Project: Ayu Maharani
Variant: Ayu Maharani
PVsyst V7.2.8
VC0, Simulation date:
02/03/23 14:18
with v7.2.8
Project summary
Geographical Site Situation Project settings
Latitude Blok B
Jl. Boulevard Grand Depok City, Grand Dahlia Cluster, -6.44 °S Albedo 0.20
Indonesia Longitude 106.83 °E
Altitude 85 m
Time zone UTC+7
Meteo data
Jl. Boulevard Grand Depok City, Grand Dahlia Cluster, Blok B
Meteonorm 8.0 (2010-2014), Sat=100% - Synthetic
System summary
Grid-Connected System No 3D scene defined, no shadings
Simulation for year no 25
System information
PV Array Inverters
Nb. of modules 6 units Nb. of units 1 Unit
Pnom total 3270 Wp Pnom total 3000 W
Pnom ratio 1.090
Results summary
Produced Energy 4502 kWh/year Specific production 1377 kWh/kWp/year Perf. Ratio PR 79.23 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 5
Loss diagram 6
Special graphs 7
PVsyst V7.2.8
VC0, Simulation date:
02/03/23 14:18
with v7.2.8
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 15 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate
PV Array Characteristics
PV module Inverter
Manufacturer JA Solar Manufacturer Huawei Technologies
Model JAM72S30_545_MR Model SUN2000-3KTL-L1
(Custom parameters definition) (Custom parameters definition)
Unit Nom. Power 545 Wp Unit Nom. Power 3.00 kWac
Number of PV modules 6 units Number of inverters 1 unit
Nominal (STC) 3270 Wp Total power 3.0 kWac
Modules 1 String x 6 In series Operating voltage 90-560 V
At operating cond. (50°C) Max. power (=>40°C) 3.30 kWac
Pmpp 3030 Wp Pnom ratio (DC:AC) 1.09
U mpp 228 V
I mpp 13 A
Array losses
Array Soiling Losses Thermal Loss factor DC wiring losses
Loss Fraction 3.0 % Module temperature according to irradiance Global array res. 188 mΩ
Uc (const) 20.0 W/m²K Loss Fraction 1.0 % at STC
Uv (wind) 0.0 W/m²K/m/s
PVsyst V7.2.8
VC0, Simulation date:
02/03/23 14:18
with v7.2.8
AC wiring losses
Inv. output line up to injection point
Inverter voltage 220 Vac mono
Loss Fraction 0.30 % at STC
Inverter: SUN2000-3KTL-L1
Wire section (1 Inv.) Copper 1 x 2 x 3 mm²
Wires length 3m
PVsyst V7.2.8
VC0, Simulation date:
02/03/23 14:18
with v7.2.8
Main results
System Production
Produced Energy 4502 kWh/year Specific production 1377 kWh/kWp/year
Performance Ratio PR 79.23 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst V7.2.8
VC0, Simulation date:
02/03/23 14:18
with v7.2.8
Loss diagram
1726 kWh/m² Global horizontal irradiation
+0.7% Global incident in coll. plane
PVsyst V7.2.8
VC0, Simulation date:
02/03/23 14:18
with v7.2.8
Special graphs
Daily Input/Output diagram