PVsyst - Simulation report


Grid-Connected System

Project: Latihan PLTS


Variant: New simulation variant
No 3D scene defined, no shadings
System power: 50.4 kWp
Mawang - Indonesia

Author
Project: Latihan PLTS
Variant: New simulation variant

PVsyst V7.2.8
VC0, Simulation date:
16/12/21 12:10
with v7.2.8

Project summary
Geographical Site Situation Project settings
Mawang Latitude -5.22 °S Albedo 0.20
Indonesia Longitude 119.49 °E
Altitude 20 m
Time zone UTC+8

Meteo data
Mawang
Meteonorm 8.0 (2010-2014), Sat=100% - Synthetic

System summary
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation Near Shadings User's needs


Fixed plane No Shadings Unlimited load (grid)
Tilt/Azimuth 18 / -5 °

System information
PV Array Inverters
Nb. of modules 160 units Nb. of units 5 units
Pnom total 50.4 kWp Pnom total 50.0 kWac
Pnom ratio 1.008

Results summary
Produced Energy 71.20 MWh/year Specific production 1413 kWh/kWp/year Perf. Ratio PR 76.09 %

Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Horizon definition 4
Main results 5
Loss diagram 6
Special graphs 7

16/12/21 PVsyst Licensed to Page 2/7


Project: Latihan PLTS
Variant: New simulation variant

PVsyst V7.2.8
VC0, Simulation date:
16/12/21 12:10
with v7.2.8

General parameters
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane Transposition Perez
Tilt/Azimuth 18 / -5 ° Diffuse Perez, Meteonorm
Circumsolar separate

Horizon Near Shadings User's needs


Average Height 7.3 ° No Shadings Unlimited load (grid)

PV Array Characteristics
PV module Inverter
Manufacturer CSI Solar Manufacturer Canadian Solar Inc.
Model CS6X - 315P-FG Model CSI-10KTL1P-GI-FL
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 315 Wp Unit Nom. Power 10.00 kWac
Number of PV modules 160 units Number of inverters 5 units
Nominal (STC) 50.4 kWp Total power 50.0 kWac
Modules 16 Strings x 10 In series Operating voltage 100-500 V
At operating cond. (50°C) Pnom ratio (DC:AC) 1.01
Pmpp 45.2 kWp
U mpp 327 V
I mpp 138 A

Total PV power Total inverter power


Nominal (STC) 50 kWp Total power 50 kWac
Total 160 modules Nb. of inverters 5 units
Module area 312 m² Pnom ratio 1.01
Cell area 280 m²

Array losses
Array Soiling Losses Thermal Loss factor DC wiring losses
Loss Fraction 3.0 % Module temperature according to irradiance Global array res. 40 mΩ
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s

LID - Light Induced Degradation Module Quality Loss Module mismatch losses
Loss Fraction 2.0 % Loss Fraction 0.4 % Loss Fraction 2.0 % at MPP

Strings Mismatch loss


Loss Fraction 0.1 %

IAM loss factor


Incidence effect (IAM): User defined profile

10° 20° 30° 40° 50° 60° 70° 80° 90°


0.998 0.998 0.995 0.992 0.986 0.970 0.917 0.763 0.000

16/12/21 PVsyst Licensed to Page 3/7


Project: Latihan PLTS
Variant: New simulation variant

PVsyst V7.2.8
VC0, Simulation date:
16/12/21 12:10
with v7.2.8

Horizon definition
Horizon from PVGIS website API, Lat=-5°52"4', Long=110°26"2', Alt=13m

Average Height 7.3 ° Albedo Factor 0.71


Diffuse Factor 0.97 Albedo Fraction 100 %

Horizon profile

Azimuth [°] -173 -165 -158 -150 -143 -135 -128 -120 -113 -105
Height [°] 0.0 1.9 5.0 5.0 6.9 8.4 8.0 8.4 9.9 9.5
Azimuth [°] -98 -90 -83 -75 -68 -60 -53 -45 -38 -30
Height [°] 10.3 11.8 11.5 12.2 11.5 11.5 11.1 9.9 9.2 6.9
Azimuth [°] -23 -15 -8 0 8 15 23 38 45
Height [°] 7.6 8.4 6.5 5.3 4.2 3.1 2.3 2.3 0.0

Sun Paths (Height / Azimuth diagram)

16/12/21 PVsyst Licensed to Page 4/7


Project: Latihan PLTS
Variant: New simulation variant

PVsyst V7.2.8
VC0, Simulation date:
16/12/21 12:10
with v7.2.8

Main results
System Production
Produced Energy 71.20 MWh/year Specific production 1413 kWh/kWp/year
Performance Ratio PR 76.09 %

Normalized productions (per installed kWp) Performance Ratio PR

Balances and main results

GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_Grid PR


kWh/m² kWh/m² °C kWh/m² kWh/m² MWh MWh ratio
January 140.5 71.81 26.57 124.6 116.2 4.925 4.799 0.764
February 117.0 77.92 26.82 109.0 101.6 4.338 4.227 0.769
March 141.3 77.10 26.95 138.3 130.0 5.435 5.301 0.760
April 151.2 67.91 27.00 156.8 148.3 6.142 5.997 0.759
May 152.9 69.01 27.58 167.6 159.0 6.591 6.438 0.762
June 144.5 64.38 26.71 162.6 154.3 6.452 6.304 0.769
July 164.3 59.45 26.71 184.4 175.0 7.242 7.076 0.761
August 180.2 68.55 27.02 193.7 183.7 7.592 7.420 0.760
September 179.7 70.98 27.23 181.3 171.0 7.058 6.897 0.755
October 188.1 71.45 27.90 178.0 167.4 6.892 6.732 0.751
November 153.6 76.86 27.14 137.9 128.7 5.427 5.295 0.762
December 140.8 73.19 27.11 122.4 114.0 4.835 4.712 0.764
Year 1854.1 848.61 27.06 1856.6 1749.3 72.929 71.198 0.761

Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings

16/12/21 PVsyst Licensed to Page 5/7


Project: Latihan PLTS
Variant: New simulation variant

PVsyst V7.2.8
VC0, Simulation date:
16/12/21 12:10
with v7.2.8

Loss diagram
1854 kWh/m² Global horizontal irradiation
+0.1% Global incident in coll. plane

-1.15% Far Shadings / Horizon

-1.74% IAM factor on global

-3.00% Soiling loss factor

1749 kWh/m² * 312 m² coll. Effective irradiation on collectors

efficiency at STC = 16.14% PV conversion

88.2 MWh Array nominal energy (at STC effic.)


-0.65% PV loss due to irradiance level

-11.97% PV loss due to temperature

-0.40% Module quality loss


-2.00% LID - Light induced degradation

-2.10% Mismatch loss, modules and strings


-1.06% Ohmic wiring loss
72.9 MWh Array virtual energy at MPP
-2.37% Inverter Loss during operation (efficiency)
0.00% Inverter Loss over nominal inv. power
0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage
0.00% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
71.2 MWh Available Energy at Inverter Output
71.2 MWh Energy injected into grid

16/12/21 PVsyst Licensed to Page 6/7


Project: Latihan PLTS
Variant: New simulation variant

PVsyst V7.2.8
VC0, Simulation date:
16/12/21 12:10
with v7.2.8

Special graphs
Daily Input/Output diagram

System Output Power Distribution

16/12/21 PVsyst Licensed to Page 7/7