3d&pvsyst Kanaan Sai Gon (12-9-22)
3d&pvsyst Kanaan Sai Gon (12-9-22)
12/2022
Version 7.2.4
Author
Project: CTY TNHH KANAAN SAI GON
Variant: KANAAN SAI GON
PVsyst V7.2.4
VC0, Simulation date:
09/12/22 16:03
with v7.2.4
Project summary
Geographical Site Situation Project settings
KANAAN SAI GON Latitude 10.80 °N Albedo 0.20
Vietnam Longitude 106.49 °E
Altitude 10 m
Time zone UTC+7
Meteo data
Đức Hòa Hạ, Hồ Chí Minh, Long An, Việt Nam
Meteonorm 8.0 (1996-2015), Sat=100% - Synthetic
System summary
Grid-Connected System Tables on a building
Simulation for year no 1
System information
PV Array Inverters
Nb. of modules 396 units Nb. of units 2 units
Pnom total 238 kWp Pnom total 200 kWac
Pnom ratio 1.188
Results summary
Produced Energy 342.7 MWh/year Specific production 1442 kWh/kWp/year Perf. Ratio PR 82.12 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Near shading definition - Iso-shadings diagram 5
Main results 6
Loss diagram 7
Special graphs 8
Aging Tool 9
P50 - P90 evaluation 11
Cost of the system 12
CO₂ Emission Balance 13
PVsyst V7.2.4
VC0, Simulation date:
09/12/22 16:03
with v7.2.4
General parameters
Grid-Connected System Tables on a building
PV Field Orientation
Orientation Sheds configuration Models used
Fixed planes 2 orientations Nb. of sheds 396 units Transposition Perez
Tilts/azimuths 6 / 177 ° Sizes Diffuse Perez, Meteonorm
6 / -3 ° Sheds spacing 1.32 m Circumsolar separate
Collector width 1.30 m
Ground Cov. Ratio (GCR) 99.0 %
Shading limit angle
Limit profile angle 81.7 °
PV Array Characteristics
PV module Inverter
Manufacturer Risen Energy Co., Ltd Manufacturer Huawei Technologies
Model RSM120-8-600M Model SUN2000-100KTL-M1-400Vac
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 600 Wp Unit Nom. Power 100 kWac
Number of PV modules 396 units Number of inverters 2 units
Nominal (STC) 238 kWp Total power 200 kWac
Array #1 - PV Array
Orientation #1
Tilt/Azimuth 6/177 °
Number of PV modules 198 units Number of inverters 10 * MPPT 10% 1 units
Nominal (STC) 119 kWp Total power 100 kWac
Modules 11 Strings x 18 In series
At operating cond. (50°C) Operating voltage 200-1000 V
Pmpp 109 kWp Max. power (=>30°C) 110 kWac
U mpp 565 V Pnom ratio (DC:AC) 1.19
I mpp 192 A
Array #2 - Sub-array #2
Orientation #2
Tilt/Azimuth 6/-3 °
Number of PV modules 198 units Number of inverters 10 * MPPT 10% 1 units
Nominal (STC) 119 kWp Total power 100 kWac
Modules 11 Strings x 18 In series
At operating cond. (50°C) Operating voltage 200-1000 V
Pmpp 109 kWp Max. power (=>30°C) 110 kWac
U mpp 565 V Pnom ratio (DC:AC) 1.19
I mpp 192 A
PVsyst V7.2.4
VC0, Simulation date:
09/12/22 16:03
with v7.2.4
Array losses
Array Soiling Losses Thermal Loss factor DC wiring losses
Loss Fraction 0.9 % Module temperature according to irradiance Global array res. 48 mΩ
Uc (const) 20.0 W/m²K Global wiring resistance 24 mΩ
Uv (wind) 0.0 W/m²K/m/s Loss Fraction 1.5 % at STC
LID - Light Induced Degradation Module Quality Loss Module mismatch losses
Loss Fraction 1.6 % Loss Fraction -0.8 % Loss Fraction 2.0 % at MPP
PVsyst V7.2.4
VC0, Simulation date:
09/12/22 16:03
with v7.2.4
Iso-shadings diagram
PVsyst V7.2.4
VC0, Simulation date:
09/12/22 16:03
with v7.2.4
Main results
System Production
Produced Energy (P50) 342.7 MWh/year Specific production (P50) 1442 kWh/kWp/year Performance Ratio PR 82.12 %
Produced Energy (P90) 334 MWh/year Specific production (P90) 1408 kWh/kWp/year
Produced Energy (P95) 332 MWh/year Specific production (P95) 1398 kWh/kWp/year
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst V7.2.4
VC0, Simulation date:
09/12/22 16:03
with v7.2.4
Loss diagram
1760 kWh/m² Global horizontal irradiation
PVsyst V7.2.4
VC0, Simulation date:
09/12/22 16:03
with v7.2.4
Special graphs
Daily Input/Output diagram
PVsyst V7.2.4
VC0, Simulation date:
09/12/22 16:03
with v7.2.4
Aging Tool
Aging Parameters
Time span of simulation 25 years
Module average degradation Mismatch due to degradation
Loss factor 0.4 %/year Imp RMS dispersion 0.4 %/year
Vmp RMS dispersion 0.4 %/year
Meteo used in the simulation
#1 Duc Hoa Ha, Ho Chi Minh, Long An, Viet Nam MN80 SYN
Years 1990 (reference year)
Years simulated 1,6,11,16,21,25
Performance Ratio
PVsyst V7.2.4
VC0, Simulation date:
09/12/22 16:03
with v7.2.4
Aging Tool
Aging Parameters
Time span of simulation 25 years
Module average degradation Mismatch due to degradation
Loss factor 0.4 %/year Imp RMS dispersion 0.4 %/year
Vmp RMS dispersion 0.4 %/year
Meteo used in the simulation
#1 Duc Hoa Ha, Ho Chi Minh, Long An, Viet Nam MN80 SYN
Years 1990 (reference year)
Years simulated 1,6,11,16,21,25
Duc Hoa Ha, Ho Chi Minh, Long An, Viet Nam MN80 SYN
PVsyst V7.2.4
VC0, Simulation date:
09/12/22 16:03
with v7.2.4
Probability distribution
PVsyst V7.2.4
VC0, Simulation date:
09/12/22 16:03
with v7.2.4
Operating costs
Item Total
EUR/year
Total (OPEX) 0.00
System summary
Total installation cost 0.00 EUR
Operating costs 0.00 EUR/year
Produced Energy 343 MWh/year
Cost of produced energy (LCOE) 0.000 EUR/kWh