PVsyst - Simulation report
Grid-Connected System

Project: prueba pro


Variant: variante 1
No 3D scene defined, no shadings
System power: 61.0 kWp

PVsyst TRIAL
Barrio Rosario - Colombia

PVsyst TRIAL

PVsyst TRIAL
Author

PVsyst TRIAL
Project: prueba pro
Variant: variante 1

PVsyst V7.4.4
VC0, Simulation date:
25/11/23 12:04

PVsyst TRIAL
with v7.4.4

Project summary
Geographical Site Situation Project settings
Barrio Rosario Latitude 10.99 °N Albedo 0.20
Colombia Longitude -74.79 °W
Altitude 35 m
Time zone UTC-5

Meteo data
Barrio Rosario
PVGIS api TMY

System summary

PVsyst TRIAL
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation Near Shadings User's needs


Fixed plane No Shadings Unlimited load (grid)
Tilt/Azimuth 30 / 0 °

System information
PV Array Inverters
Nb. of modules 112 units Nb. of units 8 units
Pnom total 61.0 kWp Pnom total 48.0 kWac
Pnom ratio 1.272

Results summary
Produced Energy 104988 kWh/year Specific production 1720 kWh/kWp/year Perf. Ratio PR 83.48 %

PVsyst TRIAL
Project and results summary

Horizon definition
Main results
Loss diagram
Table of contents

General parameters, PV Array Characteristics, System losses


2
3
4
5
6
Predef. graphs 7
P50 - P90 evaluation 8
Single-line diagram 9

PVsyst TRIAL

PVsyst TRIAL
25/11/23 PVsyst Evaluation mode Page 2/9
Project: prueba pro
Variant: variante 1

PVsyst V7.4.4
VC0, Simulation date:
25/11/23 12:04

PVsyst TRIAL
with v7.4.4

General parameters
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 30 / 0 ° Diffuse Imported
Circumsolar separate

Horizon Near Shadings User's needs


Average Height 4.3 ° No Shadings Unlimited load (grid)

PVsyst TRIAL
PV Array Characteristics
PV module Inverter
Manufacturer Generic Manufacturer Generic
Model LR5-72HBD-545M G2 Bifacial Model SUN2000-6KTL-M1-400V
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 545 Wp Unit Nom. Power 6.00 kWac
Number of PV modules 112 units Number of inverters 8 units
Nominal (STC) 61.0 kWp Total power 48.0 kWac
Modules 8 string x 14 In series Operating voltage 140-980 V
At operating cond. (50°C) Max. power (=>47°C) 6.60 kWac
Pmpp 55.9 kWp Pnom ratio (DC:AC) 1.27
U mpp 527 V Power sharing within this inverter
I mpp 106 A

PVsyst TRIAL
Total PV power Total inverter power
Nominal (STC) 61 kWp Total power 48 kWac
Total 112 modules Max. power 52.8 kWac
Module area 289 m² Number of inverters 8 units
Cell area 269 m² Pnom ratio 1.27

Array losses
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 82 mΩ Loss Fraction -0.8 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s

Module mismatch losses


Loss Fraction 2.0 % at MPP

PVsyst TRIAL
IAM loss factor
Incidence effect (IAM): User defined profile

0° 25° 45° 60° 65° 70° 75° 80° 90°


1.000 1.000 0.995 0.962 0.936 0.903 0.851 0.754 0.000

PVsyst TRIAL
25/11/23 PVsyst Evaluation mode Page 3/9
Project: prueba pro
Variant: variante 1

PVsyst V7.4.4
VC0, Simulation date:
25/11/23 12:04

PVsyst TRIAL
with v7.4.4

Horizon definition
Línea de horizonte en Barrio Rosario

Average Height 4.3 ° Albedo Factor 0.99


Diffuse Factor 1.00 Albedo Fraction 100 %

Horizon profile

Azimuth [°] -172 -40 40 123


Height [°] 19.2 0.0 0.0 0.0

Sun Paths (Height / Azimuth diagram)

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL
25/11/23 PVsyst Evaluation mode Page 4/9
Project: prueba pro
Variant: variante 1

PVsyst V7.4.4
VC0, Simulation date:
25/11/23 12:04

PVsyst TRIAL
with v7.4.4

Main results
System Production
Produced Energy 104988 kWh/year Specific production 1720 kWh/kWp/year
Perf. Ratio PR 83.48 %

Normalized productions (per installed kWp) Performance Ratio PR

PVsyst TRIAL
Balances and main results

GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_Grid PR


kWh/m² kWh/m² °C kWh/m² kWh/m² kWh kWh ratio
January 184.6 38.58 26.64 230.4 227.6 11937 11640 0.828

PVsyst TRIAL
February 184.2 37.28 26.62 209.9 207.0 10838 10567 0.825
March 198.1 56.77 26.39 198.9 195.6 10358 10096 0.832
April 182.3 75.01 27.07 164.4 161.0 8609 8382 0.835
May 200.8 66.17 27.42 162.0 157.5 8491 8265 0.836
June 169.6 71.48 26.95 132.2 127.8 6966 6769 0.839
July 191.6 65.96 27.47 150.3 145.4 7878 7659 0.835
August 175.7 75.34 27.23 151.6 147.8 7989 7775 0.840
September 147.7 81.94 27.04 140.6 137.5 7442 7241 0.844
October 145.1 69.78 26.96 152.3 149.4 8021 7801 0.839
November 128.4 59.78 25.92 147.6 145.2 7806 7597 0.843
December 173.2 45.08 26.30 220.2 217.5 11482 11197 0.833
Year 2081.2 743.16 26.84 2060.3 2019.2 107818 104988 0.835

PVsyst TRIAL
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings

PVsyst TRIAL
25/11/23 PVsyst Evaluation mode Page 5/9
Project: prueba pro
Variant: variante 1

PVsyst V7.4.4
VC0, Simulation date:
25/11/23 12:04

PVsyst TRIAL
with v7.4.4

Loss diagram
2081 kWh/m² Global horizontal irradiation

-1.00% Global incident in coll. plane


-0.13% Far Shadings / Horizon
-1.87% IAM factor on global

2019 kWh/m² * 289 m² coll. Effective irradiation on collectors

efficiency at STC = 21.12% PV conversion

123372 kWh Array nominal energy (at STC effic.)

PVsyst TRIAL
-0.75% PV loss due to irradiance level

-9.79% PV loss due to temperature

+0.75% Module quality loss

-2.00% Module array mismatch loss

-1.15% Ohmic wiring loss


107818 kWh Array virtual energy at MPP
-2.43% Inverter Loss during operation (efficiency)
0.00% Inverter Loss over nominal inv. power
0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage

PVsyst TRIAL
-0.01% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
-0.19% Night consumption
104988 kWh Available Energy at Inverter Output
104988 kWh Energy injected into grid

PVsyst TRIAL

PVsyst TRIAL
25/11/23 PVsyst Evaluation mode Page 6/9
Project: prueba pro
Variant: variante 1

PVsyst V7.4.4
VC0, Simulation date:
25/11/23 12:04

PVsyst TRIAL
with v7.4.4

Predef. graphs
Diagrama entrada/salida diaria

PVsyst TRIAL

PVsyst TRIAL Distribución de potencia de salida del sistema

PVsyst TRIAL

PVsyst TRIAL
25/11/23 PVsyst Evaluation mode Page 7/9
Project: prueba pro
Variant: variante 1

PVsyst V7.4.4
VC0, Simulation date:
25/11/23 12:04

PVsyst TRIAL
with v7.4.4

P50 - P90 evaluation


Meteo data Simulation and parameters uncertainties
Source PVGIS api TMY PV module modelling/parameters 1.0 %
Kind Not defined Inverter efficiency uncertainty 0.5 %
Year-to-year variability(Variance) 0.0 % Soiling and mismatch uncertainties 1.0 %
Specified Deviation Degradation uncertainty 1.0 %

Global variability (meteo + system) Annual production probability


Variability (Quadratic sum) 1.8 % Variability 1.89 MWh
P50 104.99 MWh
P90 102.56 MWh
P95 101.88 MWh

PVsyst TRIAL
Probability distribution

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL
25/11/23 PVsyst Evaluation mode Page 8/9
PVsyst V7.4.4
VC0, Simulation date:
25/11/23 12:04

PVsyst TRIAL
with v7.4.4

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL

PVsyst TRIAL