PROJECT : JABEL HAFFET BASE PUMPING STATION

Subject EXTERNAL PRESSURE DROP CALCULATION FOR PACKAGE UNIT


Designed : SR Date : Sep-18 Checked: SR Date : Sep-18

DUCT SIZE (mm) ACTUAL


VELOCITY DUCT FITTING PRESSURE CUMULATIVE ASHRAE
AIR FLOW VELOCITY PRESSURE
ITEM DUCT ELEMENT PRESSURE LENGTH LOSS LOSS LENGTH FITTING
(l/s) EQUIVALENT (m/s) DROP
WIDTH HEIGHT (Pa) (m) COEFFICIENT (Pa) (m) NO.
DIAMETER (Pa/m)
1 Return Grille - - - - - - - - - 25 0
2 Screen 6625 1200 1100 - 5.0 15 0 0.28 - 4.2 0.0 CR6-1
3 Fire Damper 6625 1200 1100 - 5.0 15 0 0.19 - 2.9 0.0 CD9-1
4 Motorized Damper 6625 1200 1100 - 5.0 15 0 0.18 - 2.7 0.0 CR9-4
5 Duct 1 6625 1200 1100 - 5.0 - 0.6 - 0.18 0.1 0.6
6 Bend 6625 1200 1100 - 5.0 15 0 0.21 - 3.2 0.6 CR3-3
7 Duct 2 6625 1100 1200 - 5.0 - 1.5 - 0.29 0.4 2.1
8 Branch Converging 1095 600 600 - 3.5 7 0 0.21 - 1.5 2.1 ER5-3
9 Bend 7720 1100 1200 - 6.0 22 0 0.21 - 4.5 2.1 CR3-3
10 Enlargement 7720 - - - 6.0 22 0 0.24 - 5.2 2.1 SR4-1
11 Attenuator 7720 1100 1200 - - 0 - - 50 2.1
12 Reduction 7720 - - - 6.0 22 0 0.02 - 0.4 2.1 SR4-1
13 Duct 3 7720 1100 1200 - 6.0 - 0.5 - 0.25 0.1 2.6
14 Bend 7720 1100 1200 - 6.0 22 0 0.20 - 4.3 2.6 CR3-3
15 Duct 4 7720 1100 1200 - 6.0 - 1.0 - 0.25 0.3 3.6
16 Branch Converging 7720 1100 1200 - 6.0 22 0 0.83 - 17.9 3.6 ER5-3
17 Plenum 7720 1100 1200 - 6.0 22 0 - - 25.0 3.6 SR1-1
18 Duct 5 7720 1100 1200 - 6.0 - 0.8 - 0.25 0.2 4.4
19 Motorized Damper 7720 1100 1200 - 6.0 22 0 0.18 - 3.9 4.4 CR9-4
20 Flexible Connection 7720 700 700 - - - 0 - - 10.0 4.4
21 PU 01 7720 - - - - - 0.0 4.4
22 Flexible Connection 7720 2000 1600 - - - 0 - - 10.0 4.4
23 Duct 6 7720 1100 1200 - 6.0 - 0.8 - 0.30 0.2 5.2
24 Motorized Damper 7720 1100 1200 - 6.0 22 0 0.18 - 3.9 5.2 CR9-4
25 Plenum 7720 1100 1200 - 6.0 22 0 - - 25.0 5.2 SR1-1
26 Branch Diverging 7720 1100 1200 - 6.0 22 0 0.68 - 14.7 5.2 SR5-13
27 Enlargement 7720 - - - 6.0 22 0 0.04 - 0.9 5.2 SR4-1
28 Attenuator 7720 1100 1200 - - 0 - - 50 5.2
29 Reduction 7720 - - - 6.0 22 0 0.24 - 5.2 5.2 SR4-1
30 Duct 7 7720 1100 1200 - 6.0 - 1.5 - 0.30 0.5 6.7
31 Fire Damper 7720 1100 1200 - 6.0 22 0 0.19 - 4.1 6.7 CR9-6
32 Bend 7720 1100 1200 - 6.0 22 0 0.21 - 4.5 6.7 CR3-3
33 Duct 8 7720 1100 1200 - 6.0 - 0.6 - 0.25 0.2 7.3
34 Bend 7720 1100 1200 - 6.0 22 0 0.21 - 4.5 7.3 CR3-3
35 Duct 9 7720 1100 1200 - 6.0 - 1.4 - 0.25 0.4 8.7
36 Branch Diverging 136 400 200 - 2.1 3 0 0.04 - 0.1 8.7 SR5-13
37 Bend 7584 1100 1100 - 5.9 21 0 0.20 - 4.2 8.7 CR3-3
38 Duct 10 7584 1100 1100 - 5.9 - 3 - 0.25 0.8 11.7
39 Branch Diverging 1288 600 550 - 3.8 9 0 0.06 - 0.5 11.7 SR5-13
40 Bend 6296 1100 1100 - 5.7 19 0 0.20 - 3.9 11.7 CR3-3
41 Duct 11 6296 1100 1100 - 5.7 - 2.5 - 0.25 0.6 14.2
42 Branch Diverging 4955 1000 1000 - 5.3 17 0 0.28 - 4.7 14.2 SR5-13
43 Reduction 1341 - - - 5.2 16 0 2.92 - 47.4 14.2 SR4-1
44 Duct 12 1341 600 600 3.8 - 7.6 - 0.25 1.9 21.8
45 Branch Diverging 408 600 250 - 2.8 5 0 0.06 - 0.3 21.8 SR5-13
46 Branch Diverging 932 600 450 - 3.6 8 0 0.55 - 4.3 21.8 SR5-13
47 Duct 13 932 600 450 - 3.6 - 1.6 - 0.25 0.4 23.4
48 Branch Diverging 242 500 200 - 2.5 4 0 0.08 - 0.3 23.4 SR5-13
49 Duct 14 690 500 450 - 3.3 - 6.3 - 0.30 1.9 29.7
50 Branch Diverging 514 500 350 - 3.0 5 0 0.36 - 1.9 29.7 SR5-13
51 Branch Diverging 176 400 200 - 2.3 3 0 0.32 - 1.0 29.7 SR5-13
52 Duct 15 176 400 200 - 2.3 - 2.7 - 0.30 0.8 32.4
53 Branch Diverging 49 400 150 - 1.6 2 0 2.93 - 4.5 32.4 SR5-13
54 Duct 16 128 400 150 - 2.1 - 1.4 - 0.30 0.4 33.8
55 Volume Control Damper 128 400 150 - 2.1 3 0 0.18 - 0.5 33.8 CR9-4
56 Supply Diffuser 128 - - - 25.0 33.8
SUB-TOTAL 391
15% SAFETY 59
TOTAL PRESSURE LOSS (Pa) 450

Notes:
Fitting loss coefficients as per ASHRAE Fundamentals 2009
Pressure drop across attenuators, louvers, diffusers and dampers is an estimate, to be confirmed by the manufacturer.