PVsyst - Simulation report
Grid-Connected System
PVsyst TRIAL
PVsyst TRIAL
Author
PVsyst TRIAL
Project: 50KW solar Power Plant at Nagpur
Variant: New simulation variant
PVsyst V7.3.2
VC0, Simulation date:
27/03/23 09:47
PVsyst TRIAL
with v7.3.2
Project summary
Geographical Site Situation Project settings
Nagpur Latitude 21.14 °N Albedo 0.20
India Longitude 79.09 °E
Altitude 300 m
Time zone UTC+5.5
Meteo data
Nagpur
Meteonorm 8.1 (1996-2015) - Synthetic
System summary
PVsyst TRIAL
Grid-Connected System Tables on a building
System information
PV Array Inverters
Nb. of modules 152 units Nb. of units 1 unit
Pnom total 50.9 kWp Pnom total 50.0 kWac
Pnom ratio 1.018
Results summary
Produced Energy 71773 kWh/year Specific production 1410 kWh/kWp/year Perf. Ratio PR 74.96 %
PVsyst TRIAL
Project and results summary
PVsyst TRIAL
PVsyst TRIAL
27/03/23 PVsyst Evaluation mode Page 2/8
Project: 50KW solar Power Plant at Nagpur
Variant: New simulation variant
PVsyst V7.3.2
VC0, Simulation date:
27/03/23 09:47
PVsyst TRIAL
with v7.3.2
General parameters
Grid-Connected System Tables on a building
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane Nb. of sheds 72 units Transposition Perez
Tilt/Azimuth 30 / 0 ° Sizes Diffuse Perez, Meteonorm
Sheds spacing 3.10 m Circumsolar separate
Collector width 1.70 m
Ground Cov. Ratio (GCR) 55.0 %
Shading limit angle
Limit profile angle 27.7 °
PVsyst TRIAL
Horizon Near Shadings User's needs
Free Horizon Linear shadings Unlimited load (grid)
PV Array Characteristics
PV module Inverter
Manufacturer Generic Manufacturer Generic
Model AXIprotect X HC MT BLK AC-335MG/120V Model PVS-50-TL
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 335 Wp Unit Nom. Power 50.0 kWac
Number of PV modules 152 units Number of inverters 3 * MPPT 33% 1 unit
Nominal (STC) 50.9 kWp Total power 50.0 kWac
Modules 8 Strings x 19 In series Operating voltage 300-950 V
At operating cond. (50°C) Max. power (=>30°C) 55.0 kWac
PVsyst TRIAL
Pmpp 46.0 kWp Pnom ratio (DC:AC) 1.02
U mpp 582 V No power sharing between MPPTs
I mpp 79 A
Array losses
Array Soiling Losses Thermal Loss factor DC wiring losses
Loss Fraction 3.0 % Module temperature according to irradiance Global array res. 123 mΩ
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
PVsyst TRIAL
Uv (wind) 0.0 W/m²K/m/s
Serie Diode Loss LID - Light Induced Degradation Module Quality Loss
Voltage drop 0.7 V Loss Fraction 2.0 % Loss Fraction -0.4 %
Loss Fraction 0.1 % at STC
PVsyst TRIAL
27/03/23 PVsyst Evaluation mode Page 3/8
Project: 50KW solar Power Plant at Nagpur
Variant: New simulation variant
PVsyst V7.3.2
VC0, Simulation date:
27/03/23 09:47
PVsyst TRIAL
with v7.3.2
System losses
Unavailability of the system Auxiliaries loss
Time fraction 2.0 %
7.3 days,
3 periods
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL
27/03/23 PVsyst Evaluation mode Page 4/8
Project: 50KW solar Power Plant at Nagpur
Variant: New simulation variant
PVsyst V7.3.2
VC0, Simulation date:
27/03/23 09:47
PVsyst TRIAL
with v7.3.2
PVsyst TRIAL
Iso-shadings diagram
PVsyst TRIAL
Orientation #1
PVsyst TRIAL
PVsyst TRIAL
27/03/23 PVsyst Evaluation mode Page 5/8
Project: 50KW solar Power Plant at Nagpur
Variant: New simulation variant
PVsyst V7.3.2
VC0, Simulation date:
27/03/23 09:47
PVsyst TRIAL
with v7.3.2
Main results
System Production
Produced Energy 71773 kWh/year Specific production 1410 kWh/kWp/year
Performance Ratio PR 74.96 %
PVsyst TRIAL
Balances and main results
PVsyst TRIAL
February 139.0 60.09 24.99 167.7 156.1 6664 6525 0.764
March 178.4 74.14 29.26 192.4 178.8 7448 7286 0.744
April 190.0 82.21 32.19 184.2 170.1 7033 6875 0.733
May 197.8 90.10 35.59 174.5 159.7 6565 6413 0.722
June 147.7 89.85 31.27 127.9 115.7 4937 4823 0.741
July 113.9 80.28 28.10 100.2 89.5 3933 3837 0.752
August 119.5 80.84 27.22 110.9 100.3 4386 4283 0.758
September 137.7 79.28 27.36 139.1 127.4 5510 5389 0.761
October 148.5 71.60 27.04 169.7 157.7 6717 6567 0.760
November 130.8 53.63 23.94 166.0 154.3 6620 6483 0.767
December 127.8 49.85 21.50 174.0 161.2 7007 6867 0.775
Year 1762.4 864.28 27.50 1880.4 1732.2 73835 71773 0.750
PVsyst TRIAL
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst TRIAL
27/03/23 PVsyst Evaluation mode Page 6/8
Project: 50KW solar Power Plant at Nagpur
Variant: New simulation variant
PVsyst V7.3.2
VC0, Simulation date:
27/03/23 09:47
PVsyst TRIAL
with v7.3.2
Loss diagram
1762 kWh/m² Global horizontal irradiation
+6.7% Global incident in coll. plane
PVsyst TRIAL
efficiency at STC = 19.53% PV conversion
PVsyst TRIAL
-2.18% Inverter Loss during operation (efficiency)
0.00% Inverter Loss over nominal inv. power
0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage
-0.01% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
72214 kWh Available Energy at Inverter Output
PVsyst TRIAL
PVsyst TRIAL
27/03/23 PVsyst Evaluation mode Page 7/8
Project: 50KW solar Power Plant at Nagpur
Variant: New simulation variant
PVsyst V7.3.2
VC0, Simulation date:
27/03/23 09:47
PVsyst TRIAL
with v7.3.2
Predef. graphs
Daily Input/Output diagram
PVsyst TRIAL
PVsyst TRIAL
PVsyst TRIAL
27/03/23 PVsyst Evaluation mode Page 8/8