PVsyst - Simulation report


Grid-Connected System

Project: siège RAK


Variant: Nouvelle variante de simulation
No 3D scene defined, no shadings
System power: 106 kWp
Kenitra - Maroc

Auteur
Project: siège RAK
Variant: Nouvelle variante de simulation

PVsyst V7.3.1
VC0, Simulation date:
22/05/23 00:49
with v7.3.1

Project summary
Geographical Site Situation Project settings
Kenitra Latitude 34.26 °N Albedo 0.20
Maroc Longitude -6.58 °W
Altitude 19 m
Time zone UTC

Meteo data
Kenitra
Meteonorm 8.1 (1996-2015), Sat=100 % - Synthétique

System summary
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation Near Shadings User's needs


Fixed plane No Shadings Unlimited load (grid)
Tilt/Azimuth 31.7 / 0 °

System information
PV Array Inverters
Nb. of modules 160 units Nb. of units 0.8 unit
Pnom total 106 kWp Pnom total 100 kWac
Pnom ratio 1.064

Results summary
Produced Energy 194819 kWh/year Specific production 1831 kWh/kWp/year Perf. Ratio PR 86.48 %

Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 4
Loss diagram 5
Predef. graphs 6

22/05/23 Page 2/6


Project: siège RAK
Variant: Nouvelle variante de simulation

PVsyst V7.3.1
VC0, Simulation date:
22/05/23 00:49
with v7.3.1

General parameters
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 31.7 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate

Horizon Near Shadings User's needs


Free Horizon No Shadings Unlimited load (grid)

PV Array Characteristics
PV module Inverter
Manufacturer CSI Solar Manufacturer Goodwe
Model CS7N-665MS Model GW120K-HT
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 665 Wp Unit Nom. Power 120 kWac
Number of PV modules 160 units Number of inverters 10 * MPPT 8% 0.8 unit
Nominal (STC) 106 kWp Total power 100 kWac
Modules 10 Strings x 16 In series Operating voltage 180-1000 V
At operating cond. (50°C) Max. power (=>45°C) 132 kWac
Pmpp 97.7 kWp Pnom ratio (DC:AC) 1.06
U mpp 551 V No Power sharing between MPPTs
I mpp 177 A

Total PV power Total inverter power


Nominal (STC) 106 kWp Total power 100 kWac
Total 160 modules Nb. of inverters 1 unit
Module area 497 m² 0.2 unused
Pnom ratio 1.06

Array losses
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 51 mΩ Loss Fraction -0.4 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s

Module mismatch losses Strings Mismatch loss


Loss Fraction 2.0 % at MPP Loss Fraction 0.1 %

IAM loss factor


Incidence effect (IAM): User defined profile

10° 20° 30° 40° 50° 60° 70° 80° 90°


0.998 0.998 0.995 0.992 0.986 0.970 0.917 0.763 0.000

22/05/23 Page 3/6


Project: siège RAK
Variant: Nouvelle variante de simulation

PVsyst V7.3.1
VC0, Simulation date:
22/05/23 00:49
with v7.3.1

Main results
System Production
Produced Energy 194819 kWh/year Specific production 1831 kWh/kWp/year
Performance Ratio PR 86.48 %

Normalized productions (per installed kWp) Performance Ratio PR

Balances and main results

GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_Grid PR


kWh/m² kWh/m² °C kWh/m² kWh/m² kWh kWh ratio
January 86.4 31.43 11.76 134.1 132.3 13103 12754 0.894
February 105.6 37.53 12.53 146.1 144.2 14147 13766 0.886
March 153.2 56.15 14.52 185.6 182.7 17735 17250 0.874
April 190.7 62.27 15.85 201.8 198.5 19070 18539 0.863
May 214.2 73.92 18.77 202.7 198.7 18997 18473 0.856
June 221.8 83.48 20.89 202.0 198.0 18879 18361 0.854
July 222.4 85.91 22.72 207.0 203.0 19220 18692 0.849
August 204.7 78.59 23.31 208.1 204.6 19257 18724 0.846
September 163.6 59.84 21.58 187.6 184.6 17470 16987 0.851
October 130.2 48.50 19.54 170.4 167.9 16061 15623 0.862
November 94.9 35.34 15.19 142.5 140.6 13747 13380 0.882
December 78.7 27.58 13.11 129.3 127.5 12603 12270 0.892
Year 1866.3 680.54 17.51 2117.3 2082.6 200288 194819 0.865

Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings

22/05/23 Page 4/6


Project: siège RAK
Variant: Nouvelle variante de simulation

PVsyst V7.3.1
VC0, Simulation date:
22/05/23 00:49
with v7.3.1

Loss diagram
1866 kWh/m² Global horizontal irradiation
+13.4% Global incident in coll. plane

-1.64% IAM factor on global

2083 kWh/m² * 497 m² coll. Effective irradiation on collectors

efficiency at STC = 21.49% PV conversion

222398 kWh Array nominal energy (at STC effic.)


-0.15% PV loss due to irradiance level

-7.18% PV loss due to temperature

+0.37% Module quality loss

-2.10% Mismatch loss, modules and strings

-1.11% Ohmic wiring loss


200288 kWh Array virtual energy at MPP
-2.73% Inverter Loss during operation (efficiency)
0.00% Inverter Loss over nominal inv. power
0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage
0.00% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
0.00% Night consumption
194819 kWh Available Energy at Inverter Output
194819 kWh Energy injected into grid

22/05/23 Page 5/6


Project: siège RAK
Variant: Nouvelle variante de simulation

PVsyst V7.3.1
VC0, Simulation date:
22/05/23 00:49
with v7.3.1

Predef. graphs
Diagramme d'entrée/sortie journalier

Distribution de la puissance de sortie système

22/05/23 Page 6/6