Project: AJL
Variant: Ananta Jeanswear Ltd.
No 3D scene defined, no shadings
System power: 334.02 kWp
Ananta Jeanswear Ltd. - Bangladesh
PVsyst V7.2.6
VC0, Simulation date:
02/03/23 16:26
with v7.2.6
Project summary
Geographical Site Situation Project settings
Ananta Jeanswear Ltd. Latitude 23.90 °N Albedo 0.20
Bangladesh Longitude 90.43 °E
Altitude 8m
Time zone UTC+6
Meteo data
Ananta Jeanswear Ltd.
Meteonorm 8.0 (1991-2012), Sat=100% - Synthetic
System summary
Grid-Connected System No 3D scene defined, no shadings
Simulation for year no 1
System information
PV Array Inverters
Nb. of modules 586 units Nb. of units 6 units
Pnom total 334.02 kWp Pnom total 310 kWac
Pnom ratio 1.07
Results summary
Produced Energy 466.2 MWh/year Specific production 1388 kWh/kWp/year Perf. Ratio PR 86.21 %
Apparent energy 475.7 MVAh
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 6
Loss diagram 7
Special graphs 8
Aging Tool 9
Predef. graphs 11
P50 - P90 evaluation 12
Cost of the system 13
Financial analysis 14
CO₂ Emission Balance 17
PVsyst V7.2.6
VC0, Simulation date:
02/03/23 16:26
with v7.2.6
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Sheds configuration Models used
Fixed planes 4 orientations No 3D scene defined Transposition Perez
Tilts/azimuths 23 / 15 ° Diffuse Perez, Meteonorm
23 / 16 ° Circumsolar separate
23 / 8 °
23 / 0 °
PV Array Characteristics
Array #1 - AJL Main-1
Orientation #1
Tilt/Azimuth 23/15 °
PV module Inverter
Manufacturer Jinkosolar Manufacturer Huawei Technologies
Model JKM570N-72HL4-V Model SUN2000-100KTL-M2-400Vac
(Custom parameters definition) (Custom parameters definition)
Unit Nom. Power 570 Wp Unit Nom. Power 100 kWac
Number of PV modules 198 units Number of inverters 1 unit
Nominal (STC) 113 kWp Total power 100 kWac
Modules 11 Strings x 18 In series Operating voltage 200-1000 V
At operating cond. (50°C) Max. power (=>33°C) 110 kWac
Pmpp 104 kWp Pnom ratio (DC:AC) 1.13
U mpp 693 V
I mpp 151 A
PV module Inverter
Manufacturer Jinkosolar Manufacturer Huawei Technologies
Model JKM570N-72HL4-V Model SUN2000-40KTL-M3-400V
(Custom parameters definition) (Custom parameters definition)
Unit Nom. Power 570 Wp Unit Nom. Power 40.0 kWac
Number of PV modules 279 units Number of inverters 4 units
Nominal (STC) 159 kWp Total power 160 kWac
PVsyst V7.2.6
VC0, Simulation date:
02/03/23 16:26
with v7.2.6
PV Array Characteristics
Array #3 - PWPL
Orientation #4
Tilt/Azimuth 23/0 °
Number of PV modules 144 units Number of inverters 2 units
Nominal (STC) 82.1 kWp Total power 80.0 kWac
Modules 8 Strings x 18 In series
At operating cond. (50°C) Operating voltage 200-1000 V
Pmpp 75.9 kWp Max. power (=>40°C) 44.0 kWac
U mpp 693 V Pnom ratio (DC:AC) 1.03
I mpp 110 A
PVsyst V7.2.6
VC0, Simulation date:
02/03/23 16:26
with v7.2.6
Array losses
Array Soiling Losses Thermal Loss factor Serie Diode Loss
Loss Fraction 3.0 % Module temperature according to irradiance Voltage drop 0.7 V
Uc (const) 29.0 W/m²K Loss Fraction 0.1 % at STC
Uv (wind) 0.0 W/m²K/m/s
LID - Light Induced Degradation Module Quality Loss Module mismatch losses
Loss Fraction 2.0 % Loss Fraction -0.8 % Loss Fraction 2.0 % at MPP
DC wiring losses
Global wiring resistance 10 mΩ
Loss Fraction 1.5 % at STC
PVsyst V7.2.6
VC0, Simulation date:
02/03/23 16:26
with v7.2.6
Main results
System Production
Produced Energy (P50) 466.2 MWh/year Specific production (P50) 1388 kWh/kWp/year Performance Ratio PR 86.21 %
Produced Energy (P90) 455 MWh/year Specific production (P90) 1355 kWh/kWp/year
Produced Energy (P75) 460 MWh/year Specific production (P75) 1371 kWh/kWp/year
Apparent energy 475.7 MVAh
Economic evaluation
Investment Yearly cost LCOE
Global 21'000'000.00 BDT Annuities 4'316'918.98 BDT/yr Energy cost 2.66 BDT/kWh
Specific 62.8 BDT/Wp Run. costs 366'494.94 BDT/yr
Payback period 5.8 years
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst V7.2.6
VC0, Simulation date:
02/03/23 16:26
with v7.2.6
Loss diagram
1529 kWh/m² Global horizontal irradiation
+5.3% Global incident in coll. plane
94.6 MVAR Reactive energy from the grid: Aver. cos(phi) = 0.980
475.7 MVA Apparent energy to the grid
PVsyst V7.2.6
VC0, Simulation date:
02/03/23 16:26
with v7.2.6
Special graphs
Daily Input/Output diagram
PVsyst V7.2.6
VC0, Simulation date:
02/03/23 16:26
with v7.2.6
Aging Tool
Aging Parameters
Time span of simulation 25 years
Module average degradation Mismatch due to degradation
Loss factor 0.4 %/year Imp RMS dispersion 0.4 %/year
Vmp RMS dispersion 0.4 %/year
Meteo used in the simulation
#1 Ananta Jeanswear Ltd MN80 SYN
Years 1990 (reference year)
Years simulated 1,6,11,16,21,25
Performance Ratio
PVsyst V7.2.6
VC0, Simulation date:
02/03/23 16:26
with v7.2.6
Aging Tool
Aging Parameters
Time span of simulation 25 years
Module average degradation Mismatch due to degradation
Loss factor 0.4 %/year Imp RMS dispersion 0.4 %/year
Vmp RMS dispersion 0.4 %/year
Meteo used in the simulation
#1 Ananta Jeanswear Ltd MN80 SYN
Years 1990 (reference year)
Years simulated 1,6,11,16,21,25
PVsyst V7.2.6
VC0, Simulation date:
02/03/23 16:26
with v7.2.6
Predef. graphs
Daily System Output Energy
PVsyst V7.2.6
VC0, Simulation date:
02/03/23 16:26
with v7.2.6
Probability distribution
PVsyst V7.2.6
VC0, Simulation date:
02/03/23 16:26
with v7.2.6
Operating costs
Item Total
BDT/year
Operaton & Maintenance 167'000.00
Total (OPEX) 167'000.00
Including inflation (6.00%) 366'494.94
System summary
Total installation cost 21'000'000.00 BDT
Operating costs (incl. inflation 6.00%/year) 366'494.94 BDT/year
Produced Energy 466 MWh/year
Cost of produced energy (LCOE) 2.663 BDT/kWh
PVsyst V7.2.6
VC0, Simulation date:
02/03/23 16:26
with v7.2.6
Financial analysis
Simulation period
Project lifetime 25 years Start year 2023
Depreciation
Depreciable assets 12'876'680.39 BDT
Salvage value 0.00 BDT
Total redeemable 12'876'680.39 BDT
Depreciation period 25 years
Financing
Own funds 2'310'000.00 BDT
Loan - Redeemable with fixed annuity - 5 years 18'690'000.00 BDT Interest rate: 5.00%/year
Electricity sale
Feed-in tariff 8.45 BDT/kWh
Duration of tariff warranty 25 years
Annual connection tax 0.00 BDT/kWh
Annual tariff variation +3.0 %/year
Feed-in tariff decrease after warranty 0.00 %
Return on investment
Payback period 5.8 years
Net present value (NPV) 109'716'123.96 BDT
Return on investment (ROI) 522.5 %
PVsyst V7.2.6
VC0, Simulation date:
02/03/23 16:26
with v7.2.6
Financial analysis
Detailed economic results (kBDT)
PVsyst V7.2.6
VC0, Simulation date:
02/03/23 16:26
with v7.2.6
Financial analysis
Yearly net profit (kBDT)
PVsyst V7.2.6
VC0, Simulation date:
02/03/23 16:26
with v7.2.6