Professional Documents
Culture Documents
21
PVsyst TRIAL
PVsyst - Simulation report
Stand alone system
Project: 50_m3/hr_RO
Variant: New simulation variant
Stand alone system with batteries
System power: 19.95 kWp
PVsyst TRIAL
‘Awāfī - United Arab Emirates
PVsyst TRIAL
PVsyst TRIAL
Author
PVsyst TRIAL
Project: 50_m3/hr_RO
Variant: New simulation variant
PVsyst V7.2.21
VC0, Simulation date:
28/11/22 15:20
PVsyst TRIAL
with v7.2.21
Project summary
Geographical Site Situation Project settings
‘Awāfī Latitude 24.30 °N Albedo 0.20
United Arab Emirates Longitude 52.56 °E
Altitude 9m
Time zone UTC+4
Meteo data
‘Awāfī
Meteonorm 8.0 (1992-2004), Sat=100% - Synthetic
System summary
PVsyst TRIAL
Stand alone system Stand alone system with batteries
System information
PV Array Battery pack
Nb. of modules 38 units Technology Lead-acid, vented, plates
Pnom total 19.95 kWp Nb. of units 48 units
Voltage 48 V
Capacity 2112 Ah
Results summary
Available Energy 36433 kWh/year Specific production 1826 kWh/kWp/year Perf. Ratio PR 69.53 %
PVsyst TRIAL
Used Energy 30271 kWh/year
2
3
5
Loss diagram 6
Special graphs 7
PVsyst TRIAL
PVsyst TRIAL
28/11/22 PVsyst Evaluation mode Page 2/7
Project: 50_m3/hr_RO
Variant: New simulation variant
PVsyst V7.2.21
VC0, Simulation date:
28/11/22 15:20
PVsyst TRIAL
with v7.2.21
General parameters
Stand alone system Stand alone system with batteries
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 24 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate
User's needs
Ext. defined as file
Yearly demand.csv
PVsyst TRIAL
Jan. Feb. Mar. Apr. May June July Aug. Sep. Oct. Nov. Dec. Year
2325 2100 2697 2610 2697 2610 2697 2697 2610 2697 2250 2325 30315 kWh
PV Array Characteristics
PV module Battery
Manufacturer Generic Manufacturer Generic
Model JAM72-D30-525-MB Model Enersol 250
(Original PVsyst database) Technology Lead-acid, vented, plates
Unit Nom. Power 525 Wp Nb. of units 12 in parallel x 4 in series
Number of PV modules 38 units Discharging min. SOC 33.8 %
Nominal (STC) 19.95 kWp Stored energy 67.1 kWh
Modules 19 Strings x 2 In series Battery Pack Characteristics
PVsyst TRIAL
At operating cond. (50°C) Voltage 48 V
Pmpp 18.31 kWp Nominal Capacity 2112 Ah (C10)
U mpp 75 V Temperature Fixed 40 °C
I mpp 245 A
Total PV power
PVsyst TRIAL
Nominal (STC) 20 kWp
Total 38 modules
Module area 98.2 m²
Array losses
Thermal Loss factor DC wiring losses Serie Diode Loss
Module temperature according to irradiance Global array res. 5.0 mΩ Voltage drop 0.7 V
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC Loss Fraction 0.9 % at STC
Uv (wind) 0.0 W/m²K/m/s
PVsyst TRIAL
28/11/22 PVsyst Evaluation mode Page 3/7
Project: 50_m3/hr_RO
Variant: New simulation variant
PVsyst V7.2.21
VC0, Simulation date:
28/11/22 15:20
PVsyst TRIAL
with v7.2.21
Array losses
IAM loss factor
Incidence effect (IAM): User defined profile
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL
28/11/22 PVsyst Evaluation mode Page 4/7
Project: 50_m3/hr_RO
Variant: New simulation variant
PVsyst V7.2.21
VC0, Simulation date:
28/11/22 15:20
PVsyst TRIAL
with v7.2.21
Main results
System Production
Available Energy 36433 kWh/year Specific production 1826 kWh/kWp/year
Used Energy 30271 kWh/year Performance Ratio PR 69.53 %
Excess (unused) 0 kWh/year Solar Fraction SF 99.86 %
Loss of Load Battery aging (State of Wear)
Time Fraction 0.1 % Cycles SOW 86.9 %
Missing Energy 43 kWh/year Static SOW 43.4 %
Battery lifetime 1.8 years
PVsyst TRIAL
PVsyst TRIAL
Balances and main results
PVsyst TRIAL
November 132.9 170.5 2946 0.000 0.00 2250 2250 1.000
December 120.7 160.9 2832 0.074 0.00 2325 2325 1.000
Year 2022.2 2145.0 36433 0.149 43.50 30271 30315 0.999
Legends
GlobHor Global horizontal irradiation E_User Energy supplied to the user
GlobEff Effective Global, corr. for IAM and shadings E_Load Energy need of the user (Load)
E_Avail Available Solar Energy SolFrac Solar fraction (EUsed / ELoad)
EUnused Unused energy (battery full)
E_Miss Missing energy
PVsyst TRIAL
28/11/22 PVsyst Evaluation mode Page 5/7
Project: 50_m3/hr_RO
Variant: New simulation variant
PVsyst V7.2.21
VC0, Simulation date:
28/11/22 15:20
PVsyst TRIAL
with v7.2.21
Loss diagram
2022 kWh/m² Global horizontal irradiation
+7.9% Global incident in coll. plane
-0.70%
-2.10%
-10.72% PV loss due to temperature
PVsyst TRIAL
0.00% Converter Loss due to power threshold
0.00% Converter Loss over nominal conv. voltage
0.00% Converter Loss due to voltage threshold
36433 kWh Converter losses (effic, overload)
Direct use Stored Battery Storage
64.3% 35.7%
+0.13% Battery Stored Energy balance
Missing
energy
-7.75% Battery efficiency loss
0.14%
43.5 kWh -1.11% Charge/Disch. Current Efficiency Loss
PVsyst TRIAL
30271 kWh Energy supplied to the user
PVsyst TRIAL
28/11/22 PVsyst Evaluation mode Page 6/7
Project: 50_m3/hr_RO
Variant: New simulation variant
PVsyst V7.2.21
VC0, Simulation date:
28/11/22 15:20
PVsyst TRIAL
with v7.2.21
Special graphs
Daily Input/Output diagram
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL
28/11/22 PVsyst Evaluation mode Page 7/7