Project: PLTS Suralaya
Variant: Suralaya
PVsyst V7.3.1
VC0, Simulation date:
18/06/23 16:47
with v7.3.1
Project summary
Geographical Site Situation Project settings
Kubangkepuh Latitude -5.89 °S Albedo 0.20
Indonesia Longitude 106.03 °E
Altitude 29 m
Time zone UTC+7
Meteo data
Kubangkepuh
Meteonorm 8.1 (2016-2021), Sat=100% - Synthetic
System summary
Standalone system Standalone system with batteries
System information
PV Array Battery pack
Nb. of modules 64 units Technology Lead-acid, sealed, Gel
Pnom total 3200 Wp Nb. of units 12 units
Voltage 24 V
Capacity 2000 Ah
Results summary
Available Energy 4757 kWh/year Specific production 1487 kWh/kWp/year Perf. Ratio PR 62.06 %
Used Energy 3650 kWh/year Solar Fraction SF 100.00 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 5
Loss diagram 6
Predef. graphs 7
Cost of the system 8
PVsyst V7.3.1
VC0, Simulation date:
18/06/23 16:47
with v7.3.1
General parameters
Standalone system Standalone system with batteries
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 10 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate
User's needs
Fixed constant load
417 W
Global
3650 kWh/Year
PV Array Characteristics
PV module Battery
Manufacturer Generic Manufacturer Narada
Model Mono 50 Wp 36 cells Model EosG 2000
(Original PVsyst database) Technology Lead-acid, sealed, Gel
Unit Nom. Power 50 Wp Nb. of units 12 in series
Number of PV modules 64 units Discharging min. SOC 20.2 %
Nominal (STC) 3200 Wp Stored energy 38.4 kWh
Modules 8 Strings x 8 In series Battery Pack Characteristics
At operating cond. (50°C) Voltage 24 V
Pmpp 2876 Wp Nominal Capacity 2000 Ah (C10)
U mpp 129 V Temperature Fixed 20 °C
I mpp 22 A
Total PV power
Nominal (STC) 3.20 kWp
Total 64 modules
Module area 23.2 m²
Array losses
Thermal Loss factor DC wiring losses Serie Diode Loss
Module temperature according to irradiance Global array res. 98 mΩ Voltage drop 0.7 V
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC Loss Fraction 0.5 % at STC
Uv (wind) 0.0 W/m²K/m/s
PVsyst V7.3.1
VC0, Simulation date:
18/06/23 16:47
with v7.3.1
Array losses
IAM loss factor
Incidence effect (IAM): Fresnel smooth glass, n = 1.526
PVsyst V7.3.1
VC0, Simulation date:
18/06/23 16:47
with v7.3.1
Main results
System Production
Available Energy 4757 kWh/year Performance Ratio PR 62.06 %
Used Energy 3650 kWh/year Solar Fraction SF 100.00 %
Excess (unused) 755 kWh/year
Loss of Load Battery aging (State of Wear)
Time Fraction 0.0 % Cycles SOW 95.5 %
Missing Energy 0 kWh/year Static SOW 93.3 %
Legends
GlobHor Global horizontal irradiation E_User Energy supplied to the user
GlobEff Effective Global, corr. for IAM and shadings E_Load Energy need of the user (Load)
E_Avail Available Solar Energy SolFrac Solar fraction (EUsed / ELoad)
EUnused Unused energy (battery full)
E_Miss Missing energy
PVsyst V7.3.1
VC0, Simulation date:
18/06/23 16:47
with v7.3.1
Loss diagram
1824 kWh/m² Global horizontal irradiation
+0.8% Global incident in coll. plane
PVsyst V7.3.1
VC0, Simulation date:
18/06/23 16:47
with v7.3.1
Predef. graphs
Daily Input/Output diagram
PVsyst V7.3.1
VC0, Simulation date:
18/06/23 16:47
with v7.3.1
Operating costs
Item Total
IDR/year
Total (OPEX) 0.00
System summary
Total installation cost 0.00 IDR
Operating costs 0.00 IDR/year
Excess energy (battery full) 755 kWh/year
Used solar energy 3650 kWh/year
Used energy cost 0.000 IDR/kWh