Project: Cty CP Prime Ngói Việt
Variant: New simulation variant Simulation for the year no 6 Simulation for
the year no 2
PVsyst V7.1.1
Simulation date:
24/01/22 02:56
with v7.1.1
Project summary
Geographical Site Situation Project settings
Phổ yên, Thái Nguyên Latitude 21.26 °N Albedo 0.20
Vietnam Longitude 105.67 °E
Altitude 8m
Time zone UTC+7
Meteo data
Phổ yên, Thái Nguyên
Meteonorm 7.3 (1993-2000), Sat=100% - Synthetic
System summary
Grid-Connected System No 3D scene defined, no shadings
Simulation for year no 1
System information
PV Array Inverters
Nb. of modules 3120 units Nb. of units 13 units
Pnom total 1700 kWp Pnom total 1430 kWac
Pnom ratio 1.189
Results summary
Produced Energy 1979 MWh/year Specific production 1164 kWh/kWp/year Perf. Ratio PR 86.38 %
Solar Fraction SF 16.06 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Detailed User's needs 5
Main results 6
Loss diagram 7
Special graphs 8
Aging Tool 9
Cost of the system 11
Financial analysis 12
CO₂ Emission Balance 14
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Array Characteristics
PV module Inverter
Manufacturer CSI Solar Co., Ltd. Manufacturer SMA
Model CS6W-545MS 1500V Model Sunny Tripower STP 110-60-CORE2
(Custom parameters definition) (Custom parameters definition)
Unit Nom. Power 545 Wp Unit Nom. Power 110 kWac
Number of PV modules 3120 units Number of inverters 13 units
Nominal (STC) 1700 kWp Total power 1430 kWac
Array losses
Array Soiling Losses Thermal Loss factor Serie Diode Loss
Loss Fraction 2.0 % Module temperature according to irradiance Voltage drop 0.7 V
Uc (const) 29.0 W/m²K Loss Fraction 0.1 % at STC
Uv (wind) 0.0 W/m²K/m/s
Array losses
Module Quality Loss Module mismatch losses Strings Mismatch loss
Loss Fraction -0.5 % Loss Fraction 2.0 % at MPP Loss Fraction 0.1 %
Spectral correction
FirstSolar model
Precipitable water estimated from relative humidity
Coefficient Set C0 C1 C2 C3 C4 C5
Monocrystalline Si 0.85914 -0.02088 -0.0058853 0.12029 0.026814 -0.001781
DC wiring losses
Global wiring resistance 2.1 mΩ
Loss Fraction 0.9 % at STC
System losses
Unavailability of the system Auxiliaries loss
Time fraction 2.0 %
7.3 days,
4 periods
AC wiring losses
Inv. output line up to injection point
Inverter voltage 400 Vac tri
Loss Fraction 0.0 % at STC
Inverter: Sunny Tripower STP 110-60-CORE2
Wire section (13 Inv.) Copper 13 x 3 x 70 mm²
Average wires length 0m
Main results
System Production
Produced Energy 1979 MWh/year Specific production 1164 kWh/kWp/year
Performance Ratio PR 86.38 %
Solar Fraction SF 16.06 %
GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_User E_Solar E_Grid EFrGrid
kWh/m² kWh/m² °C kWh/m² kWh/m² MWh MWh MWh MWh MWh
January 66.4 49.05 15.69 65.1 63.0 103.7 1039 96.7 0.000 941.8
February 67.2 54.31 17.50 66.0 63.9 104.3 938 102.4 0.106 835.6
March 87.9 67.23 20.70 86.5 83.7 134.3 1039 131.2 0.670 907.3
April 103.3 74.41 24.47 102.1 98.9 155.4 1005 151.6 1.113 853.4
May 141.8 94.10 28.04 140.2 135.9 210.3 1039 190.0 2.014 848.5
June 154.2 92.62 29.60 152.8 148.1 227.5 1005 221.6 2.272 783.4
July 158.1 88.02 29.60 156.6 151.9 232.7 1039 224.6 4.397 813.9
August 155.5 92.73 28.61 153.8 149.2 229.8 1039 224.3 2.005 814.2
September 130.7 77.86 26.89 129.2 125.2 195.1 1005 190.2 1.836 814.8
October 128.2 78.91 25.03 126.4 122.5 193.3 1039 170.0 0.676 868.5
November 91.1 57.29 20.74 89.7 86.8 140.0 1005 137.3 0.287 867.7
December 80.2 58.76 17.41 78.8 76.2 125.2 1039 123.2 0.000 915.3
Year 1364.6 885.28 23.72 1347.1 1305.4 2051.6 12228 1963.2 15.377 10264.3
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_User Energy supplied to the user
T_Amb Ambient Temperature E_Solar Energy from the sun
GlobInc Global incident in coll. plane E_Grid Energy injected into grid
GlobEff Effective Global, corr. for IAM and shadings EFrGrid Energy from the grid
Loss diagram
1365 kWh/m² Global horizontal irradiation
Special graphs
Daily Input/Output diagram
Aging Tool
Aging Parameters
Time span of simulation 25 years
Module average degradation Mismatch due to degradation
Loss factor 0.4 %/year Imp RMS dispersion 0.4 %/year
Vmp RMS dispersion 0.4 %/year
Meteo used in the simulation
#1 Ph yên Thái Nguyên MN73 SYN
Years 1990 (reference year)
Years simulated 1,6,11,16,21,25
Performance Ratio
Aging Tool
Aging Parameters
Time span of simulation 25 years
Module average degradation Mismatch due to degradation
Loss factor 0.4 %/year Imp RMS dispersion 0.4 %/year
Vmp RMS dispersion 0.4 %/year
Meteo used in the simulation
#1 Ph yên Thái Nguyên MN73 SYN
Years 1990 (reference year)
Years simulated 1,6,11,16,21,25
Operating costs
Item Total
VNĐ/year
CHI PHI VAN HANH VA BAO TRI 200'000'000.00
Total (OPEX) 200'000'000.00
System summary
Total installation cost 0.00 VNĐ
Operating costs 200'000'000.00 VNĐ/year
Unused energy 1963 MWh/year
Energy sold to the grid 15.4 MWh/year
Cost of produced energy (LCOE) 101.084 VNĐ/kWh
Financial analysis
Simulation period
Project lifetime 20 years Start year 2023
Electricity sale
Feed-in tariff Peak tariff 0.00 VNĐ/kWh
Off-peak tariff 0.00 VNĐ/kWh 11:00-17:00, 20:00-09:00
Duration of tariff warranty 20 years
Annual connection tax 0.00 VNĐ/kWh
Annual tariff variation 0.0 %/year
Feed-in tariff decrease after warranty 50.00 %
Self-consumption
Consumption tariff Peak tariff 3'114.00 VNĐ/kWh
Off-peak tariff 1'692.00 VNĐ/kWh 11:00-17:00, 20:00-09:00
Tariff evolution +5.0 %/year
Return on investment
Payback period 0.0 years
Net present value (NPV) 114'048'633'727.47 VNĐ
Return on investment (ROI) 100.0 %
Financial analysis
Yearly net profit (kVNĐ)