5.93 0.69 0.50 1.00
20SM9081 REG (14.29) (7.92) (63.50) (31.75) (13.46) (60.45) (44.45) (73.15) (101.60) (25.40) (8.64) (150.86) (17.53) (12.70) (25.40)
20SM12071 VEE 3/4 0.438 3.00 1.50 0.62 3.00 2.25 3.75 10.25 1.12 0.44 7.00 0.88 0.63 1.38
See
20SM12081 REG (19.05) (11.13) (76.20) (38.10) (15.75) (76.20) (57.15) (95.25) (260.35) (28.45) (11.18) (177.80) (22.35) (16.00) (35.05)
Figure 1
20SM16071 VEE 1 0.562 4.12 2.06 0.63 3.75 2.81 4.63 10.25 1.62 0.56 9.00 1.25 1.13 1.75
20SM16081 REG (25.40) (14.27) (104.65) (52.32) (16.00) (95.25) (71.37) (117.60) (260.35) (41.15) (14.22) (228.84) (31.75) (28.70) (44.4 5)
10SM9071 VEE 9/16 0.359 2.50 1.25 0.53 2.38 1.75 2.88 4.00 1.00 0.34 5.93 0.69 0.50 1.00
10SM9081 REG (14.29) (9.12) (63.50) (31.75) (13.46) (60.45) (44.45) (73.15) (101.60) (25.40) (8.64) (150.86) (17.53) (12.70) (25.40)
10SM12071 VEE 3/4 0.516 3.00 1.50 0.62 3.00 2.25 3.75 10.25 1.12 0.44 7.00 0.88 0.63 1.38
10SM12081 REG (19.05) (13.11) (76.20) (38.10) (15.75) (76.20) (57.15) (95.25) (260.35) (28.45) (11.18) (177.80) (22.35) (16.00) (35.05)
10SM16071 VEE 1 0.688 4.12 2.06 0.63 3.75 2.81 4.63 10.25 1.62 0.56 9.00 1.25 1.13 1.75
10SM16081 REG (25.40) (17.48) (104.65) (52.32) (16.00) (95.25) (71.37) (117.60) (260.35) (41.15) (14.22) (228.84) (31.75) (28.70) (44.45)
G - Packing gland mounting hole drill size * H Dimension is with stem in closed position. For prompt service, Autoclave
G1 - Bracket mounting hole size All dimensions for reference only and subject to change. stock select products.
Panel mounting drill size: 0.22” all valves. Consult factory.
Figure 1
F
G1 M M
H N G
D1
D
Test Unit BOP Control System Design Book- Rev 1 - 03312011
E
C
B
A
2-Way Straight
(DESIGN FROM API SPEC 16D)
All general terms and conditions of sale, including limitations of our liability, apply to all products and services sold. 3
55
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Outside Dimensions - inches (mm) Block
Catalog Stem Diameter Orifice Thick- Valve
Number Type Tube Diameter A B C D D1 E F G G1 H* M N ness Pattern
2-Way Angle
20SM4072 VEE 1/4 0.125 2.00 1.00 0.38 1.19 2.44 3.00 0.75 0.22 4.81 0.62 0.38 0.75
20SM4082 REG (6.35) (3.18) (50.80) (25.40) (9.65) (30.23) (61.90) (76.20) (19.05) (5.59) (122.25) (15.75) (9.65) (19.05)
20SM6072 VEE 3/8 0.219 2.00 1.00 0.47 1.19 2.44 3.00 0.75 0.22 4.81 0.62 0.38 0.75
20SM6082 REG (9.53) (5.56) (50.80) (25.40) (11.94) (30.23) (61.90) (76.20) (19.05) (5.59) (122.25) (15.75) (9.65) (19.05)
20SM9072 VEE 9/16 0.312 2.50 1.25 0.53 1.75 3.38 4.00 1.00 0.34 6.43 0.69 0.50 1.00
20SM9082 REG (14.29) (7.92) (63.50) (31.75) (13.46) (44.45) (85.85) (101.60) (25.40) (8.64) (163.56) (17.53) (12.70) (25.40)
20SM12072 VEE 3/4 0.438 3.00 1.50 0.62 2.25 4.25 10.25 1.12 0.44 7.50 0.88 0.63 1.38
See
20SM12082 REG (19.05) (11.13) (76.20) (38.10) (15.75) (57.15) (107.95) (260.35) (28.45) (11.18) (190.50) (22.35) (16.00) (35.05)
Figure 2
20SM16072 VEE 1 0.562 4.12 2.06 0.63 2.81 5.12 10.25 1.62 0.56 9.00 1.25 1.13 1.75
20SM16082 REG (25.40) (14.27) (104.65) (52.32) (16.00) (71.37) (130.05) (260.35) (41.15) (14.22) (228.84) (31.75) (28.70) (44.4 5)
10SM9072 VEE 9/16 0.359 2.50 1.25 0.53 1.75 3.38 4.00 1.00 0.34 6.43 0.69 0.50 1.00
10SM9082 REG (14.29) (9.12) (63.50) (31.75) (13.46) (44.45) (85.85) (101.60) (25.40) (8.64) (163.56) (17.53) (12.70) (25.40)
10SM12072 VEE 3/4 0.516 3.00 1.50 0.62 2.25 4.25 10.25 1.12 0.44 7.50 0.88 0.63 1.38
10SM12082 REG (19.03) (13.11) (76.20) (38.10) (15.75) (57.15) (107.95) (260.35) (28.45) (11.18) (190.50) (22.35) (16.00) (35.05)
10SM16072 VEE 1 0.688 4.12 2.06 0.63 2.81 5.12 10.25 1.62 0.56 9.00 1.25 1.13 1.75
10SM16082 REG (25.40) (17.48) (104.65) (52.32) (16.00) (71.37) (130.05) (260.35) (41.15) (14.22) (228.84) (31.75) (28.70) (44.45)
3-Way / 2 on Pressure
20SM4073 VEE 1/4 0.125 2.00 1.00 0.38 1.63 1.19 2.63 3.00 0.75 0.22 5.00 0.62 0.38 0.75
20SM4083 REG (6.35) (3.18) (50.80) (25.40) (9.65) (41.28) (30.23) (66.68) (76.20) (19.05) (5.59) (127.00) (15.75) (9.65) (19.05)
20SM6073 VEE 3/8 0.219 2.00 1.00 0.47 1.63 1.19 2.63 3.00 0.75 0.22 5.00 0.62 0.38 0.75
20SM6083 REG (9.53) (5.56) (50.80) (25.40) (11.94) (41.28) (30.23) (66.68) (76.20) (19.05) (5.59) (127.00) (15.75) (9.65) (19.05)
20SM9073 VEE 9/16 0.312 2.50 1.25 0.53 2.38 1.75 3.63 4.00 1.00 0.34 6.51 0.69 0.50 1.00
20SM9083 REG (14.29) (7.92) (63.50) (31.75) (13.46) (60.45) (44.45) (92.08) (101.60) (25.40) (8.64) (165.59) (17.53) (12.70) (25.40)
20SM12073 VEE 3/4 0.438 3.00 1.50 0.62 3.00 2.25 4.63 10.25 1.12 0.44 7.88 0.88 0.63 1.38
See
20SM12083 REG (19.05) (11.13) (76.20) (38.10) (15.75) (76.20) (57.15) (117.48) (260.35) (28.45) (11.18) (200.03) (22.35) (16.00) (35.05)
Figure 3
20SM16073 VEE 1 0.562 4.12 2.06 0.63 3.75 2.81 5.88 10.25 1.62 0.56 9.75 1.25 1.13 1.75
20SM16083 REG (25.40) (14.27) (104.65) (52.32) (16.00) (95.25) (71.37) (149.35) (260.35) (41.15) (14.22) (247.89) (31.75) (28.70) (44.4 5)
10SM9073 VEE 9/16 0.359 2.50 1.25 0.53 2.38 1.75 3.63 4.00 1.00 0.34 6.52 0.69 0.50 1.00
10SM9083 REG (14.29) (9.12) (63.50) (31.75) (13.46) (60.45) (44.45) (92.08) (101.60) (25.40) (8.64) (165.59) (17.53) (12.70) (25.40)
10SM12073 VEE 3/4 0.516 3.00 1.50 0.62 3.00 2.25 4.63 10.25 1.12 0.44 7.88 0.88 0.63 1.38
10SM12083 REG (19.03) (13.11) (76.20) (38.10) (15.75) (76.20) (57.15) (117.48) (260.35) (28.45) (11.18) (200.03) (22.35) (16.00) (35.05)
10SM16073 VEE 1 0.688 4.12 2.06 0.63 3.75 2.81 5.88 10.25 1.62 0.56 9.75 1.25 1.13 1.75
10SM16083 REG (25.40) (17.48) (104.65) (52.32) (16.00) (95.25) (71.37) (149.35) (260.35) (41.15) (14.22) (247.89) (31.75) (28.70) (44.45)
G - Packing gland mounting hole drill size * H Dimension is with stem in closed position. For prompt service, Autoclave
G1 - Bracket mounting hole size All dimensions for reference only and subject to change. stock select products.
Panel mounting drill size: 0.22” all valves. Consult factory.
Figure 2 Figure 3
F F
M M G1 M M
G G
G1 H N
N
H D D1
D
E E
C
Test Unit BOP Control System Design Book- Rev 1 - 03312011
B B
A A
2-Way Angle 3-Way / 2 on Pressure
(DESIGN FROM API SPEC 16D)
4 All general terms and conditions of sale, including limitations of our liability, apply to all products and services sold.
56
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Outside Dimensions - inches (mm) Block
Catalog Stem Diameter Orifice Thick- Valve
Number Type Tube Diameter A B C D D1 E F G G1 H* M N ness Pattern
3-Way / 1 on Pressure
20SM4074 VEE 1/4 0.125 2.00 1.00 0.38 1.19 2.44 3.00 0.75 0.22 4.81 0.62 0.38 0.75
20SM4084 REG (6.35) (3.18) (50.80) (25.40) (9.65) (30.23) (61.90) (76.20) (19.05) (5.59) (122.25) (15.75) (9.65) (19.05)
20SM6074 VEE 3/8 0.219 2.00 1.00 0.47 1.19 2.44 3.00 0.75 0.22 4.81 0.62 0.38 0.75
20SM6084 REG (9.53) (5.56) (50.80) (25.40) (11.94) (30.23) (61.90) (76.20) (19.05) (5.59) (122.25) (15.75) (9.65) (19.05)
20SM9074 VEE 9/16 0.312 2.50 1.25 0.53 1.75 3.38 4.00 1.00 0.34 6.31 0.69 0.50 1.00
20SM9084 REG (14.29) (7.92) (63.50) (31.75) (13.46) (44.45) (85.85) (101.60) (25.40) (8.64) (160.56) (17.53) (12.70) (25.40)
20SM12074 VEE 3/4 0.438 3.00 1.50 0.62 2.25 4.25 10.25 1.12 0.44 7.50 0.88 0.63 1.38
20SM12084 REG See
(19.05) (11.13) (76.20) (38.10) (15.75) (57.15) (107.95) (260.35) (28.45) (11.18) (190.50) (22.35) (16.00) (35.05)
Figure 4
20SM16074 VEE 1 0.562 4.12 2.06 0.63 2.81 5.12 10.25 1.62 0.56 9.09 1.25 1.13 1.75
20SM16084 REG (25.40) (14.27) (104.65) (52.32) (16.00) (71.37) (130.05) (260.35) (41.15) (14.22) (231.13) (31.75) (28.70) (44.4 5)
10SM9074 VEE 9/16 0.359 2.50 1.25 0.53 1.75 3.38 4.00 1.00 0.34 6.31 0.69 0.50 1.00
10SM9084 REG (14.29) (9.12) (63.50) (31.75) (13.46) (44.45) (85.85) (101.60) (25.40) (8.64) (160.56) (17.53) (12.70) (25.40)
10SM12074 VEE 3/4 0.516 3.00 1.50 0.62 2.25 4.25 10.25 1.12 0.44 7.50 0.88 0.63 1.38
10SM12084 REG (19.03) (13.11) (76.20) (38.10) (15.75) (57.15) (107.95) (260.35) (28.45) (11.18) (190.50) (22.35) (16.00) (35.05)
10SM16074 VEE 1 0.688 4.12 2.06 0.63 2.81 5.12 10.25 1.62 0.56 9.09 1.25 1.13 1.75
10SM16084 REG (25.40) (17.48) (104.65) (52.32) (16.00) (71.37) (130.05) (260.35) (41.15) (14.22) (231.13) (31.75) (28.70) (44.45)
G - Packing gland mounting hole drill size * H Dimension is with stem in closed position. For prompt service, Autoclave
G1 - Bracket mounting hole size All dimensions for reference only and subject to change. stock select products.
Panel mounting drill size: 0.22” all valves. Consult factory.
Figure 4 Figure 5
F F
G1 G1 M M
M M G
N
H N G
H D
D D E
E C
D1
C
Test Unit BOP Control System Design Book- Rev 1 - 03312011
C
B B
A A
3-Way / 1 on Pressure 2-Way Angle / Replaceable Seat
(DESIGN FROM API SPEC 16D)
All general terms and conditions of sale, including limitations of our liability, apply to all products and services sold. 5
57
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Outside Dimensions - inches (mm) Block
Catalog Stem Diameter Orifice Thick- Valve
Number Type Tube Diameter A B C D D1 E F G G1 H* M N ness Pattern
G - Packing gland mounting hole drill size * H Dimension is with stem in closed position. For prompt service, Autoclave
G1 - Bracket mounting hole size All dimensions for reference only and subject to change. stock select products.
Panel mounting drill size: 0.22” all valves. Consult factory.
Figure 6
F
G1
M M
G
H N
D1
D
E
D1
C
B
A
6 All general terms and conditions of sale, including limitations of our liability, apply to all products and services sold.
58
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
RUPTURE
DISC
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
59
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
60
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
61
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
62
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
LOW PRESSURE
AIR PUMP
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
63
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
64
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
65
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
66
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
67
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
68
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
69
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
70
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
71
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
72
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
73
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
74
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
75
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
76
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
77
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
78
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
79
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
HIGH PRESSURE
AIR PUMP
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
80
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
81
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
82
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
83
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
84
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
85
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
86
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
87
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
88
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
89
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
90
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
91
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
92
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
93
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
94
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com
John Energy
S/N 4800-T BOP Test Unit MFG : 02/12
Test Unit BOP Control System Design Book- Rev 1 - 03312011
(DESIGN FROM API SPEC 16D)
95
7614 Bluff Point • Houston TX 77086 • 281-893-5900 Voice • 281-893-5901 FAX • www.cpcmfg.com