PVsyst - Simulation report


Grid-Connected System

Project: Nouveau Projet


Variant: Nouvelle variante de simulation
No 3D scene defined, no shadings
System power: 2000 Wp
Kébili - Tunisia

Author
Project: Nouveau Projet
Variant: Nouvelle variante de simulation

PVsyst V7.2.8
VC0, Simulation date:
25/01/24 22:19
with v7.2.8

Project summary
Geographical Site Situation Project settings
Kébili Latitude 33.71 °N Albedo 0.20
Tunisia Longitude 8.97 °E
Altitude 44 m
Time zone UTC+1

Meteo data
Kébili
Meteonorm 8.0 (1991-2000), Sat=100 % - Synthétique

System summary
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation Near Shadings User's needs


Fixed plane No Shadings Unlimited load (grid)
Tilt/Azimuth 30 / 180 °

System information
PV Array Inverters
Nb. of modules 5 units Nb. of units 1 Unit
Pnom total 2000 Wp Pnom total 3000 W
Pnom ratio 0.667

Results summary
Produced Energy 1961 kWh/year Specific production 981 kWh/kWp/year Perf. Ratio PR 78.92 %

Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 4
Loss diagram 5
Special graphs 6

25/01/24 PVsyst Licensed to Page 2/6


Project: Nouveau Projet
Variant: Nouvelle variante de simulation

PVsyst V7.2.8
VC0, Simulation date:
25/01/24 22:19
with v7.2.8

General parameters
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 30 / 180 ° Diffuse Perez, Meteonorm
Circumsolar separate

Horizon Near Shadings User's needs


Free Horizon No Shadings Unlimited load (grid)

PV Array Characteristics
PV module Inverter
Manufacturer ALPHANIS.S.A Manufacturer Senergytec
Model ALPHANIS ALPHA-N Model SE 3KTL-S1
(Custom parameters definition) (Original PVsyst database)
Unit Nom. Power 400 Wp Unit Nom. Power 3.00 kWac
Number of PV modules 5 units Number of inverters 1 unit
Nominal (STC) 2000 Wp Total power 3.0 kWac
Modules 1 String x 5 In series Operating voltage 70-580 V
At operating cond. (50°C) Max. power (=>25°C) 3.30 kWac
Pmpp 1807 Wp Pnom ratio (DC:AC) 0.67
U mpp 136 V
I mpp 13 A

Total PV power Total inverter power


Nominal (STC) 2 kWp Total power 3 kWac
Total 5 modules Nb. of inverters 1 Unit
Module area 9.9 m² Pnom ratio 0.67
Cell area 7.8 m²

Array losses
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 170 mΩ Loss Fraction -0.3 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s

Module mismatch losses Strings Mismatch loss


Loss Fraction 2.0 % at MPP Loss Fraction 0.1 %

IAM loss factor


Incidence effect (IAM): Fresnel smooth glass, n = 1.526

0° 30° 50° 60° 70° 75° 80° 85° 90°


1.000 0.998 0.981 0.948 0.862 0.776 0.636 0.403 0.000

25/01/24 PVsyst Licensed to Page 3/6


Project: Nouveau Projet
Variant: Nouvelle variante de simulation

PVsyst V7.2.8
VC0, Simulation date:
25/01/24 22:19
with v7.2.8

Main results
System Production
Produced Energy 1961 kWh/year Specific production 981 kWh/kWp/year
Performance Ratio PR 78.92 %

Normalized productions (per installed kWp) Performance Ratio PR

Balances and main results

GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_Grid PR


kWh/m² kWh/m² °C kWh/m² kWh/m² kWh kWh ratio
January 83.3 34.8 10.75 31.6 26.9 50.9 45.1 0.713
February 94.6 45.2 12.61 49.5 42.0 79.5 73.6 0.744
March 136.7 71.6 17.28 91.6 82.6 153.6 146.3 0.799
April 165.7 85.0 21.01 129.1 122.0 221.4 213.1 0.825
May 194.6 101.1 25.54 167.8 161.5 285.1 275.9 0.822
June 198.2 97.9 29.43 178.0 172.4 297.3 288.0 0.809
July 214.4 95.4 32.97 189.0 182.6 309.7 300.2 0.794
August 194.8 89.5 32.38 158.6 151.2 259.6 250.6 0.790
September 157.5 72.3 28.36 110.9 101.8 179.7 172.1 0.776
October 125.1 59.4 24.29 71.9 62.1 112.4 105.6 0.734
November 92.0 39.3 16.99 37.1 30.8 56.9 50.8 0.686
December 77.8 34.2 11.99 27.6 24.4 45.8 40.1 0.725
Year 1734.8 825.7 22.02 1242.6 1160.1 2051.9 1961.3 0.789

Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings

25/01/24 PVsyst Licensed to Page 4/6


Project: Nouveau Projet
Variant: Nouvelle variante de simulation

PVsyst V7.2.8
VC0, Simulation date:
25/01/24 22:19
with v7.2.8

Loss diagram
1735 kWh/m² Global horizontal irradiation

-28.37% Global incident in coll. plane

-6.64% IAM factor on global

1160 kWh/m² * 10 m² coll. Effective irradiation on collectors

efficiency at STC = 20.26% PV conversion

2322 kWh Array nominal energy (at STC effic.)


-1.49% PV loss due to irradiance level

-8.03% PV loss due to temperature

+0.31% Module quality loss

-2.10% Mismatch loss, modules and strings


-0.69% Ohmic wiring loss
2052 kWh Array virtual energy at MPP

-4.13% Inverter Loss during operation (efficiency)


0.00% Inverter Loss over nominal inv. power
0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage
-0.07% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
-0.23% Night consumption
1961 kWh Available Energy at Inverter Output
1961 kWh Energy injected into grid

25/01/24 PVsyst Licensed to Page 5/6


Project: Nouveau Projet
Variant: Nouvelle variante de simulation

PVsyst V7.2.8
VC0, Simulation date:
25/01/24 22:19
with v7.2.8

Special graphs
Diagramme d'entrée/sortie journalier

Distribution de la puissance de sortie système

25/01/24 PVsyst Licensed to Page 6/6