Professional Documents
Culture Documents
98
02.98 7.4 Main spindle control with analog interface
!!!!!!!!!
1) Interface X432 can, depending on the version, be used as spindle encoder input for positioning, or
as WSG interface (rotor position output to the NC).
Main spindle
control with
analog setpoint in-
terface M3 / 0.8 Nm
1)
X1 X2
IR M
56 A91
14 M
24 A92
0.8 Nm 8 M
663 289
65 A11
81 A21
E1 A31
E2 A41
E3 A51
E4 A61
E5 672
E6 673
E7 674
E8
E9 AS1
9 AS2
2)
+ P –
7
Software
Version label
M3 / 0.8 Nm
Figure 7-5
Note
When using non–PELV circuits connected to terminals AS1, AS2, the connec-
tor must be prevented from being incorrectly inserted using plug coding (refer
to EN60204–1, Section 6.4).
Order No. of the coding, refer to Catalog NC 60.1.
Only PELV circuits may be connected at connector X432, pin15 or X433 pin3
(FR–).
!!!!!!!!!
1) Interface X432 can either be used as spindle encoder input for positioning or as WSG interface
(rotor position output to the NC).
2) Only available for Order No. 6SN1121–0BA11–0AA1.
Positioning on
Terminal selected: The setpoint is enabled (analog setpoint or oscillation setpoint)
When selected, the internal closed–loop position control is selected and the spindle
7
is moved into the required position.
Position reference value 1–4 Using these terminals, a total of 4 parameterizable position reference values can be
(max. 2 terminals) entered.
Incremental positioning When selected, the spindle moves from the actual position–controlled position
through a specified position difference.
Spindle re–synchronization The spindle is re–referenced: This is necessary after every mechanical gearbox
stage changeover.
C axis Changeover to a finer C–axis setpoint normalization.
Note: Only setpoint input 2 (terminal 24–8) is evaluated.
HPC axis 1) Changeover to High Precision C axis mode; i.e. finer setpoint normalization and
higher speed control loop dynamic performance with a lower functional scope (only
E1 to E6 are evaluated).
Note: Only setpoint input 2 (terminal 24–8) is evaluated.
Speed setpoint smoothing 1) The speed setpoint smoothing is activated with a time constant, which can be para-
meterized.
Suppress fault 11 1) Fault message 11 is suppressed (speed controller at its limit) for the function
”travel to endstop”.
Inverter clock frequency change- It is possible to select different inverter clock frequencies using the select terminals.
over 1)
!!!!!!!!!
1) Only these terminal functions are available in the HPC axis mode.
The select relay terminals A11 to A61 (max. 6) can be freely programmed. A
control parameter is assigned to every select relay, in which the code number of
the selected function is entered.
Table 7-10
7 Relay, star operation An external auxiliary contactor can be controlled via this relay to changeover the winding into
the star configuration.
Relay, delta operation An external auxiliary contactor can be controlled via this relay to changeover the winding into
the delta configuration.
!!!!!!!!!
1) The signals/messages are only available in the HPC–axis mode.
Table 7-11
Table 7-12
In/Is6/Imax In/Is6/Imax In/Is6/Imax In/Is6/Imax In/Is6/Imax In/Is6/Imax In/Is6/Imax In/Is6/Imax
in A in A in A in A in A in A in A in A
Code Power fT fT fT fT fT fT fT fT
No. module 3.20 kHz 4.70 kHz 6.30 kHz 7.80 kHz 2.80 kHz 3.90 kHz 5.00 kHz 5.90 kHz
type
6 LT 50A 24/32/32 20/26/26 15/20/20 10/14/14 24/32/32 22/29/29 19/25/25 16/21/21
7 LT 80A 30/40/51 26/34/44 21/28/36 17/23/29 30/40/51 28/37/48 25/33/42 22/30/38
13 LT 108A 45/60/76 39/52/65 32/43/54 26/34/43 45/60/76 42/56/71 37/50/63 34/45/57
8 LT 120A 45/60/76 39/52/65 32/43/54 26/34/43 45/60/76 42/56/71 37/50/63 34/45/57
9 LT 160A 60/80/102 51/68/86 41/54/69 31/42/53 60/80/102 56/74/95 49/65/83 43/58/73
10 LT 200A 85/110/127 73/95/109 60/78/90 48/63/72 85/110/127 79/103/119 71/91/106 63/82/95
11 LT 300A 120/150/193 101/127/163 81/102/131 62/78/101 120/150/193 111/139/179 98/122/157 86/108/139
12 LT 400A 200/250/257 169/211/217 135/169/174 104/130/134 200/250/257 185/232/238 163/203/209 144/180/185
up to including FW 2.xx
from FW 3.0
For special motors with a lower leakage induction, it may be necessary to pro-
vide a series reactor and/or increase the inverter clock frequency of the drive
converter. From experience, motors with low leakage induction are those which
can achieve high stator frequencies (maximum motor stator frequency> 300 Hz)
or motors with a higher rated current (rated current > 85 A).