You are on page 1of 1

ALSAAH0A J:\2011-2020\2018\BUILDINGS\18-dh-b3097\18-BSP-108-DCC\H110970002V00.

dgn

SAUDIARAMCO.
NOTES:
LEGEND
1. THE CONTRACTOR SHALL STRICTLY COMPLY WITH THE
REQUIREMENTS OF G1.6.012, "ISOLATION, LOCKOUT & USE OF
NEW RECESSED LED FRAMED LENSED TROFFERS HOLD TAGS" TO PROTECT PERSONNEL FROM POSSIBLE
LUMINAIRE, 50W/4000°K, 120-277V, 60Hz, UNIVERSAL ELECTRICAL SHOCK HAZARD.
17 18 18' 18" 19 20 21 22 23 24 VOLT, NON-DIMMABLE ELECTRONIC DRIVER, 600mm X
1200mm, IP-20, UL-LISTED 2. CONDUIT SYSTEM SHALL BE AS FOLLOWS:
A. EMT CONDUIT TO ALL CONCEALED TO WALL AND CEALING
INSTALLATION.
SIMILAR WITH THE ABOVE FIXTURE, BUT WITH 1.5HR

OF
B. PVC TC-8 CONDUIT TO EMBEBDED TO GROUND AND
STAND-BY POWER EMERGENCY PROVITION UL-924 CONCREATE INSTALLATION.
EL C. PVC COATED RIGID STEEL CONDUIT HOT-DEEP GALVANIZED

CONSENT
(RSC/PVC) TO ALL EXPOSED ABOVE GROUND INSTALLATION.
NEW RECESSED LED FRAMED LENSED TROFFERS
LUMINAIRE, 25W/4000°K, 120-277V, 60Hz, UNIVERSAL 3. ALL MOUNTED BOX SWITCHES AND OUTLET DEVICES SHALL BE
VOLT, NON-DIMMABLE ELECTRONIC DRIVER, 600mm X BRITISH STANDARD PRODUCT.
600mm, IP-20, UL-LISTED A. 46mm DEEP TYPE BOX (FOR SINGLE)
B. 47mm DEEP TYPE (FOR DUPLEX)

TTEN
SIMILAR WITH THE ABOVE FIXTURE, BUT WITH 1.5HR 4. ELECTRICAL WORKS SHALL BE CARRIED OUT BY QUALIFIED
STAND-BY POWER EMERGENCY PROVITION UL-924 ELECTRICIANS UNDER THE DIRECT SUPERVISION OF A DULY
EL REGISTERED ELECTRICAL ENGINEER.

WRI
5. ALL SERVICE EQUIPMENT SHALL BE PROVIDED WITH EQUIPMENT
NEW RECESSED MTD. LED DOWNLIGHT, 14.1W, 230V 60Hz, GROUNDING OF NOT LESS THAN #12 AWG GROUND WIRE OR AS
1000 LM, 4000K CCT, 6" APERTURE, NON-DIMMABLE WITH
INDICATED ON THE DRAWING & IN ACCORDANCE WITH SAES-P-111.

THE
DIE CAST ALUMINUM FRAME & ALUMINUM REFLECTOR.
DIM : 143mm INNER DIAMETER 6. ALL ELECTRICAL CABLES SHALL BE TESTED IN ACCORDANCE
MODEL: PORTFOLIO LD6AIO BY COOPER/EATON OR WITH SAES-P-104. THE CONTRACTOR SHALL MEGGER & INSTITUTE
APPROVED EQUAL A FUNCTIONAL TEST TO ALL INSTALLED ELECTRICAL ITEM.

THOUT
SAME DESCRIPTION AS ABOVE BUT WITH EMERGENCY 7. ALL MATERIALS & DEVICES TO BE USED SHALL BE UL-LISTED
BATTERY PACK FOR 1.5 HRS MINIMUM DURATION OR APPROVED EQUAL.
EL

WI
8. COORDINATE WITH THE "AUTHORITY HAVING A JURISDICTION"
NEW SURFACE MTD. OUTDOOR LED LUMINAIRE, 40W, PRIOR TO START OF WORK.
230V, 60HZ, 5000K CCT WITH INTERGRAL PHOTOCELL,

NG
DIE-CAST ALUMINUM HOUSING, BOROSILICATE GLASS 9. CONTRACTOR TO SUBMIT AT LEAST THREE (3) LIGHTING

DRAWI
LENS, IP-65, MTD. 2250mm AFFL MANUFACTURERS FOR SAUDI ARAMCO REVIEW, SELECTION &
APPROVAL.

NEW LIGHT & FAN SWITCH, BS-TYPE, 20A, 250VAC, 60Hz,


ONE-GANG 1-WAY, WITH FLUSH MTD, SMOOTH WHITE
FINISHED DEVICE & FACEPLATE, SCREW CAP

S
THI
NEW LIGHT & FAN SWITCH, BS-TYPE, 20A, 250VAC, 60Hz, REFERENCE DRAWINGS
TWO-GANG 2-WAY, WITH FLUSH MTD, SMOOTH WHITE
DWG. CONTROL FOR J.O.BSP-108 HE-110982

FROM
FINISHED DEVICE & FACEPLATE, SCREW CAP
LETTER DENOTES SWITCH CONTROL EXISTING POWER (AREA-1) LAYOUT HA-110969 SHT.001
PROPOSED POWER (AREA-1) LAYOUT HA-110969 SHT.002
EXT'G./PROP. POWER (AREA-2) LAYOUT HA-110969 SHT.003

NED
EXT'G./PROP. POWER SITE PLAN (AREA-3) HA-110969 SHT.004

OBTAI
EXT'G./PROP. POWER (AREA-3) LAYOUT HA-110969 SHT.005

P EXT'G./PROP. POWER (AREA-4) LAYOUT HA-110969 SHT.006


EXT'G. LIGHTING (AREA-1) LAYOUT HA-110970 SHT.001
EXT'G./PROP. LIGHTING (AREA-2) LAYOUT HA-110970 SHT.003

BE
P" EXT'G./PROP. LIGHTING (AREA-3) LAYOUT HA-110970 SHT.004

PART,SHALL
PANEL BOARD LOAD SCHEDULE HA-110971 SHT.001
EL ONE LINE DIAGRAM HA-110972 SHT.001
MISCELLANEOUS DETAILS-1 HA-110973 SHT.001
S
MISCELLANEOUS DETAILS-2 HA-110973 SHT.002
E X IT

N
SITTING AREA

I
(EXISTING) P"

FULL,OR
WAITING R-04
AREA
Q
EL

EL
E X IT

S S S

N
.

EL EL
3

OFFICE
8

S R-01

I
HALLWAY

ON
ACCU

T
C-24
Q'

REPRODUCTI
R-05 PB-R05 LP

PB-R05 GRASS GRASS

R
c d EXIT EXIT
b
BRICKS
GRASS

RECEPTION T
C-20 a SMOKING
SHELTER
BRICK PAVERS
(DROP OFF)

PB-R05

SAUDIARAMCO.NO
GRASS
$

W ALKW AY
$

STAMPED CONCRETE

PAVER
GRASS
GRASS

CK
BRI
BRICKS

EXISTING BRICK PAVERS

EXISTING
N.I.C. VOID
SITTING
AREA

EL
NEW OFFICE
NEW
COFFEE PROPOSED WALKWAY
AREA

LP

d d d b
STO.

SPACE BLDG. 3097

OFFICE

OFFICE OFFICE TR

PB

TOILET OFFICE AHU AHU

COMM.
ACCU

OFFICE
BRICK PAVER WALKWAY OFFICE

T
C-22 CHAIN-LINK FENCE (TYPE III) 35.73 11

36.794
36.07

PB-R05
CLASSROOM $
$

OF
OPEN OFFICE R-02

N.I.C. THIS AREA

PROPERTY
N.I.C.
d d d EL b b b

OFFICE
K E Y P L A N
CLASSROOM
NOT TO SCALE
N.I.C. R-03

SOLE
THE
c c c a a a

ARE N
MALE TOILET

HEREI
EXISTING
VOID
PANTRY SPACE
0 1.0 2.0 3.0 4.0 5.0

METERS
EL

NED
N.I.C. c c c a a EL a SCALE: 1 : 50M

CONTAI
N.I.C.
REVISION VALIDATION

THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION

EXIT REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:


b
a

ON
EXIT
18U029-029
c d

NFORMATI
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) x REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

N.I.C. OFFICE 12/12/18


GCA
12/12/18
HAK ASK
12/12/18
MAI
12/12/18

REV.NO. DATE REVISION DESCRIPTION

N.I.C.

I
00 ISSUED FOR CONSTRUCTION

THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
18U029 CONSTRUCTION UNTIL CERTIFIED AND DATED

N.I.C.
SAUDI ARABIAN OIL COMPANY

AND
DRAWING TYPE

OFFICE PROP. LIGHTING (AREA-1) LAYOUT LTG

NG
RENOVATE B#3097 & NEW FIRE PROTEC

DRAWI
OFFICE
DRAWING CERTIFIED
DRILLING & WORKOVER FACILITIES
N.I.C. 1 PROPOSED LIGHTING (AREA-1) LAYOUT DATE: 12 / 12 / 2018 DHAHRAN SAUDI ARABIA
N.I.C. HA-110970
UD REF. NO. BSP-108

S
SCALE 1 :50M PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
SH 002

24-DEC-2018 13:50
H28 P HA-110970 002 00
ALSAAH0A J:\2011-2020\2018\BUILDINGS\18-dh-b3097\18-BSP-108-DCC\H110970002V00.dgn Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-01