Project: PLTS Bumba
Variant: Simulasi PLTS Bumba
PVsyst V7.2.6
VC0, Simulation date:
18/11/21 23:59
with v7.2.6
Project summary
Geographical Site Situation Project settings
PLTS Bumba Latitude -8.90 °S Albedo 0.20
Indonesia Longitude 116.39 °E
Altitude 63 m
Time zone UTC+8
Meteo data
PLTS Bumba
Meteonorm 8.0 (2010-2014), Sat=100% - Synthetic
System summary
Grid-Connected System No 3D scene defined, no shadings
System information
PV Array Inverters
Nb. of modules 34025 units Nb. of units 67 units
Pnom total 13.10 MWp Pnom total 10.05 MWac
Pnom ratio 1.303
Results summary
Produced Energy 21706 MWh/year Specific production 1657 kWh/kWp/year Perf. Ratio PR 83.56 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 4
Loss diagram 5
Special graphs 6
P50 - P90 evaluation 7
CO₂ Emission Balance 8
PVsyst V7.2.6
VC0, Simulation date:
18/11/21 23:59
with v7.2.6
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 13 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate
PV Array Characteristics
PV module Inverter
Manufacturer Longi Solar Manufacturer SMA
Model LR6-72 HBD 385 M Bifacial Model Sunny Highpower SHP150-20-PEAK3
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 385 Wp Unit Nom. Power 150 kWac
Number of PV modules 34025 units Number of inverters 67 units
Nominal (STC) 13.10 MWp Total power 10050 kWac
Modules 1361 Strings x 25 In series Operating voltage 855-1450 V
At operating cond. (50°C) Pnom ratio (DC:AC) 1.30
Pmpp 11.88 MWp
U mpp 909 V
I mpp 13069 A
Array losses
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 1.2 mΩ Loss Fraction -0.5 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s
PVsyst V7.2.6
VC0, Simulation date:
18/11/21 23:59
with v7.2.6
Main results
System Production
Produced Energy 21706 MWh/year Specific production 1657 kWh/kWp/year
Performance Ratio PR 83.56 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst V7.2.6
VC0, Simulation date:
18/11/21 23:59
with v7.2.6
Loss diagram
1954 kWh/m² Global horizontal irradiation
+1.5% Global incident in coll. plane
PVsyst V7.2.6
VC0, Simulation date:
18/11/21 23:59
with v7.2.6
Special graphs
Daily Input/Output diagram
PVsyst V7.2.6
VC0, Simulation date:
18/11/21 23:59
with v7.2.6
Probability distribution
PVsyst V7.2.6
VC0, Simulation date:
18/11/21 23:59