Project: 281.6 KWp Rooftop Solar Power Plant for ASF CVC Rotor Unit
Variant: E/W
No 3D scene defined, no shadings
System power: 282 kWp
Bharādoba, Valuka, Mymensingh - Bangladesh
Project summary
Geographical Site Situation Project settings
Bharādoba, Valuka, Mymensingh Latitude 24.45 °N Albedo 0.20
Bangladesh Longitude 90.39 °E
Altitude 13 m
Time zone UTC+6
Meteo data
Bharādoba, Valuka, Mymensingh
Meteonorm 8.0 (1996-2015), Sat=100% - Synthetic
System summary
Grid-Connected System No 3D scene defined, no shadings
Simulation for year no 1
System information
PV Array Inverters
Nb. of modules 512 units Nb. of units 2 units
Pnom total 282 kWp Pnom total 200 kWac
Pnom ratio 1.408
Results summary
Produced Energy 364.0 MWh/year Specific production 1292 kWh/kWp/year Perf. Ratio PR 84.87 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 5
Loss diagram 6
Special graphs 7
Aging Tool 8
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Sheds configuration Models used
Fixed planes 2 orientations No 3D scene defined Transposition Perez
Tilts/azimuths 4 / -90 ° Diffuse Perez, Meteonorm
4 / 90 ° Circumsolar separate
PV Array Characteristics
PV module Inverter
Manufacturer Astronergy Manufacturer ChintPower
Model CHSM72M-HC-550 Model CPS SCA110KTL-DO/EU
(Custom parameters definition) (Custom parameters definition)
Unit Nom. Power 550 Wp Unit Nom. Power 100 kWac
Number of PV modules 512 units Number of inverters 2 unit
Nominal (STC) 282 kWp Total power 200 kWac
Modules 32 Strings x 16 In series Operating voltage 200-1000 V
At operating cond. (50°C) Max. power (=>45°C) 110 kWac
Pmpp 257 kWp Pnom ratio (DC:AC) 1.41
U mpp 605 V
I mpp 425 A
Array losses
Array Soiling Losses Thermal Loss factor DC wiring losses
Loss Fraction 2.0 % Module temperature according to irradiance Global array res. 31 mΩ
Uc (const) 29.0 W/m²K Loss Fraction 2.0 % at STC
Uv (wind) 0.0 W/m²K/m/s
Serie Diode Loss LID - Light Induced Degradation Module Quality Loss
Voltage drop 0.7 V Loss Fraction 2.0 % Loss Fraction -0.8 %
Loss Fraction 0.1 % at STC
System losses
Auxiliaries loss
Proportionnal to Power 5.0 W/kW
0.0 kW from Power thresh.
AC wiring losses
Inv. output line up to injection point
Inverter voltage 400 Vac tri
Loss Fraction 1.00 % at STC
Inverter: CPS SCA110KTL-DO/EU
Wire section (2 Inv.) Copper 2 x 3 x 95 mm²
Average wires length 59 m
Main results
System Production
Produced Energy 364.0 MWh/year Specific production 1292 kWh/kWp/year
Performance Ratio PR 84.87 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
Loss diagram
1525 kWh/m² Global horizontal irradiation
Special graphs
Daily Input/Output diagram
Aging Tool
Aging Parameters
Time span of simulation 25 years
Module average degradation Mismatch due to degradation
Loss factor 0.55 %/year Imp RMS dispersion 0.4 %/year
Vmp RMS dispersion 0.4 %/year
Meteo used in the simulation
#1 Bhar doba Valuka Mymensingh MN80 SYN
Years 1990 (reference year)
Years simulated 1-25
Performance Ratio
Aging Tool
Aging Parameters
Time span of simulation 25 years
Module average degradation Mismatch due to degradation
Loss factor 0.55 %/year Imp RMS dispersion 0.4 %/year
Vmp RMS dispersion 0.4 %/year
Meteo used in the simulation
#1 Bhar doba Valuka Mymensingh MN80 SYN
Years 1990 (reference year)
Years simulated 1-25