Project: Coca-Cola Beverages Philippines Inc. – Misamis
Oriental
PVsyst V7.3.1
Variant: New simulation variant
VC0, Simulation date:
01/19/24 16:31
with v7.3.1
Project summary
Geographical Site Situation Project settings
Villanueva, Misamis Oriental Latitude 8.58 °N Albedo 0.20
Philippines Longitude 124.77 °E
Altitude 12 m
Time zone UTC+8
Meteo data
Villanueva, Misamis Oriental
Meteonorm 8.1 (2016-2021), Sat=100% - Synthetic
System summary
Grid-Connected System No 3D scene defined, no shadings
System information
PV Array Inverters
Nb. of modules 697 units Nb. of units 6 units
Pnom total 279 kWp Pnom total 240 kWac
Pnom ratio 1.162
Results summary
Produced Energy 469044 kWh/year Specific production 1682 kWh/kWp/year Perf. Ratio PR 83.90 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 5
Loss diagram 6
Predef. graphs 7
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 10 / -160 ° Diffuse Perez, Meteonorm
Circumsolar separate
PV Array Characteristics
PV module Inverter
Manufacturer CSI Solar Manufacturer SolarEdge
Model CS3W-400P HE Model SE40K-EU-APAC/AUS
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 400 Wp Unit Nom. Power 40.0 kWac
Number of PV modules 697 units Number of inverters 6 units
Nominal (STC) 279 kWp Total power 240 kWac
Optimizer Array 17 Strings x 41 In series Operating voltage 850 V
At operating cond. (50°C) Pnom ratio (DC:AC) 1.04
Pmpp 253 kWp
Output of optimizers
Voper 850 V
I at Poper 298 A
Physical inverters
SE40K-EU-APAC/AUS
Inverters #1, #2, #3, #4, #5 with 3 strings
3 strings of 41 optimizers P401 WorldWide
SE40K-EU-APAC/AUS
Inverter #6 with 2 strings
2 strings of 41 optimizers P401 WorldWide
Array losses
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 39 mΩ Loss Fraction -0.3 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s
Array losses
IAM loss factor
Incidence effect (IAM): User defined profile
Main results
System Production
Produced Energy 469044 kWh/year Specific production 1682 kWh/kWp/year
Performance Ratio PR 83.90 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
Loss diagram
2051 kWh/m² Global horizontal irradiation
Predef. graphs
Daily Input/Output diagram