You are on page 1of 7

Version 7.2.

21

PVsyst TRIAL
PVsyst - Simulation report
Stand alone system

Project: 50_m3/hr_RO
Variant: New simulation variant
Stand alone system with batteries
System power: 19.95 kWp

PVsyst TRIAL
‘Awāfī - United Arab Emirates

PVsyst TRIAL

PVsyst TRIAL
Author

PVsyst TRIAL
Project: 50_m3/hr_RO
Variant: New simulation variant

PVsyst V7.2.21
VC0, Simulation date:
28/11/22 15:20

PVsyst TRIAL
with v7.2.21

Project summary
Geographical Site Situation Project settings
‘Awāfī Latitude 24.30 °N Albedo 0.20
United Arab Emirates Longitude 52.56 °E
Altitude 9m
Time zone UTC+4

Meteo data
‘Awāfī
Meteonorm 8.0 (1992-2004), Sat=100% - Synthetic

System summary

PVsyst TRIAL
Stand alone system Stand alone system with batteries

PV Field Orientation User's needs


Fixed plane Ext. defined as file
Tilt/Azimuth 24 / 0 ° Yearly demand.csv

System information
PV Array Battery pack
Nb. of modules 38 units Technology Lead-acid, vented, plates
Pnom total 19.95 kWp Nb. of units 48 units
Voltage 48 V
Capacity 2112 Ah

Results summary
Available Energy 36433 kWh/year Specific production 1826 kWh/kWp/year Perf. Ratio PR 69.53 %

PVsyst TRIAL
Used Energy 30271 kWh/year

Project and results summary


Table of contents

General parameters, PV Array Characteristics, System losses


Main results
Solar Fraction SF 99.86 %

2
3
5
Loss diagram 6
Special graphs 7

PVsyst TRIAL

PVsyst TRIAL
28/11/22 PVsyst Evaluation mode Page 2/7
Project: 50_m3/hr_RO
Variant: New simulation variant

PVsyst V7.2.21
VC0, Simulation date:
28/11/22 15:20

PVsyst TRIAL
with v7.2.21

General parameters
Stand alone system Stand alone system with batteries

PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 24 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate

User's needs
Ext. defined as file
Yearly demand.csv

PVsyst TRIAL
Jan. Feb. Mar. Apr. May June July Aug. Sep. Oct. Nov. Dec. Year
2325 2100 2697 2610 2697 2610 2697 2697 2610 2697 2250 2325 30315 kWh

PV Array Characteristics
PV module Battery
Manufacturer Generic Manufacturer Generic
Model JAM72-D30-525-MB Model Enersol 250
(Original PVsyst database) Technology Lead-acid, vented, plates
Unit Nom. Power 525 Wp Nb. of units 12 in parallel x 4 in series
Number of PV modules 38 units Discharging min. SOC 33.8 %
Nominal (STC) 19.95 kWp Stored energy 67.1 kWh
Modules 19 Strings x 2 In series Battery Pack Characteristics

PVsyst TRIAL
At operating cond. (50°C) Voltage 48 V
Pmpp 18.31 kWp Nominal Capacity 2112 Ah (C10)
U mpp 75 V Temperature Fixed 40 °C
I mpp 245 A

Controller Battery Management control


Manufacturer Generic Threshold commands as Battery voltage
Model Tristar TS MPPT 30 - 48V Charging 55.2 / 49.7 V
Nb. units 7 units Corresp. SOC 0.92 / 0.78
Technology MPPT converter Discharging 47.0 / 49.0 V
Temp coeff. -5.0 mV/°C/Elem. Corresp. SOC 0.28 / 0.61
Converter
Maxi and EURO efficiencies 98.5 / 97.7 %

Total PV power

PVsyst TRIAL
Nominal (STC) 20 kWp
Total 38 modules
Module area 98.2 m²

Array losses
Thermal Loss factor DC wiring losses Serie Diode Loss
Module temperature according to irradiance Global array res. 5.0 mΩ Voltage drop 0.7 V
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC Loss Fraction 0.9 % at STC
Uv (wind) 0.0 W/m²K/m/s

Module Quality Loss Module mismatch losses Strings Mismatch loss


Loss Fraction -0.8 % Loss Fraction 0.6 % at MPP Loss Fraction 0.1 %

PVsyst TRIAL
28/11/22 PVsyst Evaluation mode Page 3/7
Project: 50_m3/hr_RO
Variant: New simulation variant

PVsyst V7.2.21
VC0, Simulation date:
28/11/22 15:20

PVsyst TRIAL
with v7.2.21

Array losses
IAM loss factor
Incidence effect (IAM): User defined profile

0° 30° 50° 65° 70° 75° 80° 85° 90°


1.000 1.000 0.989 0.945 0.890 0.821 0.681 0.439 0.000

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL
28/11/22 PVsyst Evaluation mode Page 4/7
Project: 50_m3/hr_RO
Variant: New simulation variant

PVsyst V7.2.21
VC0, Simulation date:
28/11/22 15:20

PVsyst TRIAL
with v7.2.21

Main results
System Production
Available Energy 36433 kWh/year Specific production 1826 kWh/kWp/year
Used Energy 30271 kWh/year Performance Ratio PR 69.53 %
Excess (unused) 0 kWh/year Solar Fraction SF 99.86 %
Loss of Load Battery aging (State of Wear)
Time Fraction 0.1 % Cycles SOW 86.9 %
Missing Energy 43 kWh/year Static SOW 43.4 %
Battery lifetime 1.8 years

Normalized productions (per installed kWp) Performance Ratio PR

PVsyst TRIAL

PVsyst TRIAL
Balances and main results

GlobHor GlobEff E_Avail EUnused E_Miss E_User E_Load SolFrac


kWh/m² kWh/m² kWh kWh kWh kWh kWh ratio
January 130.2 170.9 3026 0.000 0.00 2325 2325 1.000
February 134.9 160.5 2823 0.000 0.00 2100 2100 1.000
March 160.0 171.1 2974 0.075 43.50 2653 2697 0.984
April 178.6 176.3 3003 0.000 0.00 2610 2610 1.000
May 207.9 192.0 3199 0.000 0.00 2697 2697 1.000
June 212.8 190.4 3152 0.000 0.00 2610 2610 1.000
July 208.0 189.3 3119 0.000 0.00 2697 2697 1.000
August 196.1 189.2 3112 0.000 0.00 2697 2697 1.000
September 179.0 187.7 3115 0.000 0.00 2610 2610 1.000
October 161.1 186.2 3134 0.000 0.00 2697 2697 1.000

PVsyst TRIAL
November 132.9 170.5 2946 0.000 0.00 2250 2250 1.000
December 120.7 160.9 2832 0.074 0.00 2325 2325 1.000
Year 2022.2 2145.0 36433 0.149 43.50 30271 30315 0.999

Legends
GlobHor Global horizontal irradiation E_User Energy supplied to the user
GlobEff Effective Global, corr. for IAM and shadings E_Load Energy need of the user (Load)
E_Avail Available Solar Energy SolFrac Solar fraction (EUsed / ELoad)
EUnused Unused energy (battery full)
E_Miss Missing energy

PVsyst TRIAL
28/11/22 PVsyst Evaluation mode Page 5/7
Project: 50_m3/hr_RO
Variant: New simulation variant

PVsyst V7.2.21
VC0, Simulation date:
28/11/22 15:20

PVsyst TRIAL
with v7.2.21

Loss diagram
2022 kWh/m² Global horizontal irradiation
+7.9% Global incident in coll. plane

-1.70% IAM factor on global

2145 kWh/m² * 98 m² coll. Effective irradiation on collectors

efficiency at STC = 20.34% PV conversion

42824 kWh Array nominal energy (at STC effic.)


-0.72% PV loss due to irradiance level

PVsyst TRIAL +0.75%

-0.70%

-2.10%
-10.72% PV loss due to temperature

Module quality loss

Mismatch loss, modules and strings

Ohmic wiring loss


0.00% Unused energy (battery full)
37174 kWh Effective energy at the output of the array

-1.99% Converter Loss during operation (efficiency)


0.00% Converter Loss over nominal conv. power

PVsyst TRIAL
0.00% Converter Loss due to power threshold
0.00% Converter Loss over nominal conv. voltage
0.00% Converter Loss due to voltage threshold
36433 kWh Converter losses (effic, overload)
Direct use Stored Battery Storage
64.3% 35.7%
+0.13% Battery Stored Energy balance
Missing
energy
-7.75% Battery efficiency loss
0.14%
43.5 kWh -1.11% Charge/Disch. Current Efficiency Loss

-8.34% Gassing Current (electrolyte dissociation)

-0.75% Battery Self-discharge Current

PVsyst TRIAL
30271 kWh Energy supplied to the user

30315 kWh Energy need of the user (Load)

PVsyst TRIAL
28/11/22 PVsyst Evaluation mode Page 6/7
Project: 50_m3/hr_RO
Variant: New simulation variant

PVsyst V7.2.21
VC0, Simulation date:
28/11/22 15:20

PVsyst TRIAL
with v7.2.21

Special graphs
Daily Input/Output diagram

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL
28/11/22 PVsyst Evaluation mode Page 7/7

You might also like